Moisture Sorption of Building Materials

Similar documents
Moisture Sorption of Building Materials

Tapered Insulation Systems

The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing

PIMA PERFORMANCE BULLETIN Foil-Faced Polyiso and Mineral Wool Board in Wall Applications

PIMA PERFORMANCE BULLETIN Foil-Faced Polyiso and Unfaced Mineral Wool Board in Commercial Wall Applications

An Introduction to Spray Foam Insulation

Incorporating Insulating Sheathing into the Design of the Thermal and Moisture Management System of the Building Enclosure

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Thermasheath-XP. Insulation for Exposed Use

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

PIMA PERFORMANCE BULLETIN Polyiso and Unfaced Mineral Wool Board Insulation in Commercial Roof Applications

ACFoam-II HCFC Free "Green" Polyiso Specification

BELOW GRADE ASSEMBLIES AND RIGID INSULATION

COMMERCIAL BUILDING APPLICATIONS

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Impact of NFPA 285 on Air Barrier Specification and Design

Figures 1A-1C Light frame and mass wall systems with continuous insulation for codecompliant. commercial building construction.

TSX Insulation for Exposed Use ROOF WALL SPECIALTY

GAF EnergyGuard Polyiso Wall Sheathing

Firestone Polyiso Boards

Graphite Polystyrene (GPS) Rigid Insulation. High Performance Thermal Innovation

Graphite Polystyrene (GPS) Rigid Insulation. High Performance Thermal Innovation

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

A. Thermal Conductivity: Thicknesses indicated are for thermal conductivity (k-value at 75 degrees F) specified for each material.

ACFoam -III Specifications Atlas Roofing

Managing Condensation and Thermal Performance with Continuous Insulation

SECTION STRUCTURAL INSULATED PANELS

INSTALLATION GUIDE EPS FOAM

EPA Seal and Insulate with ENERGY STAR Insulation Product Certification Report: GAF EnergyGuard Polyiso Insulated Sheathing Board Insulation

Technical Data Sheet

Moisture Considerations for Insulated Building Assemblies

ProGUARD Guide Specification

TSX Insulation for Exposed Use ROOF WALL SPECIALTY

Insulating Exterior Assemblies : Batt, Blown / Spray, Board and Beyond

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide.

THE PERFECT WALL IN COLD CLIMATES:

2013 COMMERCIAL PRODUCTS

United States R E S I D E N T I A L. The Value of Residing With STYROFOAM Brand XPS Insulation

ACFoam Supreme Specifications Atlas Roofing

Armourwall Stucco Systems

O82018 Hunter Panels XCI Foil

ACFoam CrossVent RB Specifications Atlas Roofing

SOPRA-ISO V ALU AND SOPRA-ISO V PLUS

SECTION SPRAY FOAM INSULATION

Use of Coatings to Improve Fire Resistance of Wood

The Construction Specifier April 2015 Selecting Polystyrene Foam Where Moisture Exposure Occurs

Differences between EnCon Insulated Precast and EIFS

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

BSC Information Sheet 500 Building Materials Property Table for All Climates

EXPLORE GEOMETRY AND SPACE

Guide Specification for the OSI QUAD Window and Door Flashing System

(Project Location) (your firm's name)

SECTION THERMAL INSULATION

Foamed-in-place insulation Sprayed insulation. Spray Foam Insulation for Residential Building Envelope Insulation

Effective Envelope Design Mitigating Risk with High Performance Panels and Acrylic Flashing Systems

/ TABLE OF CONTENTS /

Lamit Industries, Inc. 710 Marion Road Columbus, Ohio P-(614) F-(614)

SECTION THERMAL INSULATION

Thermal Control Layers: Insulation Materials and Systems

SECTION ROOF AND DECK INSULATION

Building Enclosure Design Fundamentals, Components, and Assemblies

ROOFING INSTALLATION GUIDELINES

SECTION FOIL FACED POLYISOCYANURATE FOAM BOARD INSULATION. A. Rigid polyisocyanurate foam board insulation with aluminum facers.

JOHNS MANVILLE CONTINUOUS INSULATION WALL SYSTEM MASTER SPECIFICATION June 2014 CSI FORMAT SECTION FOIL-FACED RIGID INSULATION

Innovating Continuous Exterior Insulation. Theresa A. Weston, PhD. 1

Smart Vapor Retarders

SOPRA-ISO V ALU AND SOPRA-ISO V PLUS

GA APPLICATION OF GYPSUM SHEATHING

SECTION Blown Insulation THERMAL INSULATION

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board

16 CFR-Part Test procedures for critical radiant flux (loose-fill cellulose)

Short Form Guide Specification. Specifying Extruded Polystyrene Roof Insulation- STYROFOAM DECKMATE Plus Tapered

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

2

Attic Insulation. Student Guide

ROCKWOOL Board Insulation Section Master Guide Specification Page 1 Jan 2017

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

The Role of Control Layers in Building Enclosure Design

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

ATLAS ROOFING PRODUCT GUIDE. Polyiso Roof Insulation, SPECIALTY PRODUCTS

Concrete Faced Insulated Perimeter Wall Panels. Durability. Sustainability. Energy Efficiency. Durable Finish & Superior Insulation in One Easy Step

SECTION PREPARATION FOR RE-ROOFING

Compliance for Continuous Insulation, Water Resistive Barriers & NFPA-285 What you need to Know

Subject: NRCA MRCA Joint Technical Bulletin. Date: January 2008 NOT COMPROMISE.

C. Applicable building codes should always be checked prior to proposing the application to Mule-Hide or the building owner.

Henry NFPA 285 Air Barrier Assemblies

New Opportunities For Spray Polyurethane Foam

R-Matte Plus-3: Insulation for the Building Envelope

Where to Draw the Line with Thermal Boundaries

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

1/2 in. (12.7 mm) and 5/8 in. (15.9 mm) glass mesh. It has an exceptionally hard, durable surface that can withstand prolonged exposure to moisture.

Rigid. Foam By Michael Maines. Get the Right XPS EPS. Polyisocyanurate. extruded. expanded polystyrene. $0.42 to $0.96 per bd. ft.

Subject Index. C Capillarity, 13 Capillary effects, on wood drying, 121,146 Capillary pressure, effect on moisture saturation,

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

FOAMULAR Commercial Roofing

SECTION SPRAY FOAM INSULATION

in the industry that highly permeable membranes are superior to less-permeable alternatives. This is not always the case.

Understanding Energy Codes

Transcription:

PIMA Technical Bulletin #404 Moisture Sorption of Building Materials About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70% of commercial roof construction, in commercial sidewall construction and in residential construction. The Benefits of using Polyiso include: Moisture resistance Low environmental impact Virtually no global warming potential Zero ozone depletion potential Cost effective, optimized energy performance Long service life Recyclable through reuse Recycled content (amount varies by product) Regional materials (nationwide production network) Meets new continuous insulation (ci) standards High R-value per inch of thickness Thinner walls and roofs with shorter fasteners Excellent fire test performance Extensive building code approvals Preferred insurance ratings Compatible with most wall systems Dimensional stability Compressive strength PIMA and polyiso products have received many environmental awards. These include an honorable mention in the Sustainable Buildings Industry Council s (SBIC) - Best Practice Sustainability Awards Program and the U.S. EPA s Climate Protection Award for the association s leadership in promoting energy efficiency and climate protection. The EPA also awarded PIMA and its members the Stratospheric Ozone Protection Award for leadership in CFC phase-out in polyiso insulation and in recognition of exceptional contributions to global environmental protection. Introduction This Technical Bulletin is a primer on the moisture sorption characteristics of building materials, like polyisocyanurate insulation (polyiso). When applied according to intended use in code-compliant wall and roof assemblies, polyisocyanurate insulation products manufactured in accordance with ASTM C1289 1 have demonstrated successful moisture durability performance and low moisture absorption while also providing a high level of thermal performance. The response of building materials to moisture is an important factor when considering the appropriate use of common building materials as wide ranging as wood, steel, concrete, various types of insulation, gypsum, and other natural or synthetic building products. The appropriate use of a building material depends on a variety of factors including its intended function, the actual moisture exposure in end use, and the consequence of a given level of moisture exposure. Ultimately, moisture presents a building risk that must be properly managed through intelligent design, building code compliance, and effective building maintenance. Let s explore why What is Moisture Sorption? Moisture sorption is actually a fairly complex process. But for practical purposes, there are essentially two ways that materials take-up and release moisture (see Figure 1). Perhaps the most familiar process is absorption. In this process, bulk (liquid) water is taken directly into the pores of the material and is similarly released as liquid water. For example, a sponge or paper towel absorbs liquid water which can be easily expelled again as liquid water by squeezing or drainage by gravity. However, the water that still remains is more strongly held in the material by a process that is a bit more complex and difficult to observe. This process is hygroscopic in that it deals with a process by which water molecules are attracted to and adhered to the internal pore surfaces of a material. Water intake in this manner is known as adsorption and its removal by this process as desorption. This hygroscopic form of moisture sorption can change the moisture content of a material simply based on changes in the relative humidity (water vapor content) of the surrounding air without any direct contact with liquid moisture. 1 ASTM C1289-07, Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board, ASTM International, West Conshohocken, PA.

The following relevant definitions are found in ASTM C209 2 : 3.3.4 sorption a general term in physical chemistry used to describe the combined processes of: absorption refers to the taking up of matter in bulk by other matter, for example, the penetration of substances into the bulk of another solid or liquid adsorption refers to surface retention or adhesion of an extremely thin layer of molecules to the surfaces of solids or liquids with which they are in contact. Figure 1. Illustration of two ways moisture interacts with materials to affect moisture content. Did you know?...apples are not Oranges. Moisture content is measured in two different ways. For insulation product standards, moisture content is commonly reported on the basis of the volume of the water measured within a standard size (volume) specimen. This is known as a volumetric water content. In other cases and for other materials, water content may be reported as the weight of water divided by the oven-dry weight of a standard size specimen. This is known as a dry weight (mass) based water content. While both measure the same thing, the magnitude of reported moisture content is very different and can be confusing. Be sure that moisture content measurements are reported on a common basis to avoid making an apples-to-oranges comparison. Moisture contents (MC) can be converted from one basis to another as follows: MC (% volume basis) = MC (%volume weight basis) x (Density of Material / Density of Water or 62.4 lbs/ft 3 ) 2 ASTM C209-07a, Standard Test Methods for Cellulosic Fiber Insulating Board, ASTM International, West Conshohocken, PA. 11/11 TB #404 2

Comparative Performance of Various Building Materials Building materials exhibit a wide range of moisture sorption characteristics. These characteristics are measured in two different ranges corresponding with the two types of moisture intake discussed in the previous section. The first form of moisture sorption is absorption of water in the liquid form. Various standard test methods are available to provide an index of the moisture absorption characteristics of a material. The primary purpose of such test methods is to evaluate material properties by measurements taken under standardized and repeatable laboratory conditions. These measurements are then used to ensure that minimum material properties are achieved so that acceptable performance is maintained for a specific product s intended use. Table 1 below provides a few examples of standard moisture absorption test methods and maximum moisture content criteria for the standardization and qualification of some common insulation materials. Where identical test methods are not used (e.g., ASTM C272 3 vs. ASTM C 209), comparison of results or criteria is inappropriate. Even when identical test methods are used, extrapolation of results to draw conclusions on actual end use performance for the purpose of comparison is equally inappropriate from a practical standpoint. These standardized or index test methods are not intended to replicate actual end use conditions. In fact, the primary exposure of many building materials to moisture is through the adsorption/desorption process, not the absorption process resulting from liquid water exposure (which usually has much more significant consequences than any potential singular impact to insulation performance). Most building materials are not intended for exposure to liquid moisture or even uncontrolled levels of moisture vapor. It is for this reason that wall and roof coverings, water-resistive barriers, and vapor retarders are required for code compliance and must be properly designed, located, and detailed in accordance with the applicable building code. Table 1: Standard Test Methods and Criteria for Moisture Absorption Resistance Characterization of Various Insulation Board Materials Insulation Material Type Maximum Moisture Content (% volume basis) ASTM C272 3 ASTM C 209 (24 hr water immersion test) (2 hr water immersion test) XPS (ASTM C578 4 ) 0.3% n/a EPS (ASTM C578) 2 to 4% n/a Polyiso (ASTM C1289) n/a 1-2%1 Fiberboard (ASTM C208) n/a 7-10% Table Note: 1.Values as low as 0.3% are achievable with foil-faced polyiso, even when evaluated using test methods like ASTM D2824 which calls for 96 hours of water immersion. The second process of a material s interaction with moisture is hygroscopic which, as mentioned, deals with the fixation of water molecules on the internal pore surfaces of materials. Adsorption is the intake of water in the hygroscopic range and desorption is the release of moisture in the hygroscopic range. This process is shown in hygroscopic adsorption isotherms of Figure 2 for a variety of building materials. Hygroscopic sorption isotherms are measured in accordance with ASTM C1498 5. A hygroscopic moisture isotherm is a plotted curve representing the equilibrium 3 ASTM C272, Standard Test Method for Water Absorption of Core Materials for Structural Sandwich Constructions, ASTM International, West Conshohocken, PA. 4 ASTM C 578-08, Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation, ASTM International, West Conshohocken, PA. 5 ASTM C 1498-04a, Standard Test Method for Hygroscopic Sorption Isotherms of Building Materials, ASTM International, West Conshohocken, PA. 11/11 TB #404 3

moisture content of a material (vertical axis of chart) at a given relative humidity of the surrounding air (horizontal axis of chart). These isotherms differ for moisture in-take (adsorption) and release (desorption) for any given material (see Figure 1). The sorption isotherms explain a material s response (wetting or drying) to changes in relative humidity of the surrounding environment. Roofing Materials (MC dry weight basis) 6 Key: 1 Fiberboard 2 Perlite Board 3 Exterior-Grade Plywood Polyisocyanurate Board: 4 Insulation (Core) 5 Matt-Glass Facer Glass-Fiber Board 6 Insulation (Core) 7 - Facer 30 Moisture Content (%, dry weight basis) 20 10 a b c d e f Spruce (wood) Plywood or Cellulose Insulation Fiberboard Stucco Polyisocyanurate (core) Red Clay Brick a b c d e f 10 20 30 40 50 60 70 80 90 100 Relative Humidity (%) Various Building Materials 7 Figure 2. Example of hygroscopic adsorption isotherms for common building materials. 11/11 TB #404 4

Understanding the data In Chart (1) of Figure 2 above, it is observed that polyiso insulation (material #4) is a moderately sorptive or hydrophilic material in comparison to the other common building materials. It is also interesting that at the 100% relative humidity exposure level, the moisture content (dry weight basis) maximized at 0.06 (or 6%). Using the conversion to a volumetric moisture content basis, the value is 0.06 x (2.1/62.4) = 0.002 or 0.2% moisture content. This is a relatively small amount of moisture intake under severe relative humidity conditions. It is about 1/10th the amount of moisture intake permissible under standardized water immersion testing addressed next. According to the scientific literature*, this amount of moisture intake under sustained severe humidity conditions has at most a ~10% impact on thermal performance. Source*: Tobiasson, W., Greatorex, A., and Van Pelt, D. (1991), New Wetting Curves for Common Roof Insulations, 1991 International Symposium on Roofing Technology (refer to Figure 9, p388 of proceedings) Relevance to Roof and Wall System Performance It is clear from the data presented in the previous section that different materials, including insulation products, have a wide range of moisture sorption characteristics. Even so, it is equally clear that acceptable performance can tolerate a fairly broad range of material moisture response characteristics when the materials are used in a code-compliant manner. Materials intended for or capable of long term performance under direct exposure to liquid moisture are those that are best suited to applications outside of a building s weather-resistive envelope, such as exterior below grade foundation insulation or protective membrane roof insulation where insulation is placed above the roof membrane and, therefore, is subject to frequent wetting. Polyiso insulation and many other materials are not intended for this type of wet service end-use condition. Such materials must be used within a building s weather-resistive envelope which means to the inside of the water resistive barrier on walls and underneath the roofing material(s), including underlayment if required. Consequently, some polyiso insulation board products come with an appropriate water-resistive facer to provide the necessary insulation and water-resistive barrier functions to exterior walls. In general, it is desirable to design and maintain buildings such that even moderately moisture sensitive materials remain reasonably dry. For this reason, untreated wood and uncoated steel structural materials, most insulation materials, and many other types of building materials must be protected from excessive liquid moisture exposure by use of code-compliant and functionally maintained roofing system and exterior wall coverings (including a water-resistive barrier) with flashing of wall and roof penetrations such as windows, doors and vents. In addition, moisture vapor must be controlled by code-compliant application of ventilation and/or vapor retarders in accordance with local climatic conditions as well as any special interior moisture loads. Whether due to a lack of code compliance or inadequate maintenance, a wet building does not just affect non-structural or serviceability concerns, such as indoor air-quality or insulation performance. It can also cause structural materials to degrade resulting in safety problems and eventual collapse if not detected. In short, a relatively dry building is a healthy and durable building and most building materials are meant to perform in reasonably dry, code-compliant and properly maintained buildings. Summary and Conclusions Moisture sorption involves two processes: absorption and adsorption. Both processes can cause materials to change moisture content depending on end-use conditions. In comparison to many other common building components and materials, polyisocyanurate insulation material is only moderately sensitive to moisture. When manufactured in accordance with ASTM C1289 and used in code-compliant wall and roof assemblies that are functionally maintained, polyisocyanurate board insulation products have demonstrated successful moisture durability performance and exceptionally high thermal performance. It is meant for use in building walls and roofs together 11/11 TB #404 5

with code-compliant roofing and wall covering systems. Finally, with use of appropriate waterresistive facers and installation details, polyisocyanurate board insulation products can effectively serve a dual role as the continuous insulation layer and the water resistive barrier in codecompliant exterior wall assemblies. Best Practice Recommendations for Polyisocyanurate Board Insulation a,b The following recognized properties of polyisocyanurate foam board roof insulation make it an effective insulation material: Bitumen and adhesive compatibility Component compatibility Impact resistance Durability Moisture resistance Thermal resistance Attachment capability a Roofing and Waterproofing Manual, 5th Edition (2006 Update), National Roofing Contractors Association (refer to Section 2.5.1) b Proper storage of materials, such as polyisocyanurate insulation, and protection from weather and ground moisture when stored outside is recommended. This concern is common to many common materials such as wood sheathing, lumber, gypsum sheathing, and others. For more information refer to PIMA TECHNICAL BULLETIN #109 PIMA For over 20 years, PIMA (Polyisocyanurate Insulation Manufacturers Association) has served as the unified voice of the rigid polyiso industry proactively advocating for safe, cost-effective, sustainable and energy efficient construction. PIMA produces technical bulletins in an effort to address frequently asked questions about polyiso insulation. PIMA s technical bulletins are published to help expand the knowledge of specifiers and contractors and to build consensus on the performance characteristics of polyiso. Individual companies should be consulted for specifics about their respective products. PIMA s membership consists of manufacturers and marketers of polyiso insulation and suppliers to the industry. Our members account for a majority of all of the polyiso produced in North America. SAFETY Polyiso insulation, like wood and other organic building materials, is combustible. Therefore, it should not be exposed to an ignition source of sufficient heat and intensity (e.g., flames, fire, sparks, etc.) during transit, storage or product application. Consult the product label and/or the PIMA members Material Safety Data Sheets (MSDS) for specific safety instructions. In the United States, follow all regulations from OSHA, NFPA and local fire authorities; in Canada, follow all regulations from Health Canada Occupational Health and Safety Act (WMHIS) and local fire authorities. For more information on polyisocyanurate insulation, visit www.polyiso.org PIMA 7315 Wisconsin Avenue, Suite 400E, Bethesda, Maryland 20814 Phone: 301.654.0000 Fax: 301.951.8401 www.polyiso.org pima@pima.org 11/11 TB #404 6