Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Similar documents
Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings

CFD Modelling and Analysis of Different Plate Heat Exchangers

A cooling tower combined with chilled ceiling: system optimisation

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER

Study on the heat transfer characteristics of an evaporative cooling tower B

Cooling coil optimisation in hot and humid climates for IAQ and energy considerations

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Performance Improvement of Mechanical Induced Draft Cooling Tower by Using Aluminum as Fill Medium

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Numerical simulation of plume abatement and water-saving device on the top of wet cooling tower

Heat Rejection using Cooling Towers

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

Cooling Tower Operation

Thermally operated mobile air-conditioning system

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

Effect of Drying Condition on Natural Block Rubber: Simulation and Experiments

ANALYSIS OF PERFORMANCE OF NATURAL DRAFT COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

Experimental investigation of solar-driven double ejector refrigeration system

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

EXPERIMENT FOR VERIFICATION OF GROUND SOURCE HEAT PUMP USING THE DIRECT EXPANSION METHOD

Numerical Investigation of the Air Flow in a Novel PV-Trombe Wall Based on CFD Method

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

EXPERIMENTAL AND NUMERICAL STUDY OF SMOKE CONDITIONS IN AN ATRIUM WITH MECHANICAL EXHAUST

Vipac Engineers & Scientists Ltd

Design and distribution of air nozzles in the biomass boiler assembly

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

OBJECT SYSTEM Figure 1 shows the object air conditioning system. Flesh outdoor air is supplied to desiccant system directly or via earth tube dependin

International Journal Of Scientific Research And Education Volume 3 Issue 3 Pages March-2015 ISSN (e): Website:

Review Questions for the FE Examination

ANALYSIS FOR NATURAL CIRCULATION LOOP

CFD in Ventilation, case studies from REHVA CFD guidebook

Keywords: CFD; Cooling tower; Evaporative cooling; NTU; Spray water

Modelling of Indirect Evaporative Air Coolers

ADVANCES in NATURAL and APPLIED SCIENCES

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

Administrative Building Cooling Tower. University of Tennessee Chattanooga

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

Study on Heat Transfer Enhancement of a Coil Zone for Closed Wet Cooling Towers Equipped with Longitudinal Fin Tubes

QATAR UNIVERSITY. Graduate Studies. College of Engineering INVESTIGATION OF A REGENERATIVE INDIRECT EVAPORATIVE COOLING SYSTEM.

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

The 3-D Numerical Simulation of a Walking Beam Type Slab Heating Furnace with Regenerative Burners

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Proceedings of Clima 2007 WellBeing Indoors

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc.

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2

Set Free Modular FSXN. Engineering for tomorrow. And the tomorrow after that.

Numerical Simulation of Spray Cooling Gas with High Temperature and Velocity in Compressor Inter-Stage

The planning and design of effective wet duct/stack systems For coal fired utility power plants

ME 215. Mass and Energy Analysis of Control Volumes CH-6 ÇANKAYA UNIVERSITY. Mechanical Engineering Department. Open Systems-Control Volumes (CV)

EXPERIMENTAL INVESTIGATION AND OPTIMIZATION OF COOLING TOWER EFFICIENCY BY FORCED DRAFT SYSTEM

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower

OIL POOL FIRE IN A LARGE TURBINE HALL CFD simulation

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Heat exchangers and thermal energy storage concepts for the off-gas heat of steelmaking devices

SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

Thermal Management of Densely-packed EV Battery Set

Sustainable Designed Air-Conditioned Mosque For Thermal Comfort

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS

Experimental and Numerical Study of Heat Transfer Process of Chilled Water Storage Tank

Development of a compact single room ventilation unit with heat recovery dedicated to tertiary building

COMPARISON OF THE HEAT TRANSFER THROUGH HYDROMX WITH THAT OF WATER

Atmospheric Vortex Engine Prototype

Coal Pipe Coal Flow Distribution Control for Coal Pulverizer Systems

EXPERIMENTAL INVESTIGATION OF THERMAL AND VENTILATION ANALYSIS FOR STRATUM VENTILATION CFD STUDY

Simulation of Flameless Combustion of Natural Gas in a Laboratory Scale Furnace

Thermal comfort study of a hawker center in Singapore

Compound ejectors with improved off-design performance

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Figure 1: Uncovered and covered PVT collectors

OPTIMIZATION OF PCM NUMBER IN HOT WATER TANK FOR THE APPLICATION OF SOLAR DRIVEN ADSORPTION CHILLER IN TROPICAL CLIMATE

Conventional Analysis of Performance of Cooling Tower Used for Industrial Purpose

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

Indirect Evaporative Cooling Availability and Thermal Effectiveness Characteristics in Air-Water Systems of Hot and Dry Climates

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

Experimental and numerical investigation of cooling performance of a cold storage in a pharmaceutical industry

Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008

CHAPTER 3 HEURISTIC APPROACH TO MODELING THE BOILER FURNACE

NUMERICAL APPROACH TO A LOW PRESSURE GAS-INJECTION SCROLL COMPRESSOR

Application of a cooling tower model for optimizing energy use

CFD SIMULATION OF A NOVEL VENTILATION SYSTEM OF SUBWAY STATION IN HARBIN

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

Transcription:

INTERNATIONAL JOURNAL OF ENERGY RESEARCH Int. J. Energy Res. 2000; 24:1171}1179 Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation Sa!a Ri!at*, Armando Oliveira, Jorge Faca o, Guohui Gan and Prince Doherty Institute of Building Technology, School of the Built Environment, University of Nottingham, Nottingham NG7 2RD, U.K. Faculty of Engineering, University of Porto, Department of Mechanical Engineering and Industrial Management, Rua dos Bragas, 4050-123 Porto, Portugal SUMMARY A closed wet cooling tower, adapted for use with chilled ceilings in buildings, was tested experimentally. The thermal e$ciency of the cooling tower was measured for di!erent air #ow rates, water #ow rates, spray #ow rates and wet bulb air temperatures. CFD was also used to predict the thermal performance of the cooling tower. Good agreement was obtained between CFD prediction and experimental measurement. Copyright 2000 John Wiley & Sons, Ltd. KEY WORDS: cooling tower; chilled ceiling; thermal performance; CFD 1. INTRODUCTION Increased use of IT equipment coupled with thermal comfort requirements has led to an increased demand for cooling in o$ces. A simple and economic way of cooling o$ces is to use an indirect-contact closed wet cooling tower combined with chilled ceilings. Chilled ceilings are a relatively new approach to cooling. A chilled ceiling system has several advantages over conventional cooling systems. The use of chilled ceilings allows the ventilation rate to be reduced to a minimum level, and so reduces ventilation losses. Heat transfer from indoor space to chilled ceilings is accomplished mainly by radiation. Consequently, chilled ceilings enable o$ces to have low air movement and a comfortable indoor environment. Radiative heat transfer also allows chilled ceilings to remove considerable heat loads, up to 75 W m, at a relatively small temperature di!erence between the room air and the ceiling. This makes it possible to operate the system with water supply temperatures of about 18}203C. * Correspondence to: Sa!a Ri!at, Institute of Building Technology, School of the Built Environment, University of Nottingham, Nottingham NG7 2RD, U.K. E-mail: Sa!a.Ri!at@nottingham.ac.uk Contract/grant sponsor: Commission of the European Union (DG XII). Received 5 October 1999 Copyright 2000 John Wiley & Sons, Ltd. Accepted 7 January 2000

1172 S. RIFFAT E¹ A. Because high water temperatures can be used in chilled ceilings, it is possible to use water from a closed wet cooling tower during most of the cooling period. The cooling tower could be combined with a supplementary refrigeration plant, or used alone if a short period of overheating is allowed or energy storage or night-cooling techniques are used. Closed wet cooling towers have been used to remove excess heat from various industrial processes with hot water temperatures between 32 and 463C and typical cooling capacities above 40 kw. For chilled ceilings, cooling towers with lower capacities (cooling loads )10 kw) and smaller tower dimensions can be used with hot water temperatures ranging from 22 to 253C. Most of the existing thermal models for tower design make use of empirical correlations for heat and mass transfer coe$cients obtained for large towers. The validity of such correlations cannot be extended to all geometries or air #ow patterns and so tests are often required for individual tower designs. Computational #uid dynamics (CFD) is a useful alternative tool for designing both small and large cooling towers. CFD models give information on air #ow and spray water distribution, which cannot be obtained with simpli"ed models. Such information is important for good tower design and operation. An unsatisfactory distribution of spray water over the tubes would reduce evaporative cooling and tower cooling capacity. Simultaneous non-uniform distribution of air and spray water would further degrade the tower-thermal performance. This project is concerned with designing and testing a prototype closed wet cooling tower for use with chilled ceilings. CFD has been used for the design and performance evaluation. This paper presents the experimental and computational results of the tower performance. 2. EXPERIMENTAL MEASUREMENT Figure 1 shows the schematic of the closed wet cooling tower, with notation for the main #ow variables. The cooling tower had a horizontal cross-section of 0.6 m1.2 m and a height of 1.55 m. The heat exchanger was composed of 228 staggered tubes of 10 mm outside diameter Figure 1. Schematic diagram of the closed wet cooling tower and main variables.

CLOSED WET COOLING TOWER FOR CHILLED CEILINGS 1173 Figure 2. Experimental facility for cooling tower testing. A-Anemometer, V V V -Flowmeters, T-Thermocouple or PT'10.0, p-pressure loss, ω-fan speed, P -Power, RH-Relative humidity. and had a total heat transfer area of 8.6 m. The design conditions for the tower had a cooling capacity of 10 kw, inlet water temperature of 213C, water #ow rate of 0.8 kg s and wet bulb air temperature of 163C. The tower was manufactured by Sulzer Escher Wyss (Lindau, Germany) and was much smaller than the traditional cooling towers for industrial use. A forced draft con"guration was chosen with a cross#ow fan located at the air entrance. This arrangement gave rise to a low-noise level and a low-pressure drop. It also led to good air distribution and facilitates air #ow measurements. An experimental facility was assembled at Porto to test this cooling tower. Figure 2 shows the schematic diagram of the test facility including the main instrumentation used. The facility allowed various #ow parameters such as the water #ow rate and temperature, spray water #ow rate and air #ow rate to be varied at controlled conditions. The thermal load was modelled with an electrical heater located in a water tank. The tower inlet water temperature was controlled by varying the heating power through a PID controller. The fan speed, and so air #ow rate, was controlled by means of a frequency controller. The spray water #ow rate could be changed manually through a valve with seven opening levels. The cooling water #ow rate could also be changed by varying the pump speed and by adjusting #ow valves. The air #ow rate was measured with a vane anemometer. The anemometer could be traversed across the tower outlet section to measure the air speed at di!erent points. Several thermocouples were connected to the tubes to measure cooling water temperature evolution. The data acquisition system included a data logger HP 34970A with software HP VEE.

1174 S. RIFFAT E¹ A. The thermal performance of the cooling tower was expressed by means of tower thermal e$ciency. This is de"ned as ε" ¹!¹ (1) ¹!¹ where ¹ is the inlet water temperature, ¹ outlet water temperature and ¹ wet bulb temperature of inlet/supply air. 3. CFD SIMULATION A commercial CFD software package (FLUENT User's Guide, 1993) was employed to simulate the two-phase #ow of air and water droplets in the cooling tower. Air #ow was modelled as a continuous phase and water droplets as a dispersed phase. The impact of the dispersed phase on the continuous phase #ow was accounted for by coupling the momentum and the heat and mass transfer between the two phases (Gan, Ri!at, 1999). 3.1. Continuous phase model The continuous phase model for turbulent air #ow consists of the conservation equations for mass, momentum, enthalpy, concentration and turbulence. For steady-state incompressible #ow, the model can be represented by the following equation: ' (ρ<m! ()"S ( #S ( (2) where is the #ow variable, <M is the mean air velocity (m s), ρ is the air density (kg m), ( is the di!usion coe$cient (N s m), S ( is the source for the continuous phase and S ( is the source due to the interaction between air and water droplets. 3.2. Dispersed phase model The #ow of dispersed water droplets is characterised by the trajectories. The trajectory of a water droplet is computed using the following equation: d< ρ dt "3 ρc <!< (<!< )#g(ρ!ρ)# 1 4 d 2 ρ d dt (<!< )#P (3) r where < is the instantaneous air velocity (m s), < is the instantaneous velocity of the droplet (m s), C is the drag coe$cient, d is the droplet diameter (m), ρ is the droplet density (kg m), P is the static pressure (Pa) and r is the droplet trajectory (m). 3.3. Assumptions The following assumptions were used to predict the thermal performance of the cooling tower: The tower was quite long compared with the width, so two-dimensional #ow was considered. The tower casing was adiabatic and impermeable. For the two-dimensional #ow on one vertical cross-section of the tower, the tubes representing the heat exchanger were taken as separate entities. The heat transfer from the tube surface to air

CLOSED WET COOLING TOWER FOR CHILLED CEILINGS 1175 involves evaporation and convection. However, because the software could not take account of evaporative cooling of tubes, only the sensible heat transfer was used in terms of a surface heat #ux. The estimated sensible heat transfer for a complete wet cooling tower was about 24 per cent of the total heat transfer from the heat exchanger to air and spray water. On the same vertical section, the spray water composed of 100 trajectories of droplets was injected into the tower through a nozzle at the centre line above the heat exchanger. The injection velocities of the water droplets from the nozzle varied such that the spray water would cover the entire width of the heat exchanger when falling on top of it. The mean diameter of the water droplets was estimated from the terminal velocity of the droplets at a mean velocity of air #owing over the heat exchanger. 4. MEASUREMENT RESULTS Experiments were "rst carried out to analyse the in#uence of inlet water temperature. It was found that this parameter had very little e!ect on the tower e$ciency. Tests were then carried out at various spray water #ow rates. The e!ect of spray water #ow rate can be seen from Figure 3. An increase in spray rate increases the e$ciency up to a certain level. Above a rate of about 1 kg s, an increase in spray rate does not signi"cantly improve tower performance because the tube surface is almost completely wet. This means that, there exists an optimum spray rate for a given air #ow rate, with regard to cooling capacity and water/energy (pumping) consumption. When both air and spray water #ow rates are considered, the mass #ow ratio of spray water to air can be employed and this ratio can also be optimized according to the cooling capacity and energy consumption. Figure 3. Tower e$ciency as a function of spray water #ow rate for di!erent air and water rates [(m ) "1.39 kg s, wet bulb temperature"12.63c].

1176 S. RIFFAT E¹ A. Figure 4. Tower e$ciency as a function of air and water mass #ow ratios for a wet bulb temperature of 15.83C [(m ) "0.8 kg s, (m ) "1.7 kg s]. Figure 5. In#uence of wet bulb temperature on tower e$ciency for di!erent air and water mass #ow rates. If the spray rate is kept close to the maximum or optimum value, the tower e$ciency is a function of three parameters: air #ow rate, cooling water #ow rate and wet bulb temperature. Figure 4 shows the measured e$ciency values for di!erent air and water #ow rates at a "xed wet bulb temperature. As expected, the e$ciency increases with the air #ow rate and decreases with the increasing water #ow rate (due to a decrease in water temperature di!erence). The wet bulb temperature of air has also an in#uence on the tower e$ciency as shown in Figure 5. The e$ciency increases slightly with the wet bulb temperature: about 8 per cent for temperatures varying between 10 and 203C. The increase is linear for di!erent air and water #ow rates. However, increasing the wet bulb temperature would increase the outlet water temperature from the heat exchanger, thus decreasing the cooling capacity of the chilled ceiling. A global coe$cient of performance (COP) can be calculated for the cooling tower. It is equal to the cooling capacity divided by the total energy input (pumping and fan power

CLOSED WET COOLING TOWER FOR CHILLED CEILINGS 1177 consumption). The total energy input can be determined by measuring the electricity input to the fan motor and spray pump motor. The calculated COP at maximum air and spray #ow rates was 6. 5. COMPARISON BETWEEN SIMULATION AND MEASUREMENT A number of CFD simulations were performed to compare with the experimental measurement. The thermal performance of the cooling tower was predicted according to the temperature distribution of the tubes representing the temperature of cooling water in the heat exchanger. Simulations were divided into two groups, one for tests at the design water #ow rate of 0.8 kg s and the other for tests at a lower water #ow rate of 0.4 kg s. Table I presents a comparison between the predicted and measured tower performance for four test cases at the design water #ow rate of 0.8 kg s. In the "rst two tests, the temperature of supply air was lower than that of spray water and cooling water at the outlet of the heat exchanger. The measured air #ow rate for the second test (1.08 m s) was higher than that for the "rst test (0.48 m s). In the third test, the temperature of supply air was slightly higher than the spray water temperature. In the fourth test, the temperature of supply air was higher than that of spray water and cooling water. The measured temperature drop of cooling water between the inlet and outlet of the heat exchanger for these tests was approximately 1.5 K. It is seen that the simulations (Preds. 1}4) are in good agreement with the measurement in terms of the temperature di!erence of cooling water at the inlet and the outlet. In Table II, prediction is compared with the measurement for one test at the low water #ow rate of 0.4 kg s. The predicted temperature di!erence between the top and the bottom tube rows (1.5 K for Pred 1) was much smaller than the measured temperature drop of cooling water (3 K for test). For a given cooling load, the temperature drop of the cooling water is inversely proportional to the water #ow rate in the heat exchanger. The measured water temperature drop would therefore be 1.5 K for a water #ow rate of 0.8 kg s compared with 3 K for 0.4 kg s. Table I. Comparison between the predicted and measured thermal performance of the cooling tower at the design water #ow rate of 0.8 kg s. Supply air Spray water Chilled water Q ¹ RH m ¹ m ¹ ¹ ¹ Case (m s) (3C) (%) (kg s) (3C) (3C) (3C) (K) Test 1 0.48 13.1 85 1.38 16.2 2.34 18.53 17.02 1.51 Pred 1 0.48 13.1 85 1.38 16.2 2.34 19.1 17.5 1.6 Test 2 1.08 13.0 87 1.38 13.6 1.04 15.86 14.35 1.51 Pred 2 1.08 13.0 87 1.38 13.6 1.04 16.3 14.9 1.4 Test 3 0.48 15.7 51 1.38 15.0 2.36 17.24 15.76 1.48 Pred 3 0.48 15.7 51 1.38 15.0 2.36 18.1 16.8 1.3 Test 4 0.48 20.7 45 1.38 18.1 2.41 20.38 18.90 1.48 Pred 4 0.48 20.7 45 1.38 18.1 2.41 20.6 19.2 1.4 m "m /(Qρ) : mass #ow ratio of spray water to air ¹"¹!¹

1178 S. RIFFAT E¹ A. Table II. Comparison between the predicted and measured thermal performance of the cooling tower at a water #ow rate of 0.4 kg s. Supply air Spray water Chilled water Q ¹ RH m ¹ m ¹ ¹ ¹ Case (m s) (3C) (%) (kg s) (3C) (3C) (3C) (K) Test 0.48 14.3 92 1.23 16.1 2.10 18.15 15.19 2.96 Pred 1 0.48 14.3 92 1.23 16.1 2.10 19.1 17.6 1.5 Pred 2 0.48 14.3 92 0.59 16.1 1.00 19.5 17.1 2.4 Pred 3 0.48 14.3 92 0.29 16.1 0.50 19.5 16.8 2.7 Pred 4 0.48 14.3 50 1.23 16.1 2.10 19.1 17.1 2.0 Pred 5 0.48 14.3 50 0.59 16.1 1.00 19.2 16.2 3.0 Pred 6 0.48 14.3 50 0.29 16.1 0.50 18.2 15.7 2.5 Pred 7 0.48 14.3 50 0.35 16.1 0.60 18.4 15.6 2.8 The predicted tube temperature di!erence would therefore agree with the measurement at the design water #ow rate of 0.8 kg s. The di!erence between the predicted and the measured tube temperatures at the top and bottom rows was partly attributable to the high water-to-air mass #ow ratio and high relative humidity of supply air. Consequently, air was saturated throughout the tower, at temperatures much higher than the wet bulb temperature of the supply air. Furthermore, in the wet cooling tower, evaporative cooling would also occur on the tube surfaces but this e!ect could not be included in the simulation as described in the assumption for the heat exchanger. To improve the prediction, the mass #ow ratio and the humidity of supply air were arti"cially reduced. When the mass #ow ratio was halved (Pred 2 in Table II), the relative humidity of air through the heat exchanger was still very high (over 99 per cent) but was below the saturation level. Evaporative cooling of air could take place along the heat exchanger. The di!erence in the tube temperatures at the top and bottom of the heat exchanger increased to 2.4 K. When the mass #ow ratio was further reduced to about one quarter of the original value, from 2.1 to 0.5 (Pred 3), the relative humidity varied between 95 and 96 per cent and the temperature reduction of the tubes increased to 2.7 K. When the relative humidity of supply air was reduced from 92 to 50 per cent, while the mass #ow ratio remained unchanged at 2.1 (Pred 4), the air in the tower except for the area near the bottom of the heat exchanger was still saturated and the temperature di!erence of the tubes at the inlet and the outlet increased from 1.5 to 2.0 K. For the same supply air at a relative humidity of 50 per cent but for a reduced mass #ow ratio of one (Pred 5), the air was not saturated with a minimum relative humidity of 83 per cent at the bottom and a maximum of 98 per cent at the top of the heat exchanger. The predicted tube temperatures for the top and bottom rows were 19.2 and 16.23C, respectively. The tube temperature di!erence became the same as the measured temperature drop for cooling water of 3 K. When the mass #ow ratio was reduced to 0.5 (Pred 6), the predicted tube temperatures for the top and bottom rows were 18.2 and 15.73C, respectively, which were not far from the measured cooling water temperatures at the inlet and outlet. The tube temperature di!erence between the top and bottom rows was 2.5 K. For a mass #ow ratio of 0.6, the predicted tube temperature di!erence was 2.8 K (Pred 7).

CLOSED WET COOLING TOWER FOR CHILLED CEILINGS 1179 Therefore, for a completely wet cooling tower operating at water #ow rates lower than the design value, the prediction of thermal performance can be improved by arti"cially decreasing the mass #ow ratio and supply air humidity. 6. CONCLUSIONS The performance of a closed wet cooling tower for chilled ceilings has been measured experimentally. The measurements show that, there exists an optimum spray rate for a given air #ow rate or an optimum mass #ow ratio of spray water to air according to the cooling capacity and energy consumption. The e$ciency of the cooling tower increases with the air #ow rate and decreases with the increasing water #ow rate. The e$ciency increases slightly with the increasing wet bulb temperature of the supply air. However, increasing the wet bulb temperature would increase the outlet water temperature from the heat exchanger and decrease the cooling capacity of chilled ceilings. CFD has also been used to predict the thermal performance of the cooling tower. The predicted thermal performance has been compared with experimental measurement. As the CFD package does not have the capacity to simulate the heat transfer between and within the tubes of the heat exchanger and the evaporative cooling of the tube surfaces, the e!ect of water #ow rate on the temperature drop of the cooling water in the heat exchanger could not be predicted. Despite these shortcomings, the thermal performance of the cooling tower, in terms of the cooling water temperature drop, could still be predicted at the design water #ow rate but the tower performance would be under-predicted when the water #ow rate was lower than the design value and the tower was over-#ooded with spray water. To improve the prediction for performance evaluation at water #ow rates lower than the design value, appropriate measures could be adopted to compensate for the simpli"cations in the model so that the air through the heat exchanger would not be over-saturated. One such measure would be to reduce the mass #ow ratio if it is higher than the optimum value. ACKNOWLEDGEMENTS The authors wish to thank the Commission of the European Union (DGXII) for partially funding the project, under Joule IV research programme. All partners of the ECOCOOL research project are greatly acknowledged including Sulzer Infra Lab (CH), Sulzer Escher Wyss Lindau (DE), Helsinki Univ. Technology (FIN)*HVAC Lab. REFERENCES F ;EN¹ ;ser1s Guide. 1993. Fluent Inc., U.S.A. Gan G, Ri!at SB. 1999. Numerical simulation of closed wet cooling towers for chilled ceiling systems. Applied ¹hermal Engineering 19(12):279}1296.