PROPERTY INSPECTION REPORT - Example

Similar documents
Calidad Home Inspection Colleyville, TX (817) /

Inspection Report. Property Address:

Alabama Home Inspections

Home Inspection Report

Inspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011

1234 Main St. Buyer Name. Table of Contents

Inspection Report. Prepared for: Tonia Mann. Property Address: 56 Riverview Place Douglasville, GA Date: September 19, 2012

3D Home Improvement and Inspection Services, Inc

Inspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012

Madison's Home Inspections

component was performing its intended function; installation and condition were appropriate for age and use.

Home Inspection Report

All Pro Home Inspection. Home Report South Your Town

The Inspector. Property Inspection Report

GROUNDS Grading General Grading, slope and drainage: Satisfactory N/A See Notes. Grading and slope at house wall

The Home Doctor, Inc.

Mr. Homeowner Mrs. Homeowner

Inspection Report. Prepared for: Tonia Mann. Property Address: 1295 Greyland Hills Drive Lawrenceville, GA Date: April 24, 2012

Inspection Report. Prepared for: Yaron Sternberg. Property Address: 926 Hemingway Road Stone Mountain, GA. Date: April 15, 2011

My Home Was Built In What Can I Expect To See On My Report?

Inspect Hawaii. Property Inspection Report

FAIRA TRANSPARENCY REPORTS Robert Wayne Dr, Pasco, WA July 18 th, 2017

Report Page 1 of 23 12/30/2013 Tri-City Home Inspections James Eddy ID:

SUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM

SureHome Inspection Company. Home Inspection. Grant st Street Omaha, NE 68048

Home Condition Checklist

Bearmark Home Inspection LLC

A Sample Report On The Conditions At:

All Pro Home Inspection. Home Report North Your Town

SOUTH CAROLINA HOME INSPECTOR STANDARDS OF PRACTICE

1st Defense Home Inspections, LLC

Inspection Report. 1 of 8

Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002

JBR Property Inspections

Inspection Services of the Treasure Coast

Exterior structures (fences, sheds, decks, retaining walls, detached garages) in good condition, no evidence of termite damage or rotted wood

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS

REPORT CHECKLIST SUPPLEMENT

Property Inspection Report

InterNACHI Home Inspection Report Checklist

Property Inspection Checklist

Pre-Listing Home Inspection Checklist

Home Inspection Report

PROPERTY INSPECTION REPORT

WEST MICHIGAN HOME INSPECTORS LLC 3134 Chamberlain SE Grand Rapids MI

Friendly Inspection Services

Inspection Xpress. Property Inspection Report

Home Inspection Report

RENTAL INSPECTION CHECKLIST. Helpful Definitions: Egress: the free and unobstructed access to the exterior of a habitable space.

1234 Main St Denver CO 80210

9) Home Inspection: As defined in Section 1-10 of the Act.

TITLE 68: PROFESSIONS AND OCCUPATIONS CHAPTER VIII: DEPARTMENT OF FINANCIAL AND PROFESSIONAL REGULATION

HOME INSPECTION CHECKLIST

SC Standards Of Practice for Home Inspectors

Inspections Unlimited 12:38 August 20, 2013 Page 1 of 23 Sampleweb2013.pt6

Pacific Inspection Group Keaau-Pahaoa Rd Keaau, Hawaii Somewhere In Paradise Keaau, Hawaii 96749

Section Standards of Practice. a) The following are terms commonly used in the writing of home inspection reports.

Inspection Report. Jay Coleman. Property Address: Cooper Rd Brookshire TX Bill Harvey Inspection Services

Tru-Quest Home Inspection

UP AND UP HOME INSPECTIONS

Home Inspection Report

Total Home Inspection Checklist

Property Inspection Report

Accurate Inspections Inc. Property Inspection Report

Hogue Home Inspections

SAMPLE REPORT OF COMMON INSPECTION FINDINGS

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210)

Friendly Inspection Services

Home Inspection. 123 Main St Anywhere, USA Prepared for: Happy Homeowner Prepared by: Blue Crab Inspections

SUMMARY 1234 Main St.Hamilton Ohio Buyer Name 07/03/2018 9:00AM

6954 Lakeside Dr. Property Inspection Report. - Provided by First Class Property Inspections, LLC -

Beneficial. Home Inspections. Your Home Inspection Report. John Doe. Customer Name - 02/30/2002. Inspection Date Sample Drive Inspection TX

Willamette Home Inspection

Home. Safe. Home. home inspection report

Pinnacle Home Inspections, Inc. Serving Central Arkansas

HOME INSPECTION REPORT Prarie Circle

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX

EXCEL INSPECTIONS PROPERTY INSPECTION REPORT

Advanced Home Inspections

Hawks Eye Home Inspection LLC. Shoreline, Wa Williams Rd. Renton, Wa 98057

Home Inspection. Happy Home Buyer 125 Happy Lane Anytown TN The date of the inspection

Chris Nowling Inspection Services 6608 Wolfcreek Pass Austin, TX (512)

APPLICATION FOR FINISHED BASEMENT PERMIT

Ottawa Inspections Inspection Report

Bill Ostoyic Building Inspection Report XXXXXXX XXXXX XXXXX, Fl. Licensed and Insured

SAMPLE Property Inspection Report

1623 Carol Street Downers Grove, Illinois Inspection Report for Property at: Private Home Inspection for:

SUMMARY 1234 Main St.Severn Buyer Name 02/20/2018 9:00AM

A 1 Professional Home Inspection 14 Brevoort Pl. Deer Park, NY Jamaica, NY 11434

Capstone Inspection Services LLC

Vallery Home Inspections, L.L.C.

Property Inspection Report

Friendly Inspection Services

Summary. Inspect It Like A Girl. P.O. Box 2283 Madison, MS Customer Happy Home. Address 123 Happy Home Road Jackson MS 39157

Property Condition Assessment

SUMMARY. Appliance: Corrective Action(s)

INSPECTION TEAM, INC.

The Inspection Process. Waxhaw N.C.

Inspection Report. Big Sky Home Inspection, LLC Michael J Gage TREC Lic. # Sample Lane Austin, TX 78734

Transcription:

PROPERTY INSPECTION REPORT - Example Prepared For: Smart Buyer or Seller (Name of Client) Concerning: Anystreet, Anytown Texas (Address or Other Identification of Inspected Property) By: Jeff Wampler TREC# 5592 Sheldon Conrad TREC# 9974 (Name and License Number of Inspector) (Date) (Name, License Number and Signature of Sponsoring Inspector, if required) Present At inspection: Weather Conditions: Temperature During Inspection: Arrival Time: Departure Time: Year House Built: Special Notes: ADDITIONAL INFORMATION PROVIDED BY INSPECTOR (Example) As a reference point the house faces: Filling in the above items gives us a reference point for the conditions under which your home is inspected. Sample Photo We like to use blue to indicate positive / informative comments from the inspector regarding your home. In this way, the report transforms into a marketing document. Below, items commonly identified on reports will be explained in green Promulgated by the Texas Real Estate Commission(TREC) P.O. Box 12188, Austin, TX 78711-2188, 1-800-250-8732 or (512) 459-6544 (http:\\www.trec.state.tx.us). REI 7A-0 Page 1 of 14

I. STRUCTURAL SYSTEMS A. Foundations (If all crawl space areas are not inspected, provide an explanation.) Type of foundation: Slab-on grade Pier and beam Method of inspection: Visual inspection of exterior Comments (An opinion on performance is mandatory.): The foundation is performing as intended. No significant problems were observed Minor cracks were observed in the foundation and exterior walls of the house (See Walls section for more details). This implies that some structural movement of the building has occurred, as is typical of most houses. Recommend these areas be monitored for further changes. Slightly greater than typical foundation cracking was observed. (See Walls section for more details). The amount of movement does not suggest a structural issue, as typical secondary indicators were not observed (gaps around windows, doors, and / or frieze boards, windows and doors that do not operate properly, cracks on interior walls. ceilings and floors.) As the rate of movement cannot be predicted during a one-time inspection it would be wise to have the foundation further evaluated by a structural engineer. More than normal foundation settling was observed for a house of this age. (See Walls section for more details). This implies that structural movement of the building has occurred. The rate of movement cannot be predicted during a onetime inspection. Recommend a structural engineer be consulted to further evaluate this condition and the remedies available for correction. Inspector Note: 1.The soil in this area has high clay content. Clay soils are like a sponge and expand when wet & shrinks when dry. A consistent water maintenance program is recommended year round to keep even moisture levels in the soil. 2. Areas with trees closer to the structure will require additional moisture as tree roots absorb moisture from the soil. Here, we will inform you of any foundation cracking, exposed cable ends or indicators of foundation movement. If performing a Pre-Listing Inspection, any problems can be identified early, rather than leaving a buyer suspicious. B. Grading & Drainage Common items in this area would include adding downspout extensions, identifying underground drainage systems, and watching for possible drainage improvements. Any deficiencies are generally easy to remedy, if desired. C. Roof Covering (If the roof is inaccessible, report the method used to inspect.) Type of roof covering: Asphalt Composition Wood Clay Tile Metal Method of inspection: Walked on roof Limited walk due to pitch Viewed with binoculars Verification of nailing pattern per TREC SOP s: Examined nails from attic penetrating decking Unable to verify all areas In the example below, wouldn t it be best to know about this simple item prior to listing? Many items can be repaired ahead of time by a handyman, at great savings. When discovered during an inspection, any deficiencies will be documented with photos for ease of repair. Page 2 of 14

Observed a vent stack boot on the rear elevation of the house which has deteriorated and should be repaired or replaced. D. Roof Structure & Attic (If the attic is inaccessible, report the method used to inspect.) Method of inspection: Entered attic Viewed from access hatch None no access located Estimated depth of ceiling insulation: 14 + or R30 Recommended 12 14 Common >8 Marginal Approximate average thickness of vertical insulation: Not visible 3 4 where visible >4 where visible Roof Structure: Wood rafter Trusses Roof Ventilation: Flat vents Turbines Soffit vents Gables Power vents Ridge vents Inspector Note: Radiant Barrier roof sheathing is present. Radiant Barrier provides much greater attic efficiency than traditional methods, and is the preferred material in modern roof structures. The above comment is something we like to do in our Pre-Listing inspections, to make potential buyers aware of the positive aspects of the structure. E. Walls (Interior & Exterior) Interior Wall Finish(s): Sheetrock Paneling Plaster Observed typical minor interior wall cracks. This implies that some structural movement has occurred, as is typical of most houses. These can be patched and painted as desired. Exterior Wall Finish(s): Brick Stone Siding Stucco EFIS Observed typical minor cracks on the exterior walls of the house. This implies that some structural movement has occurred, as is typical of most houses. No repairs are needed at this time. The seals on these walls will eventually need improvement This is the most common area to find areas requiring caulking and sealing. A well-sealed house remains weather-tight, and leaves a positive impression with buyers! Large or unusual cracks, identified in this section, can be data points in our evaluation of foundation performance. Other common items generally included in the walls section include caulking and sealing improvements. See example below: Page 3 of 14

Observed some minor mortar cracking in the concrete coping around some of the front windows and over the single garage. This condition is typical, and should be monitored. Any cracks or gaps should be filled as necessary to avoid water penetration. Fire Separation Between Attached Garage & Dwelling Effective Feb. 1, 2009 TREC established new Standards of Procedures for inspectors regarding fire separation between the garage, the attic and the living space. Proper fire separation includes a finished dry wall on the interior of the garage with no penetrations (unless sealed with approved fire rated materials), properly sealed attic accesses and fire rated doors between the residence and the garage. Any deficiencies in proper fire separation are checked below: Attic access (covering is comprised of combustible materials, no covering for attic access) Finished dry wall on interior of garage is missing Fire rated doors are not present between garage and residence Unapproved penetrations in garage wall abutting the residence (outlets with plastic junction boxes, holes in the wall) Other (specify) F. Ceilings and Floors Ceiling Finish(s): Sheetrock Plaster Floor Surfaces: Carpet Tile Linoleum Wood / wood like The following is a common item we discuss with buyers. Vaulted ceilings are easily understood. Observed cosmetic cracks in the seams and a few nail heads starting to pop on the vaulted ceilings. This is common on ceilings that are at an angle an have no attic space over head. G. Doors (Interior & Exterior) Page 4 of 14

H. Windows Window Glazing / Insulation: Single Pane Double Pane Storm Window This home has vinyl-framed, energy efficient windows which disconnect at the top for easy cleaning! Common window items include: Replace or repair window screens where missing or damaged. Fogged Windows Inspectors notes regarding windows the determination of broken or compromised vapor barriers on windows has several limitations. For example, dirty windows, access to windows (occupied houses), weather conditions (clear vs. cloudy, warm vs. cold, dry vs. humid), time of day (morning vs. evening) or any after market solar blocks. A compromised vapor barrier may or may not be indicated by fogging or condensation inside the window panes at time of inspection. If inspector comments above indicate windows with current or possible prior condensation, it is recommended a window professional be consulted to evaluate all windows for any active or possible prior condensation. I. Stairways (Interior and Exterior) J. Fireplace/Chimney Fireplace Material: Brick Metal / Ceramic Chimney Material: Brick Wood framing Metal Ventless: Living room When we inspect fireplaces, we look for safety and structure, examining the flue, chimney and firebox. These are items we re sure buyers and sellers would like to be aware of. K. Porches, Balconies, Decks and Retaining Walls, Carports (Attached) L. Other Page 5 of 14

II. ELECTRICAL SYSTEMS A. Service Entrance and Panels Size of Electrical Service: 120 / 240 volts 110 volts Service Entrance Wires: Buried Wiring Overhead Wiring Main Disconnect Size: 225 amps 200 amps 150 amps None, complies with code We will include a photo of the interior of any panels, as shown below and check for proper wire sizes, good connections, and identify any potential safety issues. Here is the interior photo of your electrical panel(s) - Example B. Branch Circuits - Connected Devices and Fixtures Type of branch circuit wiring: Copper Aluminum Receptacles: Grounded Not Grounded Branch Circuits refer to wiring, past the panel, running throughout the house along with the connected fixtures. It is quite common for multiple deficiencies to be discovered in this area. These items are often perceived by buyers as safety issues. Repair or improvements of these items is typically straightforward. Note: As a seller, typically these items can be repaired by a handyman. If identified at a later time, a licensed electrician will generally be required. When would you like these items identified? Page 6 of 14

Ground fault protection, ARC fault protection and smoke alarms Ground Fault Circuit Interrupters (GFCI) and GFCI enabled: Effective Feb. 1, 2009 TREC established new Standards of Procedures for inspectors. Inspectors are to inspect for GFCI outlets in all bathroom outlets, all kitchen counter top outlets, all outdoor outlets and all garage outlets. In addition, outlets located within 6 feet of the outside edge of the sink(s) located in the laundry room, utility room and wet bar sink. A ground fault circuit interrupter (GFCI) offers protection from shock or electrocution. Any departures from GFCI guidelines are checked below: Arc Fault Circuit Interrupters (AFCI) Effective Feb. 1, 2009 TREC established new Standards of Procedures for inspectors. Inspectors are to inspect for proper Arc Fault Protection (AFCI) devices for all electrical receptacles in family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreations rooms, closets, hallways, or similar rooms or areas Any departures from AFCI guidelines are checked below: AFCI protection is not installed in the house (consistent with pre 2003 NEC code) AFCI installed in the bedrooms only. No other areas have AFCI protection. (consistent with post 2003 NEC code) Effective Feb. 1, 2009 TREC established new Standards of Procedures for inspectors. Inspectors are to inspect for smoke alarm installations as follows: 1. smoke alarms connected to a central system 2. Installations of smoke alarms in all bedrooms and hallways that access each bedroom. Any departures are noted below: Smoke alarms are not centrally connected Smoke alarms are not installed in all bedrooms and appropriate hallway(s) Smoke alarms are not operating Inspector unable to determine if alarm system is connected to a monitoring service, therefore alarms not operated. Page 7 of 14

III. HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS A. Heating Equipment Type of heating system: Central Forced Air Heat Pump Energy source: Electricity Gas Proper operation of the furnace is checked, and typically we like to include filter sizes along with where they go, as shown below: Inspector Note: All filters are 20 x 25 x 1 all located in the attic. B. Cooling Equipment Type of cooling system: Central Forced Air Window Unit Energy source: Electricity Gas Unit Size(s) / Date of manufacture: Size, age and condition of each cooling unit is observed and measured. Often, service is called for if deficiencies are noted. These items can be identified and dealt with easily in a Pre-Listing Inspection. See Example below: North Middle South Temperature at air return: 80 78 78 Temperature at air supply: 59 57 58 Desired Differentials 16-21 degrees 21 21 20 Page 8 of 14

Observed rust in the bottom of the secondary drain pan of the attic portion of the north AC unit. Recommend this be serviced by a licensed HVAC technician if the unit has not been serviced in the last 6 months. Inspector Note: Please review the additional disclosures below regarding: 1. Inspections of air conditioning systems and warranties for evaporator coils. 2. How to determine / verify adequate sizing of heating and cooling systems. Disclosure regarding evaporator coils: Evaporator coil(s) are the number one item that show up on home warranty claims and are commonly disallowed due to prior lack of cleaning. The air conditioning system fan(s) and evaporator coil(s) are not readily accessible for inspection without disassembling. Because the inspector does not disassemble equipment the condition of these items are unknown. If the system does not have a history of cleaning over the past 2 to 4 years (a subjective number) then professional servicing may be justified. The only way to verify the condition of the evaporator coil for warranty purposes is for the unit to be serviced / evaluated by a licensed HVAC technician. Inspectors notes regarding limitations of sizing information disclosed above: The above information above (if available) was recorded from the manufactures nomenclature plate located on the outside condensing unit installed. An inspection of internal components was not completed. Inspectors DO NOT verify sizing of installed equipment, sizing per conditioned square foot or matching of heating and cooling system components. For adequate sizing of heating and cooling systems a "HEAT GAIN AND LOSS REPORT" must be completed. This report is completed by a licensed mechanical contractor. Heat gain and loss reports are normally completed prior to construction; this report typically would have been filed with the General Contractor. C. Ducts, Chase and Vents Duct Insulation: Aluminum Wrap Plastic Wrap Duct Material: Flex Duct Metal Duct Page 9 of 14

IV. PLUMBING SYSTEM A. Water Supply System and Fixtures Water Supply Service: Public Water System Private Well / Coop Supply Location of water meter: End of driveway Front of house Not located Location of main water supply service: Near water meter Front of house Not located Static water pressure at hose bib closest to water main: (60 80 is normal) Again, many plumbing deficiencies can easily be remedied when identified, with no need for a professional plumber as often happens when negotiating repairs. Below are a few examples of common plumbing deficiencies: Recommend minor caulk and grout improvements in the guest baths tub and shower areas. Any cracked and/or missing shower stall grout and caulk should be replaced. Observed a loose toilet in the master bathroom. Recommend this toilet be re-secured. B. Drains, Wastes, Vents Waste System: Public Sewer System Private Septic System C. Water Heating Equipment Energy source: Electricity Gas Water Heater Size / Mfg Date: 50 gallons / 2000 40 gallons / Location: Garage Attic Hall Closet Utility Closet Water heaters are a common source of problems when inspected due to improper installation, gas leaks, disconnected flues etc. Why not discover problems early and make the water heater(s) a non-issue? (as well as keeping your home safe!) D. Hydro Massage-Therapy Equipment Here is a common Jacuzzi deficiency which is easily remedied: The GFCI switch for the Jacuzzi (located in the master bedroom closet) will not trip. Recommend replacing the switch. Page 10 of 14

V. APPLIANCES Appliances are all tested for proper operation and safety A Dishwasher B. Food Waste Disposer C. Range Exhaust Vent D. Ranges/Ovens/Cooktops Oven temperature when see to 350 degrees: E. Microwave Oven F. Trash Compactor G. Mechanical Exhaust Vents and Bathroom Heaters TREC requires inspectors to verify bath room exhaust fans terminate to the exterior. H. Garage Door Operators The most common issue with garage door openers is lack of proper safety adjustment. When identified, this is an easy item to fix. I. Door Bell and Chimes J. Dryer Vents Page 11 of 14

VI. OPTIONAL SYSTEMS Optional systems include Sprinkler Systems, Pools & Equipment, Outbuildings, Outdoor Cooking Equipment, Gas Supply & More. A thorough inspection of these items now can save costly re-negotiation later! Our inspections also include a complete summary of all items, providing a quick & easy punch-list of items that may warrant attention. Don t take chances..take control of your listing by inspecting first for success! Page 12 of 14

Addendum A: Summary All items added to the report as Deficiencies will be listed with no photos in this section for quick and easy reference. Page 13 of 14

Calidad Home Inspection 517 Wagonwheel Court - Colleyville, TX 76034 Phone: 817.896.1203 Fax: 817.656.9980 www.calidad-tx.com INVOICE Property Address: Anystreet, Anytown Texas Inspection Date: Client: Smart Seller Payment amount: $ Thank you for allowing Calidad Home Inspection to be of service to you. If you have any questions please feel free to contact us at (817) 896-1203. Page 14 of 14