THE PERFORMANCE OF XLPE WATER TREE RESISTANT INSULATION SYSTEMS AGAINST THE REQUIREMENTS OF DIN VDE /A3

Similar documents
Accelerated Aging Tests for MV Cables

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

History of Cable Systems HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES. Nigel Hampton

U.V resistance UL Sunlight Resistance. Flame retardant IEC

EHV XLPE CABLES CDCC LINE

BLACK EPR INSULATED MEDIUM VOLTAGE CABLES. Ronald F. Frank, Eng. Consultant

40/69 kv to 127/220 kv XLPE

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

XLPE MATERIAL NATIONAL CABLES INDUSTRY XLPE INSULATED MEDIUM VOLTAGE CABLES

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854

FLEXIBLE POLYMERS WIRE & CABLE GRADES FOR MEDIUM/HIGH VOLTAGE POWER CABLES.... we make better polymers

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

Single core conductor BETAtherm 145

A Deep Insight on Improvement in HV and EHV XLPE AC Cable Technology

Property Unit Typical Value Test Method Density gm / cm ASTM-D-792 Melt Flow Index (190 C, 2.16

MATERIAL STANDARD FOR CABLES AND WIRES

NPS/002/023 Technical Specification for 132kV Power Cables.

STANDARD FOR CONCENTRIC NEUTRAL CABLES RATED 5 THROUGH 46 KV

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

INTERNATIONAL STANDARD

3 MODIFICATIONS TO EXISTING STANDARDS

Construction guideline

--> Buy True-PDF --> Auto-delivered in 0~10 minutes. TB/T Translated English of Chinese Standard: TB/T1484.

15~35KV Termination Kit

PILC Replacement: Getting the Lead Out

11-SDMS-01 REV. 03 ( )

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

3M Cold Shrink Joint, SC145-II/SS145-II

INTERNATIONAL STANDARD

KEMA INSPECTION REPORT

15 kv EPR Insulated, Jacketed, URD Cable

Clark Public Utilities

PRODUCT SPECIFICATION

THE PATHWAY TO POWER HIGH AND EXTRA HIGH VOLTAGE CABLES

PRY-MOULD. High Voltage Accessories for Extruded Cables

*** Supercedes: BECO E and COM , , & ***

DXL 4233 Insulation for Low Voltage Power Cables

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

WIND TURBINES DEDICATED CABLES LV AND MV VOLTAGE RUBBER CABLES

Data Sheet 110kV TD123II dry type outdoor termination

Heating Cables DATASHEET

ABSTRACT EXPERIMENTAL KEYWORDS. INTRODUCTION 1. Introduction Crosslinked polyethylene (XLPE) has been extensively used. samples.

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

Cable accessories for shipbuilding and off-shore units

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination

Accreditation No: LAB 041. Electrical Measurement & Test Laboratory (EMTL), PCSIR Labs. Complex, Lahore Pakistan.

Condition assessment of synthetic insulated cables and accessories operating more than 20 years on the French network. M. MAMMERI SILEC France France

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Asset Management of MV Cables using Data Driven Health Indices for Water Treeing

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

Termco Heatshrink.

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer

Mecoline IS RDX 5241 F

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

TI 20 PVC TI 20 INSULATED TELEPHONE WIRE

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

Thermal Oxidation and Growth of Insulators (Chapter 3 - Jaeger 3) Key advantage of Si: Oxidation of Si into SiO 2 (glass) Major factor in making

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

ENERGY PROTOLON(SMK) LWL. (N)TSKCGEWOEU Medium Voltage Reeling Cable with integrated Fibre Optics

Article-No. Type. All dimensions in mm. Subject to technical changes. Other dimensions, reel lengths or colours available on request.

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

Rayfit The advanced heat-shrinkable joint sleeve for medium voltage joints up to 36 kv NEW ENERGY DIVISION

PV Solar Wiring Solutions

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Investigation of leakage current flow through wooden poles structures on overhead distribution system

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990)

8 139 Foreword c) Technical Hydraulic oil Hydraulic/gear oil Accepted. Gear oil added throughout the standard

This document is a preview generated by EVS

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY (PEDE) TENDER DOCUMENTS FOR

Brugg Cables High Voltage Accessories. Swiss solutions for independent applications.

Thermal Management Solutions for Automotive, Lighting and Industrial Applications

catalog Copper Wires

Lightning impulse (LI) breakdown testing of a rubber-epoxy interface

«CABLE T 92» WORKSHOP BALI, INDONESIA JUNE, 1992 POWER CABLES IN TROPICAL ENVIRONMENTS : SYNTHESIS. By L. DESCHAMPS SEE / EDF (France)

6A V CVQ cable (C rank)

COMPOUNDING OF SEMICONDUCTIVES FOR HIGH VOLTAGE CABLES

Process Filtration From Pure to Sterile

SOLARLOK BREEZE Junction Box

DEVELOPMENT OF HIGH VOLTAGE EXTRUDED CABLES: THE ITALIAN EXPERIENCE

MANUFACTURER'S QUALITY ASSURANCE PLAN (QAP - Instrumentation cables)

Raychem S1297 and /97 Hot Melt Adhesive

Electric cables. CRANES APPENDIX

VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible, Heat-Shrinkable, Flame-Retardant

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

26/35kV Copper XLPE Insulation Electric Cable

TYPE TEST REPORT OF 11 KV 3 x 240 mm² CU/XLPE/SWA/PVC CABLE. Kinectrics International Inc. Report No.: K RC-0001-R00.

VLSI Design and Simulation

LONG TERM SUSTAINABILITY OF CABLES. David E. Griffiths Olex New Zealand Limited

FURUKAWA ELECTRIC TAPE FOR ELECTRICAL USES

Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths

FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I

Electrical Insulating Tapes

Transcription:

C I R E D 18 th International Conference on Electricity Distribution Turin, 6-9 June 25 THE PERFORMANCE OF XLPE WATER TREE RESISTANT INSULATION SYSTEMS AGAINST THE REQUIREMENTS OF DIN VDE 276-65/A3 M.W. Aarts*, J.B. Kjellqvist*, A. Mendelsohn +, K. Vaterrodt, *Dow Europe GmbH, Switzerland Email: jkjellqvist@dow.com Email: maarts@dow.com + The Dow Chemical Company, USA Email: mendela@dow.com Institut "Prüffeld für elektrische Hochleistungstechnik" GmbH, Germany Email: vaterrodt@iph.de INTRODUCTION Polyethylene was introduced as an insulation material for electric power cable more then 4 years ago. Polyethylene s inherent characteristics of toughness, resistance to chemicals and moisture, low temperature flexibility, and excellent electrical properties, along with low cost and easy processability, make it a very desirable material for insulating low, medium and high voltage electric cables. Since its introduction, there have been a number of significant advances in materials technology that have contributed to polyethylene s continued worldwide position as the material of choice for insulating cable. While, in North America the use of water tree resistant insulation (WTR) is predominant, the European market has diverged into the use of so-called homo-polymer systems and co-polymer systems. The use of co-polymer systems in Europe has been governed especially by the two-year wet aging requirements of VDE. The use of homo-polymers is preferably used in dry designs, where the access of water to the cable core during the life time of the cable is prevented. The harmonized standard CENELEC HD65 S1 HD 65 S1:1994/A3:22 "Electric cables - Additional test methods" is in place now. It contains the two-year aging test in water and may drive a more uniform approach to the use of insulation materials. The current study evaluates the performance of WTR insulation materials against critical European test requirements. The paper will also discuss the fundamental mechanism of the WTR technology in this material. PEROXIDE CROSSLINKING OF POLYETHYLENE The peroxide cross-linking of polyethylene will be reviewed briefly as by-products can play an important role in life time predictions of cables. The peroxide cross-linking process is a first order reaction that is initiated with the thermally driven homolytic cleavage of the peroxide bond. After thermally induced cleavage of the peroxide, and hydrogen abstraction from the polymer backbone to initiate cross-linking, an alcohol by-product is formed. In the case of di-cumyl-peroxide, the alcohol that is formed is cumylalcohol. If traces of acid are present in the material, these alcohols can dehydrate to form water. By-products, water content, and the presence of voids can alter cable test results and cable life [1]. EXPERIMENTAL Three medium voltage cables according to DIN VDE 276-62 were extruded with a triple layer die for the conductor screen, insulation, and insulation screen and were cured under nitrogen atmosphere in a continuous vulcanization process. A homo-polymer, a co-polymer, and WTR XLPE insulation were used. In all cases, the semi-conductive screens were made from the same conventional material, fully bonded to the insulation with a stranded aluminum conductor of 25 mm². The thickness of the insulation was between 3.2 and 3.3 mm. These cores were conditioned, exposed to water and tested under field strength of 6 6.7 kv/mm, analogous to 2 kv medium voltage cables. Microscopy was used to identify the development of water trees with aging. The loss factors of the cables have been measured in the range up to 18 kv (3Uo) as a function of temperature up to 13 C. They were measured in water, in hot air, and after additional dry conditioning. Measurement of the thickness of the insulation and the semi-conductive screens The measurements are carried out according to HD 65 S1: 1994/A1; 1996/pt. 2.1.11.1 and also IEC 811-1-1, pt. 1. Six measurements per test piece and layer were made, starting where the insulation was thinnest. To evaluate the whole length of the core, test pieces were taken at 1, 9, 18, 272, 363, and 453 m. Measurements were made with a profile projector Mitutoyo PJ 3. Calculation of the AC breakdown field strength The geometrical dimensions of model cables and cores, 1 Caronia P.J., Cogen, J.M., Kjellqvist J.B.L., Aarts M.W.A.M., New XLPE Insulation for HV and EHV cables, Proceedings Jicable 3, pp. 453-457. CIRED25

C I R E D 18 th International Conference on Electricity Distribution Turin, 6-9 June 25 especially the thickness of the insulation can vary. Therefore it is advantageous for a comparison between types of model cables to use the breakdown field strength instead of the breakdown voltage. Using the breakdown voltage and the core dimensions at the breakdown site, the breakdown field strength at the inner screen (effective value) is given below: U Eeff, IS = r + i a r i ln ri U : breakdown value (effective value) [kv] r i : radius above inner screen [mm] a : thickness of insulation [mm] E eff,is : AC-field strength at the inner screen [kv/mm]. Figure 1. Calculation of the field strength in the case of an eccentric core. E eff,is is the local maximum field strength at the breakdown site, which is designated as maximum field strength in the Weibull analysis. The values of r i and a were determined by help of the piece of core with the breakdown channel in it. This piece was cut into slices, which were used to measure the values by means of the profile projector. Silicone oil bath test A visual inspection was carried out by means of a strong lamp and a glass vessel of 4 mm depth with silicone oil at a temperature of 135 C. Test pieces were taken at, 9, 18, 27, and 362 m of the core length with a length of 45 mm each and the outer screen was removed. Subsequently, they were put in the bath until transparency of the insulation was achieved, which made possible an analysis of irregularities, like voids, ambers, black contaminants, etc. The presence of vented trees was detected and marked with a needle for subsequent optical analysis. Harmonized long term aging test Accelerated aging tests were carried out according to CENELEC HD 65 S1. All cable cores have been conditioned during 5 hours at (55 ± 5) C in tap water before aging to remove remaining by-products of crosslinking and also allow the insulation and screens to absorb moisture. The electrical aging was performed in a thermally isolated water tank at an aging voltage of (16 ± 3) kv. In accordance with the new harmonized CENELEC long-term test procedure, an ageing voltage of 18 kv for 1 kv cable cores is specified. It follows that the aging field strength at the inner screen is in the range form 6. to 6.7 kv/mm for conductor sizes between 95 and 4 mm². As the dimensions of the model cable are smaller, the same aging field strength at the conductor screen is reached at 16 kv instead of 18 kv. Both ends of the coils were prepared with terminations. Determination of the AC breakdown voltage The active sample length was 1 m plus an additional 5 m for water terminations. Each of the samples had to be fitted with an additional copper wire screen. After preparation, the AC step test was carried out at room temperature (2 ± 15) C, starting with 5 minutes at 18 kv and followed by 6 kv increases, each during 5 minutes, until breakdown. A small core length with the breakdown channel was cut out for further examinations. All of the AC breakdown data is reported by means of Weibull statistics and a maximum likelihood estimation of the 95% confidence intervals. The Eta parameter is the AC breakdown value at the 63 % confidentiality level. The Beta value is the shape parameter. Higher Beta values indicate a steeper slope of the failure curve. The latest draft of DIN VDE 276-62/A3 of September 23 contains a class model rather then the Weibull statistical model. The required values are summarized in Table 1. Number of Samples Breakdown Strength 6 2 kv/mm 4 26 kv/mm 2 6 32 kv/mm 26 kv/mm Table 1. Class models according to draft DIN VDE 276-62/A3 For the evaluation of the step test results after 1 and 2 years the results with both models will be reported. Measurement of the dissipation factor The dissipation factor and the capacitance were measured as a function of temperature and voltage level. Both virgin samples as well as aged samples were tested. The samples were prepared by mounting a copper wire screen on to the outer screen which was fixed with non-conductive tape. The sample ends were prepared with slip-on terminations together with guard ring configurations. Samples of virgin cores and cores after wet conditioning (55 C ± 5 C, 5 h) and after wet aging were measured in different states. Virgin samples were measured as delivered and after conditioning during 18 hours at 9 C in air. Samples after wet conditioning and wet ageing were measured in water up to 9 C and in an oven up to 13 C and partly after conditioning during 18 hours at 9 C in air. For the measurement in water the samples were electrically insulated from the water bath by means of a nonconducting flexible tube filled with de-mineralized water. Determination of the water tree pattern With the aim to look for trends and to differentiate between the insulation systems, the water tree examination was carried out in two different ways. First, the breakdown channel area of the core sample with the lowest break down strength was analyzed for water trees. A core piece containing the breakdown channel was taken and microtomed in slices of 5 µm thickness, with the main part of the breakdown channel in some of the slices. These slices were stained in a CIRED25

C I R E D 18 th International Conference on Electricity Distribution Turin, 6-9 June 25 methylene blue dye solution [2] for examination. Trees were investigated with an optical microscope with a magnification of 75. Secondly, more then 1 m per type of core were inspected in the silicone oil bath test to analyze a possible growing of vented trees at the interface between the inner semi-conductive layer and the insulation layer. Vented trees starting from the inner screen were marked with a needle and subsequently microtomed and microscopically inspected. RESULTS OF THE EXAMINATION The designation of the various produced cores is as follows: A) extra clean standard homopolymer XLPE B) extra clean standard co-polymer XLPE C) extra clean water tree resistant XLPE In all cases the same type of a standard bonded semiconductive screen was used for the inner and for the outer layer. The insulation thickness for all cores was in the range between 3.2 and 3.3 mm, i.e. it was slightly below the standard requirement of 3.4 mm for 6/1 kv cables. The thickness of the semi-conductive screens complied exactly with the standard requirements. The difference between the maximum and minimum values of the insulation thickness sometimes exceeded.5 mm. The requirements for the hot set tests as specified in DIN VDE 276-62 S1 Tab. 2A were passed at all times. Elongation under load [%] Permanent elongation [%] TYPE A 82-5 TYPE B 74-5 TYPE C 82-4 Table 2. Hot set test results of the tested cable cores. During the oil bath test no irregularities larger then 5 µm and no protrusion larger then 8 µm were found in any of the cable systems under investigation. Samples had been taken approximately every 9 m on a total of 5 m. The cores were found to be manufactured free of significant irregularities and the cleanliness was similar to standard MV cables. The quality was sufficient for further investigations. Breakdown strength with homo-polymer system slightly higher then after.5 years (28.2 kv/mm). 31. 33.4 35.9 33.4 12.8.858 Table 3. Weibull analysis after 1 year aging for the homopolymer 276-62/A3 as shown in Figure 1 below. 7 6 5 4 3 2 1 1 2 3 4 5 6 Figure 1. Class model values after 1 year aging for the homopolymer in four out of five samples was at the conductor screen. Channel width was between 43 and 56 µm. No visible origin of the breakdown cause could be detected. Breakdown strength with co-polymer system higher then after.5 years (3.8 kv/mm). 3.1 36.3 43.7 36.3 4.96.89 Table 4. Weibull analysis after 1 year aging for the copolymer 276-62/A3 as shown in Figure 2 below. in four out of five samples was at the conductor screen. 2 Larson, P.B. Dying methods used for the detection of water trees in extruded cable insulation, Elektra No. 86, January 1983, pp 53-59. CIRED25

C I R E D 18 th International Conference on Electricity Distribution Turin, 6-9 June 25 7 6 5 4 3 2 1 1 2 3 4 5 6 In order to evaluate the water treeing tendency 2 wafers of 5 µm thickness were taken following the procedure described before. No bow tie trees or vented trees were found in the WTR-polymer based In the homo- and copolymer system the bow tie tree density remained below 3/cm 3. Only the homo-polymer system showed an increased level of 11/cm 3 bow tie trees with a length between 5 and 1 µm. No vented trees were found in the homo-polymer system, whereas the density in the co-polymer system stayed below 2/ cm 3. Figure 2. Class model values after 1 year aging for the copolymer Channel width was between 4 and 56 µm, with one channel being 8 µm wide. No visible origin of the breakdown cause could be detected. Breakdown strength with WTR-polymer system slightly higher then after.5 years (28.2 kv/mm). 46.6 51.3 56.6 51.3 9.64.922 Table 5. Weibull analysis after 1 year aging for the WTR - polymer 276-62/A3 as shown in Figure 3 below. 7 6 5 4 3 2 1 1 2 3 4 5 6 Figure 3. Class model values after 1 year aging for the WTRpolymer in all samples was at the conductor screen. Channel width was between 6 and 7 µm. No visible origin of the breakdown cause could be detected. Water tree levels near break down channels Water tree levels of aged cables after silicone bath inspection. After aging, 1 m of each cable system has been inspected by means of a silicone oil bath test as described before. The level of vented trees, thus identified is summarized in Table 6. Vented trees/m After 6 months After 12 months TYPE A.5 1.3 TYPE B.3 4.2 TYPE C.2.5 Table 6. Identified vented trees per meter after silicone oil bath inspection. The tree size remained below 5 µm. Some trees after 12 months aging of TYPE B were larger. This may be explained by some statistical effects inherent to the test procedure, caused by the relatively low number of trees that can be practically detected in a length of 1 m. Dissipation factor of the various systems The dissipation factor has been measured as a function of temperature and voltage level for all investigated systems. A comparison at 9 C and at 18 kv is given in Figure 4 for new cores after production, after 5 hours at 55 C conditioning in water, and after 1 year conditioning in water at 4 C (CENELEC conditions). Dissipation Factor [E-4] 1 8 6 4 2 SYSTEM A SYSTEM B SYSTEM C New Water Aged Figure 4. Dissipation factor at 18 kv and 9 C temperature for new cores after production, after 5 hours conditioning in water and after 1 year water aging. The new cores were measured in a dry air oven, the samples after conditioning and wet ageing were measured in water. CIRED25

C I R E D 18 th International Conference on Electricity Distribution Turin, 6-9 June 25 It is evident that the performance of the WTR-polymer SYSTEM C is very similar to that of the homo-polymer SYSTEM A. The co-polymer SYSTEM C generally shows somewhat higher numbers after contact with water, due to the higher polar polymer Dissipation Factor [E-4] 6 5 4 3 2 1 SYSTEM A SYSTEM B SYSTEM C Figure 5. Dissipation factor of new cores at 18 kv and 13 C in air. DISCUSSION OF THE RESULTS initiation of the electrical break down could be visually identified. The WTR-system shows the lowest level of identified water trees both in the break down channel vicinity, as well randomly distributed in an investigated 1 m core length. This indicates a better performance in long term wet aging conditions. These results suggest that the use of WTR materials can be an excellent choice to pass the European two-year wet aging test. Such materials profit from more than 2 years experience in North America, both with strippable and fully bonded insulation screens. AKNOWLEDGEMENT Many thanks are extended to Dr. Gerd Heidmann, Berlin, for the valuable discussions on the test arrangements and data interpretation. AUTHORS M.W. Aarts, J.B. Kjellqvist, A. Mendelsohn, K. Vaterrodt, The dissipation factor of all three insulation systems meets the requirements of DIN VDE 276-62, valid for new insulation systems under all measured conditions. The difference between system A and C are probably more of a statistical nature, as typically the latter is measured to be somewhat higher. The wet aging up to 1 year so far does not raise the dissipation factor compared to unaged samples. The high retention of AC breakdown strength and the low level of tree growth for the WTR XLPE material are consistent with results from similar test programs [3]. Defects in the cable insulation may lead to trees and premature failure. The unique dissipation factor behaviour of the additive in the WTR XLPE insulation material makes it able to neutralize defects in the cable. This mechanism is based on the observation that trees initiate at points of high and divergent electrical stress such as imperfections at the semi-conductive shield-insulation interface. Sharp protrusions at the conductor shield-insulation interface can increase electrical stress by more than 2 times. At these stress points WTR XLPE will dissipate the electrical stress as heat, due to the increase of power factor as a function of electrical stress. The local increase in temperature will cause a further increase in power factor and more energy is dissipated until equilibrium is achieved. Not affecting the over-all dissipation factor of the cable core, the power factor response of the tree-retardant additive contributes to tree retardance and longer life by locally dissipating electrical stress only at defects in the cable. SUMMARY It has been found that the retention of the electrical break down strength of the WTR material shows the best performance after 1 year aging, when compared to homopolymer and co-polymer systems. No obvious causes for the 3 Mendelsohn, A., Person, T.J., Shattuck, G.B., Hartlein, R., Evaluation of tree retardant XLPE (TR-XLPE) and EPR insulated 35 kv cables after 17 years of field service, Proceedings Jicable 3, pp. 556-561. CIRED25