Guidance for installers when making connections in consumer units. electricalsafetyfirst.org.uk beama.org.uk

Similar documents
Assembling, wiring and testing electrical panels/components mounted in enclosures

Risk of fire and electrical shock. DISCONNECT POWER AT ELECTRICAL PANEL before installing or servicing this product.

Spring Pressure Connection Technology Vibration-Proof Fast Maintenance-Free

Installation, Inspection and Maintenance of Dry Type Transformers

SECTION EARTHING AND EARTH FAULT PROTECTION

Outcome one Assemble, wire and test electrical panels/ components mounted in enclosures

FAQ s. QLD Service Installation Rules

ELECTRICAL SAFETY INSPECTION REPORT

Assembling, Wiring and Testing Electrical Panels/Components Mounted in Enclosures H/508/5093 QU Restricted

ELECTRICAL SAFETY INSPECTION REPORT

Same as Client Address. 40, Havelock Close. India Way. London. Postcode: W12 7NQ

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT.

ELECTRICAL SAFETY INSPECTION REPORT

PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION

Water Level Meter User Manual

USER MANUAL MODEL 1019 and 1019S DB-9 Async. Short Range Modem With Transformer Isolation

Platform stair lift PLG7

SECTION SECONDARY UNIT SUBSTATIONS

CHAPTER 13 GROUNDING AND BONDING

ELECTRICAL SAFETY INSPECTION REPORT

Installation Instructions

ELECTRICAL SAFETY Information Bulletin

Same As Client Address SPECIMEN. operational limitations. of the inspection and. agreed with):

CHAPTER 5 METERING REQUIREMENTS

Thermocouple & Fine Wire Welder Model No. L60+

USER S OPERATING AND INSTRUCTION MANUAL

GARO Charger GLB Load Balancing and Low Tariff

CABLE TERMINALS CABLE TERMINALS

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan)

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

INTER PLANT STANDARD STEEL INDUSTRY

Power Distribution Center. Model: SUDC208V42P

POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

ELECTRICAL SAFETY INSPECTION REPORT

LSA-PLUS Series 2. Connection and Disconnection Modules and Accessories. 1 st Edition

Unit 037 Maintaining electrical equipment/systems 1

NEC 2017 Code Changes Chapter 1 - General

MICROSTAT-M. Page 1/7. Data Sheet Type /2160. Type / /

Installers Guide. Item

SECTION MOTOR CONTROL CENTER

INTERNATIONAL STANDARD

ASSEMBLY INSTRUCTIONS for DATASAFE TM HX and HX FRONT TERMINAL UBC BATTERY RACKS

AUTOMATIC CAPACITOR BANK FOR LOW VOLTAGE NETWORKS INSTRUCTION MANUAL. MIBATBT_05i

Diploma in Electrical Installations. (Buildings and Structures) Unit 204 Workbook PRE-ATTENDANCE REVISION V1

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

Building Services Engineering: Basic Electrical Installation Operations (SCQF level 5)

ELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (4th)

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING.

LIB System for UPS Installation Manual (136S)

To bond or not to bond: domestic swimming pools

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations.

SYSTEM 600 GENERAL MAINTENANCE AND ADJUSTMENT GUIDE

SECURE. UNIVERSAL. MOUNTING. Tilt Kit Installation Manual

LIFT FRONT CURVED GLASS HOT FOOD/DELI MERCHANDISERS Hot Temperature Service Display Cases

SEMPEO SQA Unit Code FP3G 04 Forming and assembling electrical cable enclosure and support systems

42-SDMS-03 SPECIFICATIONS FOR

Forming and assembling electrical cable enclosure and support systems

LIB System for UPS Installation Manual (136S)

Wiring Investigation, for Stray Voltage MPSC U17897 Szymanski Farm 1375 Argyle Rd. Snover, MI

SECTION GROUNDING

Forming and assembling electrical cable enclosure and support systems

1. Section COVER PAGE: remove and replace with new Cover Page, Attached.

INDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1

DIVISION 16. Electrical Specifications

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

ELECTRICAL SAFETY INSPECTION REPORT

GUIDANCE FOR CUT OUT WORKS

EAL Assessment Route Summary

Sound insulation technology

LIFETIME WARRANTY INSTALLATION MANUAL. Ultra thin cable. Easy to install. Fully compliant to latest regulations CE approved INSTALLATION MANUAL

Double Tidy Rail. Assembly Instructions- Please keep for future reference. Important - Please read these instructions fully before starting assembly

SPECIFICATION FOR SIMPLEX SWITCHBOARDS

booster EX2 / EX3 Operating Manual Extrusion Welder Weldy AG Galileo-Strasse 10 CH-6056 Kaegiswil / Switzerland TECHSPANGROUP

On-roof system Tau Installation manual

Drag Chain Conveyor Installation and Operation Manual

Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations.

VP2 SidePOD Instructions

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER

Point Eight Power, Inc. Switchgear Specification Low Voltage UL 1558 Metal-Enclosed Switchgear

XAP Series Busduct Storage, Installation, and Maintenance

Design 50 Power through design

WATER LEVEL METERS DIPMETER DIPMETER (WITH TEMPERATURE OPTION) ANTI-FOAM DIPMETER

SIEMENS. Instructions. Outdoor Metal Clad Switchgear. Installation Assembly OGM&SGM SG kV and 15kV. www. ElectricalPartManuals.

Mounting Screw. Channel Filler. Light Angle Adjustable Screw. LED Board Vertical stud and blocking Locking Nose. Driver.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

General Safety Information

Welding & Fabrication Tools Mini VaR Tool Kit

ELECTRICAL SAFETY INSPECTION REPORT

L-JACK Termination Procedure

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN

ELECTRICAL BULLETIN

User Manual. IWB Internally Wired Bar. Version 12/10.

SECTION PARK NON-SEGREGATED BUS SPECIFICATION


MS Training Manual. Storage, installation and maintenance for MS busbar systems

Transcription:

Guidance for installers when making connections in consumer units electricalsafetyfirst.org.uk beama.org.uk

Published by: Electrical Safety First 45 Great Guildford Street London SE1 0ES Tel: 0203 463 5100 Email: enquiries@electricalsafetyfirst.org.uk Website: www.electricalsafetyfirst.org.uk Electrical Safety First are indebted to the British Electrotechnical and Allied Manufacturers Association (BEAMA) for their assistance and support in the development of this guidance. Electrical Safety First. March 2016

Introduction In recent years there have been an increasing number of reports of fires involving consumer units. The increase in such reports is due to a number of factors, including the effects of poor workmanship, a progressively deskilled electrical contracting trade, increased surveillance activities by fire and rescue services and product evolution. As a first step to improve the situation, a requirement has been included in Amendment 3 of BS 7671 published in 2015 such that consumer units and similar switchgear assemblies shall either have their enclosure manufactured from non-combustible material or be enclosed in a cabinet or enclosure constructed of noncombustible material. At the BSI/IET working group set up to look at consumer unit fires, interested parties agreed to conduct further research into the use of the Fig 1. Consumer unit with plastic enclosure after a fire caused by a loose neutral termination types of terminal found in consumer units and to provide guidance to assist installers to make effective and electrically sound connections. This guidance produced by Electrical Safety First and BEAMA, provides practical advice and guidance on achieving safe and reliable connections for devices and terminal bars within consumer units and similar switchgear. Guidance is provided on the cable preparation required to enable a safe and reliable connection to be made based on factors relating to the conductor. 3

Introduction Recommendations are made with respect to the selection of the best type of tool to be used in order to provide sufficient tightness of screw terminals. This guidance does not comment on the suitability or otherwise of the construction of the terminals, which is outside of its scope. Manufacturers have to facilitate the termination of a range of conductors in their products. Note, in Fig 2 below, the diverse range of conductor terminations even before meter tails and final circuits are terminated. 1. 2. 3. 4. 5. 6. Fig 2. Assembled consumer unit. 1. Crimped ferrule 2. Multi-strand conductor 3. Small diameter RCBO functional earth lead 4. Large diameter neutral cable in main switch 5. Large diameter conductor and busbar connection in same terminal of main switch 6. Busbar connection into outgoing terminal of RCD and supply side of circuit-breakers 4

Tools Make sure that all tools used are in good condition. Use sharp cutters, strippers, knives. Blunt tools can be more dangerous than sharp and produce an inferior cut. Choose a screwdriver that correctly fits the screwhead (Fig 3) consumer unit manufacturers can advise on this. Choose a screwdriver that is appropriate to the size of the screw. Only those power tools specifically designed for use as torque drivers should be used to tighten electrical connections ordinary battery drills are not suitable for this purpose. Where torque drivers are employed they must be used in accordance with manufacturers instructions, set to the correct torque, subjected to regular checks of their accuracy and recalibrated when required. Fig 3. Summary of screwdriver tip types 5

Workmanship Cut conductors so that the end is as square as possible. Strip insulation sufficient to allow conductor(s) to enter terminal fully and ensure that insulation is not trapped in the termination (see Fig 4) many manufacturers give a recommended strip length. Fig 4. Termination made incorrectly as a result of insulation being trapped in the terminal clamp Fig 5.Termination made correctly Avoid damaging the conductors (Fig 6) or breaking strands (Fig 7) when removing insulation - many cable strippers have an adjustable depth of cut. Fig 6. Conductor damaged during insulation stripping Fig 7. Strands broken during insulation stripping 6

Always arrange/shape conductors such that they do not place strain on the terminals the importance of this rises as conductor size, and hence opposition to bending/shaping, increases. Where fitting one conductor only, double over the conductors of cross-sectional area 2.5 mm² or less in order to better fill the terminal (Figs 8 and 9) circuitbreaker and RCBO terminals typically have a capacity to accommodate conductors of up to 16 mm² cross-sectional area. Too long Correct Too short Fig 8. Correct and incorrect doubling over of a conductor Do not twist conductors installed in a single terminal together this may result in work hardening and conductors snapping when untwisted to permit, for example, periodic testing. Ensure that conductors are correctly located in a terminal. Incorrect Correct Fig 9. Improved termination after doubling over of a conductor 7

The manufacturer s recommendations with respect to correct tightness must be followed under-tightening will result in an excessively loose connection, and over-tightening may severely damage the conductors (Fig 10) causing them to snap when under minimal strain. One way of achieving correct tightness is through the use of a torque screwdriver. Recommended torque values are available from manufacturers and some wholesalers. BEAMA members are committed to providing torque settings with their products. Fig 10. Single core solid conductors damaged by an excessively tightened termination. Take care that conductors are not inadvertently placed on the wrong side of the clamping unit. Some manufacturers incorporate features such as a tab below the moving part of the clamping unit to minimise the likelihood of conductors being incorrectly located (see Fig 12). Fig 12. Cable entries of mainswitches showing tabs below moving part of terminal as design feature to minimise the likelihood placing conductors in terminal incorrectly 8

Always apply a pull test to each connection after it is made ensure that the tug is not excessive. The consumer unit and associated devices Devices such as circuit-breakers and RCBOs from different manufacturers must not be mixed unless documentation is obtained from the consumer unit manufacturer which confirms that the specific mixed arrangement is suitable for use. Further guidance on this can be found on the BEAMA website at www.beama.org.uk/ resourcelibrary/safe-selection-of-devices-for-installation-in-assemblies-.html Do not exceed the terminal capacity of a device In general it is not recommended to place more than three conductors in any one terminal. All terminations within the consumer unit, including those made during factory assembly, should be checked at original installation and at every subsequent periodic inspection - this is now required by BS 7671. Care should be taken to ensure conductors are not trapped or do not apply stress to the terminations when the front cover is fitted to a consumer unit. Ensure that all devices are engaged correctly on the DIN rail. Ensure that busbar tangs/fingers are located correctly in the terminal (see Fig 13). Fig 13. Circuit-breaker on left-hand side incorrectly installed with busbar tang/ finger outside the termination clamp 9

Terminating conductors into neutral and earth bars Care should be taken when stripping conductors so that excessive bare conductor does not protrude excessively beyond the rear of the bar and, in any case, does not permit the bare conductor to touch the inside surface of the enclosure. The functional earth of an RCBO should be placed in the same terminal as the associated protective conductor and should be placed behind the protective conductor to minimise the risk of damage. 10

Terminating meter tails into the main switch or RCCB Meter tails should be prepared as shown in the series of diagrams in Fig 14 below. Fig 14. Correct preparation of meter tails 11

During research carried out by Electrical Safety First, it was shown that the use of 19 stranded meter tails gave a more reliable connection than more conventional (7 stranded) tails. Accordingly, the use of 19 strand cable is recommended. The same research also showed that flattening the strands of the conductor (Fig 15) prior to terminating resulted in a more reliable connection. It is essential that flattening using, for example, pliers should therefore be carried out. Fig 15. 16 mm² 7-strand meter tail with conductors cut to length and flattened prior to termination The general advice given earlier in this guide to take measures to relieve the strain on, or disturbance of, terminations is particularly pertinent due to the larger physical size of meter tails, and hence increased opposition to bending of the tails. This may be achieved by for example: Dressing / shaping conductors prior to termination, Use of an internal clamping device (Fig 16), Fig 16. Example internal meter tail clamp 12

Securing the cables at point of entry by a stuffing gland (Fig 17), Fig 17. Stuffing gland for securing meter tails at point of entry By clipping the meter tails external to the consumer unit (Fig 18). Fig 18. Meter tails secured by clips external to the consumer unit 13

Find out more 45 Great Guildford Street London SE1 0ES Helpline 020 3463 5100 E: enquiries@electricalsafetyfirst.org.uk Electrical Safety First is the UK charity dedicated to reducing deaths and injuries caused by electrical accidents. Our aim is to ensure everyone in the UK can use electricity safely. electricalsafetyfirst.org.uk