RC9 Poke-Thru Series INSTALLATION INSTRUCTIONS Installation Instruction No.: R3 Updated April 2005

Similar documents
RC7 Poke-Thru Series INSTALLATION INSTRUCTIONS Installation Instruction No.: R2 Updated April 2005

RC4 Poke-Thru Series INSTALLATION INSTRUCTIONS Installation Instruction No.: R2 Updated April 2005

Evolution Series. 8" Poke-Thru Devices I N S T A L L A T I O N I N S T R U C T I O N S. IMPORTANT: Please read all instructions before beginning.

Evolution Series. 8" Poke-Thru Devices I N S T A L L A T I O N I N S T R U C T I O N S. IMPORTANT: Please read all instructions before beginning.

Evolution Series. 6" Poke-Thru Devices I N S T A L L A T I O N I N S T R U C T I O N S. IMPORTANT: Please read all instructions before beginning.

WIREMOLD Furniture Feed Style Poke-Thru Devices

F E A T U R E S & B E N E F I T S

WIREMOLD Pedestal Style Poke-Thru Devices

Pedestal Style Poke-Thru Devices from Wiremold/ Legrand

FPT4 SERIES POKE-THROUGHS INSTALLATION INSTRUCTIONS

The RFB11 and RFB9 Series Floor

Abuilding s Wire Management System may be able to

IMPORTANT - PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING. SAVE THESE INSTRUCTIONS FOR REFERENCE AND ADDITIONAL WORK REQUIRED AFTER CONCRETE POUR.

Flush Service Floor Boxes

FLOOR FLOOR AND ANY VISION. FOR ANY WIREMOLD FLOOR BOXES. designed to be better.

WALKER FLOOR BOXES STILL LOOKING AT FLOOR BOXES IN THE SAME OLD WAY?

WIREMOLD Evolution Series Floor Boxes

Introducing the next generation in innovative surface raceway systems. The new 4000 Designer Series Aluminum

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

For large capacity, easy installation and

FLOOR AND ANY VISION. FOR ANY FLOOR. designed to be better.

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

PRE-INSTALLATION GUIDE

Youngstown State University

WIREMOLD Trenchduct Feeder Systems

SECTION OUTLET, PULL, AND JUNCTION BOXES

SECTION PATIENT BED SERVICE WALLS

SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

Special Applications. Dorn Equipment, Corporation 27 Upham Street Melrose, MA Phone: Fax:

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual

INSTALLATION MANUAL. FOOTWALL/SINKWALL (floor mount)

FORM HEADWALL. FORM HEADWALL (floor mount) (floor mount) Installation Manual

WIREMOLD Flush Style Poke-Thru Devices

8461C 4SQ, 1"RSD Rndopnw/Ers CVR

ROBERTSON "3 + 1" SLAB-ON-GRADE SINGLE LEVEL RACEWAY SYSTEM (Revised July 2000)

INSTALLATION MANUAL SURFACE-MOUNTED HEADWALL

CAJ. Combos. C-AJ of 5. Through Penetrations Series. Concrete. 3Fire Protection Products

Tepidus Wire Installation instructions for Electric Radiant Floor Heating INDEX

FORM FOOTWALL. FORM FOOTWALL (floating) (floating) Installation Manual

SECTION GROUNDING

Raceway and Boxes for Electrical Systems Page 1 of 7

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

DETAIL INSTRUCTION No. 1

1 data PIC location (with 2 ports) typically asf for multiple staff members

`bfifkd=c^k=prmmloq=molar`qp

Communications Page 1 of 9

Linear Drainage ZF806 ZF812

System No. C-AJ-8048

AMTC412 Wiremold Amtc-412 TPP Blank Alum. Features Made in USA. Material, Color, and Finish. Dimensions and Weight.

VITALink 2-Hour Fire Resistive Circuit Integrity Cable with Hose Stream

HALSEY TAYLOR OWNERS MANUAL Classic TM Series Barrier-Free Water Coolers Refrigerated Fountains with Back Panel

ELECTRICAL SECTION 2

PRODUCTS AND SYSTEMS FOR ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

A. Hazardous Areas: Hazardous areas as defined by the NEC as Class I, Division 1, Group D, or Class I, Division 2, Group D hazardous are as follows:

Floor Box Assembly. Features. Dimensions and Weight. Descriptions. Catalog Number

SAVE THIS INSTRUCTION MANUAL

Wall studs. Wall Studs

INSTALLATION MANUAL RECTANGULAR COLUMN

Raceway Solutions TM. Conventional Underfloor Duct. Multi-Compartment Conventional Duct Saves Time and Money in Your In-Slab Wire Management System

TW Series THRU-WALL BARRIER Cable/Conduit Sealing Device

4CS12 4CS-1/2 4X1-7/8D Handybox. Features. Dimensions and Weight. Long Description. Catalog Number

Site Preparation... 2

PrevaLED Linear, Bar and Area G3

A. Flat corner wall-to-wall See page 8. C. Outside corner wall-to-wall See page 8. B. Inside corner kit wall-to-wall See page 7

SECTION NON-STRUCTURAL METAL FRAMING

4. Optional Auto Drain Valve Connection

SECTION GROUNDING AND BONDING

FORMWORK 66 x 40 x 24 Lithic Freestanding or Alcove Box Bathtub Installation Guidelines. STYLE No. CAUTION: BATHTUB IS EXTREMELY HEAVY

Trench Duct Class Catalog 5230CT9601R10/08

Zurn Z886. 6" Perma-Trench. Installation Instructions

System No. C-AJ-8096

In-Wall Slide-out OEM INSTALLATION MANUAL

FIXED CEILING COLUMN. Installation Manual FIXED CEILING COLUMN

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

Steel Square Box, Height 4 Inch; Width 4 Inch; Depth 1-1/2 Inch; Capacity 21 Cu Inch; 17 Knockout(S); Knockout Location (5) Bottom, (12) Side

CONTENTS. B. System Design and Performance Requirements

NORTHWESTERN UNIVERSITY PROJECT NAME JOB #

SYSTEM 600 BILL CHANGER INSTALLATION INSTRUCTIONS Congratulations...

SUBSTITUTION REQUEST (After the Bidding/Negotiating Phase)

(3) 1/2 INCH CONDUIT BOTTOM, (2) 3/4 INCH CONDUIT BOTTOM, (8) 1 INCH CONDUIT SIDES Box

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6

4. Optional Auto Drain Valve Connection

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

Multi-Piece Shower with Trench Drain

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1

HALSEY TAYLOR OWNERS MANUAL Classic TM Series Barrier-Free Water Coolers Refrigerated Fountains with Back Panel

Electrical Metallic Tubing (EMT) Fittings

SECTION FIELD PANELS

WIRING METHODS CHAPTER 38

Exterior Door & PA System Replacement, Domestic Water Piping System and B/F Access Upgrades

QTY 7/374 8/346 11/375 12/348 17/298 18/324 19/ / /472 24/473 3 QTY

Steel Door Frame Installation in Masonry Construction

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

22.1 USED FOR: MATERIALS: all regular length 22 components stainless steel tool, silicon protective cover. DESCRIPTION

Transcription:

RC9 Poke-Thru Series INSTALLATION INSTRUCTIONS Installation Instruction No.: 1 002 947 R3 Updated April 2005 Wiremold Electrical Systems conform to and should be installed and properly grounded in compliance with requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local authorities. All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold electrical products are UL Listed to U.S. and Canadian safety standards, made for interior use only, and should be installed in conformance with current local and/or the National Electrical Code. IMPORTANT: Please read all instructions before beginning. Products Covered: RC9STC, RC9A15TC, RC9CTC, RC9SHTC, RC9A15TC-LJB and RC9A15TCLJB25 CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of the product. Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code. Step 1 Layout and locate position of hole(s). CAUTION: Holes shall be spaced a minimum of 2' [610mm] on center and not more than one hole per each 65 sq. ft. [6 sq. m] of floor area in each span. Step 2 Remove 6 1/2" [165mm] section from carpet or tile. Use template provided. 6 1/2" [165mm] Diameter 24" [610mm] Min Center Center NOTE: Be certain to drill hole at least 4" [102mm] from any wall or pillar to leave enough room for poke-thru cover assembly. NOTE: For tile installations up to a maximum of 3/4" [19.1 mm] thick. For tile thickness greater than 3/4" [19.1mm] consult factory. Step 3 Core drill hole. Step 4 Stem Assembly Catalog No. RC9STC Insert stem into hole. Push Down Step 5 Cover Assembly Catalog No.: RC9CTC Remove disposable plate and replace with carpet/tile flange. Install with (4) #6-32 x 1/4" [6.4mm] FHMS #6-32 x 1/4" FHMS (4) required 3" [76mm] Diameter Core Drill 3 1/16" [78mm] Actual Diameter CAUTION: Poke-Thru cannot be rotated in hole after insertion into floor.

COMPLETE ASSEMBLY Step 6 Cat. No. RC9A15TC Wire the Poke-Thru device (Can be completed above floor). Refer to wiring schematic in Step 8. Step 7 Wire the POWER circuit. Slide Cover Mounting Screws Two #6-32 Outlet Box Cover Plate Screw NOTE: When installing Cat No. RC9CTC to existing stems, apply wiring label to the inside of the junction box cover. Step 8 Connect Poke-Thru conductors according to required device configuration. See schematic below. SLIDE HOLDER ASSEMBLY Step 9 If circuit is connected to an isolated ground, apply IG icon on receptacle slide as shown. WARNING: Ground wire from junction box must be connected to SYSTEM GROUND. CAUTION: Receptacle mounting means not grounded. Grounding wire connection required. For isolated ground wiring, connect ground leads to a separate isolated grounding conductor. See NEC 250-146(d). NOTE: The orange triangle shall only be placed on devices that are wired for isolated ground. See NEC 250-146(d). 2

Step 10 Communication Wiring For cable pass-through, remove the egress knockout located on the underside of the cover Step 11 Attach Slide Cover with (2) #6 screws. Passthrough cabling must pass through internal gasket and data slide. Pass-through knockout Slide Cover Mounting Screws (2) #6-32 Align Gasket over Receptacle and press bead into Flange. Cut Slot in Gasket for Cable pass-through CAUTION: To maintain UL Fire Classification, Slide Cover must be replaced when communication cables are removed. Order Cat.No. RC9SHTC. CAUTION: Gasket must be set in place to provide scrub water seal. Do not over-tighten Cover Mounting Screws. Step 12 Installation complete Step 13 RC9 Less Junction Box Cat No. RC9A15TC-LJB, and RC9A15TCLJB25 (Applies to installations in the City of Chicago or other locations where local codes require the use of a communication adapter, EMT compression fittings, and a junction box suitable for use in environmental air spaces.) Follow Steps 1-11 for installation. Attach COM75 Adapter (included with LJB Units) per instructions supplied with Unit. Once Poke-Thru is pushed into the cored hole, from below, install an EMT compression fitting (not supplied) and junction box to the conduit system. Complete installation per NEC and local codes. 3

The RC9TC Series Poke-Thru Device is UL Listed and Classified to U.S. and Canadian safety standards to the following conditions: The RC9STC Poke-Thru Stem with the RC9CTC Service Head Fitting, the RC9A15TC factory assembled Poke-Thru device, and the RC9APTC Abandonment Fitting are for use with 1-, 1 1/2-, or 2-hour rated unprotected reinforced concrete floors and 1-, 1 1/2-, or 2-hour rated floors employing unprotected steel floor units and concrete topping (D900 Series Designs), or concrete floors with suspended ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling area below the poke-thru fittings). The assembled Poke-Thru stem and service fitting or the abandonment fittings will not reduce the ratings of the floor assembly when the thickness and type of concrete (required for the specific rating) are within the specified limits and the fittings are installed as specified: 1. Spacing Minimum of 2' [610mm] OC and not more than one unit per 65 sq. ft. [6 sq. m] of floor area in each span. 2. Concrete Minimum thickness of structural concrete topping of 2 1/4" [57mm] over metal deck or a minimum 3" [76mm] thick reinforced concrete slab. Unit weight of concrete to be 110 to 155 pcf. 3. Installation Mounted in a 3" diameter core-drilled hole in concrete per installation instructions accompanying the fittings or abandonment fittings. For use with power circuits, data and/or telephone cables as tabulated below: POKE-THRU SERVICE POWER COMMUNICATION FITTING TYPE FITTING TYPE CONDUCTORS (A) CONDUCTORS (B) RC9A15TC 3 16 (.01536 sq. in.) [9.910mm 2 ] (.00800 sq. in.) [5.162mm 2 ] RC9STC RC9CTC 3 16 (.01536 sq. in.) [9.910mm 2 ] (.00800 sq. in.) [5.162mm 2 ] The TC suffix letters indicate that device may be installed on tile or carpet covered concrete floors. The LJB suffix letters indicate units supplied without a junction box. The "25" suffix numbers indicate units supplied with 25 foot receptacle leads. (A) Maximum number of No. 12 AWG Type THHN conductors in power compartment of Poke-Thru fitting. (B) Maximum number of 22 AWG conductors in low voltage compartment of poke-thru fitting (4-pair cables have (8) conductors). When conductors larger than No. 22 AWG are used, the aggregate cross-sectional area of the copper conductors shall not exceed the aggregate cross-sectional area of the 22 AWG conductors permitted in the low voltage compartment. COPPER CROSS SECTIONAL AREA OF COMMONLY USED CONDUCTORS SIZE SOLID #24.00032 sq. in. [.20645mm 2 ] #22.00050 sq. in. [.32258mm 2 ] #14.00323 sq. in. [2.08386mm 2 ] #12.00512 sq. in. [3.30321mm 2 ] #10.00815 sq. in. [5.25805mm 2 ] # 8.01296 sq. in. [8.36127mm 2 ] NOTE: Use above values for solid or stranded conductors. For use on carpet covered and tile floors up to 3/4" [19.1mm] thick. CAUTION: Receptacle supplied with this Poke-Thru is not suitable for direct field wiring. Contact manufacturer for replacement. Field modifications will void UL Listing and Classification. Repalcement receptacle is limited to this manufacturers Catalog No. RC9REC or RC9REC-25. 4

5

Carpet Cutout Template Carpet Cutout 6 1/2" [165mm] Core Hole 3 1/16" [78mm] CAUTION: When printing copies of this template please be sure template is scaled correctly and is the correct size once it is printed. Wiremold / Legrand U.S. and International: 60 Woodlawn Street West Hartford, CT 06110 1-800-621-0049 FAX 860-232-2062 Outside U.S. 860-233-6251 Canada: 570 Applewood Crescent Vaughan, Ontario L4K 4B4 1-800-723-5175 FAX 905-738-9721 Copyright 2005 The Wiremold Company All Rights Reserved 1 002 947 R3 0405