GLASS FIBER-REINFORCED PLASTIC POLES FOR TRANSMISSION AND DISTRIBUTION LINES: AN EXPERIMENTAL INVESTIGATION

Similar documents
INNOVATIVE FIBRE REINFORCED BRIDGE DECK MODULES ABSTRACT

Behavior of Concrete-Filled FRP Tubes Under Bending, Axial Loads, and Combined Loading. Amir Fam, Bart Flisak and Sami Rizkalla

Concrete-filled fiber reinforced polymer tube-footing interaction in bending

FRP Tubes Filled With Concrete and Subjected to Axial Loads, Bending and Combined Loads

INFLUENCE OF PRSTRESS LEVEL ON SHEAR BEHAVIOR OF SEGMENTAL CONCRETE BEAMS WITH EXTERNAL TENDONS

RESILIENT INFRASTRUCTURE June 1 4, 2016

The Use of Sustainable Materials for Quick Repair of Aging Bridges

Chapter 7. Finite Elements Model and Results

1514. Structural behavior of concrete filled carbon fiber reinforced polymer sheet tube column

Numerical Study on Behaviour of Concrete Filled Tubes (CFT) under Static Load

FE Review Mechanics of Materials

BUCKLING ANALYSIS OF PULTRUDED GFRP HOLLOW BOX BEAM

Slenderness ratio effect on the behavior of steel and carbon-frp reinforced concrete-filled FRP tubes

FRP-confined concrete-encased cross-shaped steel columns: stub column tests

Hybrid FRP-concrete-steel double-skin tubular columns: Cyclic axial compression tests

TENSION AND COMPRESSION TESTING OF FIBRE REINFORCED POLYMER (FRP) BARS

SEISMIC REHABILITATION OF REINFORCED CONCRETE BRIDGE COLUMNS IN MODERATE EARTHQUAKE REGIONS USING FRP COMPOSITES

DESIGN GUIDELINES FOR BRIDGE DECK SLABS REINFORCED by CFRP and GFRP

BEHAVIOUR OF BRIDGE DECKS REINFORCED BY GFRP

New approach to improving distortional strength of intermediate length thin-walled open section columns

FE MODELING OF CFRP STRENGTHENED CONCRETE BEAM EXPOSED TO CYCLIC TEMPERATURE, HUMIDITY AND SUSTAINED LOADING

Flexural Behaviour of Composite Girders Using FRP and Precast Ultra-High-Strength Fiber-Reinforced Concrete Slabs

Introduction. Crossarm Design

Tension and compression testing of fibre reinforced polymer (FRP) bars

DETERMINATION OF ULTIMATE FLEXTURAL CAPACITY OF STRENGTHENED BEAMS WITH STEEL PLATES AND GFRP INTRODUCTION

Strengthening of RC Beams subjected to Combined Torsion and Bending with GFRP Composites

Behaviour of GFRP tube reinforced concrete columns under eccentric loading

Analysis and optimization of Composite Sandwich Structures using Optistruct

DURABILITY OF GFRP IN LOW-HEAT HIGH-PERFORMANCE CONCRETE. D. Svecova,. H. RlZkaUa,H. Vogel, A. Jawara ABSTRACT

CHAPTER 5 FINITE ELEMENT MODELLING

Experimental research and finite element analysis of square concrete columns confined by FRP sheets under uniaxial compression

with Fillers Department of Civil Engineering, National Taipei University of Technology, Taiwan, R.O.C

Effect of Bar-cutoff and Bent-point Locations on Debonding Loads in RC Beams Strengthened with CFRP Plates

EXPERIMENTAL STUDY ON DOUBLE LAP JOINTS COMPOSED OF HYBRID CFRP/GFRP LAMINATE

ABC-UTC. Research Progress Report (Feasibility Study) Title: Alternative ABC Connections Utilizing UHPC. March, 2017

FLEXURAL AND SHEAR STRENGTHENING OF REINFORCED CONCRETE STRUCTURES WITH NEAR SURFACE MOUNTED FRP RODS

FRP STRENGTHENING OF 60 YEAR OLD PRE-STRESSED CONCRETE BRIDGE DECK UNITS

Upgrading Flat R.C. Slab with Haunch Using F.R.P

Todd F. Shupe Associate Professor School of Renewable Natural Resources Louisiana State University AgCenter Baton Rouge, LA 70803

MODELING OF CARBON FIBER REINFORCED POLYMER (CFRP) STRENGTHENED REINFORCED CONCRETE (RC) BEAMS: EFFECT OF BEAM SIZE AND CFRP THICKNESS

PULLOUT CAPACITY BEHAVIOUR OF FRP-HEADED REBARS

NUMERICAL SIMULATION OF CIRCULAR HOLLOW STEEL COLUMNS CONFINED WITH FIBER REINFORCED POLYMER UNDER AXIAL COMPRESSION

BEHAVIOR OF INFILL MASONRY WALLS STRENGTHENED WITH FRP MATERIALS

SHEAR AND BUCKLING STRENGTHENING OF STEEL BRIDGE GIRDER USING SMALL-DIAMETER CFRP STRANDS

In-plane testing of precast concrete wall panels with grouted sleeve

CYCLIC LOADING TEST OF REINFORCED CONCRETE COLUMN WITH HOLLOW SECTION AND HIGH LONGITUDIAL STEEL RATIO UNDER HIGH AXIAL LOADING

Question Paper Code : 11410

Seismic performance of New Steel Concrete Composite Beam-Columns

Experimental investigation of the use of CFRP grid for shear strengthening of RC beams

FRACTURE OF LAYERED FIBERCONCRETE WITH NON-HOMOGENEOUS FIBER DISTRIBUTION

Ultimate strength prediction for reinforced concrete slabs externally strengthened by fiber reinforced polymer (FRP)

AN INVESTIGATION OF SEISMIC RETROFIT OF COLUMNS IN BUILDINGS USING CONCRETE JACKET

GFRP HOLLOW-CORE REBARS FOR CONCRETE BEAMS

Analysis of the Flexural Behaviour of Glass Fiber-Reinforced Plastic

BEHAVIOR OF FRP SANDWICH PANELS FOR TRANSPORTATION INFRASTRUCTURE

On the Structural Responses of Simply Supported PFRP Channel Beams under Three-point Loading

Effect of Different Patterns and Cracking in FRP Wrapping on Compressive Strength of Confined Concrete

Corrugate Fiber Reinforced Plastic Sheet in Repairing Tunnel Linings

Strengthening of Timber Bridges

MECHANICAL CHARACTERIZATION OF SANDWICH STRUCTURE COMPRISED OF GLASS FIBER REINFORCED CORE: PART 1

STUDY ON THE FLEXURAL BEHAVIOUR OF CFRP-GRID REINFORCED CONCRETE ONE-WAY SLABS

SHEAR STRENGTHENING USING CFRP SHEETS FOR PRESTRESSED CONCRETE BRIDGE GIRDERS IN MANITOBA, CANADA

CRACKING BEHAVIOR AND CRACK WIDTH PREDICTIONS OF CONCRETE BEAMS PRESTRESSED WITH BONDED FRP TENDONS

Influence of Longitudinal FRP Straps on the Behaviour of Circularised and FRP Wrapped Square Hollow RC Concrete Specimens

SHEAR BEHAVIOR OF RC BEAMS USING U-SHAPED UFC PERMANENT FORMWORK WITH SHEAR KEYS OR BOLTS

An Experimental and Analytical Study on Flexural Behaviour of Pultruded GFRP Members by ANSYS

beni-suef university journal of basic and applied sciences 5 (2016) Available online at ScienceDirect

RESILIENT INFRASTRUCTURE June 1 4, 2016

Non Linear Analysis of Composite Beam Slab Junction with Shear Connectors using Ansys.16

RESILIENT INFRASTRUCTURE June 1 4, 2016

Angle Cleat Base Connections

FRP FOR SUSTAINABLE PRECAST CONCRETE STRUCTURES

2.0 REVIEW OF LITERATURE. In the last few years, the use of fiber-reinforced plastic (FRP) rebars to replace steel

Behaviour of Corner Beam Column Joint with Rectangular Spiral Reinforcement and Longitudinal FRP Bars

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 3, No 1, 2012

NLFEA Fire Resistance of 3D System Ceiling Panel

Nonlinear Finite Element Analysis of Composite Cantilever Beam with External Prestressing

Strengthening of Reinforced Concrete Beams using Near-Surface Mounted FRP Mohamed Husain 1, Khaled Fawzy 2, and Mahmoud Nasr 3

ISSN: ISO 9001:2008 Certified International Journal of Engineering and Innovative Technology (IJEIT) Volume 5, Issue 5, November 2015

Numerical Modelling of Concrete Filled Frp Tubes Subjected Under Impact Loading

FEM performance of concrete beams reinforced by carbon fiber bars

Pullout Test of Concrete Blocks Strengthened with Near Surface Mounted FRP Bars

Modal Behaviors of Spun-Cast Pre-Stressed Concrete Pole Structures

Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit

IDEA OF HYBRID COLUMN WITH ENERGY ABSORPTION ELEMENT

Flexural Behavior of Concrete Beam Reinforced with Steel and FRP Re-bars

SEISMIC BEHAVIOR AND DAMAGE EVALUATION OF SELF-SENSING CONCRETE-FILLED FRP/FRP-STEEL COMPOSITE TUBULAR COLUMNS FOR BRIDGE PIERS

Upgrading ductility of RC beam-column connection with high performance FRP laminates

EXPERIMENTAL STUDY AND ACTUAL STRUCTURE DESIGNING OF LOOP JOINT USED FOR SEGMENTED PRECAST CONCRETE BRIDGE PIER AND CAISSON.

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Confining concrete cover of GFRP tube reinforced concrete columns with polymer grids

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 1, 2011

Flexural Behavior of Steel I Beams Bounded With Different Fiber Reinforced Polymer Sheets

BEHAVIOR OF REINFORCED CONCRETE BEAM WITH OPENING

Effect of prestressed CFRP plate location on behavior of RC beam strengthened with prestressed CFRP plate

TEST AND ANALYSIS OF A SHORT-SPAN RAILWAY BRIDGE

Effect of Distribution in Cross Sectional Area of Corroded Tensile Reinforcing Bars on Load Carrying Behaviour of RC Beam

SHEAR STRENGTHENING OF RC BRIDGE PIERS BY STEEL JACKETING WITH EXPANSIVE CEMENT MORTAR AS ADHESIVE

The Study of FRP Strengthening of Concrete Structures to Increase the Serviceable Design Life in Corrosive Environments

Finite Element Analysis of RC Beams Strengthened with FRP Sheets under Bending

Transcription:

GLASS FIBER-REINFORCED PLASTIC POLES FOR TRANSMISSION AND DISTRIBUTION LINES: AN EXPERIMENTAL INVESTIGATION D. Polyzois, S. Ibrahim, V. Burachynsky, and S. K. Hassan Department of Civil and Geological Engineering, University of Manitoba, Winnipeg, MB, R3T 2N2,Canada SUMMARY: An extensive research project is currently being carried out at the University of Manitoba, Canada, to develop lightweight glass fiber-reinforced plastic (GFRP) poles for use in transmission and distribution lines. In this paper, results from tests involving full-scale tapered GFRP poles with hollow a circular cross-section subjected to cantilever bending are presented. The filament winding process was employed to produce those poles using vinylester resin reinforced with E-glass fibers. Twelve bending tests were conducted on full-scale poles up to failure. Test parameters included fiber orientation and number of layers. Extensive theoretical work preceded the test program and a theoretical model was developed. The results to-date indicate that the developed theoretical model can predict quite well the ultimate capacity and behavior performance of GFRP poles. KEYWORDS: Transmission and distribution poles, filament winding, fiber-reinforced plastics. INTRODUCTION Traditional materials such as wood, steel, and concrete are commonly used to construct electrical transmission and distribution poles. However, the shortage of wooden poles, their short life expectancy, and various environmental concerns have promoted hydro-electric utility companies to search for a cost-effective alternative. Wooden poles are continuously exposed to weather, fungi, woodpeckers, etc., which result in a very significant deterioration of their load bearing capacity with the time. The service life of wooden poles is approximately 20 years [1]. Any extension of this service life requires continuous inspection and follow-up care. In a number of European countries, concrete poles are used. The main disadvantage of concrete poles is their weight, which drastically increases transportation and erection costs. Chemical influences on the concrete surfaces due to environmental impact can also affect their long term performance. As in the case of other concrete structures, concrete poles are subject to corrosion of the steel reinforcement, resulting in further strength deterioration and expensive maintenance. Steel is the most common material for the construction of transmission poles in North America. These poles, however, are very expensive. Corrosion protection is of primary concern in steel poles which must be painted or galvanized, a process which does not always 1

guarantee long term protection. Generally, traditional poles made of wood, concrete, or steel are subject to deterioration under environmental attacks. Regular maintenance is essential to prolonging serviceability of these poles. On the other hand, Glass Fiber-Reinforced Plastic (GFRP) poles are lightweight and corrosion resistant. Being lightweight is a major advantage of GFRP poles making them suitable for transportation and installation in mountain terrains and marshes. Although the initial cost of GFRP poles may be higher than traditional poles, the long term benefits these poles provide, make their selection attractive. The use of GFRP poles is not new. A number of companies are already involved in the production of such poles. Research in this area, however, is limited. In 1988, Bell initiated its own investigation of GFRP poles, and conducted an experimental program at the Centre de Recherche du Reseau Exterior (CERRE) [2]. The specimens were tapered with hollow cross section and were manufactured by centrifugal casting. The test results indicated that GFRP poles could safely resist loads comparable to those of wooden poles. The behavior of these GFRP poles was found to be truly elastic even for large deflections. An experimental investigation was also conducted by Shakespeare Inc. on filament wound GFRP poles in 1993 [3]. Class 4 GFRP poles were tested at the national test labs of Engineering Data Management (EDM) in Colorado, USA. The tests were successful as each pole met or exceeded the strength requirement specified for wooden poles. The research program at the University of Manitoba, Canada, was to: a) develop a theoretical model for determining the ultimate strength and performance of GFRP poles; b) evaluate the developed theoretical model through a series of small and full-scale testing; and c) develop design guidelines for the use of GFRP. To-date, twelve small scale specimens (2.5 m long) and twelve full-scale specimens (6.25 m long) have been tested under cantilever bending load up to failure. This paper presents the results from the full-scale tests. Specimens and Test Setup EXPERIMENTAL PROGRAM The poles were fabricated through the filament winding wet process at the ISIS-Faroex Filament Winding Research Facility. E-glass fibers and vinylester resin (DERAKANE 470-300) were used for manufacturing these poles. The material properties and strength for both the fiber and the resin were provided by the manufacturer [4] and are presented in Table (1). 2

Table 1: Properties of E-Glass and Vinylester resin Properties E-Glass Vinylester resin (DERAKANE 470-300) Tensile modulus (GPa) 72.4 3.58 Poisson s ratio 0.2 0.3 Tensile Strength (MPa) 2400 85 Shear Modulus (GPa) 30 1.38 Density (gm/cm 3 ) 2.54 1.08 The specimens were tapered hollow sections, 6250 mm in length. The inner diameters at the base and at the top were 416 mm and 305 mm, respectively. The wall thickness for each specimen varied depending on the number of layers, which ranged from 4 to 8, in two layer increments, giving a total thickness of between 2.75 mm and 5.5 mm at the base. Three fiber angles with respect to the longitudinal axis of the pole were used: 5/-5, 10/-10, and 20/-20. Hoop winding was also employed in ten of the specimens with different ratios, while only two of the specimens were fabricated without hoop winding. The fiber volume fraction was measured during the manufacturing process by determining the weight of fiber and resin used and transforming those weights into volume fractions. The configurations as well as the fiber volume fraction for the tested specimens are listed in Table (2). Table 2: Configuration and fiber volume fraction of full-scale specimens Specimen Number Longitudinal Fiber Orientation Number of Hoop Layers Total Number of Layers Base Thickness (mm) Fiber Volume (%) Total Weight (Kg) 1 (10/-10) 0 8 5.5 49 99.40 2 (10/-10) 2 8 5.0 60 80.25 3 (10/-10) 4 8 4.5 60 68.15 4 (10/-10) 2 6 4.0 54 60.85 5 (10/-10) 2 4 2.4 60 39.00 6 (20/-20) 0 8 5.5 53 94.30 7 (20/-20) 2 8 5.0 60 81.00 8 (20/-20) 4 8 4.9 58 72.05 9 (20/-20) 2 6 4.0 57 59.40 10 (20/-20) 2 4 2.75 51 38.20 11 (5/-5) 2 6 4.6 50 62.50 12 (5/-5) 2 4 2.8 52 38.00 The fixed support for the specimens consisted of a square reinforced concrete base measuring 800 mm wide by 1000 mm high. It was made up of two segments with a tapered circular hole in the middle with dimensions that matched the outer diameter of the specimens. The two segments of the base were clamped together using four dwyidag bars, as shown in Fig. 1. To insure the stability of the portion of the specimen within the base, a GFRP tapered sleeve, 1000 mm long, and 25 mm thick, was inserted in the specimen. The concrete base was clamped to a rigid structural wall using four hollow square steel (HSS) sections (250 x 250x 6 mm), two on each side of the base, as shown schematically in Fig.1. Four high strength 3

dwyidag bars were used to clamp the HSS section and the concrete base to the structural wall. To ensure full fixity of the specimen within the concrete base, the gap between each specimen and the concrete base was filled with plaster of Paris. The load was applied horizontally, 600 mm below the top, according to the ANSI standard [5]. An electronic load cell was used to monitor the applied load, as shown in Fig. 1. Loading was applied at a rate of approximately, 0.25 mm/second. The lateral deflection of the poles at the loading position was monitored through an electronic linear measurement transducer (LMT). The LMT was mounted on a fixed steel column 10000 mm away from the specimen. The stroke range for each LMT is 2500 mm. Two LMTs attached on two opposite sides of the poles, approximately, 1000 mm above the base, were used to monitor the change in the specimen diameter, as shown in Fig.1. These LMTs had a range of 350 mm. The difference between the readings between the two LMTs represented the change of the specimen diameter at that height. This method allowed continuous monitoring of the change in the diameter with loading. Strain along the specimen near the base was monitored through 24 electrical resistance strain gauges. The strain gauges had 5 mm gauge length and 120 ohm electrical resistance. Three strain gauges were mounted at eight different locations, to measure strains in the longitudinal, circumferencial and 45 degrees off-axis. Four strain gauges were located on tension side and the other four on the compression side at heights 30, 400, 800, and 1200 mm above the concrete base. The load cell, the LMTs, and the strain gauges were connected to a computer controlled 32 channel Data Acquisition System to monitor and record all data. Visual observations were also made during the test. The load was applied until complete failure of the specimen occurred. 5650 mm 600 mm R.C. Structural Wall LMT Specimen Load cell LMT LMT HSS 1000 mm 1000 mm Applied Load LMT Fig. (1): Schematic drawing of the full-scale test setup 4

Test Results A summary of all test results is shown in Table (3). The equivalent wooden pole class is also shown in this table. It should be noted that specimen 2 failed prematurely inside the concrete base because no internal stiffener was used for that specimen. Two specimens (4, and 11) satisfied the requirement of class 1 pole, according to Ref.(5), by carrying an ultimate load equal to or exceeding 20 KN (4500 lb). The top displacement of those two specimens was less than 10% of the free height of the pole. Specimens 4, and 11 consisted of only 6 layers and weighed about 60 kg. Specimen 9, which also consisted of 6 layers but had a fiber orientation of 20 o, failed at ultimate load 18.9 KN. This is less by 5% of that required for class 1, so this specimen was classified as class 2 pole. Five specimens (1, 3, 6, 7, and 8) exceeded the class 1 requirement and were classified in the heavier categories (H2 and H3). The maximum lateral displacement of pole was less than 12.7%. Table (3): Performance of full-scale GFRP poles Specimen Number Weight (Kg) Ultimate Capacity (KN) Top Displacement (mm) Equivalent Wooden Pole Class Displacement As % of Free Height Load/ Weight (KN/Kg) 1 99.40 34.2 486 H3 9.7 0.34 2 80.25 See Note 3 68.15 30.1 608 H2 12 0.44 4 60.85 20.8 430 1 8.6 0.34 5 39.00 7.55 240 6 4.8 0.19 6 94.30 30.4 431 H2 8.6 0.32 7 81.00 36.4 634 H3 12.7 0.47 8 72.05 28.1 593 H2 11.9 0.39 9 59.40 18.9 416 2 8.3 0.32 10 38.20 6.9 252 6 5.0 0.18 11 62.50 20 403 1 8.1 0.32 12 38.00 8.8 278 5 5.6 0.23 Note: This specimen failed prematurely due to the lack of internal stiffener within the concrete base. Since each specimen had a different weight and a different carrying capacity, the load capacity-to-weight ratio (KN/Kg) was used to compare the performance of different specimens. Specimen 7, which consisting of 8 layers (6 longitudinal layers and 2 circumferencial layers), had the highest performance ratio of approximately 0.47 KN/Kg. Specimens 3, and 8, which consisting of 8 layers (4 longitudinal layers and 4 circumferencial layers), had a load-to-weight ratio of 0.4 KN/Kg. Specimens 1, and 6, consisting of 8- longitudinal layer without any circumferencial ones, did not perform as well as the other 8- layer pole group and had a value of 0.32 KN/Kg. 5

A significant drop in performance ratio was observed when the number of layers was reduced to 6 or 4 layers. This was due to the high reduction in the wall thickness which in turn reduced the buckling load significantly, much more than the reduction the weight of the specimen. As shown Table 3, the weight ratio for specimen 4 was approximately, 0.34 KN/Kg. This is almost the same value as that specimen 1 that had 8 longitudinal layers without circumferencial layers. This indicate the importance of including circumferencial layers to achieve the same performance of pole having larger number of layers but with only longitudinal fibers. Based on the dimensions of a class 1 wooden poles of total height 6.1 m (20 ft) the load capacity-to-weight ratio is 0.095 KN/Kg. The load-to-weight ratio for an equivalent class 1 GFRP pole (specimen 4 or 11) is 0.3 KN/Kg. This means that GFRP poles are more efficient than wooden poles and are approximately only one third of the weight of equivalent wooden poles. All specimens with circumferencial layers (with the exception of specimen 2), failed by local buckling on the compression side of the specimens at a height which varied from 200 mm to 800 mm above the concrete base, as shown in Fig.2. Specimen 1, which had no circumferencial winding, also failed by local buckling on the compression side 200 m above the base and failure was combined with excessive splitting, and delamination of the fibers. Fig.2: Local buckling failure mode 6

The failure mechanism of specimen 6 is shown Fig.3. A diagonal crack extending to a height between 200 mm to 1200 mm above the base developed on the compression side. Fig. 3: Diagonal fracture failure mode THEORETICAL ANALYSIS The ANSYS program [6] was used to develop a nonlinear finite element model of GFRP poles. The geometric boundaries of the FRP poles were defined, as the first step in the modeling process. Eight-node quadrilateral layered shell element was used to model GFRP poles. Detailed formulation of this element is given by Ref. [7]. The portion of the specimen, which was embedded inside the concrete base, was also included in the model. In the current study, a geometric nonlinear analysis was used taking into account the cross section distortion as well as the large deflection at the top. The proposed model used to predict the ultimate failure load, whether it was due to instability (local buckling) or material failure. Fig. 4 shows a comparison between the experimental and the predicted ultimate loads for the tested specimens. The average ratio of the experimental-to-theoretical ultimate load was approximately 0.99 with a standard deviation of 12%. As evident from this figure, it is clear that there is a strong correlation between the results obtained from the proposed model and the experimental results. 7

Ptest/PF.E. 1.3 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 1 2 3 4 5 6 7 8 9 10 11 12 Specimen Number Fig. 4: Comparison between theoretical and experimental ultimate load CONCLUSIONS An experimental study was employed to investigate the ultimate capacity and performance of tapered filament wound GFRP poles subjected to cantilever bending. GFRP poles proved to carry the same ultimate load equivalent to wooden poles. However, a significant saving in the weight is achieved by utilizing GFRP. The load capacity-to-weight ratio of GFRP poles is almost three times higher than the equivalent wooden poles. Maximum load capacity-to-weight ratio was achieved by incorporating circumferencial winding along with longitudinal fibers. Amongst the 8-layer GFRP poles, the maximum load capacity-toweight ratio was attained when only two circumferencial layers were combined with six longitudinal layers. Local buckling was the most dominant mode of failure in most of the specimens because of the high radius-to-thickness ratio of the specimens. On the other hand, only one specimen failed due to material failure on the compression side because of the absence of circumferencial layers in that specimen. The finite element method employed in this investigation provided an excellent prediction of the critical buckling and material failure loads as well as the corresponding modes of failure for thin-walled GFRP poles. ACKNOWLEDGEMENT The research project in this study was sponsored by ISIS-Canada, Faroex Ltd. of Manitoba, and The Province of Manitoba. The specimens were fabricated at the ISIS-Faroex filament winding Research Facility and the testing was conducted at the Structural Engineering and Construction R&D Facility at the University of Manitoba. 8

REFERENCES 1. Vanderbuilt, M. D. and Criswell, M. E., Reliability Analysis of Pole-Type Transmission Structures Computer and Structures, Vol. 6, No. 2, 1988, pp. 335-343. 2. McClure, G., Boire, L., and Carriere, J. C., Applications of Advanced Composite Materials in Overhead Power Lines and Telecommunications Structures Advanced Composite in Bridges and Structures, K.W. Neale and P. Labossiere, Editors, Canadian Society of Civil Engineering, 1992, pp.543-549. 3. Derrick, G. L., Fiberglass Composite Distribution and Transmission Poles Manufactured Distribution and Transmission Pole Structures Workshop Proceeding, Electric Power Research Institute, July 25-26, 1996, pp. 55-61. 4. Dow Plastics Company, Technical Product Information, Midland, MI, 1997. 5. American National Standards Institute (ANSI), American National Standard for Wood Poles 05.1 Specifications and Dimensions, 22 West 42nd Street, New York, 1992. 6. ANSYS, Inc., ANSYS User s Manual for Revision 5.2 - Volumes I to IV 1995, Houston, PA. 7. Yunus, S., Kohnke, P. C., and Saigal, S. An Efficient Through-Thickness Integration Scheme in Unlimited Layered Doubly Curved Isoparametric Composite Shell Element International Journal for Numerical Methods In Engineering, Vol. 28, 1989, pp. 2777-2793. 9