MS-2A LINER SPECIFICATIONS: for STRUCTURAL REPAIR and SEALING of MANHOLES

Similar documents
HIGH PERFORMANCE MIX SPECIFICATIONS

profile-mix-plus, Page 1 of 8, Rev

BENCH MIX SPECIFICATIONS for REPAIR OF BENCHES IN MANHOLES WITH INERT LINES

Strong-Seal Sealant Specification, a permanent method of sealing the interior of the chimney and casting in manholes and catch basins.

STRONG-SEAL GROUT 250 AND GROUT 1000 SPECIFICATIONS for Void Filling And Leak Stoppage.

SEWER MANHOLE/WET WELL REHABILITATION, SEVERE SULFIDE (as provided by WBE Dorcas, Inc.)

Process Specification. Structural Rehabilitation & Corrosion Protection for Circular Structures in Wastewater Collection and Potable Water Systems

STANDARD SPECIFICATIONS FOR CONSTRUCTING SANITARY SEWER FACILITIES DIVISION III - CONSTRUCTION SPECIFICATIONS SECTION 4

SECTION 822 MANHOLE REHABILITATION

A. ASTM C 150 Standard Specification for Portland Cement. B. ASTM C 595 Standard Specification for Blended Hydraulic Cements.

Effective Date: Revision #: 1. Section N: Concrete. Concrete/ Type S Mortar. Cement/ Calcium Aluminate

TECHNICAL SPECIFICATION FOR CURED-IN-PLACE MANHOLE REHABILITATION LINER SYSTEM

CITY OF TAMPA ADDENDUM NO. 3. DATE: February 15, 2017

FIVE STAR PRODUCTS, INC. (800)

City of Mt. Pleasant, Michigan CONTRACT DOCUMENTS 2018 MANHOLE REHABILITATION PROJECT. ALLISON LENTS Mayor. NANCY RIDLEY City Manager

DIVISION 3 - CONCRETE Section Concrete Rehabilitation

SAN ANTONIO WATER SYSTEM 2013 REHABILITATION WORK ORDER CONSTRUCTION CONTRACT 4 SAWS Job No SAWS Solicitation No.

REHABILITATION. Geopolymer & Hybrid Cements. > Manholes > Sewer & Storm Pipes > Other Civil Infrastructure. vortexcompanies.com

CITY OF TAMPA ADDENDUM NO. 1. DATE: September 15, Contract 11-C-00001; Wastewater Sewer Rehabilitation by Cured-in-Place Pipe (C.I.P.P.

Section Shotcrete

Madewell Products Corporation December Industrial Court Alpharetta, GA Office: (770) Fax: (770)

CP-24CC Potassium Silicate Concrete

Madewell Products Corporation December Industrial Court Alpharetta, GA Office: (770) Fax: (770)

SECTION 806 MANHOLE REHABILITATION

DIVISION 3 - CONCRETE Section Concrete Rehabilitation

QUADEX SEWER STRUCTURE RESTORATION MATERIALS INSTALLATION SPECIFICATION

TECHNICAL SPECIFICATION

FIVE STAR PRODUCTS, INC. (800)

TECHNICAL SPECIFICATIONS FOR MANHOLE REHABILITATION

REHABILITATION. PRODUCTS & MATERIALS Geopolymers Hybrid Cements Polymerics Ancillary Products. vortexcompanies.com

CITY OF ODESSA SPECIAL SPECIFICATIONS ITEM 1000 GLASS-FIBER REINFORCED POLYESTER (FRP) REHAB/REPLACEMENT MANHOLE

GUIDE SPECIFICATION SECTION CRYSTALLINE WATERPROOFING

DATA SHEET UNIQUE FLEXICRETE XP Polymer Modified Mortar

SPECIAL SPECIFICATION 5787 Manhole Rehabilitation

STRUCTURAL CEMENTITIOUS LINER PERMACAST BY AP/M PERMAFORM

SECTION 39 - MANHOLES TABLE OF CONTENTS

DIVISION 3 CONCRETE Section Concrete Rehabilitation

SECTION STORM DRAIN REHABILITATION. 1. Protection of environment; Section O Trench excavation, backfill, and compaction; Section

SPECIFICATIONS FOR PREMIER-PIPE USA CURED-IN-PLACE TECH LINER

SUGGESTED MANHOLE FRAME SEALING SPECIFICATION (Rehabilitation)

SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS

Easy to apply Nonflammable Low odor Castable Make excellent materials of construction

ASH GROVE KOLORSTONE BROOMCOAT MIXING KIT. Spec Sheets Contents: Kolorstone Broomcoat Mixing Spec Sheet Kolorflex Admixture Spec Sheet

SECTION 920 SANITARY AND STORM SEWER MANHOLES

FIVE STAR PRODUCTS, INC.

PRODUCT DATA SHEET Sikadur 31 CF Normal (formerly Sikadur 731)

ITEM 431 PNEUMATICALLY PLACED CONCRETE. All material shall conform to the pertinent requirements of the following items:

SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS

DIVISION 3 - CONCRETE Section Concrete Toppings Section Concrete Resurfacing Section Concrete Rehabilitation

SECTION 44 SHOTCRETE, CAST CONCRETE CHANNEL LINING, AND GROUTED COBBLE TABLE OF CONTENTS

SECTION SURFACE-APPLIED CRYSTALLINE WATERPROOFING AND CONCRETE REPAIR

Concrete Repair & Restoration

FIVE STAR PRODUCTS, INC. (800)

ARDEX GUIDE SPECIFICATION ARDEX TRM Transportation Repair Mortar Fast-Setting Concrete Repair Mortar

Paragraph Description Page No General Materials Concrete Masonry Work Altitude Valve Vault Cover 25-4

Product Data Sheet Sikadur -31 CF Normal Product Description Uses ruction Const Characteristics / Advantages

SPECTRASHIELD. Total System for Manholes (Brick/Concrete)

Applications (As provided by Avanti International)

Special Specification SS1- INTERNAL CIPP POINT REPAIR OF PIPELINES. A. General. 1. Scope

TECHNICAL DATA SHEET SIKADUR 31 CF NORMAL 6KG

3-part thixotropic epoxy patching mortar

SECTION SUBSURFACE PREPARATION FOR FLOOR FINISHES

CELCORE CELLULAR INSULATING CONCRETE SPECIFICATION FOR RETROFIT PLACEMENT OVER EXISTING ROOF MEMBRANES

FOREWORD PART 1 - GENERAL. A. Requirements for surface preparation, repairs and 100% Solids epoxy coating application to specified surfaces.

A. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.

CSC SPECIFICATIONS SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section

CSI SPECIFICATIONS SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section

SECTION CAST-IN-PLACE CONCRETE

B. All work of the section shall comply with the conditions of the contract, the drawings and any special conditions forming a part of the contract.

Protective Coatings for Underground Utility Concrete Structures. By: John E. Davis Inside Sales & Marketing Specialist: Sauereisen, Inc.

BONDGROUT GP ( GENERAL PURPOSE NON-SHRINK STRUCTURAL GROUT) Page 1 / 7.

1 Exam Prep Guide to Shotcrete Questions

SECTION PRECAST CONCRETE MANHOLES

SECTION MORTAR

CC-1004 Ultra High Temperature Epoxy Adhesive

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK

San Antonio Water System Specifications for Construction ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES

By CTS Cement Manufacturing Corp.

Application Guidelines for PPC Coatings Flooring

UNIQUE. Product Description. Recommended Uses. For Best Results be between 55ºFF and 75ºF. the material. holes. masonry walls. cracks and holes in

3910 E. McKinney Denton, TX P.O. Box Dallas, TX EZ WALL CONCENTRATE, INC

POLYMER CONCRETE 800 NON-SHRINK VINYL ESTER POLYMER CONCRETE, CONCENTRATED HYDROFLUORIC ACID RESISTANCE

Introducing Raven 760 HPPC

A. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.

SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES

CSI SPECIFICATIONS SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section

SEWER MANHOLE REHABILITATION - STRUCTURAL COMPOSITE LINING (as provided by AP/M Permaform)

SPECIAL SPECIFICATION 4411 Cured-In-Place Pipe (CIPP) (Drainage Structures)

DIVISION 9 - FINISHES Section SPECIAL COATINGS Section Coating Systems for Steel

SPECIAL SPECIFICATION 4491 Type CAC Concrete

SIDER-POOL. Product Data. Features and Uses

VALLECITOS WATER DISTRICT SECTION PRECAST REINFORCED CONCRETE MANHOLES

CSI SECTION MAINTENANCE OF CONCRETE Repair & Resurfacing with Rapid Hardening, High Strength, Low-Shrink, Non-Metallic Cementitious Materials

prospec.com Concrete Repair & Restoration

FIVE STAR PRODUCTS, INC.

SECTION IRRIGATION PIPELINE LINING (CURED-IN-PLACE PIPE)

Multi-Institutional Academic Health Science & Research Center Evansville, IN

September 1, 2003 CONCRETE MANUAL SPECIAL TYPES OF CONCRETE

DIVISION 9 - FINISHES Section Protective Coatings

SECTION BRICK MASONRY ASSEMBLIES

Transcription:

MS-2A LINER SPECIFICATIONS: for STRUCTURAL REPAIR and SEALING of MANHOLES INTENT: To provide a system for reconstruction of concrete or masonry structures to stop inflow, infiltration, exfiltration, and restore structural integrity in installations showing no evidence of hydrogen sulfide (biogenic) corrosion. 1.0 GENERAL 1.1 This specification shall govern all work, materials, and equipment required for substrate rehabilitation for the purpose of eliminating infiltration, repair of voids, and restoration of the structural integrity of the substrate as a result of applying a monolithic fiber-reinforced structural cementitious liner to the wall and bench surfaces of brick, concrete, or any other masonry construction material. 1.2 Described are procedures for cleaning, preparation, application and testing. The applicator, approved and trained by the manufacturer, shall furnish all labor, equipment and materials for applying a cementitious mix to form a structural monolithic liner of a minimum 1/2 inch thickness, with machinery specially designed for the application. All aspects of the installations shall be in accordance with the manufacturer s recommendation and per the following specifications which includes: 2.0 MATERIALS A. The removal of any loose and unsound material B. Cleaning of the area to be sprayed C. The elimination of active infiltration prior to liner application D. The repair and filling of voids E. The repair and sealing of the invert and benches F. The spray application of a cementitious mix to form a structural monolithic liner 2.1 PATCHING MATERIAL (Strong-Seal QSR): Strong-Seal QSR, a quick setting fiber reinforced calcium aluminate corrosion resistant cementitious material, shall be used as a patching material and is to be mixed and applied according to manufacturer s recommendations and shall have the following minimum requirements: Last Revision: 10-6-15-1 -

Strong-Seal QSR Minimum Requirements Compressive Strength ASTM C109 >1800 psi, 1 hr. >2600 psi, 24 hrs. >3000 psi, 28 days Bond ASTM C882 >1600 psi, 28 days Calcium Aluminate Cement Applied Density Sulfate resistant 105 pcf 5 lbs. Shrinkage ASTM C596 0% at 90% R.H. Placement Time Set Time 5 to 10 minutes 15 to 30 minutes 2.2 INFILTRATION CONTROL MATERIAL (Strong-Seal Strong-Plug ): Strong-Plug, a rapid setting cementitious product specifically formulated for leak control, shall be used to stop minor water infiltration and shall be mixed and applied according to manufacturer s recommendations and shall have the following minimum requirements: Strong-Seal Strong-Plug Minimum Requirements Compressive Strength ASTM C109 >1000 psi, 1hr. >2500 psi, 24 hrs. Sulfate Resistance ASTM C267 No weight loss after 15 cycles @ 2000 ppm Freeze/Thaw ASTM C666 "Method A" 100 cycles Pull Out Strength ASTM C234 14,000 lbs. Set Time 2.3 GROUTING MATERIAL: <1.0 minute 2.3.1 Strong-Seal Grout 250, a cementitious grout, shall be used for stopping very active infiltration and filling voids and shall be mixed and applied according to manufacturer s recommendations. The cementitious grout shall be volume stable, and have a minimum 28 day compressive strength of 250 psi. 2.3.2 Strong-Seal Grout 1000, a cementitious grout, shall be used for the same application as Grout 250, but is designed for special soil conditions, and shall be used per manufacturer s recommendations. The cementitious grout shall be volume stable and have a minimum 28 day compressive strength of 1000 psi. Last Revision: 10-6-15-2 -

2.3.3 Chemical grouts may be used for stopping very active infiltration and shall be mixed and applied per manufacturer s recommendation. 2.4 STRONG-SEAL MS-2A LINER MATERIAL: Strong-Seal MS-2A cementitious liner product shall be used to form a structural monolithic liner covering all interior substrate surfaces and shall have the following minimum requirements: MS-2A Compressive Strength ASTM C109 28 days >9000 psi Tensile Strength ASTM C496 28 days >800 psi Flexural Strength ASTM C293 28 days >1200 psi Shrinkage @90% R.H. ASTM C596 28 days 0% Bond ASTM C882 28 days >2000 psi Density, When Applied Freeze/Thaw ASTM C666 N/A 134 ± 5lbs/ft3 300 cycles no visible damage 2.4.1 Strong-Seal MS-2A shall be made with Type I Portland Cement and shall be used according to manufacturer s recommendations in applications where there is no evidence of sulfide conditions (substrate surface of ph 3.0 or higher). Strong-Seal MS-2A product or approved equal shall be factory blended requiring only the addition of water at the jobsite. The bag weight shall be 63-67 pounds. The contents shall have a dry bulk density of 82-85 pounds per cubic foot. When mixed with manufactures' recommended amount of water it shall have a wet nozzle density in the range of 129-139 pounds per cubic foot and shall have a typical yield of.57 cubic feet per bag. 2.4.2 Strong-Seal MS-2A products shall be reinforced with alkaline resistant fiberglass rods not less than 1/2 inch in length. 2.4.3 The material should meet or exceed industry standards and shall not have any basic ingredient that exceeds EPA maximum allowable limits for any heavy metals. Last Revision: 10-6-15-3 -

2.5 WATER: Water used to mix product shall be clean and free from contaminants. Questionable water shall be tested by a laboratory per ASTM C-94 procedure. Potable water need not be tested. 2.6 OTHER MATERIALS: 3.0 EQUIPMENT No other material shall be used with the mix described in 2.4.1 without prior approval or recommendation from Strong-Seal Systems. 3.1 Applicator must use approved equipment designed and manufactured by the material supplier specifically for the application of cementitious liners in sanitary systems. 3.2 Specially designed machines consisting of a progressive cavity pump and an air system for low velocity spray application of product, shall be used for applying Strong-Seal Systems products. Equipment is complete with water storage and metering system. SprayMate models 35C, 35D and Minimate II are approved machines for applying Strong-Seal Systems products. Other models may be approved after review by Strong-Seal personnel. 4.0 APPLICATION 4.1 PREPARATION: 4.1.1 Place covers over invert to prevent extraneous material from entering the sewer lines before cleaning. 4.1.2 All foreign material shall be removed from the manhole wall and bench using a high pressure water spray (minimum 3000 psi). If grease, chemicals, previous coatings or other surface contaminants are present, the surface will be cleaned with steam, chemical cleaning compounds or surface abrading as necessary to provide a clean substrate. Loose and protruding brick, mortar, and concrete shall be removed using a mason's hammer and chisel and/or scraper. Fill any large voids with quick setting patching mix Strong-Seal QSR (2.1). 4.1.3 Active leaks shall be stopped using quick setting, specially formulated mixes, such as Strong-Plug (2.2) according to manufacturer s recommendations. Some leaks may require weep holes to localize the infiltration during the application. After Last Revision: 10-6-15-4 -

4.2 INVERT REPAIR: application the weep holes shall be plugged with the quick setting material Strong-Seal Strong Plug (2.2) prior to final coat. When severe infiltration exists, drilling may be required in order to pressure grout using a cementitious grout, Strong-Seal Grout 250, Strong-Seal Grout 1000 or chemical grouts (2.3). Manufacturer s recommendations shall be followed when pressure grouting is required. 4.2.1 After all preparations have been completed, remove all loose material and wash wall again. 4.2.2 Any bench, invert, or service line repairs shall be made at this time using the quick setting patching mix, Strong-Seal QSR (2.1) and shall be used per manufacturer s recommendations. 4.2.3 Invert repair shall be performed on all inverts with visible damage or where infiltration is present or when vacuum testing is specified. After blocking flow through the manhole and thoroughly cleaning invert, the quick setting patch material, Strong-Seal QSR (2.1) shall be applied to the invert in an expeditious manner. The material shall be troweled uniformly onto the damaged invert at a minimum thickness of 1/2 inch at the invert extending out onto the bench of the manhole sufficiently to tie into the structural monolithic liner to be spray applied. The finished invert surfaces shall be smooth and free of ridges. The flow may be re-established in the manhole within 30 minutes after placement of the material. 4.3 MIXING OF LINER MATERIALS: 4.3.1 For each bag of product, use the amount of water required per manufacturer s recommendations following mixing procedures noted on product bag. Only enough water will be used to produce a mix consistency to allow application of liner material up to one inch thick in a single application without material "sagging" on vertical surface and using the approved equipment for mixing and application. 4.3.2 Prepared mix shall be discharged into a hopper and another batch prepared to occur in such a manner as to allow spraying continuously without interruption until each application is complete. Last Revision: 10-6-15-5 -

5.0 CURING 4.4 SPRAYING: 4.4.1 The surface shall be clean and free of all foreign material and shall be damp without noticeable free water droplets or running water, but totally saturated just prior to the application of material. Materials shall be applied up to one (1) inch thick in one or more passes from the bottom of the frame; however, minimum total thickness shall not be less than 1/2 inch. The surface is then troweled to a relatively smooth finish being careful not to over trowel. 4.4.2 A brush finish shall be applied to the trowel-finished surface. Manufacturer s recommendations shall be followed whenever more than 24 hours have elapsed between applications. 4.5 BENCH APPLICATION: 4.5.1 The wooden covers shall be removed at this time and the bench sprayed with materials mixed per specifications as per 4.3 and spray applied in such a manner that a gradual slope is produced from the walls to the invert with the thickness at the invert to be no less than 1/2 inch. The wall/bench intersection shall be rounded to a uniform radius the full circumference of the intersection. 5.1 Caution will be taken to minimize exposure of applied product to quick surface drying and air movement. If time between application of additional coats is to be longer than 15 minutes, place cover over manhole. In extremely hot and arid climates, manhole should be shaded while reconstruction is in progress and a concrete curing agent should be used. Contact manufacturer for curing compound recommendations. 5.1.1 Strong-Seal MS-2A liner product shall have the following minimum cure times before being subjected to flow: Hold Times Before Releasing Flow Storm Run-off & Surcharge Force Main Impact 8 hrs. 12 hrs. Hold Times Before Allowing Traffic After final application of the Strong-Seal liner product, street traffic shall be held 12 hrs. Last Revision: 10-6-15-6 -

6.0 WEATHER 6.1 No application shall be made if ambient temperature is below 40 degrees Fahrenheit. No application shall be made to frozen surfaces or if freezing is expected to occur within the substrate within 24 hours after application. 6.2 Precautions shall be taken to keep the mix temperatures at time of application below 90 degrees Fahrenheit. Water temperature shall not exceed 80 degrees Fahrenheit. Chill with ice if necessary. 7.0 PRODUCT TESTING 7.1 Four (4) - two inch cubes shall be cast each day or from every pallet of product used, and shall be properly packaged, labeled and returned to manufacturer for testing in accordance with the owner s or manufacturer s directions for compression strength per ASTM C109 procedure. 8.0 FINAL ACCEPTANCE TESTING 8.1 At the direction of the owner or his assignee, the reconstructed structure shall be tested by any one of the following methods: 8.1.1 Visually verify the absence of leaks. 8.1.2 Perform an exfiltration test. 8.1.2 Perform an exfiltration test. 8.1.2.1 For manholes 0 to 6 foot deep, if water loss is 1 inch or less in 5 minutes, manhole reconstruction is acceptable. 8.1.2.2 For manholes over 6 feet deep, if water loss is 1 inch plus 1/8 inch for each additional foot of depth or less in 5 minutes, manhole is acceptable. 8.1.3 Vacuum testing per ASTM C1244-93 procedure. Vacuum testing shall not be conducted earlier than 7 days after application. 9.0 LIMITED WARRANTY The Strong Company, Inc. warrants that this product was produced in conformity with its standard specification or formulations within recognized tolerances, free of adulteration or contamination, and that the product will perform in accordance with representations in Strong-Seal Systems literature and Technical Data Sheets when properly applied in strict conformance with the printed instructions on container and prescribed in technical data instructions and when applied to a properly prepared surface. Last Revision: 10-6-15-7 -

The sole remedy of the purchaser shall be replacement of the product or refund of the purchase price of the product if any defect in material or variance in the product beyond recognized tolerances in the specifications are found to exist. No other remedy including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss shall be available to the purchaser. DISCLAIMER THE WARRANTY DESCRIBED IN THE ABOVE PARAGRAPHS SHALL BE IN LIEU OF ANY OTHER WARRANTY, EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. The Strong Company, Inc. 4505 Emmett Sanders Road Pine Bluff, AR 71601 (800) 982-8009 Fax (870) 850-6933 Website: www.strongseal.com E-mail: info@strongseal.com Last Revision: 10-6-15-8 -