Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators

Similar documents
CONDITION ASSESSMENT OF A FIELD-AGED 150 kv HTV SIR SUSPENSION INSULATOR FOLLOWING FLASHOVER

Comparative study on field collected samples of aged silicon rubber composite coatings for high voltage insulators

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test

Insulators pollution problem: Experience from the coastal transmission system of Crete

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Mapping HV Insulators Pollution in the Mediterranean Island of Crete

Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case

Composite Insulator Components

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE

INSULATOR REQUERIMENTS:

Panagiotis Charalampidis

Electrical Field Simulation for Different Cases of Polymer Insulators Using FEM

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

R&D in TALOS High Voltage Test Station- Assessing aging and performance of polymer insulators

Composite Outdoor High Voltage Insulators in Crete - 37 Years of Experience

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Performance of Thermoplastic Elastomeric and Thermoset Insulators under Accelerated Acid Rain Multistress Conditions

Different Characteristics of Artificially Polluted High Voltage Composite Insulators

fire Charcoat Charcoat IC Passive Protection

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages:

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications

Development of Composite Line Spacers for Distribution Lines

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS

Experimental analysis of hydrophobic characteristics of Silicone rubber (SiR) insulators under different climatic conditions

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation

BEHAVIOUR OF NANO SIO 2 FILLED SILICONE RUBBER NANOCOMPOSITESS

The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

Effect of pollution severity and dry band location on the flashover characteristics of silicone rubber surfaces

Effect of pollution severity and dry band location on the flashover characteristics of silicone rubber surfaces

Evaluation of Actual Field Ageing on Room Temperature Vulcanized Silicone Rubber Coating of Ceramic Insulators on 230/63 Substation

Polluted Outdoor Insulators Maintenance and Washing

Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines

The Role of Inorganic Fillers in Silicone Rubber for Outdoor Insulation Alumina Tri-Hydrate or Silica

Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions

Effect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators

INVESTIGATION OF THE AGING CHARACTERISTICS OF CST TERMINATION MADE OF SILICONE RUBBER AT CONTAMINATION AREA

Outdoor High Voltage Non-Ceramic Insulators

Computation of power released during corona treatment on polymeric insulators under ac and dc excitation

Formation of hydrophobic coating on glass surface using atmospheric pressure non-thermal plasma in ambient air

ILMOS Insulator Leakage Current Monitor

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

Surface Analysis of Asymmetrically Aged 400 kv Silicone Rubber Composite Insulators. Y. Xiong; S. M. Rowland; J Robertson; R Day;

Evaluation of Silicone Rubber Insulators used in High-Voltage Transmission Lines Anwar Ul-Hamid, Khaled Y. Soufi, and Ibrahim AI-Hamoudi

Prediction of flashover voltage of non-ceramic insulators under contaminated conditions

Modification of Glass Surface by Atmospheric Pressure Plasma

Surface Degradation of Outdoor Polymeric Insulators Resulting from Electrical and Environmental Stress

Thermal Aging, Water Absorption, and Their Multiple Effects on Tracking Resistance of Epoxy for Outdoor Use

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN

Accreditation Scope by Certification Test Order

Electric field analysis of 132kV EPDM insulator and correlation with ageing features

COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and

Polymer Cutout Testing Recommendations

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1.

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator

C Pollution measurement based on DDG method for different type s of insulator profile

Pins Insulator. Composite/Polymers Insulators

ΔΡΑΣΗ ΕΘΝΙΚΗΣ ΕΜΒΕΛΕΙΑΣ "ΣΥΝΕΡΓΑΣΙΑ 2011"

Ozone and by-products generation characteristics by novel air-fed ozone generator which combines homogeneous discharge and filamentary discharge

Characterisation of Textured Insulators for Overhead Lines and Substations

Leakage Current and Carbon Track Analysis of LLDPE-Natural Rubber Blends Filled with Nano Silica

Comments on Document from Richard Martin, Canada

Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions

A-PDF PPT TO PDF DEMO: Purchase from to remove the watermark

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

TROPICAL CLIMATE EFFECT OF HYDROPHOBICITY AND SURFACE LEAKAGE CURRENT ON ELECTRICAL INSULATION MATERIALS (SILICONE RUBBER AND FLY ASH)

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

Luiz Meyer, Shesha Jayaram and University of Waterloo, 200 University Av. W. Waterloo, N2L 3G1, Ontario, Canada

PS2: Lifetime management, deterioration and ageing of substation equipment

Evaluation of Coating Materials. 2 Evaluation Items for Coating Materials. 3 Evaluation Test with 5 Coating Materials

Comparison of effects of Various Contaminations on SiR insulators


Liu et al.: Characterization of a Se erly Degraded Silicone Elastomer HV insulator-an Aid

Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions

Silicone rubber Product information

Asset Management Frameworks for Outdoor Composite Insulators

Available online at ScienceDirect. Study on Dissolved Gas Due Tue Thermally Degraded Insulating Paper in Transformer Oil

CHAPTER 1 INTRODUCTION

Overview of Silicone Elastomers, Gels & Auxiliary Materials for Cable Accessory Applications

INTERNATIONAL STANDARD

Diagnostic Techniques of Composite Insulators

NPS/003/001 Technical Specification for 33kV, 66kV and 132kV Voltage Transformers

Field-test at Betonstal Sp. z.o.o. Szczecin/ Poland

ΔΡΑΣΗ ΕΘΝΙΚΗΣ ΕΜΒΕΛΕΙΑΣ "ΣΥΝΕΡΓΑΣΙΑ 2011"

Introduction to Polymer-Dispersed Liquid Crystals

Industrial Coatings: HIGHLY DURABLE, SUPERHYDROPHOBIC AND OLEOPHOBIC. (White Paper) NeverWet LLC

Aliphatic amine cured PDMS epoxy interpenetrating network system for high performance engineering applications Development and characterization

Polymer Core Composite Conductor (PCCC) Research at the University of Denver

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators

Polymer Suspension Insulators 69kV to 765kV

Transcription:

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators N. Mavrikakis Faculty of Engineering Aristotle University of Thessaloniki nmavrika@auth.gr K. Siderakis Technological Educational Institute of Crete ksiderakis@staff.teicrete.gr P. N. Mikropoulos Faculty of Engineering Aristotle University of Thessaloniki pnm@eng.auth.gr Abstract- Evaluation of the field performance of composite insulators is essential for maintaining the desired levels of reliability in power networks. Field performance of composite insulators depends on many factors, including the insulator design, material quality and service conditions experienced. The most critical part of the composite insulator is its external housing, usually made of silicone rubber having the advantage of recovering its hydrophobic properties in polluted conditions. Thus, condition assessment of the hydrophobic properties of the housing material especially under erosion and tracking processes is of major importance. In this study performance evaluation of the housing material of 150 kv field-aged silicone rubber insulators is carried out through physical, electrical and material analysis techniques. The hydrophobic properties of the housing material were found degraded to a different extent between field-aged insulators due to differences in material structure and pollution conditions. Hydrophobicity can be better assessed if the relevant diagnostic techniques are also applied after inclined plane tests. Index Terms- Ageing, Composite, Erosion, Hydrophobicity, Insulator, Silicone rubber, Tracking I. INTRODUCTION Insulators are one of the most important components affecting reliability of high voltage power networks. Ceramic insulators, made of either porcelain or glass, are increasingly replaced by composite insulators, commonly made of silicone rubber, due to their superior performance in polluted conditions. However, this advantage comes together with a comparably weak structure, vulnerable in ageing mechanisms mostly related to partial discharge activity. Thus, evaluation of the field performance of composite insulators is essential for maintaining the desired levels of reliability in power networks. The field performance of composite insulators depends on many factors, including insulator design, material quality and service conditions experienced. In the present study results on performance evaluation of the housing material of field-aged silicone rubber (SIR) insulators are presented. Insulators were sampled from the 150 kv transmission network of Crete, which being exposed to sea influence suffers from severe pollution. Over 50% of the insulators in the 150 kv transmission network of Crete are SIR insulators, operating from 2 up to 20 years. Hydrophobicity classification and structural analysis of the housing material of the field-aged insulators were performed before and after inclined plane tests; the latter were conducted as specified by IEC 60587 [1] so as to evaluate the resistance against tracking and erosion. The hydrophobic properties of the housing material were found degraded to a different extent between field-aged insulators due to differences in material structure and pollution conditions. II. CONDITION ASSESSMENT PROCEDURE Condition assessment of the housing material of composite insulators is conducted by physical, electrical and material analysis techniques [2] - [6]. In this study, the following diagnostic procedure was adopted in order to evaluate the hydrophobic properties and the resistance against tracking and erosion of field-aged silicone rubber (SIR) insulators: i. Insulator sampling. ii. Visual inspection according to STRI [7] and EPRI [8] visual inspection guides. iii. Pollution measurements according to IEC 60815 [9], to classify insulator samples based on pollution severity. iv. Hydrophobicity assessment according to IEC 62073 [10]. v. Fourier Transform Infrared (FTIR) spectroscopy, providing information on material structural bonding. vi. Inclined plane test (IPT) according to IEC 60587 [1], to evaluate the tracking and erosion resistance of the housing material. vii. Hydrophobicity assessment and FTIR spectroscopy are conducted repeated after the IPT, so as to evaluate the hydrophobic properties of the SIR insulators as affected by accelerated ageing. Composite insulators aged in service were sampled from the 150 kv transmission network of Crete. Insulators A and B (Fig. 1) were removed after seventeen years in service without having experienced any failures. There was limited data concerning the chemical structure of the housing material of the insulator samples; however, FTIR spectroscopy showed silicone rubber and alumina trihydrate (ATH) fillers as structural compounds. Insulators A and B were operated at coastal overhead transmission lines, thus, exposed to severe environmental stress conditions, including high UV radiation and salt deposition. Fig. 1 shows the

observed for insulator A than B. Actually, according to the pollution severity classification for composite insulators suggested by IEC [9], the pollution levels for insulators A and B are heavy and medium, respectively (Fig. 2). The higher pollution levels of insulator A can be attributed to the fact that it was subjected to, besides marine, industrial pollution. TABLE I ESDD AND NSDD MEASUREMENTS OF FIELD INSULATORS Insulator A B Temperature, o C 17.7 16.8 Collecting pollutants area, cm 2 448.428 318.645 Salinity, kg/m 3 0.1096 0.0424 ESDD, mg/cm 2 0.0978 0.0532 NSDD, mg/cm 2 0.1668 0.0951 Fig.1: Meteorological data (1955-1997) for the region of installation of the line composite insulators. monthly variation in weather conditions for the city of Heraklion over the period of 1955-1997; these climatic data, obtained from the Hellenic National Meteorological Service [11], can be considered as typical for the region of installation of the evaluated line composite insulators. III. CONDITION ASSESSMENT RESULTS A. Visual inspection Increased levels of contamination were observed by visual inspection for both field aged insulators. Pollution was more notable in the insulator upper sheds, near to the suspension tower end. After cleaning the polymer housing, thin surface scratches and partial surface discolouration were detected especially for insulator A. In addition, local oxidation of metal end fittings was detected. These findings do not impose a need for immediate replacement of the field insulators according to STRI [7] and EPRI [8] guides. It must be noted, however, that, due to intense dust accumulation on the housing of the insulators, it was not possible to draw reliable conclusions on the degradation severity classification of each insulator sample. B. Pollution measurements Both insulators were operated at Crete s northern coastal line (Fig. 1), along which large amounts of sea salt are carried by strong onshore winds and deposited on equipment. Thus, to determine the amount and type of pollution deposition, equivalent salt deposit density (ESDD) and non soluble deposit density (NSDD) measurements were performed according to IEC 60815 [9]. These measurements were conducted by the Hellenic Electricity Distribution Network Operator immediately after insulator samples collection. As shown in Table I, higher ESDD and NSDD values were Insulator A Insulator B Fig. 2: Pollution severity classification of field composite insulators [9] C. Hydrophobicity measurements Hydrophobicity measurement of insulators was conducted in accordance to IEC 62073 [10], implementing methods C (spray method) and method A (contact angle method). Using the spray method, based on the appearance of the insulator surface after water mist exposure, wettability classes (WC) 6 and 2 were determined for insulators A and B respectively (Fig. 3). It must be noted that these results were obtained without removing surface pollutants prior to water spraying. Contact angle measurements were performed with the aid of the KSV-CAM 101 instrument [12]. Water droplets about 10 μl in volume were applied with a syringe on nine samples taken from different areas of the housing of each insulator (Fig. 4), the latter cleaned with distilled water. Average static contact angles of 84 and 103 degrees were measured for insulators A and B, respectively. Fig. 3: Insulators A (left) and B (right) after water mist exposure; middle area of insulators

0.9 0.8 0.7 C_new A_field-aged B_field-aged Si-O-Si stretching 0.6 Static contact angle: 95 o ; high voltage Static contact angle: 97 o ; ground area area of insulator A of insulator B 140 Insulator A Insulator B Absorbance 0.5 0.4 0.3 0.2 0.1 ATH C-H stretching in CH 3 Si-CH 3 symmetric deformation Contact Angle ( o ) 120 100 80 60 40 20 0 Top Bottom Sheath Top Bottom Sheath Top Bottom Sheath High voltage area Middle area Ground area Fig.4: Static contact angle variation along the housing of insulators A and B From the wettability classification and contact angle measurements (Figs. 3, 4) it is evident that the hydrophobic properties were certainly more degraded for insulator A than B. For insulator B the measured values of WC and contact angle, the latter similar to that of PDMS (~101 o ) [13], indicate that the hydrophobicity transfer mechanism was still functioning; this, however, must be confirmed through tests on hydrophobicity transfer property according to Cigre [14]. D. FTIR analysis Fourier Transform Infrared (FTIR) spectroscopy is a useful technique for identifying chemical bonds in a molecule by producing an infrared absorption spectrum. The infrared absorptions of the bonds containing silicon are quite strong. In general, the spectra of siloxanes are simple thus substituent molecular groups as methyl can be identified [15]. Characteristic absorption bands for chemical bonds of the housing material of SIR insulators are listed in Table II. FTIR spectrum of insulators was obtained by using the IRPrestige-21 Shimadzu measuring system [16]. Fig. 5 shows the FTIR spectra for the field-aged insulators; this figure also includes the FTIR spectrum of a new SIR insulator (insulator C) used as reference. Lower levels of absorbance for all TABLE II SIR ABSORPTION BANDS Bond Wavenumber (cm -1 ) Si-O 1100-1000 [17], [18] Si-CH 3 1240-1280[17] C-H in CH 3 2960-2962[17] ATH 3435, (3300-3650) [19] 0.0 4000 3500 3000 2500 2000 1500 1000 Wavenumber (cm -1 ) Fig. 5: FTIR spectra of field-aged and new SIR insulators chemical bonds are observed for insulator A than B; this indicates depolymerisation of insulator A top surface areas due to ageing [20]. On the other hand, there was no significant difference in the FTIR spectra between the fieldaged insulator B and new insulator C. It is important that the FTIR spectrum of insulator A shows reduced absorbance specifically for bonds that are related to the hydrophobic properties of PDMS, namely Si-CH 3 and C- H (Fig. 5). Actually, the ratios of integrated absorbance areas between certain bonds may indicate the hydrophobicity degradation level of the housing material [21]. Combining the hydrophobicity measurement results with those shown in Table III, it can be deduced that the higher the ratio of Si- O/Si-CH 3 the more degraded the hydrophobic properties of housing material are. Thus, the ratio of integrated absorbance areas of Si-O to Si-CH 3 can be indicative of the level of hydrophobicity degradation of SIR housing material; this must be substantiated by FTIR spectroscopy of a greater number of aged insulators. TABLE III INTEGRATED ABSORBANCE AREAS OF BONDS OF SIR INSULATORS Insulator Si-O Si-CH 3 Ratio C, new 59.19 3.76 15.74 A, field-aged 21.21 0.75 28.28 B, field-aged 68.39 3.11 21.99 IV. INCLINED PLANE TEST A. Experimental arrangement The inclined plane test (IPT) method, as specified in IEC 60587 [1], was used to assess the performance of the housing material of the field aged SIR insulators against tracking and erosion. A schematic diagram of the test arrangement is shown in Fig. 6. From each insulator five samples were formed by cutting the silicone rubber sheds in hemicyclic shape. The area of the samples where partial discharges were taken place during the IPT had a thickness of 4-5mm. The samples were washed with distilled water in order to clean their field polluted surfaces by using an ultrasonic cleaner for 15 minutes and then they were mounted carefully at an angle

5100 51 0 5 511 0 5115 5120 12 10 8 6 4 2 0 Leakage current - rms value (ma) 12 10 8 6 4 2 Insulator A Insulator B Fig. 6: Inclined plane test arrangement of 45 o from the horizontal. A contaminant solution, consisting of natrium chloride of 2.53 ms/cm conductivity at 23 o C and a small amount of non-ionic agent TRITON X-100, was fed from the top electrode with a constant flow rate of 0.6 ml/min. After establishing a uniform flow of contaminant over the surface of the test samples, by using eight layers of filter paper between the top electrodes and the samples, a test power frequency voltage of 4.5 kv (rms) was applied for 6 hours in the five samples simultaneously; leakage current never exceeded the value of 60 ma (rms) for 2 sec [1]. The electrodes were made of stainless steel grade 304. In addition a 33 kω, 300 W resistor with 5% tolerance was connected in series with each sample at the high voltage side. Leakage current was measured through Hall sensors connected in series with the ground electrodes (Fig. 6). Current waveforms were acquired, with a sampling rate of 2 ks/sec, using a data acquisition system PCI 6143 of National Instruments. Operation and control of the measurement system were accomplished using the LabView software. B. Experimental results Fig. 7 shows the variation of the leakage current (one second rms values) during 20 s of the IPT procedure for the field-aged SIR insulator samples. These leakage current values are typical for the accelerated ageing of the evaluated insulators since similar values were recorded until the end of the test. Continuous leakage current activity is observed for insulator A during the IPT, resulting from the establishment of a conductive path along the surface of the insulator. This is not the case for insulator B, continuous flow of leakage current is not observed; leakage current is interrupted several times during the IPT (Fig. 7). Thus, leakage current behavior during IPT could provide useful information on degradation severity of the housing material of aged insulators. Table IV shows the average and maximum one second rms values of the leakage current measured for all SIR insulator samples. These currents, being higher for the field-aged insulators than the new one, are highest for insulator A, which showed strongly degraded hydrophobic properties. Also, as can be deduced for Fig. 5 and Table IV, mass loss was lesser for insulators with higher quantity of ATH fillers. This could 0 5100 5105 5110 5115 5120 Time (seconds) Fig. 7: Leakage current (LC) measurements of field aged insulators during 20 seconds of the inclined test procedure TABLE IV INCLINED PLANE TEST RESULTS Insulator Leakage current Leakage current Average Mass Average RMS (ma) Maximum RMS (ma) Loss (mg) C, new 4.1 31.6 348 A, field-aged 8.2 45.6 52 B, field-aged 4.6 36.5 132 be associated with the increased heat conductivity due to higher amount of ATH fillers resulting in lesser mass loss [22]-[24]. To better assess the hydrophobic properties of the SIR insulators, static contact angle and FTIR measurements were performed for all insulator samples after the IPT procedure. A significant reduction in the contact angle, up to 50%, was observed for all specimens (Figs. 4 and 8). From the comparison of the FTIR spectra of the field-aged insulators obtained before and after the IPT procedure (Fig. 9) it is evident that there is a marked reduction in absorbance for all chemical bonds of housing material caused by the accelerated ageing. It is important that the latter affects also significantly the ratio of integrated absorbance areas between chemical bonds, as evinced in Table V. The hydrophobic properties of insulator B were not influenced by the accelerated ageing, as suggested by the rather constant ratio of Si-O/Si-CH 3 ; the main effect of accelerated ageing on this insulator was the marked reduction in the amount of ATH fillers. On the contrary, the relatively poor hydrophobic properties of insulator A were further degraded, as indicated by the ~ 40% increase in the ratio of Si-O/Si-CH 3. Static contact angle: 52 o ; high voltage Static contact angle: 74 o ; ground area area of insulator A of insulator B Fig. 8: Static contact angle measurements after the IPT

TABLE V RATIOS OF INTEGRATED ABSORBANCE AREAS OF BONDS OF SIR INSULATORS Insulator Si-O/ATH Si-O/Si-CH 3 A-field aged 1.30 28.28 A-field/Lab. aged 1.46 40.57 B-field aged 5.31 21.99 B-field/Lab. aged 15.43 22.01 Absorbance 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 A_field-aged A_after IPT B_field-aged B_after IPT 0.0 4000 3500 3000 2500 2000 1500 1000 Wavenumber (cm -1 ) Fig. 9: FTIR spectra of field and laboratory aged SIR insulators V. CONCLUSIONS Condition assessment of the housing material of two 150 kv field-aged silicone rubber (SIR) insulators has been made through physical, electrical and material analysis techniques. Pollution severity measurements, hydrophobicity classification and structural analysis of the housing material were performed. Following, the resistance of the housing material to tracking and erosion was evaluated through the inclined plane test procedure. The hydrophobic properties of the SIR housing material were found more degraded for the field-aged insulator that had experienced more severe pollution and had a higher amount of ATH fillers. This insulator also showed higher degradation in hydrophobic properties, higher leakage current values but lesser mass loss caused by inclined plane testing. Thus, the combination of physical and electrical analysis methods may provide a better assessment of the housing material degradation severity of field-aged SIR insulators. In addition to wettability classification and contact angle measurements, the ratio of absorbance peak integrations between chemical bonds obtained thought FTIR spectroscopy may assist in evaluating the hydrophobicity degradation of the housing material. The hydrophobic properties of housing material could be better assessed if hydrophobicity measurements are also performed after accelerated ageing through inclined plane tests. Certainly, further work is needed, involving additional diagnostic techniques, for the better evaluation of the housing material of field-aged composite insulators. ACKNOWLEDGEMENTS This work was partly supported by the Polydiagno research project (project code 11SYN-7-1503) which is implemented through the Operational Program Competitiveness and Enterpreneurship. Action Cooperation 2011 and is cofinanced by the European Union and Greek national funds (National Strategic Reference Framework 2007-2013). The material analysis measurements were supported by the Center of Materials Technology and Photoionics of the Technological Educational Institute of Crete. REFERENCES [1] International Standard for Electrical insulating materials used under severe ambient conditions Test methods for evaluating resistance to tracking and erosion, IEC 60587, Third Edition, May 2007 [2] R. Hackam, Outdoor HV composite insulators, IEEE Trans.on Dielec. and Elec. Insul., vol. 6, no 5, October 1999, pp.557-585. [3] J. Reynders and I. Jandrell, Review of ageing and recovery silicone rubber insulation for outdoor use, IEEE Trans. on Dielec. and Elec Insul., vol.6, no.5, October 1999, pp.620-631. [4] S. Gubanski, A.Dernfalk, J. Anderson and H. Hilborg Diagnostic methods for outdoor polymeric insulators, IEEE Trans. on Dielec. and Elec. Insul., vol. 14, issue 5, October 2007, pp.1065-1080. [5] International Standard for Insulators for overhead lines - Composite Suspension and Tension Insulators for A.C systems with a nominal Voltage greater than 1000V - Definitions, Test Methods and Acceptance Criteria, IEC 61109 Edition Second, 2008. [6] Guide for the Assessment of Composite Insulators in the Laboratory after their Removal from Service, CIGRE, Working Group B2.21, December 2011. [7] Guide for Visual Identification of Deterioration and Damages on Suspension Composite Insulators, STRI Guide 5, 2003. [8] Field Guide for Visual Inspection of Polymer Insulators, Electric Power Research Institute, EPRI, May 2006. [9] Technical Specification for Selection and dimensioning of high-voltage insulators intended for use in polluted conditions Definitions, information and general principles, IEC/TS 60815-1, First Edition, October 2008. [10] Guidance on the measurement of wettability of insulator surfaces, IEC/TS 62073, First Edition, June 2003. [11]ψ»http://www.hnms.gr/hnms/english/climatology/climatology_region_di agrams_html?dr_city=heraklion. [12] http://users.metropolia.fi/~karisv/nanopinta/cam101.pdf. [13] D. Owens and R. Wendt, "Estimation of the surface free energy of polymers", J. Appl. Pοlym. Sci., vol. 13, pp. 1741-1747, 1969. [14] Guide for Evaluation of Dynamic Hydrophobicity Properties of Polymeric Materials for Non-Ceramic Outdoor Insulation, Retention and Transfer of Hydrophobicity, CIGRE Working Group D1.14, December 2010. [15] R. Sovar, Novel analytical techniques for the assessment of degradation of silicone elastomers in high voltage applications, Master of Applied Science by Research and Thesis, QUT, July 2004. [16] Instruction Manual and User System Guide for IRPrestige-21, Shimadzu Fourier Transform Infrared Spectrometer, Shimadzu Corporation, Analytical & Measuring Instruments Division, Kyoto, Japan. [17] T. Sorqvist, Polymeric Outdoor Insulators, a long-term study, Doctor of Philosophy, Dep. Of Electric Power Engineering, Chalmers University of Technology, Goteborg 1997. [18] S. Kumagai, X. Wang and N.Yoshimura, Solid residue formation of RTV silicone rubber due to dry-band arcing and thermal decomposition, IEEE Trans. on Dielec. and Elec. Insul., vol.5, no.2, April 1998, pp.281-289. [19] H. Hilborg, S. Karlsson and U.W.Gedde, Ageing of silicone rubber under ac and dc voltages in a coastal enviroment, IEEE Trans. on Dielec. and Elec. Insul., vol.8, no.6, December 2001, pp.1029-1039. [20] R. Gorur, G. Karady, A.Jagota, M. Shah and A. M Yates, Aging in silicone rubber used for outdoor insulation, IEEE Trans. Power Del., vol. 7, no 2, pp. 525-538, April 1992.

[21] H. Cao, D. Yan, J. Han, M. Lu and Z. Lv, Investigation and corroboration of a novel method to estimate the hydrophobicity of composite insulators, IEEE Trans. on Dielec. and Elec. Insul., vol 19, no 6, December 2012. [22] L. Meyer, S. Jayaram and E. Cherney, Correlation of damage, dry band arcing energy, and temperature in inclined plane test of silicone rubber for outdoor insulation, IEEE Trans. on Dielec. and Elec. Insul., vol.11, no.3, June 2004, pp.424-432. [23] K. Siderakis, D. Agoris, S. Gubanski, Influence of heat conductivity on the performance of rtv sir coatings with different fillers, Journal of physics D: Applied Physics, 38(2005), pp.3682-3689. [24] K. Siderakis, D. Agoris, S. Gubanski, Salt fog evaluation of RTV SIR coatings with different fillers, IEEE Trans. Power Del., vol. 23, issue 4, October 2008.