Renewable Energy Based Active Cooling System

Similar documents
The impact of hot and cold storages on a solar absorption cooling system for an office building

Experimental analysis of a solar absorption system with interior energy storage

Experimental investigation of solar-driven double ejector refrigeration system

SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

EFFICIENT SOLAR COOLING

Experimental Research and Performance Analysis of a Solar-Powered. Air-conditioning System in a Green Building

Performance Analysis of a Solar Powered Adsorption Cooling System

Energy Mix Opportunity of Vapor Absorption Refrigeration System Integrated With Solar Collectors: A Case Study of Hotel Shangri-La

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia

Figure 1: Uncovered and covered PVT collectors

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Thermodynamic Simulation of an Advanced Hybrid Solar-Gas Seawater Desalination System

Solar cooling plants: how to arrange solar collectors, absorption chillers and the load

Analysis of Solar Thermal Cooling System Using TRANSOL

Modeling and analyzing solar cooling systems in Polysun

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

Comfort Cooling Application Using Fixed Focus Solar Parabolic Dish Concentrator Integrated with Double Effect Vapor Absorption Machine

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Thermodynamic analysis of a direct expansion solar assisted heat pump water heater

Advanced heat driven cooling cycles for low-temperature waste heat recovery

PERFORMANCE OF SOLAR AIR-CONDITIONING SYSTEM USING HEAT PIPE EVACUATED TUBE COLLECTOR. M. Moorthy

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

Simulation Studies on Performance of Solar Cooling System in UAE Conditions

International Journal of Mechanical Civil and Control Engineering. Vol. 1, Issue. 3, June 2015 ISSN (Online):

Optimization of Solar Cooling Systems with Simulation Modeling

SorTech package solution description

Evaluation of efficiency and collector time constant of a solar flat plate collector

Customized Absorption Heat Pumps for Utilization of Low-Grade Heat Sources

Experimental analysis of heat-pump integrated with solar energy

Performance enhancement of a photovoltaic thermal (PVT) and ground-source heat pump system

Control strategies study of a complete solar assisted air conditioning system in an office building using TRNSYS.

Parametric Study of a Double Effect Absorption Refrigeration System

Utilization of f-chart Method for Designing Solar Thermal Heating System

Department of Mechanical and Materials Engineering. Solar Energy Research Institute Faculty of Engineering and Built environment.

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems

THERMAL ENERGY ANALYSIS OF SOLAR POWERED VAPOUR ABSORPTION COOLING SYSTEM

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Asian Journal on Energy and Environment ISSN Available online at

Simulation of Solar Thermal Cooling System for an Office Building in Indian Climates using Evacuated Tube Collector

Performance Modeling of a Solar Driven Absorption Cooling System for. Carnegie Mellon University s Intelligent Workplace

Solar Trigeneration: a Transitory Simulation of HVAC Systems Using Different Typologies of Hybrid Panels

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Design and optimization of solar water heating system for a five star hotel in Varanasi

Simulation and economic analysis of solar cooling for building in tropical climate of Surabaya, Indonesia

Performance analysis of solar powered absorption chiller and thermal storge system for commercial buildings for Turkey

Cool Producing Systems Based on Burning and Gasification of Biomass

Energy and Exergy Economic Analysis of Cogeneration Cycle of Homemade CCHP With PVT Collector

COMPARATIVE STUDIES ON THERMAL EFFICIENCY OF SINGLE AND DOUBLE GLAZED FLAT PLATE SOLAR WATER HEATER

Simulation And Optimization of a Solar Absorption Cooling System Using Evacuated Tube Collectors

Myth Busters Absorption Cooling Technology. Rajesh Dixit

Optimization of Absorption Chiller by Assisting it with Solar Thermal Energy

Solar chilled drinking water sourced from thin air: modelling and simulation of a solar powered atmospheric water generator

Computational Study of Hybrid Water Heater with Evacuated Glass Tube Solar Collector and Rice Husk Combustion

On the Night Heat Losses in Thermosyphon Solar Water Heaters

ASSESSMENT OF R290 AS A POSSIBLE ALTERNATIVE TO R22 IN DIRECT EXPANSION SOLAR ASSISTED HEAT PUMPS

State of the Art of Air-source Heat Pump for Cold Regions

Peer Reviewed 2014 Solar Research Conference

A STUDY ON PERFORMANCE OF SOLAR SEAWATER DISTILLATION SYSTEM WITH AN AUXILIARY HEAT SOURCE FROM SOLAR COLLECTOR

DEVELOPMENT OF A HYBRID AIR-CONDITIONING SYSTEM DRIVEN BY LOW TEMPERATURE WASTE HEAT

Energy Efficient Solar Milk Chiller

Performance Evaluation of Solar Assisted Heat Pump Water Heating System

Innovative Systems for Solar Air Conditioning of Buildings

Solar cooling design: a case study

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Simulation of Solar Air-Conditioning System with Salinity Gradient Solar Pond

The Present and Future of Refrigeration, Power Generation and Energy Storage. R.Z. Wang Shanghai Jiao Tong University

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Performance analysis of a new single effect hot water absorption chiller system

Life cycle analysis of thermosyphon solar water heaters

M. Karagiorgas, M. Tsagouris, K. Galatis BONAIR Meletitiki, Greece. A. Botzios-Valaskakis CRES, Greece ABSTRACT

Heat pumps. WP5 Education and Economic Promotion

DESIGN AND MODELING THE Φ-F

Heat rejection systems for solar driven sorption systems

New developed solar thermal systems for heating and cooling Budapest, 16 th April 2009 Tsekouras Panagiotis Mech. Engineer NTUA Centre for Renewable

The Novel Solar Water Heating by Means of Thermoelectric Modules

SOLAR COOLING FOR ENERGY SAVING. CAN WE AFFORD NOT TO USE THE HEAT OF THE SUN?

COMPARISONS BETWEEN TRNSYS SOFTWARE SIMULATION AND F-CHART PROGRAM ON POOL HEATING SYSTEM

Introduction to Geothermal Comfort Systems in INDIA

Solar Powered Vapour Absorption Refrigeration (SPVAR) System as a rural microenterprise

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

OPTIMIZATION OF PCM NUMBER IN HOT WATER TANK FOR THE APPLICATION OF SOLAR DRIVEN ADSORPTION CHILLER IN TROPICAL CLIMATE

Identified technologies for the InfraSUN pilot plant

Performance analysis of a new single effect hot water absorption chiller system

Financial Evaluation of Solar Powered Absorption Cooling System for Computer Laboratory

EXPERIMENTAL DEVELOPMENT TO DETERMINE TIME CONSTANT FOR POLYMER COLLECTOR

Enhancement of LNG Propane Cycle through Waste Heat Powered Absorption Cooling

AR No. # - Solar Thermal

Modelling and Simulation of Solar-Biomass Hybrid Trigeneration using ORC-VCC

Mathematical Modeling of Basic Parts of Heating Systems with Alternative Power Sources

A Fundamental Study for Designing a Safe and Eco-friendly Community

Design and Experiments of a Solar Low-temperature Hot Water Floor Radiant. Heating System 1

A STUDY OF ABSORPTION CHILLER/HEATER APPLICATION IN MARINE ENGINEERING

DEVELOPMENT OF A HIGH EFFICIENCY ABSORPTION CHILLER-HEATER AND A COMPACT ABSORPTION CHILLER-HEATER

A New Absorption Machine for Both Cooling and Heating

EVALUATION OF SOLAR SORPTION REFRIGERATION SYSTEM PERFORMANCE IN LATVIA

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

CMR Journal of Engineering and Technology Vol.2 Issue.2 April, 2018

2

Packaged AHR (Advanced Heat Recovery) Systems for Engines, Gas Turbines, & Industrial Waste Heat. Tom Pierson

Introduction to Geothermal Comfort Systems in INDIA

Transcription:

1th Eco-Energy and Materials Science and Engineering Symposium, Ubon ratchathani, Thailand, December -8. 212 Renewable Energy Based Active Cooling System Boonrit Prasartkaew Department of Mechanical Engineering, Faculty of Engineering, Rajamangala University of Technology Thanyaburi, Klong 6, Thanyaburi, Pathumthani 1211 E-mail: prasartkaew@yahoo.com Abstract To address the serious problems of energy crisis and global warming, renewable energy is one of the major options. This paper reports on the experimental study of a solar-biomass hybrid air conditioning system. The research aims at developing a fully renewable energy based air conditioning system and assessing the feasibility of this new hybrid system. The experimental results demonstrate that when the chiller was operated at about 7% of nominal capacity its coefficient of performance was about.6. To compare the performance of solar cooling system with different driving energy sources, the experimental results of three modes of operation, with the same operating parameters and almost the same weather conditions, were compared. The results show that the proposed system can be operated with higher reliability and performance compared to the conventional systems which operate with and without auxiliary heater. Therefore, application of a solar-biomass hybrid air conditioning system is promising. Keywords Solar, Absorption, Biomass, Active cooling, Hybrid 1. INTRODUCTION The global warming problem is strongly affecting all lives on earth. The main greenhouse gas, CO 2 is generated from combustion processes. Air conditioners consume about 7% of the building s electricity consumption [1]. To address the environmental problems caused by the use of fossil fuel and chlorofluorocarbons, the development of an environmental-friendly renewable based cooling system become important. The use of solar energy for cooling purpose is attractive because the cooling load is roughly in phase with solar energy availability and it uses the environmental friendly refrigerant. Currently, solar energy based air-conditioning systems are available [2,3]. However, solar energy is intermittent, and so an auxiliary heat source becomes inevitable. Furthermore, the weakness of a solar (solely) absorption cooling systems is that it can be used only during day time. There are few experimental studies on such systems [3] and []. Reference [3] reported the experimental results from field testing of a solar energized cooling system without auxiliary heater. The experimental results show that their system was operated during hours of bright sunshine. Cooling was provided for 8.67 hours with a maximum instantaneous, daily average and period average coefficient of performance were.6,.42 and.34, respectively. Reference [] also presented experimental results on solar absorption cooling system. Their facility is based on an on-campus field of m 2 flat plate solar collectors driving a single-effect commercial 3 kw absorption machine. Their results show that it produced a daily average cooling power of 3 kw for 6. hours with a low efficiency. Though the current research related to solar powered absorption cooling, most of this kind system use auxiliary based on fossil fuel, e.g.: electricity, gas, and oil [6-1]. So, these systems still are fossil energy based systems. To develop the fully renewable energy cooling system, renewable energy source must be considered to function as an auxiliary heater. Regarding the use of biomass, which is a CO 2 neutral energy source, gasification of biomass offers advantages over other sources. Using solar and biomass can significantly contribute to the reduction of CO 2 emission. A theoretical study on the performance of a solar-biomass hybrid air conditioning (SBAC) system has been done [11]. Their results show that the proposed SBAC system for tropical locations is feasible, and can replace conventional vapor compression systems, thus reducing the need for fossil fuel based energy systems for cooling purposes. This study aims at evaluate the performance of SBAC system as an alternative system and compare with conventional solar cooling systems. On this basis, the performances of a SBAC system, quantity of biomass use, coefficient of performance of the chiller and the overall system were investigated. Section 2 describes the experimental system. Section 3 presents the instrumentation and data acquisition system used. Section 4 presents the experimental procedure. Section reports the observations and discusses the experimental results. Section 6 presents the comparison study. The conclusion of study is presented in section 7. 2. DESCRIPTION OF EXPERIMENTAL SYSTEM The experimental system of solar-biomass hybrid absorption cooling system was set up as shown in Figure 1. It consists of three main parts: solar water heating (SWH) system with a storage tank, biomass gasifier-boiler (BGB) system, and single-effect LiBr-H 2 O absorption chiller. The solar energy is absorbed for heating the water as a working fluid at the collector field and pumped to the tank by the forced pump. This pump will be activated by controller. Usually, it remains off until the difference

1th Eco-Energy and Materials Science and Engineering Symposium, Ubon ratchathani, Thailand, December -8. 212 Solar collector Controller 2 Hot water storage tank Controller 1 P1 M P2 Absorption Chiller P3 Cooling tower Generator 7 Condenser Biomass Gasifierboiler 3 2 1 4 Solution heat exchanger 6 P hi P lo 8 9 P4 Cooling space Absorber 1 Evaporator Fig.1. Schematic diagram of the solar-biomass hybrid absorption cooling system between collector outlet and tank temperatures is above the upper dead band value [12]. The controller will switch the pump off when this difference reaches the lower dead band. The second part is automatic on/off biomass gasifierboiler located between hot water storage tank and absorption chiller machine. This insulated boiler has two functions: works as auxiliary boiler when solar energy is not enough and works as main heat source when the solar radiation is not available. Because of its intermittent working conditions, this kind of gasifier boiler is proposed to utilize the available biomass resources. The automatic gasifier boiler is controlled by controller and supplies hot water for chiller. The cooling is provided by a single-effect LiBr-H 2 O absorption chiller. Heat from solar collector or from biomass-boiler evaporates the water in the generator of the absorption chiller. This is led to the condenser, where it rejects heat to the ambient and condenses. This is taken to the evaporator (through the expansion valve), where it receives heat from the space to be cooled and evaporates. The evaporated refrigerant (water) is absorbed by the weak solution in the absorber (from the generator). The absorption process also releases heat to the ambient, and the solution, now rich in water (strong solution) is taken to the generator (by a pump) to complete the cycle. The heat required for its generator is drawn from hot water pumped from a storage tank fed by the solar collectors and/or sometimes boosted/fed by biomass boiler. The condenser and absorber of chiller are cooled by cooling water pumped through a cooling tower. The chilled water produced from evaporator is pumped for cooling purposes. The experimental SBAC system consists of 26-flat plate collector field with total area of about 49 m 2, a hot water storage tank of.4 m 3 and a 7 kw single-effect LiBrwater absorption chiller. 3. DATA ACQUISITION SYSTEM To carry out the study of the performance evaluation of the SBAC system, measurements of temperatures, flow rates, electricity and solar insolation were carried out. A data logger (Campbell Scientific Inc. model CR-1X) equipped with multiplexer (solid-state type AM2T) were used to record temperature with type-k thermocouples installed at different locations and solar insolation data were measured at the meteorological station. These data were recorded every five-minute intervals. The others data were manually measured and recorded every half an hour. 4. EXPERIMENTAL PROCEDURE The experimental studies consisted of three modes of operation: A) solar cooling system with electrical auxiliary boiler, B) solar-biomass hybrid cooling system, and C) solar solely cooling system. Mode A) and C) of experiments were done aims at estimating performance of the system as base cases. The quasi-steady state condition for each experimental result was defined with the criteria that all variation between time steps of each measured

Temperature [C] Solar insolation [w/m 2 ] insolation [W/m2] Ambient temperature [C] 1th Eco-Energy and Materials Science and Engineering Symposium, Ubon ratchathani, Thailand, December -8. 212 parameters must be less than 1% for all measuring parameters over a period of 3 minutes or longer. The data during the quasi-steady state conditions will be chosen and used for the performance analysis. The SWH and BGB systems were started at about 8:. The water flow rate of collector, generator, cooling tower and chilled water pumps were set at 1,2, 1,,,4 and 9 kg/hr, respectively. To prevent crystallization, the chiller was started later when the boiler temperature was higher than 7 C. The BGB was switched OFF whenever the average tank temperature reached 84 C and switched ON whenever this temperature is lower than 8 C. When the BGB is switched on, the hot water temperature was controlled at the set point temperature of 84 C. When the temperature difference between the collector outlet and average tank temperature was less than 2 C, the collector pump was switched off. To analyze the transient energy balance of each component and overall system during the experimental day, the energy transfer (in MJ) of each -minute interval was determined. The daily average or quasi-steady state energy balance results can be used for pointing out the amount of energy at each direction. The overall system performance/efficiency can be directly improved using this result, especially reducing the major losses of the culprit components. Weather Condition during the Experiment Figure 3 shows the solar insolation and ambient temperature of the experimental day. The maximum insolation of this partly cloudy day is about 1, W/m 2 and the daily radiation incident on the tilted collector is about 19 MJ/m 2 day. The ambient temperature varied in the range of 2 to 3 C.. RESULTS AND DISCUSSION The SBAC system was tested during 3 to 3 September 21. The experimental data of system components and overall system performances during a partly cloudy day (16 Sep 21) are demonstrated as an example. An overview of measured temperatures and quasi-steady state periods during this experimental day are shown in Figure 2. The other experimental days were used for the daily average performance analysis. 1 9 8 7 6 4 3 Solar radiation Ambient temperature 4 4 3 3 2 2 1 2 16/9/1 1 2 1 1 8 1 2 3 4 6 7 8 9 1 11 12 13 14 1 16 17 18 19 2 21 22 23 24 1 1 S1 S2 B3 6 Fig.3. Solar insolation and ambient temperature of the experimental day 4 System Performance 2 The energy balance of the SBAC system can be described as shown in Figure 4 and determined using (1). 8 9 1 11 12 13 14 1 16 17 18 19 BI BII Chiller in operation collector inlet (T1) collector outlet (T2) tank temperature (T3) tank inlet (T4) tank outlet (T) boiler temperature (T6) boiler inlet (T7) boiler outlet (T8) flue gas temperature (T9) generator inlet (T1) generator outlet (T11) entering cooling water (T12) leaving cooling water (T13) entering chilled water (T14) leaving chilled water (T1) evaporator temperature (T16) condenser temperature (T17) fan coil unit temperature (T18) room temperature 1 (T19) room temperature 2 (T2) solar insolation BIII Fig.2. Temperature profiles and quasi-steady state periods of an example day As shown in Figure 2, the BGB was operated in three periods: 8: to 1:4 (BI), 1: to 11:3 (BII) and 1:1 to 18: (BII) and for rest, the chiller was energized by solar energy. Considering the quasi-steady state condition criteria, there are three periods of quasi-steady state condition: running on solar from 11:2 to 12:1 (S1), running on solar from 13:1 to 14:1 (S2) and running on biomass from 1: to 17:1 (B3). The performances of the components and overall system are described using these quasi-steady state period s data. Fig.4. Energy balance of a solar-biomass hybrid air conditioning system G T + Q BM + Q ev = Q re + U sys + Q l (1) Figure shows the energy transfer of each -minute interval of the overall system. The average values during each quasi-steady state condition are summarized as shown in Table 1. When the system was operated on solar energy (S2, 13:1 to 14:1), the average solar energy

COP Energy [MJ] 1th Eco-Energy and Materials Science and Engineering Symposium, Ubon ratchathani, Thailand, December -8. 212 input was about 13 MJ. Due to its very large surface loss and fluid loss during long water circulation loop, the total energy loss is high, and the average value is 1.24 MJ or about 78.% of solar input energy. The system energy loss, when it was energized by BGB, was 4.6 MJ or about 72% of biomass input energy. 2 1 1 - Fig.. Energy balance of SBAC system Table 1. Average values of energy transfer (in MJ) during each quasi-steady state condition Steady Solar Biomass Absorbed Rejected Internal Loss state S1 13.2.62 1.2 3.3 1.3 1.89 S2 13.. 1.6 3.62.61 1.24 B3.74 6.34 1. 3.3 -.4 4.6 Figure 6 shows the chiller coefficient of performance (COP) and the overall system coefficient of performance (COP sys ) calculated using (2) and (3), respectively, where Q ge is generator heat rate, A c is collector area, m BM is biomass consumption rate and LHV BM is biomass heating value. Since the chilled water was produced at around 1:1 (about 1.4 hr from the start), both COP and COP sys values were higher than zero at this time. During quasisteady state conditions, the COP sys varied in the range.4 to.64 and.1 to.33, respectively. The average value of COP is.3. 1..9.8.7.6..4.3.2.1. 1 2 3 4 6 7 8 9 1 11 12 13 14 1 16 17 18 19 2 21 22 23 24 Solar energy Biomass energy Evaporator heat Rejected heat Internal Energy Overall heat loss COP COPsys 6 7 8 9 1 11 12 13 14 1 16 17 18 Fig.6. Chiller and overall system coefficient of performance COP = Q ev Q ge (2) COP sys = Q ev (G T A c + m BMLHV BM ) (3) 6. CONCLUSIONS The performance of a solar biomass hybrid air conditioning system was evaluated by an experimental study. The experimental system was tested for three modes of operation: conventional solar cooling with electrical heater, proposed system and solar solely system. The experimental results show that the developed solarbiomass hybrid absorption cooling system is promising. The experimental data demonstrate that the system was operated at about 7% of nominal capacity a COP about.6 was achieved. The results show that the proposed system can be operated with higher reliability than the conventional solar solely cooling system. It can be used when there are not enough or fluctuating solar energy, especially in rainy season, and at night time. Finally, the results show that the average COP and COP sys of the proposed system outperform the conventional systems. ACKNOWLEDGMENT The author wishes to thank Rajamangala University of Technology Thunyaburi (RMUTT) for providing financial support for his research. REFERENCES [1] Vangtook, P.; and Chirarattananon, S. (27). Application of radiant cooling as a passive cooling option in hot humid climate, Building and Environment 42 (2): 43-6. [2] Argiriou, A.A.; Balaras, C.A.; Kontoyiannidis, S.; and Michel, E. (2). Numerical Simulation and Performance Assessment of a Low Capacity Solar Assisted Absorption Heat Pump Coupled with a Subfloor System, Solar Energy 79: 29-31. [3] Syed, A.; Izquierdo, M.; Rodriguex, P.; Maidment, G.; Missenden, J.; Lecuona, A.; and Tozer, R. (2). A Novel Experimental Investigation of a Solar Cooling System in Madrid, International Journal of Refrigeration 28: 89-871. [4] Casals, X.G. (26). Solar Absorption Cooling in Spain: Perspectives and Outcomes from the Simulation of Recent Installations, Renewable Energy 31: 1371-1389. [] Hidalgo, M.C.R.; Aumente, P. R.; Millan, M.I.; Neumann, A. L.; and Mangual, R.S. (28). Energy and carbon emission savings in Spanish housing airconditioning using solar driven absorption system, Applied Thermal Engineering 28: 1734 1744. [6] Qu, M.; Yin, H.; and Archer, D.H. (21). A solar thermal cooling and heating system for a building: Experimental and model based performance analysis and design, Solar Energy 84: 166 182. [7] Vinaspre, M.P.; Bourouis, M.; Coronas, A.; Garcia, A.; Soto, V.; and Pinazo, J.M. (24). Monitoring and analysis of an absorption air-conditioning system, Energy and Buildings 36: 933 943.

1th Eco-Energy and Materials Science and Engineering Symposium, Ubon ratchathani, Thailand, December -8. 212 [8] Hamza, A.; Ali, H.; Noeres, P.; and Pollerberg, C. (28). Performance assessment of an integrated free cooling and solar powered single-effect Lithiumbromide-water absorption chiller, Solar Energy 82: 121-13. [9] Pongtornkulpanich, A.; Thepa, S.; Amornkitbamrung, M.; and Butcher, C. (28). Experience with fully operational solar-driven 1-ton H 2 O/LiBr singleeffect absorption cooling system in Thailand, Renewable Energy 33: 943-949. [1] Sumathy, K.; Huang, Z.C.; and Li, Z. F. (22). Solar Absorption Cooling with Low Grade Heat Source - A Strategy of Development in South China, Solar Energy 72 (2): 1-16. [11] Prasartkaew, B.; and Kumar, S. (21). A low carbon cooling system using renewable energy resources and technologies, Energy and Buildings 42: 143 1462. [12] Duffie, J. A. and Beckman, W. A. (1991). Solar Engineering of Thermal Processes, second ed., John Wiley & Sons, New York, USA.