TECHNICAL BULLETIN POLYISOCYANURATE VS. CELLULAR GLASS IN LOW TEMPERATURE MECHANICAL INSULATION

Similar documents
TECHNICAL BULLETIN 0214 (update of 0111) PERFORMANCE/COST COMPARISON OF POLYISO vs. XPS PIPE INSULATION SYSTEMS

TECHNICAL BULLETIN 0714 Elastomeric Insulation versus Polyisocyanurate in Low Temperature Applications

TECHNICAL BULLETIN 0314 PHENOLIC vs. CELLULAR GLASS INSULATION IN COLD PIPING APPLICATIONS (WHEN 25/50 RATINGS ARE REQUIRED)

CUSTOMER BULLETIN A COMPARISON OF ISO-C1 and HT-300 POLYISOCYANURATE INSULATION

Ammonia. Product performance for insulation of ammonia piping

Chilled Water. Product performance for insulation of chilled water piping

TECHNICAL BULLETIN 0414 What You Should Know About Thermal Conductivity and Aging of Low-Temperature Mechanical Insulation

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

PERMATHERM PIPE INSULATION PRODUCTS

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

Specified to be the Best

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

PERMATHERM, INC. SPECIFICATION FOR CHILLED WATER PIPE INSULATION

ITW INSULATION SYSTEMS

PIMA PERFORMANCE BULLETIN Foil-Faced Polyiso and Mineral Wool Board in Wall Applications

ITW INSULATION SYSTEMS

Redi-Klad 1000 Pipe Insulation

GUIDE SPECIFICATION: DUCT LINER

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

INSTALLATION GUIDELINE FOR TRYMER INSULATION

TECHNICAL BULLETIN 0116 INSULATION PERFORMANCE ON LNG PIPE AND OTHER CRYOGENIC APPLICATIONS

TECHNICAL BULLETIN 1215 COMPARISONS BETWEEN AEROGEL AND POLYISO IN LOW TEMPERATURE MECHANICAL INSULATION

Solving Corrosion Under Insulation Utilizing FOAMGLAS Cellular Glass Insulation Systems

PIMA PERFORMANCE BULLETIN Foil-Faced Polyiso and Unfaced Mineral Wool Board in Commercial Wall Applications

ITW INSULATION SYSTEMS

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

GUIDE SPECIFICATION: MECHANICAL SYSTEMS

Tube Insulation. Fiber Free

The Right Insulation for Cold Systems

Plumbing Pipe Insulation Specification Submitted by: Armacell LLC. Plumbing Pipe Insulation Specification Armacell LLC 1

Quality NBR Insulation

Cool Science for Cold Service.

armaflex cryogenic systems for oil & gas FLEXIBLE INSULATION SYSTEMS FOR INDUSTRIAL PROCESS PIPEWORK AND TANKS.

armaflex cryogenic systems

ITWIS is setting the industry standard for reliability, quality, support, and responsiveness.

Cryogenic Pipe Support Systems

FIRE STATION 55 June 14, 2010

NIA s 62nd Annual Convention Sheraton Grand at Wild Horse Pass March 29 April 1, Barry Schmitt of Value Engineered Products

B. Refer to Section : Air Distribution for lined ductwork requirements.

K-FLEX DUCT LINER GRAY

Gulf Cool Therm Polyisocyanurate (PIR) Insulation

DS131 EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

Project Specification. Tarec. Insulation for the LNG, Petrochemical and Process Industries

INVINSA & INVINSA FR ROOF COVER BOARDS. Manual for Design Professionals and Contractors

SECTION HVAC INSULATION

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

KwikFlex Pipe & Tank Insulation. Knauf Data Sheet PE-DS

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

Suggested Insulation Layering Chart

Mechanical Insulation for Refrigeration Systems

SECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

PRODUCT SELECTION GUIDE

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

FOAMGLAS INSULATION SPECIFICATION

KwikFlex Pipe & Tank Insulation

Gulf Cool Therm Polyurethane (PUR) Insulation

1 of 17. PO Box Bellevue Rd, Newark, DE V F

Design & Construction Standards, Revised January

Expanded Polystyrene DataSheet

Foamed-in-place insulation Sprayed insulation. Spray Foam Insulation for Residential Building Envelope Insulation

INSTALLATION GUIDELINE FOR TRYMER SUPERCEL PHENOLIC INSULATION

LT/ArmaFlex. Industrial INSULATION FOR THE OIL AND GAS INDUSTRY. High density industrial grade FEF installation

Thermasheath-XP. Insulation for Exposed Use

Invinsa. Defy the Elements

Insulation Board. Knauf Data Sheet PE-DS

Earthwool Redi-Klad 1000 Pipe Insulation

This specification describes the minimum requirements for industrial thermal insulation.

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC INSULATION

BELOW GRADE ASSEMBLIES AND RIGID INSULATION

Knauf Data Sheet AH-DS-5E Friendly Feel. Duct Wrap. with ECOSE Technology

PIP INSA1000 Acoustic Insulation Systems Specification

Pipe & Equipment Insulations Product Selection Guide

OptiLiner Banded Liner System, Thermal, Metal Building

SECTION PIPING INSULATION

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

SUPERIOR CAL-SHIELDS Features & Benefits FAST

Lamit Industries, Inc. 710 Marion Road Columbus, Ohio P-(614) F-(614)

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

Knauf Data Sheet PE-DS-2e Insulation Board. with ECOSE Technology

Phenolic Foam (PF) Insulation

DyTherm Phenolic Pipe Insulation 3-Part Specifications per Construction Specification Institute (CSI)

FOR FURTHER INFORMATION ON THE NILFLAM RANGE OF PRODUCTS PLEASE TELEPHONE THE KINGSPAN TECHNICAL SERVICES DEPARTMENT (01457)

Standard and Mini Split Line Sets

Note to Specifier: Use this product for coated glass-mat faced polyisocyanurate insulation boards such as Rboard.

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

ProGUARD Guide Specification

PITTWRAP CW PLUS JACKETING Product Datasheet

.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.

ARIFLEX. Rubber Insulation Foam Tube & Foam Sheet

Purdue e-pubs. Purdue University. Weiwei Zhu Oklahoma State University, United States of America,

PIMA PERFORMANCE BULLETIN Polyiso and Unfaced Mineral Wool Board Insulation in Commercial Roof Applications

High density foams & chemicals For Dual and Cryogenic temperature insulation

SECTION SPRAY FOAM INSULATION

Transcription:

TECHNICAL BULLETIN 0114 1 POLYISOCYANURATE VS. CELLULAR GLASS IN LOW TEMPERATURE MECHANICAL INSULATION PURPOSE This Technical Bulletin is an update in our series of white papers aimed at providing our clients, engineers, specifiers, contractors, fabricators, and friends with objective information on our products and those of our competitors. This Bulletin focuses on a comparison of the physical properties of closed cell 2 polyisocyanurate 3 (polyiso or PIR) rigid foam insulation products with those of cellular glass insulation products for demanding below-ambient applications such as cryogenic, refrigerant, and chilled water where energy efficiency, moisture intrusion, and condensation are issues. We strive to be objective and believe in full-disclosure. In that vein it should be said that cellular glass is a proven product made by several reputable manufacturers, and it may be the most appropriate insulant in some situations; for example in a chemically corrosive environment when 25/50 flame spread/smoke development 4 is required there is no better choice. Yet, as they say, the devil is in the details and insulation systems for low-temperature applications require engineering expertise that we do not purport to offer in this short Bulletin. Rather, we desire to raise issues that should be addressed by your engineer/specifier, and we will gladly provide any support or clarifying detail we may have. Simply, we offer that polyiso insulation products are the preferable choice for a range of low temperature applications, particularly cryogenic, refrigeration, HVAC, and even domestic hot and cold water applications ranging from -297 F up to +350 F (-183 C to +177 C) and 375 F (190 F) intermittent service temperatures. Specifiers, engineers, and end-users should additionally note that while this Bulletin is focused on generic differences between cellular glass and PIR foams, yet there are indeed additional differences between the physical properties and performance characteristics of competing PIR insulations. We recommend end-users view other Technical Bulletins from Dyplast that address ISO-C1 and ISO-HT properties in comparison to alternative polyiso insulation products. 1 Update on Technical Bulletin 0213 2 Determination of closed celled versus open celled is not as simple as it would first seem, since there are variations in the % of closed cells, as well as variation in cell structure and whether they can retain insulating gases. We could not find a statement from cell glass manufacturers re: % closed cells, but it is logical that it is very high. ISO-C1 has >95% closed cells in its 2 lb/ft 3 density, and >98% in higher density. 3 Polyisocyanurate is a form of polyurethane (PUR), but the chemistry and properties are different to improve flame spread, smoke development, and dimensional stability - - among other properties. 4 No U.S. manufactured polyiso currently meets the 25/50 criteria; however Dyplast s ISO-C1 and ISO-HT meet Class 1 per ASTM E84. Technical Bulletin 0114 Page 1 of 7 January 2014

SUMMARY K-factor: the aged thermal conductivity (k-factor) at 75 F of ISO-C1 polyiso is 0.176 Btu in/hr ft 2 F whereas cellular glass is nominally 0.29; thus the thermal insulation performance of cellular glass is roughly 65% worse than polyiso, which results in cellular glass insulation systems being much thicker (important from a weight, volume, quantity of accessory products such as sealants, jackets, etc., and space aspects). Brittleness and Shipment/Handling: cellular glass is more susceptible than polyiso to vibration, thermal shock, and mechanical shock; thus cellular glass may have breakage during transportation to the job site and subsequent handling; polyiso is not of course immune to damage during shipment or handling but typically requires less mitigation efforts; thumbrules for cellular glass from insulation specifiers and contractors sometimes assume 5% breakage during shipment, 15% breakage from handling on job site. Brittleness and Operations: cellular glass may be less suitable for application in process environments with high vibration, movement, or thermal/mechanical shock; cellular glass breaks or cracks may create a path for heat and/or moisture to pass; polyiso is not brittle and is not as susceptible to vibration, movement, or thermal/mechanical shock; when polyiso is installed in areas where mechanical abuse is expected, such as workers stepping on the insulation, higher density polyiso with higher compressive strengths should be considered; even when abused, since polyiso is not brittle so it will not crack like cellular glass so such thermal/moisture leaks are less likely to form. Thermal Expansion/Contraction: since cellular glass has a thermal expansion coefficient less than polyiso, expansion joints are less of an issue; pipe metallurgy and the range/duration of temperature cycling are determining factors yet our experience is that the cost of additional expansion joints is not material when insulant selections are being made. Water Vapor Transmission and Joints/Cracks: (i.e. WVT, or permeability): both polyiso and cellular glass are low perm materials; cellular glass manufacturers generally advertise zero perm; polyiso insulation has low (but not zero 5 ) water vapor permeability; for both materials the risk of moisture infiltration is less determined by the inherent property of polyiso or cell glass and more-so dependent on the quality of the vapor retarder/barrier, the number of joints between insulant segments 6, the performance of joint sealants, and the likelihood of cracks in the insulation; both cellular glass and polyiso manufacturers recommend vapor retarders in cold service, and vapor barriers at even lower temperatures. Vapor Barriers: although cell glass manufacturers sometimes advertise that vapor barriers 5 ISO-C1 polyiso has 1.65 perm-inch WVT; Trymer polyiso advertises 4.0 6 Polyiso is manufactured as large continuous bunstock that can be fabricated into pipe insulation many times larger than is possible with cell glass, thus minimizing the number of joints and seams; ask your supplier for specific dimensions Technical Bulletin 0114 Page 2 of 7 January 2014

are not required, polyiso manufacturers more often recognize that in low temperature applications engineers almost always specify that a vapor retarder or barrier be applied over the insulant - - not so much to compensate for the WVT of the insulant but rather as a second line of defense for the joints, seams, and cracks; vapor retarders are more often used at chilled water temperatures while vapor barriers are increasingly important as temperatures drop below refrigerant temperatures; thus given the facts in the prior paragraph, vapor retarders/barriers could arguably be more important in cell glass systems than polyiso systems. Water Absorption (WA): Although different ASTM standards govern the testing of WA in polyiso and cellular glass 7, each have excellent water absorption properties, and water absorption should not be a factor in a properly installed insulation system. Installation the insulation system : A particular insulation product can perform at its peak only when properly installed within a more complete insulation system with sealants, adhesives, vapor barriers, weather mastics, jacketing, and so forth; while some cellular glass manufacturers advertise that neither vapor barriers nor jackets are required, the fact is that the vast majority of engineer/specifiers require similar accessory components; in fact, cellular glass insulation systems may require more complexities than a comparable polyiso insulation system, and thus may be more time-consuming to install and thus may have more potential for errors during the installation process; for example, a cellular glass system for LNG pipe may require an abrasive-resistant coating, a latex mastic as a weather barrier mastic (3-4 gal./100 ft 2 ), then a layer of synthetic mesh fabric, and then a second coat of weather barrier coating, and possibly a metal jacket whereas a polyiso system installation would require only a sealant on seams/joints/ buttends, and a vapor barrier sheeting over the insulation (and this could actually be shop applied, making field installation even easier) and protective metal jacketing; note of course that polyiso systems as well as cellular glass systems require mastics at vapor stops and potentially other discontinuities; thumbrules from insulation contractors indicate that cellular glass requires a minimum of 30% more labor to apply than polyiso. Installation field fabrication: installation contractors may have varied opinions on whether cellular glass or polyiso is easier to field fabricate (change shape/dimensions at the jobsite); cellular glass can be shaped by abrading it against a rough surface (or even the pipe itself, although maybe not advisable) or by using a rasp; some installers have minor complaints relating to abrasion to a worker s hands, glass dust, and odor; and the density/weight of cellular makes it somewhat more difficult for workers to handle; on the other hand, polyiso is shaped or re-shaped in the field typically with a sharp knife also it can also be shaped with a rasp; the most common complaint from installers is dust. Installation number of insulation segments: the maximum dimensions of cellular glass insulation blocks are less than those of polyiso bunstock, and therefore when larger pipe 7 The percent by volume WA for ISO-C1 polyiso is 0.04%, and for Trymer <0.7%; and for cellular glass <0.2% Technical Bulletin 0114 Page 3 of 7 January 2014

diameters are involved, the cellular glass blocks must be joined together with adhesives; for very large pipe, multiple (more than two) cellular glass segments are required, resulting in more joints and seams to seal, which means more labor, more consumption of materials, and more possibility of improper installation (e.g. a seam not sealed, or a cracked piece of insulation) - - which can lead to thermal and/or moisture leaks; polyiso bunstock on the other hand is large enough to be fabricated into two half-shells even for the largest of pipe diameters; due to cellular glass s poorer insulating properties, a cellular glass insulation system is also likely to have more layers than a comparable polyiso system thus requiring more steps in the process, more joints to seal, and resulting in more consumption of sealants, tapes, adhesives, etc. Insulation Thickness: The thickness of the insulation is primarily dependent on the k- factor (addressed in the first bullet); the materially better k-factor of polyiso will always lead to polyiso requiring less thickness that cell glass; for instance, a 4 inch thick layer of polyiso (at a 0.176 k-factor) is typically equivalent to almost 7 inches of cellular glass (at 0.29 k). Number of Layers: Multiple layers of insulant are generally specified not to add more thermal efficiency 8 (since polyiso and cell glass can be fabricated to virtually any thickness 9 ) but rather to allow offsetting joints and seams - - thus mitigating risks of moisture infiltrations; there is no logical reason that cell glass manufactures should argue their insulant requires fewer layers; to the contrary small billets of cell glass must be glued together to make fir larger pipe segments, while in theory polyiso can be manufactured to accommodate virtually any pipe diameter and length to minimize the number of seams and thus the requirement for more layers. Weight: Cellular glass has a density of generally 7.5 lb/ft 3 versus 2.0 lb/ft 3 for the most commonly used polyiso 10 ; the low thermal efficiency of cellular glass (65% worse than polyiso) compounds the problem since cellular glass installations may require closer to double the thickness to provide the same insulating performance; the result is a significant increase in weight and volume on a given pipe run [for example assume an 8 inch diameter run of piping requiring 2 inch of polyiso insulation at 2 lb/ft 3 density; every linear foot of insulation would weigh 0.87 lbs; since 3.5 inch thick 11 cellular glass must be applied to achieve the same R-value, a linear foot of cell glass would be 6.6 lbs - - 7.5 times more weight than polyiso]; the costs of additional pipe hangars, stress on joints that can lead to failure, and inability to run multiple pipes in a small space may make cellular 8 Two 3-inch layers of polyiso have the same thermal resistivity as a single 6-inch layer, yet two layers allow staggered joints & seams to provide another line of defense against moisture intrusion. 9 Note cell glass high density can lead to very heavy segments at greater thicknesses. 10 For some refrigeration and LNG applications, density of polyiso may be 2.5 lb/ft 3, and higher for pipe hangars. 11 Using 3E-Plus software developed by North American Insulation Manufacturers Association, rounded to nearest ½ inch thickness. Technical Bulletin 0114 Page 4 of 7 January 2014

glass a less suitable insulation. Combustibility: Cellular glass has a zero flame spread index (FSI) and a zero smoke developed index (SDI) per ASTM E84; polyiso insulation products for mechanical insulation made in the U.S. currently meet only Class 1, and cannot be installed when air plenum conditions are required; caution must be exercised when installing any insulant in air plenum environments since vapor retarders, weather barriers, sealants, mesh, or adhesives must each have compliant FSI/SDI characteristics; note also that cellular glass can shatter and lose its insulating integrity when severely thermally or mechanically shocked; when exposed to flame, polyiso insulation will char, but maintain its shape, providing precious minutes of thermal protection to pipe, equipment, and vessels to allow response. [Important Note: Section 602.2.1 of the International Mechanical Code states that materials within return air plenums shall be either non-combustible or have less than or equal to a 25/50 fire spread index and developed smoke index when tested in accordance with ASTM E84. Interpretations by other code authorities allow compliance with NFPA 255 or UL 723 as substitutes for ASTM E84. Essentially this means that insulation systems (and all accessory components within, such as sealants, vapor barriers, etc.) installed in either air plenums or inhabited areas to be non-combustible or 25/50. Name-brand cellular glass such as FoamGlas meets this 25/50 requirement. ISO-C1 polyiso is 25/130, so it should not be installed in air plenums or in indoor inhabited areas. Caution should be observed when using cellular glass in such applications that all related sealants, barriers, and such are 25/50.] Cost: The cost of cellular glass per linear foot generally exceeds that of polyiso by a significant margin; the installation cost of cellular glass can also be much more expensive than polyiso; life-cycle costs relating to energy loss and maintenance also will favor polyiso over cellular glass. Chemical resistance: Cellular glass is arguably impervious to the majority of chemicals and is indeed resistant to organic solvents and nearly all acids; yet in the vast majority of cryogenic, refrigerant, and chilled water applications such chemical resistance is not required; it is appropriate to caution that a chemical resistance concern must include accessory products such as sealants, mastics, and vapor retarders. Compressive Strength: Cellular glass, at 7.5 lb/ft 3 density indeed has high compressive strength up to typically 90 lb/in 2, yet it should be noted that the compressive strength of 6 lb/ft 3 density ISO-C1 is typically greater than 135 lb/in 2 (parallel to rise); higher compressive strengths are most commonly required only in pipe saddle applications and in areas of high mechanical abuse, and in these applications polyiso insulation can offer high strength while enabling higher thermal efficiencies than cell glass - - and with fewer problems associated with cracking and weight management. Coefficient of Linear Thermal Expansion (CLTE): Cellular glass has a CLTE close to that of metal, and thus requires fewer contraction/expansion joints than a polyiso insulation system; polyiso, however, is much easier to work in the field and polyiso Technical Bulletin 0114 Page 5 of 7 January 2014

contraction/expansion joints are relatively easy to install. Dimensional Stability: Dimensional stability is a combination of both reversible and irreversible changes in linear and volumetric units; cellular glass product data sheets typically advertise excellent to extraordinary dimensional stability, yet polyiso insulants have very good to excellent characteristics; the bottom line is that with properly installed contractions/expansion joints the issue is mute since any temporary or permanent changes in dimension can be accommodated by insulation system design; note that some cellular glass manufacturers make comparisons against polyurethane insulation without noting that polyisocyanurate is a different chemical formulation with much improved dimensional stability; note also that ISO-C1 has the best dimensional stability when compared with competitive polyiso products. Independent Testing and Auditing of Physical Properties: Although physical properties of insulants reported by manufacturers are generally credible, it is always prudent to demand validation of results by an independent third-party laboratory; even better, expect that the manufacturing and quality control protocols be periodically audited by an accredited agency. The following table displays key physical properties of polyiso (ISO-C1) and cellular glass (FoamGlas). Note that these are product values, and not insulation system values. Insulation Material Units Polyiso FoamGlas Aged k-factor (at 75 F) Btu in/hr ft 2 F 0.176 0.29 WVT Perm-in 1.65 <0.01 Flammability ASTM E84 rating (insulation only) FSI/SDI 25/130 per FM Density lb/ft 3 2.0 7.5 <25/50 Water Absorption 12 % by volume <0.04 <0.2 Qualitative Comparison Chart: Quality Polyiso Cellular Glass Thermal Performance Excellent Fair WVT without vapor barriers Very good Excellent WVT with vapor barriers Excellent Excellent 12 Measured by different ASTM standards; cellular glass manufacturers frequently note that the water is retained on the surface only. Technical Bulletin 0114 Page 6 of 7 January 2014

ASTM E84 FSI/SDI Very Good (Class 1) Excellent (< 25/50; sometimes advertised as 0/0) Available with factory-applied vapor barrier Yes Yes Closed cell structure Yes Yes Fiber free Yes Yes Non-porous Yes Yes Mold resistant Yes Yes Resistant to vibration/movement Yes Less so Requires a metal jacket Generally Generally Thicknesses available Virtually unlimited, from 1/8 upwards Limited, 1 minimum Lengths Virtually any Sold in 3 foot maximum In-field fabrication Easy Less easy Technical Bulletin 0114 Page 7 of 7 January 2014