APPENDIX 6 (not yet reviewed by UCCS) STRUCTURAL ANALYSIS/VIBRATION CRITERIA

Similar documents
The designer shall also submit additional information required by the University as described and underlined below.

A/E REVIEW CHECKLIST STRUCTURAL

Technical Assignment #3 November 15, 2004 Lateral System Analysis and Confirmation Design

BROCHURE # 108 CONSTRUCTION PLAN COMPONENTS

See the IRC for additional information. See CPD-DS Information Bulletin 100 for Requirements for 1 & 2 Family Dwelling plan submittals.

ROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA Tel: Fax:

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5

Texas Tech University Health Sciences Campus - MSBII Supplemental Bid Instructions March 3, 2017

North Shore at Canton Baltimore, MD Beau Menard Technical Report 1

Project Address: Name of Person Completing Form:

2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.

Prescriptive Engineering Helix TM Above Grade Tables

REINFORCING TABLES INSTALLATION MANUAL

Simplified Building Schematic for Typical Floor (Levels 9 through 22):

Statement of Special Inspections Michigan Building Code 2012 (MBC 2012)

Structural Inspection

SFR SUBMITTAL REQUIREMENTS

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Rutgers University Law School Building Addition and Renovation Camden, NJ

Dead Loads (psf): Concrete Floor Slab on Metal Deck 45 psf Mechanical and Ceiling 7 psf Miscellaneous 5 psf Exterior Wall 80 psf

SEATTLE CENTRAL COLLEGE BROADWAY PERFORMANCE HALL SEATTLE, WASHINGTON STRUCTURAL EVALUATION FOR PREPARED BY PCS STRUCTURAL SOLUTIONS

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Structural Technical Report 1 Structural Concepts/ Structural Existing Conditions Report

Sponsored by The Boston Association of Structural Engineers and the Structural Engineers Association of Massachusetts

Structural Concepts and Existing Conditions Report

Fundamentals of Building Construction: Materials and Methods

SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division. Project Address:

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Table of Contents.2. Introduction...3 Gravity Loading and Deflections..4. Existing Structural System..8

OF THREE NEW BUILDINGS BEING CONSTRUCTED TO REPLACE THE EXISTING COMPLEX. THE FLOOR SYSTEM OF GEORGE READ HALL IS A HAMBRO COMPOSITE SYSTEM

SPECIAL INSPECTION AGREEMENT

PENTABLOCK Technical Information 190mm Series

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage

Structural. Professional Engineers Ontario

An information series from the national authority on concrete masonry technology. Drainage swale. (optional) Cap unit. (optional)

STATE UNIVERSITY CONSTRUCTION FUND

Thesis Proposal. University Hospitals Case Medical Center Cancer Hospital. Daniel C. Myers. December 12, 2009

Stone and Masonry Veneer

SECTION STAY-IN-PLACE INSULATED CONCRETE FORMING SYSTEM

Statement of Special Inspection Requirements

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

0103 Plan Reading 4% Read plans to verify the project conforms with the code, approved plans, and construction documents.

* RESIDENTIAL PLAN REVIEW *

DIVISION: SPECIALTIES SECTION: PROTECTIVE COVERS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC EVALUATION SUBJECT:

Amity Design Ltd. House #7&9, Road #9 Block #D, Section #11 Mirpur Dhaka 1216, Bangladesh (23.820N, E) 03.MARCH.2014

This specification describes the minimum requirements for Vale's standard practice for Concrete drawings.

INFORMATIONAL PACKAGE ACCESSORY RESIDENTIAL BUILDINGS (INCLUDING DETACHED GARAGES, STORAGE BUILDINGS & WORKSHOPS)

ABOVEGROUND HOME FALLOUT SHELTER H-12-2 / November 1983 (Supercedes H-12-2 dated June 1980)

SECTION PRECAST CONCRETE BIOSOLIDS STORAGE TANK

EFFECTIVE USE OF THE IBC/CBC

Armopanel Concrete Wall System. Design Guide B-3.1. BASEMENT WALLS

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

SPECIAL INSPECTION AGREEMENT FORM

SOUTHERN NEVADA AMENDMENTS TO THE 2009 INTERNATIONAL RESIDENTIAL CODE

PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA (831) FAX: (831)

FOUNDATIONS. Foundations Copyright G G Schierle, 2006 Press Esc to end, for next, for previous slide 1

CIVIL BREADTH Exam Specifications

Project Seismic Vulnerability Assessment For SFCC District Building 33 Gough Street San Francisco, California 94103

North Mountain IMS Medical Office Building

DESIGN STANDARDS WASHINGTON UNIVERSITY SCHOOL OF MEDICINE

BUILDING STANDARDS COMMISSION (BSC) EF EMERGENCY EXPRESS TERMS

UCC Permit Application Procedures

ANCHOR BOLT ANGLE (AISC) ARCH. A. BOLT LBS. ARCHITECTURAL POUNDS B.O. DOUBLE ANGLE (AISC) BCI BOTTOM OF I-JOIST (BOISE CASCADE) LVL

ANCHOR BOLT ANGLE (AISC) ARCH. A. BOLT LBS. ARCHITECTURAL POUNDS B.O. DOUBLE ANGLE (AISC) BCI BOTTOM OF I-JOIST (BOISE CASCADE) LVL

Structural Support 1212 Main Street April 15, 2013 Belmar NJ 07719

A Design Review of Waterproofing Codes

KORA_Req._for_Eng._Studies_on_Stouffer_Apts. KU Reference No

Building Department Informational Handout

TOWN OF ROTTERDAM BUILDING DEPARTMENT RESIDENTIAL ACCESSORY BUILDINGS AND STRUCTURE PERMIT APPLICATION Ext 395

Great Lakes District

Structural Requirements

SECTION / ENGINEERED AGGREGATE PIERS (SOIL REINFORCEMENT AND FOUNDATION SYSTEM)

APPLICATION FOR A BUILDING PERMIT (Retaining Wall/Garden Wall Construction Details)

Borough of Doylestown Building and Zoning Department

Structural Engineering Services by Licensed Professional Structural Engineers in Caledon, Ontario

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:

RESIDENTIAL PATIO COVER Submittal/Permitting Guidelines

BUILDING A NEW HOME. Construction Permit Tips For Home Owners

SPECIAL INSPECTION AND TESTING AGREEMENT

Building Guide. Colorado Chapter of the International Conference of Building Officials. Building Guide

PENNSAFE BUILDING INSPECTION SERVICES LLC NEW COMMERCIAL BUILDING UCC PLAN REVIEW HANDOUT AND CHECKLIST

Structural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Building B

Building Permit Application ~Commercial~ *** All Drawings Must be Sealed by an Architect or an Engineer *** Company Name at Site Address.

Jackson Crossing Located in Alexandria, VA. Technical Report 1 Michael Bologna

Lantz-Boggio Architects, P.C LBA Project No

GUIDELINES FOR RETAINING WALLS 4-0 IN HEIGHT OR LESS

REQUEST FOR PROPOSAL FOR MATERIAL TESTING AND SPECIAL INSPECTION SERVICES

SECTION BUILDING EARTHWORK

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures

Mondol Fabrics Ltd. Nayapara,kasimpur, Gazipur ( N, E0) 8th March 2014

Product Information Bulletin

Lintel Tables Design Notes and Limitations

Ordinance No July 1, 2016

Structural Technical Report I October 5, 2006 Structural Concepts / Structural Existing Conditions Report

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3%

DIVISION: SPECIALTIES SECTION: PROTECTIVE COVERS REPORT HOLDER:

STRUCTURAL. Technical. Option COLLEGEE. Susque hanna. Page 1

mortarless Design Manual Part 1 (AS 3600:2009) Section 1 Page 1 AS 3600:2009 PLAIN AND REINFORCED CONCRETE - CODE OF PRACTICE

Position Statement on Sealed Truss Placement Diagrams for Projects in the State of California

Transcription:

APPENDIX 6 (not yet reviewed by UCCS) STRUCTURAL ANALYSIS/VIBRATION CRITERIA GENERAL The purpose of this standard is to identify structural submittal requirements, as well as identify vibration design criteria for campus buildings. A. During Schematic Design, the design engineer shall submit: Code and Loadings: State the governing code used for design. State the live loading to be used, including floor loads, wind, snow, and seismic, together with data to justify any difference from established criteria. Seismic design shall be in accordance with IBC. State the seismic zone and values used for K and C. Structural System: Provide a comparative description of feasible structural systems for the building, i.e., consider wood, steel, concrete, masonry. Give a description of the type of construction proposed and reasons therefore, including the structural framing system. The structural design should be carried only to the point where the total framing systems are determined and a realistic cost estimate can be made. Foundation Design: Describe the type of foundation proposed and define the basis for selection. Include bearing capacity, anticipated settlement, alternatives considered, and other pertinent design factors. Also include the depth of excavation, disposition of excavated material, whether in place foundation material will be compacted, whether imported fill is required, whether compacted backfill will be utilized as foundation, and the frost penetration. State ground water level and method of waterproofing. State needs for drainage or vapor barrier. Describe pertinent corrosion control methods. Refer to the Soils Report included in the supplements. Vibratory Design: The structural design engineer shall submit a summary report of the vibration criteria that will be used in the structural design of the building. Structural drawings should include: Foundation plan Floor and roof framing plan Details are not required B. During the Design Development phase the following plans shall be submitted: 1

Structural drawings should include: Foundation plan Floor(s) and roof framing plans: The majority of the framing members and columns shall have sizes indicated. Some typical foundation details. Foundation plan shall show type of foundation proposed, depths, sizes and reinforcing of footings, relationship of walls and floor slab to foundation system, overall dimensions, column spacing, joint pattern in slab on grade, tie beams, grade beams, etc. Some typical roof framing details C. During the Construction and Contract Documents phase, the following shall be submitted: Full or representative computations (depending on the size of project) Present complete structural calculations covering all parts of the structure and miscellaneous facilities. Calculations shall be bound and indexed. When a computer is utilized to perform design calculations, the analysis will include, but not be limited to, the following information. Design methods will be described, including assumptions, theories, and technical formulas employed in design solutions. Present copies of computer input data and output summaries in user friendly language, accompanied by diagrams which identify joints, members, areas, etc., according to the notations used in the data listings, will form integral parts of the design analysis in lieu of manual computations otherwise required. Complete listing of all computer output will be provided in a separate binding when it is too voluminous for including in the design analysis. These listings will be augmented with intermediate results where applicable, so that sufficient information is available to permit manual checks of final results. Live loads shall be placed to produce maximum stresses and minimum stresses where there is a possibility of stress reversal. Vibrational criteria and supporting calculations demonstrating compliance with UCCS vibrational criteria. If special methods of solution, tables, etc., are employed, references shall be made in the calculations to the sources of such material. Adequacy of existing structure, where applicable, to account for new functional loads or new criteria. Drawings All drawings shall be complete and represent coordination by the architect with all disciplines. Evidence of this coordination shall be provided by the Architect at the Final Design Review. 1.3 VIBRATION DESIGN CRITERIA FOR BUILDINGS 2

A. In order to minimize building construction costs associated with increased vibration control, laboratory areas and areas of sensitive equipment shall be designed to be located at grade or below in the proposed building or addition. B. Facilities Services may require that a vibration consultant be employed to analyze both overall building structure and specific placement and isolation of machinery and equipment with moving parts. The structural engineer, mechanical engineer, electrical engineer, and the architect will be required to coordinate their work with this consultant and to follow Facilities Management direction based upon the recommendations of the vibration consultant. C. Vibration analysis shall conform to industry standards, such as American Institute of Steel Construction s Design Guide 11. D. General office spaces shall be designed to meet a recommended floor vibration velocity limit of 400 micrometers per second (Residential Day Criterion Curve, see Figures 1 & 2). E. Classrooms and computer lab spaces shall be designed to meet a recommended floor vibration velocity limit of 200 micrometers per second (Residential Day Criterion Curve, see Figure 1). F. General laboratory/research areas, where optical microscopes or other similarly sensitive equipment will be operated, shall be designed to meet a recommended floor vibration velocity limit of 50 micrometers per second (VC A Criterion Curve). Figure 2 shall be used as a basis for vibration velocity limits when the sensitive equipment manufacturer s recommendations are not available. G. Precision instrument spaces shall be designed according to the sensitive equipment manufacturer s recommendations. These areas should be designed considering the effects of adjacent equipment, other sources of vibration, and operations. The use of a consultant specializing in vibration analysis and control is required for both new construction and renovations. H. The above criteria may be relaxed on a case by case basis provided the relaxed velocity limit will not affect the current and future utility of the space. 3

1.4 VIBRATION CONTROL ON MECHANICAL EQUIPMENT A. Provide vibration isolation devices for limiting transmittance of vibration from vibration producing equipment to the structure on which it is supported or attached. The type of vibration isolation device is a function of building uses, size of mechanical equipment, and the frequency at which the equipment operates. The mechanical engineer or a vibration consultant shall consider these factors when designing the vibration isolation system. B. Provide the types of vibration isolation devices as recommended by the respective mechanical equipment manufacturers or vibration consultant, to isolate vibrations for each particular piece of equipment. Include a schedule of equipment (i.e. pumps and fans) to be isolated. 4

FIGURE 1: Taken from Colin Gordon s Generic Vibration Criteria for Vibration Sensitive Equipment 5

FIGURE 2: Taken from Colin Gordon s Generic Vibration Criteria for Vibration Sensitive Equipment END OF APPENDIX 6 6

7