SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

Similar documents
MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 07 THERMAL AND MOISTURE PROTECTION

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 07 Thermal and Moisture Protection 8400 Firestopping

SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

NEW CONSTRUCTION (digital copy available Firestop Solutions Inc.) FIRESTOPPING SPECIFICATION SECTION FIRESTOPPING

OUTLET PUTTY PADS SPECIFICATIONS

FIRESTOPPING & SMOKE SEALS

SECTION PENETRATION FIRESTOPPING PART 1- GENERAL PART 2- PRODUCTS 1.1 RELATED DOCUMENTS

SECTION FIRESTOP SYSTEMS

SECTION FIRESTOPPING

St. Monica Food Pantry

SECTION FIRE RESISTIVE JOINT SYSTEMS Display hidden notes to specifier. (Don't know how? Click Here)

1. Division 15 Sections specifying duct and piping penetrations. 2. Division 16 Sections specifying cable and conduit penetrations.

SECTION FIRE RESISTIVE JOINT SYSTEMS

Construction Standards PAGE

THERMAL INSULATION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

A. Source Limitations: Obtain each type of building insulation through one source.

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012

SECTION (07100) - DAMPPROOFING AND WATERPROOFING

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

Note to Specifier: Use this product for coated glass-mat faced polyisocyanurate insulation boards such as Rboard.

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

A. Section includes Sprayed Fire-Resistive Materials: (SFRM) A. Pre-Installation Conference: Conduct conference at Project Site.

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

SECTION MULTICOLOR INTERIOR FINISHING

SUNY GENESEO RED JACKET DINING HALL RENOVATION SECTION JOINT SEALANTS

SECTION DAMPPROOFING AND WATERPROOFING

ACOUSTICAL WALL TREATMENT SECTION 09840

SECTION JOINT SEALERS 1.03 THIS SECTION INCLUDES JOINT SEALERS FOR THE FOLLOWING LOCATIONS:

SECTION THROUGH-PENETRATION FIRE STOP SYSTEMS

SECTION INTUMESCENT MASTIC FIREPROOFING

SECTION ACOUSTICAL PANEL CEILINGS

SECTION JOINT SEALANTS PART 1 - GENERAL 1.01 RELATED DOCUMENTS

CR# Issued Date: June 14, 2016 Waterville, OH

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS

Life Hall Renovation Issued: July 9, 2014 Montclair State University Addendum No. 1 Owner's Project No Cannon Design Project No

ROOF REPLACEMENT AND ALTERATIONS TO WOODSTOCK Barrett Architecture, PC WASTE WATER TREATMENT FACILITY - Woodstock, VT February 28, 2019 SECTION

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

Protecting Penetrations in Fire Rated Construction

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

SECTION MECHANICAL INSULATION

Normal, Medium And High Density Fireproofing Materials

SECTION GYPSUM BOARD

BuildingName The Description of the Project P DOCUMENTS

SECTION SOUND-ABSORPTIVE PANELS

SECTION (07810) - APPLIED FIREPROOFING

SECTION INSULATED CONCRETE FORMS - RASTRA 1.01 SUMMARY

Common Firestop Issues in Wood Framed Commercial Construction

FCIA Barrier Management Series. Barrier Management Policies

SECTION RESILIENT SHEET FLOORING

B. Refer to Section : Air Distribution for lined ductwork requirements.

FCIA Education Standards L - Ratings ASTM Movement Standard DRAFT. Eric Keeton, Tracy Smith, Luke Woods. May 2, 2013

SECTION SELF-ADHERING SHEET FLASHING

RECOMMENDED DESIGN SPECIFICATION

SECTION BUILDING INSULATION. Display hidden notes to specifier. (Don't know how? Click Here)

Barrier Management. FCIA Barrier Management Series Barrier Management Policies

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

DiSorb Diffuser Product Specifications Section Sound Diffuser-Absorber for Ceilings and Walls (DiSorb Diffuser-Absorber)

SECTION INJECTED or CAVITY-FILL POLYURETHANE FOAM (IPF)

Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp.

DIVISION 6 SOLID SURFACE FABRICATIONS SECTION 06650

PROJECT NO August 19, 2014 SENATE CHAMBER MEZZANINE RENOVATION MISSOURI STATE CAPITOL BUILDING SECTION JOINT SEALANTS

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

ONE SCHOOL STREET SEPTEMBER 18, 2008 GOWANDA, NEW YORK ARCH PROJECT NO

SECTION PENETRATION FIRESTOPPING

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

Construction Standards PAGE

SECTION METAL WALL PANELS

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

THERMAL AND MOISTURE PROTECTION

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS

A. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board manufacturer's written instructions, whichever are more stringent.

Approval Standard. for. Approval of Firestop Contractors

ADDENDUM NUMBER TWO. for SWIM TEAM LOCKER ROOM RENOVATIONS REBID UNIVERSITY OF SOUTH CAROLINA COLUMBIA, SOUTH CAROLINA. DATE OF ISSUE: June 19, 2014

Approval Standard for Firestop Contractors

Expansion Joint Covers

SECTION FLUID-APPLIED WATERPROOFING

Architectural precast Concrete EARTH FRIENDLY BLOCK

SECTION FIBER REINFORCED CEMENTITIOUS PANEL CLADDING

University of New Hampshire Scholars' Repository

SECTION COLD-FORMED METAL TRUSSES

ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018

Bid Opportunity Pacific Avenue, Winnipeg, Manitoba Page 1..1 CGSB 51-GP-23M-[78] Thermal Insulation, Urethane, Spray in Place.

A. This Section includes steel cable trays and accessories.

SECTION SOUND-ABSORPTIVE PANELS

FIRE STATION 55 June 14, 2010

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Transcription:

BuildingName The Description of the Project P00000000 0000 DOCUMENTS Title Page Table of Contents Instruction to Bidders Form of Proposal Equal Opportunity Statement Form of Guarantee Supplemental General Conditions SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION 07841 - THROUGH-PENETRATION FIRESTOP SYSTEMS ARCHITECTURE, ENGINEERING AND CONSTRUCTION ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 END OF CONTENTS TABLE

DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION 07841 - THROUGH-PENETRATION FIRESTOP SYSTEMS THIS NEW SECTION REPLACES THE BRIEF DESCRIPTION OF FIRE- STOPPING WHICH WAS FORMERLY INCLUDED IN SECTION 07920 JOINT SEALANTS. INCLUDE THIS SECTION FOR ALL PROJECTS WHERE PIPING, DUCTWORK OR ELECTRICAL CONDUIT IS BEING MODIFIED OR INSTALLED OR WHERE IMPROPERLY INSTALLED CONCEALED OR EXPOSED PENETRATIONS ARE BEING REPAIRED. EXISTING CONDITIONS SHOULD BE SURVEYED AT THE BEGINNING OF A PROJECT, AND INADEQUACIES (I.E., UNPROTECTED OPENINGS IN WALLS AND FLOORS, IMPROPER PENETRATIONS, ETC.) SHOULD BE IDENTIFIED AND CORRECTED WHENEVER FUNDING CAN BE OBTAINED FOR THIS PURPOSE. 1.1 SUMMARY A. This Section includes through-penetration firestop systems for penetrations through fire-resistance-rated constructions, including both empty openings and openings containing penetrating items. ALWAYS INCLUDE THE FOLLOWING WHEN THERE ARE MECHANICAL AND ELECTRICAL PENETRATIONS. SLEEVES ARE RECOMMENDED FOR FLOOR PENETRATIONS TO PROTECT CONTENTS ON THE FLOOR BELOW THE PENETRATION FROM LEAKAGE OR FLOODING CAUSED BY PIPE BREAKS, SPRINKLER DISCHARGE, ETC. EVALUATE LEVEL OF PROTECTION DESIRED BY OWNER AND THE LIKELIHOOD OF WATER DAMAGE IN CONSULTATION WITH MECHANICAL ENGINEER. SLEEVES ARE TYPICALLY SHOWN ON MECHANICAL AND ELECTRICAL DRAWINGS SINCE THEY ARE USUALLY THE RESPONSIBILITY OF THE CONTRACTOR MAKING THE PENETRATION. ALTHOUGH THE SLEEVE ITSELF IS NOT PART OF THE FIRESTOP SYSTEM, IT MAY AFFECT WHICH FIRESTOPPING SYSTEM IS SELECTED, SINCE THE ENTIRE ASSEMBLY MUST BE TESTED AND NOT ALL SYSTEMS HAVE BEEN TESTED WITH SLEEVES. B. Related Sections include the following: 1. Division 15 Sections specifying duct and piping penetrations. 2. Division 16 Sections specifying cable and conduit penetrations. 1.2 REFERENCES A. ASTM E 84 Test Method for Surface Burning Characteristics of Building Materials. B. ASTM E 119 Test Method for Fire Test of Building Construction and Materials. C. ASTM E 814 Fire Tests of Through-Penetration Fire Stops. D. Firestop Contractors International Association (F.C.I.A.) Manual of Practice (M.O.P.). Error! Unknown document property name. 07841-1

1.3 PERFORMANCE REQUIREMENTS A. General: For penetrations through fire-resistance-rated constructions, including both empty openings and openings containing penetrating items, provide through-penetration firestop systems that are produced and installed to resist spread of fire according to requirements indicated, resist passage of smoke and other gases, and maintain original fire-resistance rating of construction penetrated. 1. For through-penetration firestop systems in non-rated walls, a fire-resistance rating shall not be required. B. Rated Systems: Provide through-penetration firestop systems with the following ratings determined per ASTM E 814: 1. F-Rated Systems: Provide through-penetration firestop systems with F-ratings indicated, but not less than that equaling or exceeding fire-resistance rating of constructions penetrated. AS A GENERAL RULE, T-RATED SYSTEMS ARE REQUIRED WHERE PENETRATING ITEMS PASS THROUGH OCCUPIABLE AREAS WHERE THEY MAY CONTACT COMBUSTIBLE MATERIALS. DELETE PARAGRAPHS BELOW IF T- RATED SYSTEMS ARE NOT REQUIRED. 2. T-Rated Systems: For the following conditions, provide through-penetration firestop systems with T-ratings indicated, as well as F-ratings, where systems protect penetrating items exposed to potential contact with adjacent materials in occupiable floor areas: a. Penetrations located outside wall cavities. b. Penetrations located outside fire-resistance-rated shaft enclosures. C. For through-penetration firestop systems exposed to view, traffic, moisture, and physical damage, provide products that, after curing, do not deteriorate when exposed to these conditions both during and after construction. THREE SUBPARAGRAPHS BELOW ARE EXAMPLES OF SPECIAL REQUIREMENTS. DELETE THOSE NOT APPLICABLE; INSERT OTHERS TO SUIT PROJECT. 1. For piping penetrations for plumbing and wet-pipe sprinkler systems, provide moisture-resistant through-penetration firestop systems. 2. For floor penetrations with annular spaces exceeding 4 inches (100 mm) in width and exposed to possible loading and traffic, provide firestop systems capable of supporting floor loads involved, either by installing floor plates or by other means. 3. For penetrations involving insulated piping, provide throughpenetration firestop systems not requiring removal of insulation. DELETE PARAGRAPH BELOW IF NOT APPLICABLE. VERIFY THAT THROUGH-PENETRATION FIRESTOP SYSTEMS SELECTED USE A FILL MATERIAL THAT COMPLIES WITH THE REQUIREMENT BELOW. Error! Unknown document property name. 07841-2

D. For through-penetration firestop systems exposed to view, provide products with flame-spread and smoke-developed indexes of less than 25 and 450, respectively, as determined per ASTM E 84. 1.4 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: For each through-penetration firestop system, submit documentation, including illustrations, from a qualified testing and inspecting agency, showing each type of construction condition penetrated, relationships to adjoining construction, and type of penetrating item. C. Product Test Reports: From a qualified testing agency indicating through-penetration firestop system complies with requirements, based on comprehensive testing of current products. 1.5 QUALITY ASSURANCE A. Fire-Test-Response Characteristics: Provide through-penetration firestop systems that comply with the following requirements and those specified in Part 1 "Performance Requirements" Article: 1. Firestopping tests shall be performed by Underwriters Laboratories (UL), Omega Point Laboratories or Intertek Warnock/Hersey. 2. Through-penetration firestop systems are identical to those tested per testing standard referenced in "Part 1 Performance Requirements" Article. Provide rated systems bearing testing agency's classification marking. B. Coordinate construction of openings and penetrating items to ensure that through-penetration firestop systems are installed according to specified requirements. 1.6 PROJECT CONDITIONS A. Environmental Limitations: Do not install through-penetration firestop systems when ambient or substrate temperatures are outside limits permitted by through-penetration firestop system manufacturers or when substrates are wet due to rain, frost, condensation, or other causes. B. Ventilate through-penetration firestop systems per manufacturer's written instructions by natural means or, where this is inadequate, forced-air circulation. 1.7 ENVIRONMENTAL REGULATIONS A. All materials shall be asbestos free. B. Disposal of hazardous firestop materials: Contact UM Occupational Safety and Environmental Health Hazardous Materials (734-763-4568) for instructions regarding disposal. Error! Unknown document property name. 07841-3

PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Products: Subject to compliance with requirements, provide products of one of the following manufacturers: 1. A/D Fire Protection Systems Inc. 2. Hilti, Inc. 3. Johns Manville. 4. Rectorseal Corporation 5. Specified Technologies Inc. (STI) 6. 3M; Fire Protection Products Division. 7. Tremco; Sealant/Weatherproofing Division. 8. USG Corporation. 2.2 FIRESTOPPING A. Compatibility: Provide through-penetration firestop systems that are compatible with one another; with the substrates forming openings; and with the items, if any, penetrating throughpenetration firestop systems, under conditions of service and application, as demonstrated by through-penetration firestop system manufacturer based on testing and field experience. B. Accessories: Provide components for each through-penetration firestop system that are needed to install fill materials and to comply with Part 1 "Performance Requirements" Article. Use only components specified by through-penetration firestop system manufacturer and approved by qualified testing and inspecting agency for firestop systems indicated. PART 3 - EXECUTION 3.1 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLATION A. Examination: Examine substrates and conditions for compliance with requirements for opening configurations, penetrating items, substrates, and other conditions affecting performance of firestopping. Notify the Owner's Representative in writing if unsatisfactory conditions are present. Do not proceed with installation until unsatisfactory conditions have been corrected. B. Use masking tape to prevent firestopping from contacting adjoining surfaces that will remain exposed upon completion of Work. Remove tape as soon as it is possible to do so without disturbing the firestopping seal with substrates. C. General: Install through-penetration firestop systems to comply with Part 1 "Performance Requirements" Article and with firestop system manufacturer's written installation instructions and published drawings for products and applications indicated. D. Install forming/damming/backing materials and other accessories of types required to support fill materials during their application and in the position needed to produce cross-sectional shapes and depths required to achieve fire ratings indicated. Error! Unknown document property name. 07841-4

DELETE SUBPARAGRAPH BELOW IF NONE OF THE SYSTEMS SPECIFIED REQUIRES USING REMOVABLE FORMING MATERIALS AND OTHER ACCESSORIES. 1. After installing fill materials and allowing them to fully cure, remove combustible forming materials and other accessories not indicated as permanent components of firestop systems. E. Install fill materials for firestop systems by proven techniques to produce the following results: 1. Fill voids and cavities formed by openings, forming materials, accessories, and penetrating items as required to achieve fire-resistance ratings indicated. 2. Apply materials so they contact and adhere to substrates formed by openings and penetrating items. 3. For fill materials that will remain exposed after completing Work, finish to produce smooth, uniform surfaces that are flush with adjoining finishes. INCLUDE IDENTIFICATION REQUIREMENT BELOW FOR ALL BFS JURISDICTION BUILDINGS. CONSIDER FOR INCLUDING FOR NON-BFS BUILDINGS. 3.2 IDENTIFICATION A. Identify through-penetration firestop systems with preprinted metal or plastic labels. Attach labels permanently to surfaces adjacent to and within 6 inches of edge of the firestop systems so that labels will be visible to anyone seeking to remove penetrating items or firestop systems. Use mechanical fasteners for metal labels. For plastic labels, use self-adhering type with adhesives capable of permanently bonding labels to surfaces on which labels are placed and, in combination with label material, will result in partial destruction of label if removal is attempted. Include the following information on labels: 1. The words "Warning - Through-Penetration Firestop System - Do Not Disturb. Notify Building Management of Any Damage." 2. Contractor's name, address, and phone number. 3. Through-penetration firestop system designation of applicable testing and inspecting agency. 4. Date of installation. 5. Through-penetration firestop system manufacturer's name. 6. Installer's name. 3.3 CLEANING AND PROTECTION A. Clean off excess fill materials and sealants adjacent to opening and joints as Work progresses. Use methods approved by manufacturer of firestopping products. B. Protect firestopping during and after curing period from contact with contaminating substances. END OF SECTION 07841 Error! Unknown document property name. 07841-5