Inspection Report. Property Address: 908 Black Hills Drive Spearfish, SD 57783

Similar documents
Inspection Report. Property Address:

Home Inspection Report

Alabama Home Inspections

The Inspector. Property Inspection Report

1234 Main St. Buyer Name. Table of Contents

Inspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011

Inspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012

GROUNDS Grading General Grading, slope and drainage: Satisfactory N/A See Notes. Grading and slope at house wall

Inspection Report. 1 of 8

component was performing its intended function; installation and condition were appropriate for age and use.

Inspection Report. Prepared for: Tonia Mann. Property Address: 1295 Greyland Hills Drive Lawrenceville, GA Date: April 24, 2012

Madison's Home Inspections

Inspection Report. Prepared for: Yaron Sternberg. Property Address: 926 Hemingway Road Stone Mountain, GA. Date: April 15, 2011

Inspection Report. Prepared for: Tonia Mann. Property Address: 56 Riverview Place Douglasville, GA Date: September 19, 2012

Inspection Report. Provided by: Cummins Services LLC. Inspector: Bill Cummins. Phone:

Friendly Inspection Services

Friendly Inspection Services

WEST MICHIGAN HOME INSPECTORS LLC 3134 Chamberlain SE Grand Rapids MI

Friendly Inspection Services

Property Inspection Checklist

Pre-Listing Home Inspection Checklist

The Home Doctor, Inc.

Exterior structures (fences, sheds, decks, retaining walls, detached garages) in good condition, no evidence of termite damage or rotted wood

SureHome Inspection Company. Home Inspection. Grant st Street Omaha, NE 68048

Home Inspection Report

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free

Inspect Hawaii. Property Inspection Report

Rental Inspection Checklist

SINGLE FAMILY HOME SPECIFICATIONS

Total Home Inspection Checklist

1234 Main St Denver CO 80210

SUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM


FAIRA TRANSPARENCY REPORTS Robert Wayne Dr, Pasco, WA July 18 th, 2017

Inspection Services of the Treasure Coast

All Pro Home Inspection. Home Report North Your Town

3D Home Improvement and Inspection Services, Inc

Home Condition Checklist

Property Inspection Report

State Home Inspector Lic. # HI3986 Termite Inspector License # JE187661

SAMPLE Property Inspection Report

JBR Property Inspections

Report Page 1 of 23 12/30/2013 Tri-City Home Inspections James Eddy ID:

1st Defense Home Inspections, LLC

Tru-Quest Home Inspection

1623 Carol Street Downers Grove, Illinois Inspection Report for Property at: Private Home Inspection for:

J & M Solutions, LLC

The Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits

JM Rodkey, Co., Inspections

$308,900. Caleb Crescent Collection The Algonquin Model 1113 Sq. Ft. Elevation A. Updated: September 28, Elevation B

Home Inspection Report

RB Homes, Inc. 152 Witherspoon St. Princeton, NJ P: (609) / F: (609)

RB Homes, Inc. 152 Witherspoon St. Princeton, NJ P: (609) / F: (609)

New Hope Inspections, LLC Property Inspection Report

Z & C Construction, Inc. Subdivision:

Pinnacle Home Inspections, Inc. Serving Central Arkansas

Date of Inspection: April 30th 2006 Client: Ivan M. House Inspector: Lee Ottewell (CPBC License #: 47384)

FAIRA TRANSPARENCY REPORTS SW 100th St, Seattle, WA June 15 th, 2017

6954 Lakeside Dr. Property Inspection Report. - Provided by First Class Property Inspections, LLC -

Edouard AVANT GROVE U I C U I C. Modern Living Made Easy uichomes.com

Cheshire, CT. By: A.M. Napolitano, LLC. Project Manager: Carolyne Sakonchick Ext. 323

FoundationsRealty.com Hickory Hills The. Condominiums

RB Homes, Inc. 152 Witherspoon St. Princeton, NJ P: (609) / F: (609)

Property Inspection Report

Chapter 33 - Checklists

BCT 102 Printreading SAMPLE DESCRIPTION OF MATERIALS #STORIES: WATER SUPPLY PUBLIC: WELL: BEARING SOIL TYPE FOOTING MATERIAL:

TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM. Form 15 Work Write-Up

Home Inspection Checklist

pershing+ desperes uichomes.com 6005 and 6007 Pershing Avenue pershing+desperes call or

Permit Posting and Inspection Procedures

The Poplar. Hickory Hills. Condominiums. FoundationsRealty.com

Building Inspection Report

FINEGAN INSPECTION SERVICES, INC.

RB Homes, Inc. 152 Witherspoon St. Princeton, NJ P: (609) / F: (609)

Anthracite Home Inspections

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS

Inspection Report. Provided by: L.A.Selleck inspections and Consulting. Inspector: Larry Selleck

A 1 Professional Home Inspection 14 Brevoort Pl. Deer Park, NY Jamaica, NY 11434

Boyle. contemporary new homes with great curb appeal. boyle call or 3br/2.5bth, 1905sf

RB Homes, Inc. 152 Witherspoon St. Princeton, NJ P: (609) / F: (609)

9) Home Inspection: As defined in Section 1-10 of the Act.

TITLE 68: PROFESSIONS AND OCCUPATIONS CHAPTER VIII: DEPARTMENT OF FINANCIAL AND PROFESSIONAL REGULATION

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210)

All Pro Home Inspection. Home Report South Your Town

Safety Money Repair Maintenance Evaluate Monitor Comment

Advanced Home Inspections

Section Standards of Practice. a) The following are terms commonly used in the writing of home inspection reports.

Home Inspection Report

L&A Home Inspections

National Property Inspections

Feasibility Report. Property Inspection Engineers, Inc. (248) Property Address. 405 Fairgrove Royal Oak, MI.

BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY

Karl Tarango (970)

BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY

A Summary of the Basic Duties of Maintenance, Repair and Replacement for CARRIAGE PARK CONDOMINIUM ASSOCIATION

Hogue Home Inspections

Calidad Home Inspection Colleyville, TX (817) /

Walnut Creek Mutual Seventy

Transcription:

Inspection Report Provided by: Inspector: Jeff Samona PO Box 111; Spearfish, SD 57783 (605) 717-0486 www.jandkinspections.com home@jandkinspections.com Property Address: 908 Black Hills Drive Spearfish, SD 57783

Report Information Client Information Client Name Dave and Gladis Grace Client Phone (804) 555-0640 Property Information Approximate Year Built 2008 Approximate Square Footage 1360 sq. ft. finished Number of Bedroom 3 Number of Bath 2 Direction House Faces South Inspection Information Inspection Date 6/10/16 Inspection Time Weather Conditions 9:40 am Sunny, clear Outside Temperature 85 Price for Inspection $325.00 Page 2 of 42

Table of Contents: Section Content 1...Disclaimer 2...Grounds 3...Exterior 4...Roofing 5...Heating/Air 6...Electrical 7...Plumbing 8...Interiors 9...Kitchen 10...Bath(s) 11...Basement 12...Garage/Laundry 13...Foundation/Crawl Space 14...Summary Page Page 3 of 42

Disclaimer An inspection addresses only those components and conditions that are present, visible, and accessible at the time of the inspection. While there may be other parts, components or systems present, only those items specifically noted as being inspected were inspected. The inspector is not required to move furnishings or stored items. The inspection report may address issues that are code-based or may refer to a particular code; however, this is NOT a code compliance inspection and does NOT verify compliance with manufacturer's installation instructions. The inspection does NOT imply insurablility or warrantability of the structure or its components. Although some safety issues may be addressed in this report, this inspection is NOT a safety/code inspection, and the inspector is NOT required to identify all potential hazards. Page 4 of 42

1 Grounds Grading 1 Grounds Grading Slope The site is flat. 1) Grading Conditions AS Grading of the soil near the foundation appears to be in serviceable condition. Driveways - Sidewalks - Walkways Driveway Material Concrete 2) Driveway Conditions R Major cracks were found in the driveway. Cracks need to be sealed to prevent water intrusion and further deterioration. Sidewalk Material Concrete 3) Sidewalk Conditions S The surface of the front walk where it meets the driveway was raised or settled. This may cause tripping hazards. This should be repaired for safety. Any rise less than four inches is considered a trip step. The cracks in the sidewalk should be sealed or caulked to prevent water intrusion and further deterioration. Page 5 of 42

1 Grounds 4) Vegetation Vegetation next to home. 5) Fences Chain link. Appeared serviceable at the time of the inspection. Page 6 of 42

2 Exterior Front - Back Entrance 2 Exterior Front Entrance Type Covered Deck 6) Front Entrance Conditions R The front deck does not appear to have flashing behind it which can cause water intrusion and rotting behind the ledger board and siding. The deck is not properly secured to the home with lag bolts. Recommend repairs as needed. Back Entrance Type Covered Deck 7) Back Entrance Conditions R The back deck is not properly secured to the home with lag bolts. The deck has a lot of deflection. There should be a mid-span support under the girder. Recommend repairs as needed. Page 7 of 42

2 Exterior Exterior Walls Structure Type Exterior Wall Covering Wood frame Diamond Coat 8) Exterior Wall Conditions R There are several siding joint splices that don't fully cover the siding joint which can allow moisture and insect intrusion. There are some areas of chipped paint exposing bare wood which can lead to moisture damage. There are several locations where there is mortar missing beside the stone veneer which can lead to moisture damage to the exterior sheathing. Recommend repairs as needed. Fascia - Soffit - Trim Page 8 of 42

2 Exterior 9) Fascia - Soffit - Trim Conditions R On soffit in front, there is J-Channel missing exposing an open joint which can lead to insect, bat, rodent intrusion. On side man door going into the front garage is a gap that needs to be sealed. Also there is a big gap around the man door going into garage that needs to be caulked. On all exterior outside corners the corner boards are separating and curling away from the home. These need to be resecured and pulled together and joints caulked to prevent insect and moisture intrusion. 10) Exterior continued R On front right side of overhead garage door, the stone cap needs to be sealed to prevent water intrusion (and in the winter the water freezing and resulting in popping loose of stones). Archway over left side overhead garage door has exposed OSB sheathing. This needs to be covered. On right overhead garage door the head piece of brick mold is missing aluminum wrap. Page 9 of 42

2 Exterior 11) Exterior continued - R On left side on back deck under decorative barn board is a large gap in the soffit that needs to be sealed. On back deck, on right hand upper corner there is a large gap that needs to be sealed to prevent insect, bat, rodent, etc., intrusion. Page 10 of 42

2 Exterior Exterior Windows - Doors Window Type Window Material Sliding Vinyl 12) Window Conditions R The two egress basement windows on east side of home are missing escape ladders. The screens are torn on the basement windows on east and north side of home. Page 11 of 42

2 Exterior 13) Exterior Door Conditions S Weather stripping is damaged on the back man door to garage. Recommend repairs as needed. Sliding door on rear deck is missing a locking lever and catch assembly so door cannot be latched or locked. On man door going from house to garage "breezeway" there are no self-closing hinges. Page 12 of 42

2 Exterior 14) Door Bell The doorbell was in serviceable condition at the time of the inspection. 15) Screen Door R On sliding glass door at rear deck, the screen is totally missing. 16) Exterior Electrical S At back sliding glass door, the light fixture is missing which results in an open junction box with a wire not properly placed in conduit. Page 13 of 42

2 Exterior Exterior Water Faucet(s) Faucet Location North side of home. 17) Faucet Conditions AS The hose faucets appeared to be in serviceable condition at the time of the inspection. Page 14 of 42

3 Roofing Roof Covering 3 Roofing Method of Inspection Roof Style Roof Covering Material Number of Layers The roof was inspected by walking the safe and accessible areas. Gable Asphalt composition shingles. One 18) Roof Covering Condition R The ridge cap/vent on east rear side has nails that are too short, not able to penetrate through roof sheathing. On west side gable under gable overhang, there are gaps in the roofing material where rain/snow can run underneath the roof shingle causing moisture damage. On east side gable under gable overhang, there is a gap in the roofing material where rain/snow can run underneath roof shingle causing moisture damage. Page 15 of 42

3 Roofing 19) Flashing Conditions R There is no step flashing, just a common flashing on the gable ends. Step flashing is the proper flashing method. There is no kick out flashing on west side which will cause water to run behind the siding and rot the back of the siding and sheathing of home. It is suggested that a "Licensed Roofing Contractor" be contacted for further evaluation and repair. Page 16 of 42

3 Roofing 20) Gutter & Downspout Conditions R The gutter on the rear (north) side of home is bent and gutter hanger is damaged. Recommend repairs as needed. Attic Area Attic Access Method of Inspection Roof Frame Type Hallway Entered attic area. The roof framing is constructed with 2x4 truss framing and 2x4 top cord. 21) Attic Conditions AS The solar tube for main bath is separated and coming apart in the attic. Recommend repairs as needed. Page 17 of 42

3 Roofing Attic Ventilation Type Attic Ventilation Conditions Attic Insulation Type Baffles every 4th bay; ridge vents, soffit vents Adequate. Blown cellulose 22) Attic Insulation Conditions AS No moisture or signs of previous moisture were present at time of inspection; 14 inches of blown insulation. Page 18 of 42

4 Heating - Air Heating 4 Heating - Air Location of Unit Heating Type Energy Source Basement Forced Air Electric 23) Unit Conditions AS AC on. Heating system was not tested. Manufacture date on heating/ac unit is 2008. Model#FSM2X3600A; Serial #A081787140 Distribution Type The visible areas of the heat/ac distribution system are ductwork with registers. 24) Distribution Conditions AS The visible and accessible areas of the distribution system appeared to be in serviceable condition at the time of inspection. 25) Thermostat Condition AS One zone with the thermostat upstairs. Air Condition - Cooling Type of Cooling System Central 26) AC Unit Conditions AS AC unit appeared to be in serviceable condition at the time of the inspection. Page 19 of 42

5 Electrical Service Drop - Weatherhead 5 Electrical Electrical Service Type Electrical Service Material The electrical service is underground. Aluminum 27) Electrical Service Conditions AS The main service entry appeared to be in serviceable condition at the time of inspection. Main Electrical Panel Main Disconnect Location Electric Panel Location At Main Panel The main electric panel is located in the basement. Panel Amperage Rating The electrical capacity of main breaker was listed / labeled as 200 amps. Circuit Protection Type Breakers 28) Wiring Methods AS The main power cable is aluminum. The branch cables are copper. 29) Electrical Panel Conditions AS The main panel appeared to be in serviceable condition at the time of the inspection. Electrical Subpanel Subpanel Location One is being installed in the garage. 30) Subpanel Conditions AS n/a 31) Electrical Conditions R The garage is being wired with 14 gage wire for receptacles which will allow for a 15 amp circuit which is not recommended for receptacle circuit. 12 gage wire and 20 amp circuits are recommended. Page 20 of 42

5 Electrical Page 21 of 42

6 Plumbing Water Main Line 6 Plumbing Main Shutoff Location Main Line Material The main valve is located at the basement laundry room. The visible material of the main line / pipe appears to be plastic. 32) Main Line & Valve Conditions AS The visible portion of the main pipe and valve appeared to be in serviceable condition at the time of the inspection. Water Supply Lines Supply Line Material The visible material used for the supply lines is plastic. 33) Supply Line Conditions AS The visible portions of the supply lines appeared to be in serviceable condition at the time of inspection. All of the supply lines were not fully visible or accessible at the time of the inspection. Drain - Waste Lines Drain Line Material The visible portions of the waste lines are plastic. 34) Drain Line Conditions AS The visible portions of the waste lines appeared to be in serviceable condition at the time of inspection. All of the waste lines were not fully visible or accessible at the time of the inspection. Water Heater(s) Page 22 of 42

6 Plumbing Water Heater Type Water Heater Location Water Heater Capacity Electric Basement laundry room. 85 Gallon 35) Water Heater Conditions AS Rheem Marathon Model #MR85238 36) Water Softener AS Present, but no salt in brine tank. Page 23 of 42

7 Interiors Walls - Ceilings - Floors 7 Interiors 37) Wall Conditions AS The general condition of the walls appeared to be in serviceable condition at the time of the inspection. 38) Ceiling Conditions AS The general condition of the ceilings appeared to be in serviceable condition at the time of the inspection. 39) Floor Conditions AS The general condition of the visible and accessible portions of the floors appeared to be in serviceable condition at the time of the inspection. 40) Bedrooms R The bi-fold door track hardware in the two smaller bedrooms is damaged/bent. (Eventually they will pop out of track.) Recommend repairs as needed. Page 24 of 42

7 Interiors Windows - Doors 41) Interior Window Conditions R Window not operable. Crank missing from Master Bedroom casement window on east wall. 42) Interior Door Conditions AS The interior doors appeared to be in serviceable condition at the time of the inspection. Electrical Conditions 43) Electrical Conditions R The electrical switches in living room and front entry door are 3-way switches which inspector could not find what they operated. Client will have to discuss with current owner. Receptacle (below light switch) in southeast bedroom is loose. Light switch at man door going to "breezeway/garage" off of kitchen has a light switch that inspector could not determine what it operated. Page 25 of 42

7 Interiors 44) Lighting Conditions AS Adequate. 45) Ceiling Fan Conditions AS Ceiling fans were not present in two smaller bedrooms. 46) Smoke Detector Conditions AS Smoke detectors were present and operable, but not wired together. With this home being built in 2008, smoke detectors should have been wired together. Page 26 of 42

8 Kitchen Walls - Ceilings - Floors 8 Kitchen 47) Wall Conditions AS The general condition of the walls appeared to be in serviceable condition at the time of the inspection. 48) Ceiling Conditions AS The general condition of the ceilings appeared to be in serviceable condition at the time of the inspection. 49) Floor Conditions AS The general condition of the visible and accessible portions of the floors appeared to be in serviceable condition at the time of the inspection. Windows - Doors 50) Kitchen Window Conditions AS The kitchen window was tested and was operational at the time of the inspection. 51) Kitchen Door Conditions AS n/a Electrical Conditions 52) Electrical Conditions AS GFCI tested. 53) Lighting Conditions R Can light above kitchen sink not operable. Recommend repairs as needed. Page 27 of 42

8 Kitchen 54) Ceiling Fan Conditions AS n/a Kitchen Sink - Counter tops - Cabinets 55) Counter Conditions AS Laminate. The visible portion kitchen counters appeared to be in serviceable condition at the time of the inspection. 56) Cabinet Conditions AS The kitchen cabinets appeared to be in serviceable condition at the time of inspection. 57) Sink Plumbing Conditions AS Shut off valves present. Functional flow and drainage. The kitchen sink appeared to be in serviceable condition at the time of the inspection. The faucet appeared to be in serviceable condition at the time of the inspection. The visible areas of the plumbing under the kitchen sink appeared to be in serviceable condition at the time of the inspection. 58) Garbage Disposal Condition AS Half Horse Badger garbage disposal. The sink disposal was operable at the time of the inspection. Client should consult a licensed plumber, manufacturer, or disposal supply company for information on proper usage and safety related concerns. Appliances Stove - Range Type Electric ceramic top stove/electric range. 59) Stove - Range Condition AS Stove - range appeared to be in serviceable condition at the time of the inspection. 60) Hood Fan Conditions AS Recirculates air. 61) Dishwasher Conditions AS The dishwasher appeared to be in serviceable condition at the time of the inspection. This does not however guarantee future performance or conditions. 62) Refrigerator Conditions R Refrigerator is missing bottom cover. Page 28 of 42

8 Kitchen Page 29 of 42

9 Bath 1 - Main Walls - Ceilings - Floors 9 Bath 1 - Main 63) Wall Conditions AS The general condition of the walls appeared to be in serviceable condition at the time of the inspection. 64) Ceiling Conditions AS The general condition of the ceilings appeared to be in serviceable condition at the time of the inspection. 65) Floor Conditions AS The general condition of the visible and accessible portions of the floors appeared to be in serviceable condition at the time of the inspection. Windows - Doors 66) Bathroom Window Conditions AS n/a 67) Bathroom Door Conditions AS The general condition of the bathroom door appeared to be in serviceable condition at the time of the inspection. Electrical Conditions 68) Electrical Conditions AS GFCI receptacle above vanity and was tested. 69) Lighting Conditions AS Adequate. 70) Vent Fan Conditions AS The vent fan appeared to be in serviceable condition at the time of the inspection. Bathroom Sink 71) Counter - Cabinet Conditions AS The counter - cabinet appeared to be in serviceable condition at the time of the inspection. 72) Sink Conditions R Sink stopper not hooked up. The bathroom sink appeared to be in serviceable condition at the time of the inspection. The faucet appeared to be in serviceable condition at the time of the inspection. The visible areas of the plumbing under the bathroom sink appeared to be in serviceable condition at the time of the inspection. Page 30 of 42

9 Bath 1 - Main Shower - Tub - Toilet 73) Shower - Tub Conditions AS Fiberglass tub and shower surround appeared to be in serviceable condition at the time of the inspection. 74) Toilet Conditions AS The toilet appeared to be in serviceable condition at the time of the inspection. Page 31 of 42

10 Bath 2 - Master Walls - Ceilings - Floors 10 Bath 2 - Master 75) Wall Conditions AS The general condition of the walls appeared to be in serviceable condition at the time of the inspection. 76) Ceiling Conditions AS The general condition of the ceilings appeared to be in serviceable condition at the time of the inspection. 77) Floor Conditions AS The general condition of the visible and accessible portions of the floors appeared to be in serviceable condition at the time of the inspection. Windows - Doors 78) Bathroom Window Conditions AS n/a 79) Bathroom Door Conditions AS The general condition of the bathroom door appeared to be in serviceable condition at the time of the inspection. Electrical Conditions 80) Electrical Conditions AS GFCI receptacle tested. 81) Lighting Conditions AS Adequate. 82) Vent Fan Conditions AS The vent fan appeared to be in serviceable condition at the time of the inspection. Bathroom Sink 83) Counter - Cabinet Conditions AS The counter - cabinet appeared to be in serviceable condition at the time of the inspection. 84) Sink Conditions AS The bathroom sink appeared to be in serviceable condition at the time of the inspection. The faucet appeared to be in serviceable condition at the time of the inspection. The visible areas of the plumbing under the bathroom sink appeared to be in serviceable condition at the time of the inspection. Page 32 of 42

10 Bath 2 - Master Shower - Tub - Toilet 85) Shower - Tub Conditions AS Fiberglass tub and shower surround appeared to be in serviceable condition at the time of the inspection. 86) Toilet Conditions AS The toilet appeared to be in serviceable condition at the time of the inspection. Page 33 of 42

11 Basement Walls - Ceilings - Floors 11 Basement 87) Basement Stair Conditions AS The interior stairs appeared serviceable at the time of the inspection. 88) Wall Conditions R Unfinished basement. Some frame walls are not secured at the top plate. 89) Ceiling Conditions AS Unfinished basement. Open trusses. 90) Floor Conditions AS Unfinished basement. Cement floor. Windows - Doors 91) Basement Window Conditions AS Plastic sheeting on basement walls also covering windows so inspector could not operate windows to determine if they are operable. 92) Basement Door Conditions AS Unfinished basement. No basement doors in place. Electrical Conditions 93) Electrical Conditions S Receptacle in the area of the furnace is not properly secured to a stud. Page 34 of 42

11 Basement 94) Lighting Conditions AS Adequate. 95) Sump Pump Conditions R Basement is below grade. No sump pump pit found in basement. Page 35 of 42

12 Garage - Laundry Walls - Ceilings - Floors 12 Garage - Laundry Garage Type The garage is attached to the house. 96) Wall Conditions S Front wall in garage has open mortar joint showing daylight to the outside. Needs to be sealed to prevent moisture, insect, rodent intrusion. Open studs. On walls where there is drywall, it needs to be fire-taped. 97) Ceiling Conditions S Open trusses. When garage is finished with 5/8" drywall, it will need to be fire-taped. 98) Floor Conditions S The raised "breezeway" floor trusses are not supported with top flange hangers. The support under the outside joist needs at least 3 inches of bearing under it (double 2x4). Page 36 of 42

12 Garage - Laundry 99) Window Conditions AS n/a 100) Door Conditions R Garage side man door needs to be adjusted because it is hitting the jamb towards the top. The door jamb is also cracked under the strike plate. Recommend repairs as needed. 101) Vehicle Door Conditions AS The vehicle doors appeared to be in serviceable condition at the time of the inspection. 102) Electrical Conditions S Extension cord plugged into back deck outlet runs through rear "breezeway" window to power garage door opener. Page 37 of 42

12 Garage - Laundry 103) Lighting Conditions AS No lights in garage. Laundry Room Location The laundry facilities are located in the basement. 104) Laundry Room Conditions AS The visible and accessible portions of the laundry plumbing components appeared to be in serviceable condition at the time of inspection. Page 38 of 42

13 Foundation - Crawl Space Foundation 13 Foundation - Crawl Space Foundation Type Foundation Material Basement Concrete 105) Foundation Conditions AS Walls are furred out and insulation in place. The inspector was unable to fully inspect the foundation walls. Page 39 of 42

Section Condition # Comment 2 Repair 3 Safety Major cracks in driveway. Cracks need to be sealed to prevent water intrusion and further deterioration. The surface of the front walk where it meets the driveway is raised or settled. This may cause tripping hazards. This should be repaired for safety. Any rise less than four inches is considered a trip step. The cracks in the sidewalk should be sealed or caulked to prevent water intrusion and further deterioration. 6 Repair 7 Repair 8 Repair 9 Repair The front deck does not appear to have flashing behind it which can cause water intrusion and rotting behind the ledger board and siding. The deck is not properly secured to the home with lag bolts. Recommend repairs as needed. The back deck is not properly secured to the home with lag bolts. The deck has a lot of deflection. There should be a mid-span support under the girder. Recommend repairs as needed. There are several siding joint splices that don't fully cover the siding joint which can allow moisture and insect intrusion. There are some areas of chipped paint exposing bare wood which can lead to moisture damage. There are several locations where there is mortar missing beside the stone veneer which can lead to moisture damage to the exterior sheathing. Recommend repairs as needed. On soffit in front, there is J-Channel missing exposing an open joint which can lead to insect, bat, rodent intrusion. On side man door going into the front garage is a gap that needs to be sealed. Also there is a big gap around the man door going into garage that needs to be caulked. On all exterior outside corners the corner boards are separating and curling away from the home. These need to be resecured and pulled together and joints caulked to prevent insect and moisture intrusion. 10 Repair 11 Repair On front right side of overhead garage door, the stone cap needs to be sealed to prevent water intrusion (and in the winter the water freezing and resulting in popping loose of stones.) Archway over left side overhead garage door has exposed OSB sheathing. This needs to be covered. On right overhead garage door the head piece of brick mold is missing aluminum wrap. On left side on back deck under decorative barn board is a large gap in the soffit that needs to be sealed. On back deck, on right hand upper corner there is a large gap that needs to be sealed to prevent insect, bat, rodent, etc., intrusion.

12 Repair 13 Repair 15 Repair 16 Safety 18 Repair 19 Repair The two egress basement windows on east side of home are missing escape ladders. The screens are torn on the basement windows on east and north side of home. Recommend repairs as needed. Weather stripping is damaged on the back man door to garage. Recommend repairs as needed. Sliding door on rear deck is missing a locking lever and catch assembly so door cannot be latched or locked. On man door going from house to garage "breezeway" there are no self-closing hinges. On sliding glass door at rear deck, the screen is totally missing. At back deck sliding glass door, the light fixture is missing which results in an open junction box with a wire not properly placed in conduit. The ridge cap/vent on east rear side of roof has nails that are too short, not able to penetrate through roof sheathing. On west side gable under gable overhang, there are gaps in the roofing material where rain/snow can run underneath the roof shingle causing moisture damage. On east side gable under gable overhang, there is a gap in the roofing material where rain/snow can run underneath roof shingle causing moisture damage. There is no step flashing, just a common flashing on the gable ends. Step flashing is the proper flashing method. There is no kick out flashing on west side which will allow water to run behind the siding and rot the back of the siding and sheathing of home. It is suggested that a "Licensed Roofing Contractor" be contacted for further evaluation and repair. 20 Repair 31 Repair 40 Repair 41 Repair 43 Repair The gutter on the rear (north) side of home is bent and gutter hanger is damaged. Recommend repairs as needed. The garage is being wired with 14 gage wire for receptacles which will allow for a 15 amp circuit (which is not recommended for receptacle circuit.) 12 gage wire and 20 amp circuits are recommended. The bi-fold door track hardware in the two smaller bedrooms is damaged/bent. Eventually they will pop out of the track.) Recommend repairs as needed. Window not operable. Crank missing from Master Bedroom casement window on east wall. The electrical switches in living room and front entry door are 3-way switches which inspector could not find what they operated. Client will have to discuss with current owner. Receptacle (below light switch) in southeast bedroom is loose. Light switch at man door going to "breezeway/garage" off of kitchen has a light switch that inspector could not determine what it operated.

53 Repair Can light above kitchen sink not operable. repairs as needed. 62 Repair Refrigerator is missing bottom cover. 72 Repair Sink stopper not hooked up. 88 Repair 93 Safety 95 Repair 96 Safety 97 Safety Unfinished basement. the top plate. Recommend Some frame walls are not secured at Receptacle in the area of the furnace is not properly secured to a stud. Basement is below grade. basement. No sump pump pit found in Front wall in garage has open mortar joint showing daylight to the outside. Needs to be sealed to prevent moisture, insect, rodent intrusion. Open studs. Safety - On walls where there is drywall, it needs to be fire-taped. Open trusses. Safety - When garage is finished with 5/8" drywall, it will need to be fire-taped. 98 Safety 100 Repair 102 Safety The raised "breezeway" floor trusses are not supported with top flange hangers. The support under the outside joist needs at least 3 inches of bearing under it (double 2x4). Garage side man door needs to be adjusted because it is hitting the jamb towards the top. The door jamb is also cracked under the strike plate. Recommend repairs as needed. Extension cord plugged into back deck outlet runs through rear "breezeway" window to power garage door opener.