Pedestrian Flood Door

Similar documents
PEDESTRIAN FLOOD DOOR

Bottom Hinged Flood Barrier Operation & Maintenance Manual

To Contact PS DOORS:

SINGLE SWING DOOR PAIRED SWING DOOR

Pallet Gate Installation Instructions and Operators Manual

Installation Instructions/Operation and Maintenance Manual. Models PLG-60 PLG-72. PS DOORS Contact Information. Website psdoors.

To Contact PS DOORS:

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

HATCHSAFE Installation Instructions/Operation and Maintenance Manual Models: All Models

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

PAIRED LADDER SAFETY GATE Installation Instructions/Operation and Maintenance Manual

Installation Instructions/Operation and Maintenance Manual

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

SECTION A. Manufacturer's data sheets on each product to be used, including:

PAIRED LADDER SAFETY GATE Installation Instructions/Operation and Maintenance Manual

SECTION WATERTIGHT FLOOD PLANKS. A. ASTM A 36 - Standard Specification for Carbon Structural Steel.

LADDER SAFETY GATE Installation Instructions/Operation and Maintenance Manual

SECTION WATERTIGHT DOORS. A. Horizontal Sliding Flood Barrier with frame and hardware.

Installation Instructions/Operation and Maintenance Manual

Installation Instructions/Operation and Maintenance Manual

Installation Instructions/Operation and Maintenance Manual

SECTION INDUSTRIAL ACCESS / INSPECTION HATCH. A. Industrial Access / Inspection Hatch: Model AH-710

A. ASTM A 36 - Standard Specification for Carbon Structural Steel.

SECTION SOUND CONTROL DOORS

SECTION / STC 52 METAL SOUND CONTROL DOORS

OWNER S MANUAL SERIES MDS-96-BK, SM, DR

OWNER S MANUAL SERIES MDS-96-BK, SM, DR

SECTION VERTICAL MEZZANINE GATE U.S. Patent No:

TrueClean ToteTilter TM

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N

PalletPal Low Profile Disc Turntable

Installation, Operating and Maintenance Instructions Incognito Series Air Curtain

Installation Guide Document No BioSafe Cleanroom Windows Copyright 2017 Terra Universal Inc. All rights reserved. Revised December 2017

Mechanical Post Lift. Owner s Manual

RAY-CORE Structural Insulated Roof and Wall Panels

BASIC LOUVER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Installation Guide Document No Transaction Windows Copyright 2017 Terra Universal Inc. All rights reserved. Revised October 2017

55-Gallon Tilting Drum Ring

PLEASE SAVE THESE INSTRUCTIONS FOR FUTURE USE

BBL-4 FORK-MOUNTED BULK BAG LIFTER USE AND MAINTENANCE MANUAL

A. OSHA 1910, Subpart D, Fixed Industrial Ladders. C. ANSI A14.3, Safety requirements for Fixed Ladders

GF6580BH-1 PATRIOT LIBERTY QUARTER RAILS:

SECTION Motor Operated Horizontal Sliding Sound Control Door

6 Closet light. Model Due to continuing improvements, actual product may differ slightly from the product described herein.

Dandy Leveler UDLV-150 & UDLV-500 (New Style)

SECTION U.S. ALUMINUM SERIES BAL-350 HURRICANE RESISTANT BALCONY/TERRACE DOOR

Owner s Manual & Safety Instructions

SECTION HARDWARE

METAL LADDERS (LADDER SAFETY GATE FALL PROTECTION)

Festoon Manual Heavy Duty C-Track

AUTOMATIC FOLDING DOOR

DRUM-GRAB INSTRUCTION MANUAL

INSTALLATION GUIDE MODELS DMV2401 / DMV3001 / DMV3601 DMV4801 / DMV6001 / DMV60DS / DMV72DS

Model Defibrillator Platform OPERATIONS/MAINTENANCE MANUAL. IMPORTANT Keep manual on file at all times.

117-Bin Wire Shelf Storage Rack

SPECIFICATION SECTION 05515: LADDERS O Keeffe s Aluminum Ladders

SERIES G1A, G1B & G1C SLIDE GATES

INSTALLATION GUIDE MODELS DMV2402 / DMV3002 / DMV3602

SECTION DOOR HARDWARE

Pallet Puller. Owner s Manual

executive safe with Override Key Limited Warranty Operation & Installation Guide Read These Instructions Very Carefully! ENGLISH

Mobile Drum Carrier. Owner s Manual

AMBICO Limited Section and ACOUSTIC STEEL DOOR AND FRAME ASSEMBLIES Page 1

66-Bin Wire Shelf Storage Rack

Owner s Manual & Safety Instructions

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

DGF-P 2001 CONVEYORS

Model Defibrillator Platform OPERATIONS/MAINTENANCE MANUAL. IMPORTANT Keep manual on file at all times.

SQ-1 ROOF TRUSS WEG-IT TABLE

Stretch Wire. P/N Rev. 2. IOM Stretched wire festoon manual

SECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

VISE MOUNTED. Model 97359

Drag Chain Conveyor Installation and Operation Manual

PRODUCT INFORMATION PACKET. PRODUCT NAME: CC-500 Crowd Control Barrier

Double-Drum Forklift Gripper

SECTION ALUMINUM-FRAMED HIGH PERFORMANCE THERMAL ENTRANCE DOORS

Hardware. A. PRODUCT DATA: Submit manufacturer's technical information for each item of hardware.

Aero Tec Models 700 & 750 (115 vac)

Installation Instructions For Overly Acoustical / Bullet Resistant Window

Gun Safe 6720F / 6740F. Operation & Installation Guide. FIRE 30minutes /1100ºF RATED THEFT. Manual # M

Edge-of-Dock Leveler 'BA' - 'BX' Series. Owner s Manual and Installation Instructions

SERIES S1R & S2R ACCESS COVERS

SERIES H2R ACCESS COVER With Retro-Grate

SECTION 39 - MANHOLES TABLE OF CONTENTS

L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System

Owner s Manual & Safety Instructions

CR-SERIES CARPET POLES INSTRUCTION MANUAL

COMPLETE REVISION June Process Industry Practices Architectural. PIP ARS08390 Blast Resistant Doors, Frames, and Related Hardware Specification

SECTION WATERTIGHT GATES & BARRIERS FOR FLOOD & SPILL CONTROL

V 2.0 ASSEMBLY GUIDE. TS Platform Scale Series 2

SECTION TRANSPARENT BULLET RESISTANT ASSEMBLIES

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN

4 rotary milling table

N-SERIES: NTH3500 SPECIFICATIONS Hollow Metal Sliding Door System

SERIES W1S & W2S ACCESS COVERS. With Grating Panels

MASTERCRAFT EXTERIOR FIBERGLASS DOOR

Installation Guide Document No Fire-Rated Pass-throughs Copyright 2017 Terra Universal Inc. All rights reserved. Revised Sept.

Transcription:

Pedestrian Flood Door Operations & Maintenance Manual Models PD-520 PD-522FFR Table of Contents Product Information...2 Inspection & Maintenance...6 Inspection & Maintenance Log...7 Warranty Information...8 PS DOORS Contact Information Mail PS DOORS PS Flood Barriers 1150 South 48th Street Grand Forks, ND 58201 Local Phone 701.746.4519 Toll Free Phone 877.446.1519 Websites www.psdoors.com www.flooddoors.com Email 4psinfo@psdoors.com Hours of Operation 8 A.M. to 5 P.M. CST Monday Friday IMPORTANT! Read entire Instruction and Operations Manual to become familiar with the product. NOTICE This product is a flood protection product. The effectiveness of the product is directly related to the proper installation and operation of this product. Failure to properly maintain this product will affect performance. Publication Notice This manual has been compiled and published covering the latest product descriptions and specifications. The contents of this manual and the specifications of this product are subject to change without notice. PS DOORS reserves the right to make changes without notice in the specifications and materials contained herein and shall not be responsible for any damages (including consequential) caused by reliance on the materials presented, including but not limited to typographical and other errors relating to the publication.

If you need to contact Customer Service Please complete the following information and retain for future reference: Serial Number: Purchase Date: PS DOORS Job Number: Project Name: Safety Precautions The following icons are used throughout this Manual. DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderated injury. NOTICE Indicates manufacturer s statement of additional information. IMPORTANT! Indicates a required action. CRITICAL Indicates a vital component to product performance. Pedestrian Flood Door Product Information The Pedestrian Flood Door is a specially designed pedestrian door capable of providing flood protection. The Pedestrian Flood Door is always in place, giving you 24/7 flood protection, while still allowing access to your facility on a daily basis. Please keep these instructions for later reference and read them before attempting any maintenance or operation of the product. NOTICE Additional Information 1. No additional allowances have been included for hydrodynamic loads, debris impact loads or wave loads, unless specifically detailed in additional documentation provided. 2. All water pressure loads, impact loads, and operating loads are transferred to the building structure. Building structure design, capacity to accept loads from flood barriers, and evaluation of loads to structure is by others. 3. PS DOORS recommends that the owner implement an regular maintenance program to inspect the gaskets and doors. This program may require the replacement of gaskets; touch up painting and accounting for of all the latching devices. 4. If the water height exceeds the level of any door penetrations or water protective design height, leakage will occur. 5. This product is equipped with compressible seals, which are not dependent on inflation devices. 6. PS DOORS recommends a flood preparedness plan be developed, trained on, and implemented to be activated during times of potential flooding conditions. 7. PS DOORS AND/OR ITS RESPECTIVE SUPPLIERS MAY MAKE IMPROVEMENTS AND/OR CHANGES IN THE PRODUCT(S) OR SERVICE(S) OFFERED AND/OR THE PROGRAM(S) AT ANY TIME WITHOUT NOTICE. 2

Pedestrian Flood Door Product Information Product Description The PS DOORS Pedestrian Flood Door, Model Pedestrian Flood Door is to be constructed in accordance with PS DOORS standard design, specification, and fabrication methods for custom flood barriers. The following components, in accordance with description provided, are included: 1. Flood Door Panel: To be fabricated as a welded steel structural frame, and sheeted both sides with flat sheeting welded in place. Flood door panel to be designed for maximum water height as indicated in drawings. All loads transferred to adjacent structure. This design is subject to a uniformly increasing fluid pressure (hydrostatic pressure loading of water at 62.5 pcf). 2. Flood Door Frame: To be of PS DOORS design, for field installation on existing structure and/or embedded within structure. Frame members to be fabricated from structural shapes and formed members. Field grouting is required. 3. Gaskets: To be factory mounted to the flood door frame. Gaskets to be compressible, field replaceable. 4. Flood Barrier Door Panel and Frame Finish: Finish on all exposed surfaces to be one (1) shop coat of manufacturer s standard shop primer (S-W Kemflash Primer E61-R-26), and two (2) coats of Standard Industrial Enamel (S-W Industrial and Marine Coatings B54 Series) applied in accordance with manufacturer recommendations and instructions. (Note: Touch up of finish will be required as scratches will occur during shipment, handling, and installation). 5. Latching Hardware: 1. PD-520L: To be Von Duprin 98/99 Series Rim Exit Device (Interior, Dry Side) and 996L Classroom function Lever Handle with Lock (Exterior latch, Wet Side). 2. PD-520R: To be PS DOORS 2PT GTR Turn Latch Assembly (Pad-lockable). 3. PD-522FFR: VonDuprin 98F Series Rim Exit Device (fire rated), Sargent 8225 Mortise Lever/lever (fire rated), High-Secuirty Hardware System (consult factory), Controlled Access Door Lever Hardware (consult factory). 6. Installation Hardware: PS DOORS includes all sealants, water-stop, anchors, and hardware necessary for installation, hinging, latching and retaining flood doors as designed. Note: Anchors are engineered for load design and shall not be changed without factory authorization. 7. Warranty: PS DOORS warrants this product and components to be free from manufacturing defects for a period of one (1) year from date of shipment. The following information is available upon request: Structural Calculations: A copy of PS DOORS design calculations by a qualified engineer, to verify the flood barrier s ability to withstand the design loading, is available upon request. The following optional services are available upon request: Optional: Registered professional engineer stamped calculations from within the state or territory where the building will be constructed or substantially improved may be available at additional cost. 3

Pedestrian Flood Door PS DOORS AND/OR ITS RESPECTIVE SUPPLIERS MAY MAKE IMPROVEMENTS AND/OR CHANGES IN THE PRODUCT(S) OR SERVICE(S) OFFERED AND/OR THE PROGRAM(S) AT ANY TIME WITHOUT NOTICE. NOTICE Unauthorized modification of this product voids the PS DOORS Limited Product Warranty. Accordingly, you can expect any request for warranty repair to be charged to you, if it requires service after modification. Authorized modifications, received in writing from PS DOORS, as long as the modification is accomplished strictly in accordance with PS DOORS instructions, does not void warranty. To request product modifications contact PS DOORS. I. General Information This manual contains information regarding operation and maintenance of custom water resistant flood barrier assemblies. This product is manufactured to specific guidelines. Unauthorized alteration in any way will result in voiding Factory Warranty, some certifications, and may cause product to fail. II. Operation Guidelines The following procedures and information are supplied for the operation of the Pedestrian Flood Door assemblies. Operation in a manner other than intended could result in damage or less than acceptable performance at time of need, for which the manufacturer will not be held responsible. This product has been tested to withstand hydrostatic water pressure to an elevation as indicated on drawings. This design has been tested to allow a minimum amount of leakage. Always plan for potential leakage and condensation that can occur during flooding conditions. WARNING The flood protective barrier panel is heavy, verify panel weights and use appropriate lifting procedures and equipment. III. Safety Precautions A. Ensure opening is clear of all obstructions through the entire travel of the door during operation of door panels. B. Use the handle when contacting panel, staying clear of pinch points. C. Do not force panels or components if they do not operate freely. D. If removing panels or hardware for maintenance, consult documents for panel weights, and use appropriate hoisting equipment. Protect all gaskets and hardware. Always consult original factory drawings for all installation dimensions, details, hardware, and specifications. IV. Operation Under Flooding Conditions A. Under normal (non-flooding) conditions, operates as a normal swing door. 1. Lever Handle: To operate the lever handle, turn lever handle downward approximately 45 degrees to release the latch mechanism. Pull door toward you and swing door to an open position far enough to provide a clear path to pass through the door opening. Once through the door opening move away from the door panel and return the door panel to the closed position. 4

Pedestrian Flood Door 2. Panic Device: To operate the panic device, firmly push the panic bar fully to its stopping position to release the latch mechanism. Push the door away from you and swing door to an open position far enough to provide a clear path to pass through the door opening. Once through the door opening move away from the door panel and to return the door panel to the closed position. 3. Latching Mechanism: Typically, no physical interaction with the latching mechanism is necessary, as long as it is properly adjusted (see latching installation and adjustment documentation). Depending upon the environmental conditions present (refer to Maintenance and Inspection Section), the door may not completely latch and may require a person to physically push/pull the door to engage the latch. Fire rated doors are required to close and latch w/o intervention. NOTICE PS DOORS recommends all facilities subject to flooding conditions, and employ any type of flood protection have a Flood Preparedness Plan in place for activation prior to, or in times of flooding conditions. B. Pre-flooding or Potential Flooding Conditions: 1. At a minimum, conduct Inspection and Maintenance activities as described in this Operations & Maintenance Manual. 2. Ensure Pedestrian Flood door is closed and latched. 3. Routinely verify that the Pedestrian Flood door remains closed and latched. C. Flooding conditions are Present: 1. Ensure Pedestrian Flood Door is not opened at any time when flooding conditions are present. 2. If feasible, check door for leakage or condensation accumulation. D. Post-flooding Conditions: 1. At a minimum, conduct Inspection and Maintenance activities as described in the Operations & Maintenance Manual. CAUTION When operating door keep clear of pinch points at the latching mechanism, hinge locations, and out of the travel of the door panel at all times. CRITICAL Flood Protective Barrier must be latched to engage flood protective seals. WARNING THIS IS A FLOOD PROTECTION BARRIER. NEVER OPEN DURING ANY FLOODING CONDITIONS AS WATER LEAKAGE WILL OCCUR AND YOU MAY NOT BE ABLE TO RECLOSE THE DOOR 5

Inspection and Maintenance V. Inspection and Maintenance A. Sills, frames, and embedded items: 1. Inspect items for damage and misalignment. Adjust, repair, or replace as needed, to meet original design tolerances. 2. Check all embedded connections, making sure they meet original design standards (refer to original product drawings). B. Fasteners and mechanical connections: 1. All fasteners must be in place and adjusted to their original design standards. Replace any damaged components (refer to original product drawings). C. Sealants: 1. Inspect all sealants used on frames and connections to ensure their effectiveness. Replace any cracked, loose, or otherwise non-performing sealants. 2. Use only factory approved/supplied products. CRITICAL Gaskets are a critical component of the flood protective barrier performance and must meet minimum compression tolerances in the latched position. D. Gasketing: Check all gaskets around perimeter of opening. 1. Inspect for gasket and corner splice damage, and for continuous adhesion to the attached surface. 2. Visually inspect all gaskets for proper positioning, compression, and continous contact with door panel. 3. Replace or repair if damage or deterioration to gaskets has occurred. 4. Use only factory approved materials (consult manufacturer for original design standards). 5. Use only factory approved installation guidelines (refer to Gasket Replacement Instructions). CRITICAL Gaskets and sealing surfaces are a critical component of the flood protective barrier performance. IMPORTANT! Consult drawings before replacing fasteners, as most have specific design load requirements. E. Latching: 1. Operate all latching hardware to ensure smooth, uninhibited movement of all mechanical components. 2. Close door and check latches for proper engagement. If gaskets are not properly positioned and properly compressed, unlatch door panel and adjust latching accordingly (refer to original product drawings). 3. Insure that door hardware is installed and adjusted so as to not interfere with proper door closing, latching, and continued gasket compression. F. Lubrication 1. Periodically lubricate hardware and other components according to manufacturer s instructions (refer to applicable hardware guides). G. Finishes: 1. Inspect and clean finishes periodically. 2. Touch-up repair finishes, or refinish as necessary to protect the structural integrity of the product. H. Labels and Placards: 1. Inspect all labels and placards. Replace any labels and placards which are unreadable (refer to Label and Placard Placement instructions). I. Housekeeping: 1. Clean sill and jambs of any debris and keep the area clean throughout the operating area of the door. 6

Inspection & Maintenance Log CRITICAL Periodic Inspection and Maintenance Required. Date Purchased: Product: Model Number: Door Identifier / Number: Serial Number: Location: DATE INSPECTED INSPECTED BY (Print & Sign) INSPECTION ITEMS NOTED CORRECTIVE ACTION CORRECTED BY (Print & Sign) 7

PS DOORS Limited Warranty Limited Warranty - Fill out warranty registration and return to PS DOORS. PS DOORS warrants this product and components to be free from defects in material and workmanship for a period of one (1) year from date of shipment. If within the term of this warranty, any Pedestrian Flood Door or component is found to be defective upon inspection by an authorized PS DOORS representative, PS DOORS will replace or repair, at PS DOORS discretion, any part found to be defective. Any field labor charges incurred are the sole responsibility of the customer. To make a claim under this warranty, contact PS DOORS at the address shown below. PS DOORS Attention: Warranty 1150 South 48th Street Grand Forks, ND 58201 Toll Free: 877.446.1519 Warranty Phone: 701.746.4519 Fax: 701.746.8340 E-mail: 4psinfo@psdoors.com Unauthorized modification of or to this product voids the PS DOORS Limited Warranty. Accordingly, you can expect any request for warranty repair to be charged to you, if the product requires service after unauthorized modification. Authorized modifications, received in writing from PS DOORS, as long as the modification is accomplished in strict accordance with PS DOORS instructions, does not void warranty. To request product modifications contact PS DOORS, 1150 South 48th Street, Grand Forks, ND 58201, phone 877.446.1519, email: 4psinfo@psdoors.com. PS DOORS SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES. All other warranty s, express or implied including any warranty of merchantability, are expressly excluded. Some states do not allow the exclusion or limitation of consequential or incidental damages, so the above limitation or exclusion may not apply to you. WARRANTY DOES NOT APPLY TO ANY DAMAGE OR DETERIORATION CAUSED BY MODIFICATION, ABUSE, APPLIED PAINT FAILURE OR FAILURE TO PROVIDE REASONABLE AND NECESSARY MAINTENANCE. This warranty gives you specific legal rights, and you may also have other rights, which vary, from state to state. IMPORTANT! ACTION REQUIRED! Warranty Registration - Do not cut this out of the manual. Make a copy. In order to Validate your Warranty the following information must be completed and returned to PS DOORS, failure to completely fill out this information, or to return information to PS DOORS may void warranty. Owner Name: Company: Address: City: State/Providence: Postal Code: Country: Please answer the following questions: 1. Has the installed product been tested? Yes No Product: Model: Serial Number(s): Date Installed: Warranty Registration must be returned to: PS DOORS 1150 South 48th Street Grand Forks, ND 58201 Fax: 701.746.8340 Email: 4psinfo@psdoors.com 2. Test witnessed by, Name: Date: 3. Product initial inspection by, Name: Date: Warranty Registration Information will be used for activation of product warranty only. 8