PHYSICAL AND OPERATING CONDITIONS EFFECTS ON SILICA GEL/WATER ADSORPTION CHILLER PERFORMANCE

Similar documents
Mathematical and CFD modeling for a rectangular finned tube adsorption bed for automotive cooling system

A Three-Stage Adsorption Cycle with Three Silica-Gel Beds

Thermally operated mobile air-conditioning system

Module 05 Lecture 35 : Low temperature process design Key words: Refrigeration system

OPTIMIZATION OF PCM NUMBER IN HOT WATER TANK FOR THE APPLICATION OF SOLAR DRIVEN ADSORPTION CHILLER IN TROPICAL CLIMATE

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

Experimental Research and Performance Analysis of a Solar-Powered. Air-conditioning System in a Green Building

THEORETICAL STUDY AND DEVELOPMENT OF ABSORPTION CHILLERS WITH ENHANCED AUXILIARY WASTE HEAT RECOVERY

FLOWRATE DEPENDENT HEAT-PUMP MODEL

Advanced heat driven cooling cycles for low-temperature waste heat recovery

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

Modelling of an adsorption chiller with Modelica

SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

MULTI-OBJECTIVE OPTIMIZATION OF A TWO-BED SOLAR ADSORPTION CHILLER BASED ON EXERGY AND ECONOMICS

Study of the performance of a solar adsorption cooling system

SIMULATION OF ADSORPTION GENERATORS FOR OPTIMAL PERFORMANCE

Conceptual Design of Nuclear CCHP Using Absorption Cycle

Water zeolite adsorption heat pump combined with single effect evaporation desalination process

DEVELOPMENT OF A HYBRID AIR-CONDITIONING SYSTEM DRIVEN BY LOW TEMPERATURE WASTE HEAT

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

System Analysis on Absorption Chiller Utilizing Intermediate Wasted Heat from Micro Gas Turbine and Solid Oxide Fuel Cell Hybrid System

SorTech package solution description

Modeling and analyzing solar cooling systems in Polysun

High efficient heat reclaim with CO2

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY

1. To improve heat exchange between a gas & a liquid stream in a heat exchanger, it is decided to use fins. Correct the suitable option.

New age adsorption cooling & recuperative power. Enwave District Energy Pacific Northwest National Laboratory. June Brandon Oyer, P.E.

Analysis of Heat Exchanger Pinch Point in a Waste-Heat Recovery SCO2 Rankine Cycle

The Present and Future of Refrigeration, Power Generation and Energy Storage. R.Z. Wang Shanghai Jiao Tong University

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Theoretical analysis of an integrated thermoelectric-absorption cooling system

MODELLING OF COMMERCIAL ABSORPTION HEAT PUMP WITH INTEGRAL STORAGE

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector

Optimization of longitudinal finned-tube adsorber bed in an exhaust waste heat driven adsorption cooling system

JJMIE Jordan Journal of Mechanical and Industrial Engineering

Innovations in Chiller Technology

Comparison of micro gas turbine heat recovery systems using ORC and trans-critical CO 2 cycle focusing on off-design performance

HEATING SYSTEM RETURN TEMPERATURE EFFECT ON HEAT PUMP PERFORMANCE

Absorption Chillers & Heatpumps

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS

High Performance Cascading Adsorption Refrigeration Cycle with Internal Heat Recovery Driven by a Low Grade Heat Source Temperature

Thermodynamic Performance Assessment of R32 and R1234yf Mixtures as Alternatives of R410A

Performance analysis of a new single effect hot water absorption chiller system

Performance Improvement on Water-cooled Cold-Plate

DEVELOPMENT OF A HIGH EFFICIENCY ABSORPTION CHILLER-HEATER AND A COMPACT ABSORPTION CHILLER-HEATER

Customized Absorption Heat Pumps for Utilization of Low-Grade Heat Sources

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

Available from Deakin Research Online:

Conceptual Design of Nuclear CCHP Using Absorption Cycle

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

Combined Heat and Power

System cost and efficiency optimization by heat exchanger performance simulations

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

Sustaining thermal power plant production in low water supply regions using cooling towers

Parametric Study of a Double Effect Absorption Refrigeration System

1 History. 2 Line-up

Performance analysis of a new single effect hot water absorption chiller system

ISOBUTANE GEOTHERMAL BINARY CYCLE SENSITIVITY ANALYSIS

Investigation on effects of piping on heating performance of multi-split variable refrigerant flow system

Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD

ABSTRACT INTRODUCTION

Eurovent Association Eurovent Certification Activities related to ENERGY EFFICIENCY

OBJECT SYSTEM Figure 1 shows the object air conditioning system. Flesh outdoor air is supplied to desiccant system directly or via earth tube dependin

EXPERIMENTAL ANALYSIS OF ABSORPTION REFRIGERATION SYSTEM DRIVEN BY WASTE HEAT OF DIESEL ENGINE EXHAUST

New Suggestions for Centrifugal Chiller Technologies to Realize High Efficiency and High Functionality

DOUBLE-EFFECT SOLAR ABSORPTION THERMAL ENERGY STORAGE

329 - The AC-Sun, a new concept for air conditioning

Design and modeling of a hybrid reversible solid oxide fuel cell organic Rankine cycle

EVALUATION OF SOLAR SORPTION REFRIGERATION SYSTEM PERFORMANCE IN LATVIA

A cooling tower combined with chilled ceiling: system optimisation

Exergy Analysis of a Ground-Source Heat Pump System. University of Cambridge, Department of Engineering, Cambridge, UK, 2

Thermodynamic Analysis of Organic Rankine Cycle using Different Working Fluids

Thermal Management of Densely-packed EV Battery Set

Performance Analysis of a Solar Powered Adsorption Cooling System

Permanent City Research Online URL:

Innovation in carbon-ammonia adsorption heat pump technology: a case study

Mathematical Modeling of Basic Parts of Heating Systems with Alternative Power Sources

A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc.

Energy Mix Opportunity of Vapor Absorption Refrigeration System Integrated With Solar Collectors: A Case Study of Hotel Shangri-La

Design considerations for integration of two 5 MW vapour compression heat pumps in the Greater Copenhagen district heating system

MULTI-OBJECTIVE OPTIMIZATION OF TURBO-EXPANDER IN ORGANIC RANKINE CYCLE SYSTEM

Modeling and Simulation of Multi Purposes Concentrated Solar Power System

Energy Saving Report. Frigi-Tech Oil Additive. Application. In HKU Central Plant. Chiller No. 3

THEORETICAL STUDY OF HEAT PUMP SYSTEM USING CO 2 /DIMETHYLETHER AS REFRIGERANT

Design, modelling, performance optimization and experimentation of a reversible HP/ORC prototype.

A Matlab-Based Program for the Design And Simulation of Wet Cooling Towers

Modeling of Air-Source Integrated Heat Pumps

Validation of Deration of Heat Transfer Coefficient with Brine Usage

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS

Providing free cooling from low temperature waste heat

Heat Load Calculation for the Design of Environmental Control System of a Light Transport Aircraft

Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery

Design and Off-Design Analysis of an ORC Coupled with a Micro-Gas Turbine

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Packaged AHR (Advanced Heat Recovery) Systems for Engines, Gas Turbines, & Industrial Waste Heat. Tom Pierson

Thermodynamic Analysis of Ground Source Heat Pump for Space Heating Using R-22

Critical exergy analysis of counterflow reversibly used cooling towers

Transcription:

PRO-TEM Network Sustainable Thermal Energy Management Conference (SusTEM2010) PHYSICAL AND OPERATING CONDITIONS EFFECTS ON SILICA GEL/WATER ADSORPTION CHILLER PERFORMANCE Ahmed Rezk Raya Al-Dadah (1/25)

Background Chiller modeling Simulated chiller Modeling technique Governing equations Performance indicators Validation study Fin spacing Bed physical performance Bed thermal performance Chiller performance Operation temperature Cooling capacity and GT lift Efficiency and GT lift COP and GT lift Cycle time Operation modes Cooling capacity Optimum timing combination Conclusion Presentation outline (2/25)

Background Advantages of adsorption refrigeration systems Environmentally friendly system. Large energy saving potential when it is applied in: Combined Cooling, Heating and Power (CCHP) system Sustainable Building Climatisation (SBC) using solar energy as heat source. Durability, long life time and low maintenance cost. Advantages of silica gel/water adsorption system Silica gel/water adsorption cycle can be powered using low grade heat sources (55-100 C). Silica gel/water pair has relatively high equilibrium Ads/Des rate. Water has high latent heat of evaporation. Water is thermally stable within wide range of operating temperatures. Water is combatable with wide range of materials (3/25)

TWO-BED SILICA GEL/WATER ADSORPTION CHILLER SIMULATION MODEL (4/25)

Chiller modeling: Simulated chiller The simulated two-bed silica gel/water adsorption chiller is produced by Weatherite Holding Ltd, UK Adsorption chillier produced by Weatherite Schematic diagram for the adsorption chillier produced by Weatherite One module construction One module covered by fine mesh Bed design of the adsorption chillier (5/25)

Chiller modeling: Modeling technique (1) Adsorption refrigeration system modeling is a primary tool for design and optimisation purposes. The published simulation techniques so far are: Lumped-parameter simulation technique. Lumped analytical simulation techniques. Dynamic simulation technique. Distributed parameter simulation technique. Simulation using object oriented simulation tool MODELICA. All these simulation techniques present the overall heat transfer coefficient for all heat exchangers and adsorbent bed as a constant value. That limits the prediction capability of any physical change effect on the adsorption chiller performance, especially the adsorbent bed. (6/25)

Chiller modeling: Modeling technique (2) This paper presents a new adsorption chiller simulation technique Empirical lumped analytical simulation model. Empirical lumped analytical sub-models were constructed for evaporator, condenser, adsorber and desorber based on their physical characteristics. They were integrated to form the chiller simulation model. PC MATLAB The governing equations were solved by MATLAB platform and materials thermophysical properties are calculated using REFPROP REFPROP Condenser Desorber Adsorber Evaporator Eqn (7/25)

Chiller modeling: Modeling governing equations Energy balance Adsorbent bed ( ζm C ( T ) M w Cp ( T ) + M C + M C ) dt dt = ( 1 ζ ) + bed w w ( φ ) γ h ( T ) h ( P, T ) Evaporator + sg sg ref bed sg sg bed met bed met bed dua LMTD [ { } + ( 1 γ ){ h ( P, T ) h ( P, T )}] M dw dt + φm H dw dt g bed Hex g Hex [ Cpref, f ( Tevap ) M ref, evap + Cevap metm evap met ] dtevap + φ[ h h ] M dw dt + de dt ref, evap, in Condenser ref, evap, out Refrigerant mass balance bed [ Cp ( T ) M C M ] + φ ref, l cond Water vapor adsorption rate sg sg g pump Hex Hex dt = UA [( h h ) + Cp ( T T )] M dw dt ref, cond, l ref, cond ref, cond, g + cond met cond met ref cond bed dt ( dw dt dw dt) dm ref, f, evap dt = φ M sg des + dw dt = * ( 15D R ) ( E RT )( w w) 2 exp so p a ads cond sg g evap dt = UA sg bed bed LMTD cond evap LMTD cond sg sg n = N bed n= 1 sg bed n sg sg bed (8/25)

Adsorbent bed Chiller modeling: Performance indicators Heat capacity ratio HCR = M sg C sg M met C met Number of transfer unit NTU = UA bed m& w C w Chiller cooling capacity Chiller heating capacity Chiller COP Chiller efficiency t cycle ( Tchw, in Tchw out ) dt tcycle Q evap = m& chwcw, 0 Q heat t cycle = m& 0 hw C w COP = Q evap Q heat ηchiller = COP COP Carnot ( Thw, in Thw, out ) dt tcycle (9/25)

Water Outl let Temperatures [ o C ] 100 90 80 70 60 50 40 30 20 10 Chiller modeling: validation study (1) 0 Tchwi_Mod Tchwo_Pred Tcwi_Mod Tcwo_Pred Thwo_Pred Thwi_Act Thwo_Act Tcwi_Mod Tcwo_Act Tchwi_Act Tchwo_Act Thwi_Mod 0 240 480 720 960 1200 1440 1680 1920 Cycle Time [ S ] Comparison between predicted and actual heating, cooling and chilled water outlet temperature Based on the Comparison between predicted and actual heating, cooling and chilled water outlet temperature, there are a good agreement. (10/25)

Chiller modeling: validation study (2) Using 372 data point the deviation analysis have been achieved A PD = (% Deviation ) N data point ABS (% Deviation ) data point Term A-PD ABS-PD Hot water outlet temperature -1.6% 2.4% Cooling water outlet temperature -1.1% 3.4% Chilled water otlet temperature -16.5% 16.5% Cooling capacity 12.9% 12.9% Heating capacity 10.9% 10.9% Chiller COP 2.8% 2.7% PD abs = N Based on average inlet and predicted data of one steady cycle using 4 different runs ABS-PD have been analysed as Model absolute average percent deviation should be below 30% to be acceptable Term RUN-1 RUN-2 RUN-3 RUN-4 T hw,o 1.6 1.5 1.6 0.9 T cw,o 0.9 0.8 1.0 0.0 T chw,o 12.3 13.1 13.3 15.7 Q heat 10.3 9.9 9.9 10.6 Q cool 13.1 13.6 13.5 17.8 COP 3.7 3.9 3.8 7.8 (11/25)

FIN SPACING AND CHILLER PERFORMANCE (12/25)

Fin spacing: Bed physical performance Tight fins arrangement Loose arrangement The effect of fin configuration on fin height The effect of fin configuration on HCR HCR is the ratio between heat capacity of silica gel and adsorbent bed heat exchanger metal. Higher HCR means higher heat absorbed by silica gel relative to metal which is necessary to improve adsorption chiller heat transfer performance. (13/25)

Fin spacing: Bed thermal performance NTU is a dimensionless parameter whose magnitude influences heat exchanger thermal performance. The effect of fin configuration on bed NTU during heating The effect of fin configuration on bed NTU during cooling As fin width does not affect the adsorbent bed thermal performance the effect of fin spacing only on chiller performance have been achieved. (14/25)

Fin spacing: Chiller performance In normal bed design as fin spacing reduces from max to min ratio: Chiller cooling capacity increased by 27.7%. Heating capacity increased by 32.4% to heat up the excess amount of metal. Chiller COP slightly reduces by 3.7% because of the rate of heating capacity increase higher than the rate of cooling capacity increase Chiller Cooling and Heating Ca apacity [ kw ] 750 700 650 600 550 500 450 400 350 Heating Capacity Cooling Capacity Chiller COP 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.40 0.35 Chiller COP [ - ] 300 0.30 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 Fin Spacing Ratio [ o C ] Chiller performance versus fin spacing (15/25)

OPERATING TEMPERATURES AND CHILLER PERFORMANCE (16/25)

Operation temperature: Cooling capacity and GT lift To evaluate the influence of operating temperatures on chiller performance a term named Generation Temperature Lift (GTL) is used which is the difference between heating and cooling water inlet temperatures. Chilled water inlet temperature is mainly based on zone load, where it is kept constant. As generation temperature lift increases chiller cooling capacity increases gradually for all cooling water inlet temperature. At fixed generation temperature, as cooling water inlet temperature reduces chiller cooling capacity increases. Chiller Cooling Capa acity [ kw ] 550 500 450 400 350 300 250 200 150 100 50 0 Tcw_in = 25.0 Tcw_in = 30.0 Tcw_in = 35.0 Tcw_in = 40.0 Experiments 20 25 30 35 40 45 50 55 60 65 70 75 80 470 460 450 440 430 Generation Temperature Lift [ K ] 420 59.1 59.2 59.3 59.4 59.5 59.6 59.7 Chiller cooling capacity versus generation temperature lift (17/25)

Operation temperature: Efficiency and GT lift At low cooling water inlet temperature, the chiller efficiency decreases with increasing the generation temperature lift over the tested range. At higher cooling water temperature (T cw >30 o C), the chiller COP initially increases to a certain point and then reduces with increasing the generation temperature lift. Dropping chiller efficiency The first reason of dropping chiller efficiency is the insufficient refrigerant circulation to generate cooling power. That can be recognised while chiller operates under low generation temperature lift accompanied with high cooling water temperature. The second one is the significant heat losses in case of high generation temperature lift. Chiller Efficiency [ COP P/COP carnot ] 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 COP Carnot = COP = Q evap Q heat Tcw_in = 25.0 Tcw_in = 30.0 Tcw_in = 35.0 Tcw_in = 40.0 [( T ads T des ) T des ] [ T evap ( T ads T evap )] η chiller = COP COP Carnot 20 23 26 29 32 35 38 41 44 47 50 53 56 59 62 65 68 71 74 77 Generation Temperature Lift [ K ] Chiller efficiency versus generation temperature lift (18/25)

Operation temperature: COP and GT lift At low cooling water temperature, the chiller COP decreases with increasing the generation temperature lift over the tested range. At higher cooling water temperature (T cw >30 o C), the chiller COP initially increases to a certain point and then remains relatively constant with increasing the generation temperature lift. Load control strategy(t cw >30 C): (T cw Example, at cooling water temperature of 35 C, the chiller cooling capacity increased almost linearly (from 180 to 342kW) with increasing the generation temperature lift (from 40 to 65K). That reduces chiller COP by extremely tiny value (from 0.63 to 0.60) and its efficiency as well (from 0.68 to0.52). Chiller COP [ - ] 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 Tcw_in = 25.0 Tcw_in = 30.0 Tcw_in = 35.0 Tcw_in = 40.0 Experiments 20 25 30 35 40 45 50 55 60 65 70 75 80 0.80 0.75 0.70 0.65 Generation Temperature Lift [ K ] Chiller COP versus generation temperature lift 0.60 59.1 59.2 59.3 59.4 59.5 59.6 59.7 (19/25)

CYCLE TIME AND CHILLER PERFORMANCE (20/25)

Cycle time: Operation modes (1) Mode [ A ] Ads/Des Mode [ B ] -Mass recovery Ads/Des Mode 425 second Total cycle time 480 second Heat Rec Mode 20 second Mass Rec Mode 35 second Mode [ C ] -heat recovery (21/25)

Cycle time: Operation modes (2) Mode [ D ] Ads/Des Mode [ E ] -Mass recovery Ads/Des Mode 425 second Total cycle time 480 second Heat Rec Mode 20 second Mass Rec Mode 35 second Mode [ F ] -Heat recovery (22/25)

Cycle time: Cooling capacity While investigating the influence of cycle time on chiller performance the adsorbent bed fin configuration and operating temperatures are kept at its design values. Zone of maximum cooling capacity 6.1% Increase in cooling capacity compared by design conditions Chiller cooling capacity versus Ads/Des time and mass recovery time and at recovery time of 60 seconds Chiller cooling capacity versus Ads/Des time and mass recovery time and at recovery time of 20 seconds Chiller cooling capacity versus Ads/Des time and mass recovery time and at recovery time of 100 seconds (23/25)

Cycle time: Optimum timing combination A global optimisation technique is required, where most of the currently published work on the effect of operation conditions are based on parametric runs of chosen optimum parameters. Genetic algorithm technique is used where: One of the robust population based global optimisation techniques GA has the advantage over standard optimisation algorithms of solving problems of discontinuous, non differentiable, stochastic and/or highly nonlinear objective function Optimisation parameters: The cooling capacity is the objective function. Number of population for each individual per generation = 20 Number of elite individuals = 2 Crossover fraction = 0.8 The rest of individuals were managed by means of mutation. The global optimum time periods obtained are off designvalues : 345secondsforAds/Destime---------- (425s). 12 seconds for mass recovery time---- 0(35s). 14secondsheatrecoverytime----------0(20s). Chiller performance changed compared by design cycle timing where: Chiller cooling capacity increased by 8.27%. Chiller COP reduced from 0.66 to 0.60. A/D time = 250 450 M/R time = 10 50 H/R time = 10-50 (24/25)

Conclusion The following points canbe concluded: The presented simulation model predicted the performance of actual 450kW adsorption water chiller with good accuracy. The modelisaglobal model thathas theabilitytoinvestigate theeffectofvarious physical and operation parameters on the performance of the adsorption chiller. Reducing fin spacing can increase the cooling capacity but can reduce the chiller COP due to increasing the metal content of the chiller. Using cooling water inlet temperature over 30, generation temperature lift can be used as a load control tool. Using optimal cycle time, chiller cooling capacity can be increased by 8% and the COP reduces from 0.66 to 0.6. (25/25)

(26/25)