Steam Cooling Systems and Hybrid Cooling. Andrew G. Howell Xcel Energy

Similar documents
Steam Cycle Chemistry in Air-Cooled Condensers. NV Energy ACC User s Group * November 12-13, 2009 Andrew Howell * Xcel Energy

ACC Industry Status and Developments

Advances in Dry Cooling Deployed at South African Power Stations

Xcel Energy / ACC Users Meeting

A Comparative Study of Heat Rejection Systems for sco 2 Power Cycles

OPTIMISATION OF WATER USAGES IN THERMAL POWER PLANTS AND A STUDY ON DRY COOLING SYSTEM

MARAMA Webinar August 7, Angelos Kokkinos Chief Technology Officer Babcock Power, Inc.

Gas Turbine Inlet Air Cooling System

Kogan Creek Power. Condenser. Contents. Update For ACC User Group. Kogan Creek Power Station and its Air

Front Range Power Plant: Air Cooled Condenser Tom Cook, PE Colorado Springs Utilities, Operating Engineering Group Air Cooled Condenser User Group:

Modeling Techniques for Increased Accuracy

Heller Indirect Dry Cooling System: Dry cooling solution from the polar circle to hot deserts

C. heating turbine exhaust steam above its saturation temperature. D. cooling turbine exhaust steam below its saturation temperature.

Cooling Tower Improvement Study Using PEPSE

TECHNICAL EVALUATION OF OPTIONS FOR LONG-TERM AUGMENTATION OF THE COLORADO RIVER SYSTEM

2. TECHNICAL DESCRIPTION OF THE PROJECT

The Latest on ACC Corrosion Mechanisms The Lack of any Further Understanding

North Anna Unit 3 Hybrid Cooling

Amines in Air Cooled Condensers San Diego Annual Conference September 24, Bill Stroman

Power Plant Water Usage and Loss

Developing Water Conserving Cooling Options for Existing and New Power Generation Plants

Geothermal Steam Turbines for Various Purposes

Low temperature cogeneration using waste heat from research reactor as a source for heat pump

Rankine (steam) Cycle Cooling Options

PERFORMANCE TESTING OF HYBRID WET-DRY COOLING SYSTEMS: INSIGHTS FROM NUMERICAL MODELING

Overall nuclear power plant thermal efficiency will decrease if... A. the temperature of the steam at the turbine exhaust increases.

Emerging Issues and Needs in Power Plant Cooling Systems

Advanced Coal Power Plant Water Usage

Waste Heat Recovery Research at the Idaho National Laboratory

20/06/2011 Seminar on Geothermal Exploitation Santiago de Chile

Plant Utilities and Energy Efficiency CH505

TransPacific Energy Advantage: Case Studies

IMTE AG, Switzerland Power Consulting Engineers DRY SYSTEMS FOR POWER PLANT COOLING. 1. Need for Water Conservation in Power Plant Cooling

Demonstration of IAEA program for water management (WAMP) K. Kavvadias. Ph.D Chemical Engineer

Impact of novel PCC solvents on existing and new Australian coal-fired power plants 1 st PCC Conference, Abu-Dhabi

Hybrid cooling systems for low-temperature geothermal power production

Thermal Distribution in District Energy and Cogeneration Systems

Equipment Design. Detailed Plant Conceptual Design. Version 7.0

Energy Penalty Analysis of Possible Cooling Water Intake Structure Requirements on Existing Coal- Fired Power Plants

Lecture (6) on. Schematic of a Thermal Power Plant. By Dr. Emad M. Saad. Mechanical Engineering Dept. Faculty of Engineering.

1 INTRODUCTION Purpose and Scope... 1

A. the temperature of the steam at the turbine exhaust increases. B. additional moisture is removed from the steam entering the turbine.

SOME ENERGY-EFFICIENT TECHNOLOGIES IN JAPAN

Observations from Several Condition Assessments of Prestressed Concrete Cylinder Pipe used at Energy Generation Facilities

AP1000 European 21. Construction Verification Process Design Control Document

Water Use, Electric Power, and Nuclear Energy: A Holistic Approach to Environmental Stewardship

Water and the Electric Power Sector

Chapter 3.7: Cooling Towers

Wastewater Reuse in Combined Cycle Power Plants Behrang (Ben) Pakzadeh, PhD, PE

POWER Proceedings of the ASME 2014 Power Conference POWER2014 July 28-31, 2014, Baltimore, Maryland, USA

Post Combustion CO 2 Capture Scale Up Study

ENERGY FACILITY LICENSING PROCESS

Drying of High-Moisture Coals For Power Production & Gasification

Centerpoint Energy. Energy Efficiency & Technology Conference. Steam and Process Heat Recovery. May 23, 2017

MD Water Resources Research Center Fall 2010 Symposium. Water and Electricity. Peter Dunbar Director, MD Power Plant Research Program

Utilization of Atmospheric Heat Exchangers in LNG Vaporization Processes:

Boiler Energy Efficiency & Overview of Economizers

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Handout 1: Thermodynamic Resources in the 2016 IRP

Selection and Installation of a Full- Flow Condensate Filtration System

ORGANIC RANKINE CYCLE TECHNOLOGY PRODUCTS AND APPLICATIONS APRIL 2013 EAR 99 - NLR

BESTPRACTICES STEAM PROGRAM STEAM TOOLS SPECIALIST QUALIFICATION TRAINING PREREQUISITE STUDY GUIDE (1/12/2004)

How an ACC Unit Releases Iron, a 3-Month Study with Particle Analyzers

The Prescriptive Promise

Condenser Cleaning, NDE and Leak Detection Part I: Condenser Cleaning

ENERGY OPTIMIZATION IN COOLING TOWER DURING WINTER

Conco Services Corporation

Power Optimization Center Leveraging plant process data for advanced analytical diagnostics. June 16, 2016

LIST OF ACRONYMS / ABBREVIATIONS USED IN THIS DOCUMENT Acronym / abbreviation Definition

Equipment Design. Detailed Plant Conceptual Design. Version 9.0

Thermal Power Plant Cooling

AUXILIARY POWER MEASUREMENT, OPTIMIZATION & ANALYSIS. Steag Energy Training Center EEC WORKSHOP to

Waste Heat Recovery using Organic Rankine Cycle turbines

How Cooling Towers Function

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

Eurammon Symposium Ammonia Absorption Refrigeration. Colibri b.v.

Geothermal Power Plant

December 13, 2012 Energy Efficient Cooling Information Service Webinar Series Christine Brinker and Gearoid Foley CHP with Absorption Chilling

Western Regional Boiler Association

Estimating Freshwater Needs to Meet Future Thermoelectric Generation Requirements 2008 Update

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

Water Savings Using The Thermosyphon Cooler Hybrid Heat Rejection System: Case Studies From Atlanta, Phoenix, Seattle, and Boston

SUMMARY OF VARIABLE NON-FUEL OPERATION AND MAINTENANCE ( O&M ) COSTS

CONDENSATE-FEEDWATER-BOILER SYSTEM ON-LINE ANALYZERS. On-Line Analyzer Sample Point Alarm Points Comments

ACC.01: Guidelines for Internal Inspection of Air-Cooled Condensers

Technology Options for Existing Coal Units

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

Boilers & Fired Systems. Clean Coal Technology Dr. Tanveer Iqbal

Heat Recovery Steam Generators for Flexibility

High Bridge Combined Cycle Plant

Cogeneration. Thermal Chillers. and. .. ASHRAE National Capital Chapter. Arlington, VA 10/10/2012

Water Use and Conservation in the Electric Power Industry

Company Introduction HEATERS. Joint Venture: TIME FOR A COOL CHANGE

Chapter Two { TC "Chapter Two " \l 1 } Detailed System Description

BEST PRACTICES IN THERMAL POWER PLANT. Confederation of Indian Industry CII Godrej Green Business Centre, Hyderabad, India

Development of Large-Capacity Single-Casing Reheat Steam Turbines for Single-Shaft Combined Cycle Plant

Products II 1 VERTICAL LINE SHAFT PRODUCT AND OIL LUBRICATED PUMPS II 2 SUBMERSIBLE PUMPS II 3 MIX FLOW PRODUCT AND OIL LUBRICATED PUMPS

Combined Heat and Power. Applications and Guidelines Jeffrey Ihnen, P.E.

Waste Heat to Power Economic Tradeoffs and Considerations

The Company and the Geothermal Applications. Doc.: 12-COM.P-22-rev.20

Transcription:

Steam Cooling Systems and Hybrid Cooling Andrew G. Howell Xcel Energy

Steam Cooling Systems Once-through Recirculating Cooling Tower Direct Dry Cooling (air-cooled condenser) Indirect Dry Cooling (Heller) Hybrid or Parallel Cooling (wet + dry)

Once-through Cooling large volume of water required (river, ocean) temperature increase at discharge minimal actual water consumption inlet fouling / condenser tube biofouling section 316(b), CWA: fish entrainment if > 50M gpd

Recirculating Cooling Tower relatively low water supply volume required dissolved constituents concentrate chemical treatment required consumption: ~ 75% of water evaporated cooling tower maintenance blowdown handling discharge monitoring / limitations elimination of discharge - ZLD

Direct Dry Cooling (air cooled condenser) no water required high capital cost significant maintenance gearbox, fans, finned tube cleaning increased fuel cost (high backpressure) fan energy consumption ~15% energy loss in hot weather minimal system contamination with tube leaks iron transport can be major issue

Indirect Dry Cooling (Heller) similar performance to ACC but closed loop through WCC lower construction & maintenance costs use of parabolic natural-draft tower aluminum components

Hybrid (Parallel) Cooling WCC + ACC operation in parallel with no isolation lower backpressure depending on water/air cooling ratio achieves full load in hot weather major contamination risk with WCC tube leak if condensate polisher present

Comanche Station Unit 3

Evaporative (Wet) Cooling Tower

Dry (Air) Cooling

Ambient Temp [F] Design Day: dry bulb vs. wet bulb T July 14, 2004 Ambient Conditions 120 100 80 60 Dry Bulb Wet Bulb 40 20 0 0100 0600 1100 1600 2100 Time

Turbine Exhaust Pressure (inches Hg) Ambient T vs. Condenser Backpressure 4 3.5 3 2.5 2 1.5 1 0.5 0 10 30 50 70 90 Dry Bulb Temp (F)

Net Heat Rate (HHV, BTU/KWH) Ambient T vs. Fuel Efficiency 9,000 8,950 8,900 8,850 8,800 8,750 8,700 10 30 50 70 90 Dry Bulb Temp (F)

Output (KW) Ambient T vs. Generation Output 860,000 850,000 840,000 830,000 820,000 810,000 800,000 790,000 780,000 770,000 10 30 50 70 90 Dry Bulb Temp (F)

Parallel Cooling Schematic

Comanche Station Unit 3: design for low water use low water use technology to optimize unit efficiency and water conservation Cooling tower and air cooling systemsdesigned to operate in parallel Below 55ºF (13 o C), ACC alone can handle full heat rejection of plant Water-cooling alone cannot provide full load operation without ACC

Comanche s Water Supply 8,700 acre-feet/year (2.8 billion gal/year, 10.7 million m 3 /year) for existing Units 1, 2 (660 net MW total) Hybrid (Parallel) cooling utilized for Unit 3 reduced contract amount to 6,000 acre-feet/year (1.9 billion gal/year, 7.4 million m 3 /year) (750 net MW) Pueblo Board of Water Works Pueblo Reservoir

Comanche 3 condensate / cooling system LP turbine air-cooled condenser water-cooled condenser CW out cooling tower CW in hotwell hotwell condensate pumps (3) DA LP heaters polishers 3 x 50% filters 2 x 100%

Water Use Optimization Low Water Use Plant Efficiency Air Cooled Condenser Cooling Tower

Comanche 3 Air Cooled Condenser

Comanche 3 Air-Cooled Condenser

Steam Turbine MHI (Mitsubishi) design 829 gross MW capacity 4 inch (13.5 kpa) backpressure design 7 inch (24 kpa) alarm point 10 inch (34 kpa) trip point

Water-Cooled Condenser 2-pass, upper / lower waterboxes 31,520 UNS S44660 alloy tubes (SeaCure) 44 foot (13.4 m) length 1.25 inch (3.2 cm) outside diameter 0.022 inch (0.56 mm) wall thickness condensing surface area 453,000 ft 2 (42,000 m 2 )

Air-Cooled Condenser 45 fans, drawing ~8 MW combined 9 streets or bays, 20,358 tubes total tubes: single-row 35.3 feet (10.8 m) length 8.2 by 0.75 inch (21 by 2 cm) cross-section carbon steel with aluminum exterior fins 0.059 inch (1.5 mm) wall thickness 1,158,902 ft 2 internal (107,000 m 2 ) 16,514,080 ft 2 external (1,500,000 m 2 )

WCC Hotwell ACC Hotwell

Estimated / Approximate Water Consumption by Generation Type Fuel, Plant Cooling System Water Consumption (gal/mwh) Coal, Steam Wet, recirculating 512 Coal, Steam Hybrid wet/dry cooling 324 Gas, Combustion Turbine None 0* Gas, Combined Cycle Wet, recirculating 180 Gas, Combined Cycle Dry Cooling 2* Nuclear Wet, recirculating 609 *Limited water use for non-cooling purposes. Sources: Protecting the Lifeline of the West, Western Resource Advocates/EDF, 2010 http://www.westernresourceadvocates.org/water/lifeline/lifeline.pdf Xcel Energy operating experience

Units with Air-Cooled Condensers: - Must address corrosion product release from large internal carbon steel surface area (1,158,902 square feet for Comanche 3) - Must be concerned with through-wall corrosion of tubes and consequent air inleakage.

Potential Consequences of Iron Transport from ACC

Potential Consequences of Corrosion in the ACC Flow

Management of Iron Corrosion & Transport Condensate particulate filter Elevation of steam cycle ph to 9.6 10.0

Conclusions Parallel wet-dry cooling achieves water savings while permitting improved fuel efficiency (vs. dry cooling) and full load operation with high ambient temperatures Operation of a hybrid cooling system on units with condensate polishing forces compromise between corrosion minimization and polisher optimization.

Questions?