Piping layout for fire sprinkler system: An overview

Similar documents
Environmental Engineering-I

WATER SUPPLY ENGINEERING

The purpose of distribution system is to deliver water to consumer with appropriate quality, quantity and pressure. Distribution system is used to

ADVANCED WATER DISTRIBUTION MODELING AND MANAGEMENT

Task 5. Christopher Mack Zack Kaldy MET 330 Fluid Mechanics November 8, Purpose

CITY OF SASKATOON DESIGN AND DEVELOPMENT STANDARDS MANUAL SECTION FOUR WATER DISTRIBUTION SYSTEM

EXAMPLE SHEET FOR TOPIC 2 AUTUMN Q1. What is the significance of the Reynolds number Re for the flow of fluid in a circular pipe?

Environmental Engineering-I

Water supply components

Water and Wastewater Engineering Dr. B. S. Murty Department of Civil Engineering Indian Institute of Technology, Chennai

COLLECTION AND DISTRIBUTION OF WATER

EPANET. Ivan Solinas

CHAPTER 2: Pressure piped irrigation techniques

Chapter 6 Pump Ops 1. Match to their definitions terms associated with pressure.

WASTEWATER & STORM WATER COLLECTION AND REMOVAL

SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES

Water Distribution Systems

Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7: Hydraulic Design of Sewers and Storm Water Drains

Effluent Conveyance. Paul Trotta, P.E., Ph.D. Justin Ramsey, P.E. Chad Cooper

Learning objectives. Upon successful completion of this lecture, the participants will be able to:

Preface to the First Edition Preface to the Second Edition. Acknowledgment

CHAPTER 17: Low-cost pipes distribution system

Water-side Systems. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology

255 NORTHFIELD DRIVE EAST

Domestic Water Use and Piped Water Supply (PWS)

FINAL Examination Paper (COVER PAGE) Programme : Diploma in Mechanical Engineering. Time : 8.00 am am Reading Time : 10 Minutes

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

Wastewater Collection System

APPENDIX B. WSSC Design Criteria for Water Distribution Systems

THE HONG KONG INSTITUTION OF ENGINEERS 香港工程師學會. Admission Requirements for the Fire Discipline (Normal Route)

Hydroelectric power plants

STUDY OF WATER DISTRIBUTION NETWORK USING EPANET

Fire Protection Underground Piping. ASCE Meeting 12/17/14 Columbia, SC

Session 2 Pump Selection. Mark Markham, P.E. Gresham, Smith and Partners September 14, 2017

COMPUTER APPLICATIONS HYDRAULIC ENGINEERING

Pumps and Pumping Stations

Section V WATER DISTRIBUTION SYSTEM DESIGN GUIDELINES

Assignment I Design of a Marine Outfall

INS 310 Water Supply and Sewerage

BUREAU OF INDIAN STANDARDS. Preliminary Draft Indian Standard

Ejectors in a Compressible Network for Gas Turbine Extended Operability

INTRODUCTION TO HDPE PIPES : -

Storm Sewer Design - Introduction

IMPACT AND PUNCTURING OF JARI TUNNEL AND ENLARGEMENT OF EXISTING TAPPINGS FOR ADDITIONAL WATER SUPPLY AND POWER GENERATION

4A General Information A. Concept... 1 B. Conditions... 1

SCHULTE & ASSOCIATES Building Code Consultants 3500 Creighton Road, K5 Pensacola, FL

TABLE OF CONTENTS PART III MINIMUM DESIGN STANDARDS Section 115 WATER DISTRIBUTION SYSTEM GENERAL SIZING LINES 115.

Dynamic Pump Design of Complex Rising Main Injector Systems

Unit 1. FLUID AND FLUID PROPERTIES.

Doc No.:FAD17 (2224)C Draft INDIAN STANDARD IRRIGATION EQUIPMENT RAIN GUN SPRINKLER Specification PART 2 TEST METHOD FOR UNIFORMITY OF DISTRIBUTION

GRUNDFOS isolutions IN COMMERCIAL BUILDINGS

Index. Page numbers followed by f indicate figures.

HY-12 User Manual. Aquaveo. Contents

By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY. May ALDEN RESEARCH LABORATORY, INC. 30 Shrewsbury Street Holden, MA 01520

HYDRANT FLOW TESTING

Mixing, Short-Circuiting, Stratification, Buoyant Jet, DBPs, Water Quality, Water Age

Analysis of Side Sluice in Trapezoidal Channel

Course: Wastewater Management

ENGINEERING REPORT WATER SUPPLY

Pump selection: a real example

ScienceDirect. Network analysis of water distribution system in rural areas using EPANET

Numerical Simulation of the Flue Gas Desulfurization in the Sieve Tray Tower

Level 6 Graduate Diploma in Engineering Hydraulics and hydrology

Reducing the electricity cost of a Three-Pipe Water Pumping System a case study using software

CHAPTER 11: Microsprinklers

Tank Name: Cornwell 0.5MG Reservoir

The SuDS Manual Frequently asked questions

WWTE113. Hydraulic Modeling for Water Network Design. H.H. Sheikh Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE CONS 322 HYDRAULICS

SAWEA Workshop 2010 Innovative Water and Wastewater Networks Presented by Greg Welch, AECOM

ENGINEERING STANDARD FOR DRAIN AND SEWER SYSTEMS OUTSIDE BUILDINGS FIRST EDITION NOVEMBER 2013

level control gates Waterman Industries of Egypt WATERMAN

Calculate the Costs of Piping System Elements

About Me. Overview. Seattle Regional Water System. Seattle Regional Water System. Water System Analysis and Design at Seattle Public Utilities

DESIGN OF WATER SUPPLY PIPE NETWORKS

INCOMPRESSIBLE FLOW TURBOMACHINES Design, Selection, Applications,

ENVIRONMENTAL ENGINEERING-I

VI.3 Application of Computational Fluid Dynamics to Simulate the Behaviour of Fluids inside Vertical Stack of Building Drainage System

Centraflow Introduction

Conflict Resolution: Pump & System Interaction. April 13, 2017

Fundamentals of Urban Drainage CT-4491 Pressurised systems

Heat Rejection using Cooling Towers

SPRINKLE IRRIGATION SYSTEM Appropriate irrigation technology for smallholder farmers

Hancor, Inc. Drainage Handbook Hydraulics 3-1

Simulation of Existing Water Distribution Network by using EPANET: A Case Study of Surat City

Introduction to Water Supply System OUTLINE

Validation of Regression Models for the Fraction of Fitting Loss in Index Pipe Runs (Part 2: Water Distribution to Groups of Buildings)

CVE 372 HYDROMECHANICS OPEN CHANNEL FLOW I

Public Water System Description. Contact Information Contact Type Name Phone Current Address. Public Water System Name: PWS ID: Date:

Technical Assignment 1 10/8/03

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS

UBC Technical Guidelines Section Edition Sanitary Sewerage Utilities Page 1 of 6

CHAPTER 5. COLLECTION SYSTEM ALTERNATIVES

: Plan Review and Project Services

23 Supply Drinking Water Without Power

Hydraulics Laboratory Experiment Report

CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD

SCHOOL OF COMPUTING, ENGINEERING AND MATHEMATICS SEMESTER 1 EXAMINATIONS 2014/2015 ME257. Fluid Dynamics. Answer FOUR out of SIX questions

DALTON FIRE DEPARTMENT 404 School Street Dalton, GA 30720

FLEMING HILL WTP FINISHED WATER PUMP STATION ELECTRIFICATION PROJECT TECHNICAL MEMORANDUM NO. 1 HYDRAULIC ANALYSIS AND PUMP SELECTION

Transcription:

Piping layout for fire sprinkler system: An overview Kshitiz Vishnoi Abstract In today s times, the designing of piping systems has become an important field. With increased urbanization, and construction of complex infrastructures like advanced warehouses, factories, power distribution centers, refineries, multi-storied residential and commercial buildings, etc., having a good piping system is a must for supplying adequate amount of clean water for fighting against fire threats. Earlier, piping design was done by using many manual calculations and formulation methods. This made piping design a laborious and time-consuming process and it was also prone to large amount of errors. However, modern piping design is done by using software such as ANSYS, CFD, AUTOCAD, etc. for doing calculations and drawing/designing the required layout. This not only reduces the computation times, but also allows us to have a virtual simulation of the chosen design, thereby giving us a better idea about how effective the chosen piping design will be before it is implemented, thus allowing us to fine tune the design for better output and also reducing the errors. In this paper, we highlight the requirements of a good piping system, and we elaborate upon the various steps involved in designing of such systems, and choosing the suitable type of piping layout for the required conditions such as available pressure, consumption demand, flow rate, etc. and performing various calculations on the basis of the above factors. Index Terms Fire protection, Piping layout, Sprinkler system, System Design. I. INTRODUCTION Piping Network is a system of pipes and trenches which provide the appropriate quality and quantity of water to a community. The design, construction and layout of the piping network have to be carefully prepared in order to ensure that there is enough flow pressure to supply hygienically safe water. Once the network is constructed, its maintenance has to be performed, which includes repairs, leakage control, prevention of recontamination, etc. Along with maintenance, the proper operation of pumping stations has to be ensured for areas where gravity pressure alone is not enough (Figure 1). Figure-1: Model showing sprinkler network Kshitiz Vishnoi, Design Department, EAST Corp, Mumbai, INDIA, +91 9869193090. II. THEORY Design flow direction Water flow direction Figure-2: System design vs water flow direction Requirements of an Adequate Distribution System: For an adequate water distribution system, the requirements are as follows: 1. Water quality should not deteriorate while flowing through the distribution pipes. 2. The system should be capable of supplying water to all the intended places with sufficient pressure head. 3. It should be capable of supplying the required amount of water during firefighting. 4. The layout should be such that no consumer is without water supply, during the repair of any section of the system. 6. It should be fairly watertight to minimize losses due to leakage. The design of water distribution for firefighting (Figure 2) consists of the following main steps: 1. Preliminary Studies 2. Design Phases 3. Network Layout 4. Hydraulic Analysis 1. Preliminary Studies: - This is the first and the most important step in the designing of water distribution system. Before any design work can commence, thorough observations and studies have to be carried out. Preliminary studies consist of the following sub-steps: a. Topographical studies must be performed before starting the actual design work. b. Digital maps showing present (and future) houses, streets, lots, and so on should be made. c. Location of water sources and pumping stations should be considered so that distribution reservoirs can be easily located. Water Demand Studies: Studies have to be made on the amount of water that is required to a particular area on the basis of the fire demand, the population and the area of the structure/land under 17 www.ijeas.org

Piping layout for fire sprinkler system: An overview consideration. This can be determined by the following formulae: (Fire demand formulae) 2. Design Phases: After the preliminary studies are performed, the next step is setting the Design Criteria. This step involves setting the required design limitations/parameters that are required to get the most effective and economical water-distribution in the chosen network. The required limitations/parameters can determined on the basis of the following factors: a. Hazards classification: System depends not only on the size of the risk but also on its fire growth and spread potentialities, the risk are to be categorized under following classes (Figure 3) for the purpose of system design. a) Light hazard b) Ordinary hazard 1 c) Ordinary hazard 2 d) Extra-ordinary hazard 1 e) Extra-ordinary hazard 2 is always under pressure. As per codes, it is mandatory to have a minimum pressure of 0.5 bars at the remotest nozzle for the operation with the water hammering and cooling effect. e. Flow: The flow rate or the discharge from a sprinkler head or water mist nozzle can be calculated from the formula below: Flow (q) = k P Where k is the K-factor P is the pressure Assuming K-factor = 80 and pressure = 0.5 Therefore, Flow = 80 0.5 Flow (q)= 56.568 l/m This is minimum flow required for the system. f. Pipe size: Water pipe sizing procedures are based on a system of pressure requirements and losses (Figure 4), the sum of which must not exceed the minimum pressure available at the supply source. The required pipe size is chosen to maintain the flow/cost effectiveness (Figure 5). Figure-4: Friction loss in pipes due to the flow Figure- 3 : Density/Area curve (NFPA 13 chapter 3 clause 3.3.15) b. Demand: Demand is the quantity of water required to flow from a fire sprinkler. Mathematically, Demand (Quantity) = Area X Density The area of sprinkler head (coverage) and the required design density can be chosen from figure 3 as per the hazard classification. Therefore if we have ordinary-1 hazard, area = 186m 2 & density = 5.9mm/min ( from figure 3) Demand = Area X Density Demand = 186 X 6.1 Demand = 1134.6 l/m This would be the minimum flow rate required for the sprinkler head to prove the correct design density. c. K-Factor: K-factors are known as the coefficient of discharge. The larger the K factor in number, the more water it can discharge at a given pressure. d. Pressure: Pressure is an expression of force exerted on a surface per unit area. A fire pipe carrying water Figure-5: Pipe sizing with pipe schedule method g. Velocity: The equilibrium speed of flow of water in the pipe shall not exceed 6 m/s at any valve or flow monitoring device, or 10 m/s at any other point in the system for the stabilized flow condition at the demand point involving an AMAO. h. Head loss: Head loss cannot be prevented but can be minimised. Head loss is due to water flow against gravity, pipe fittings (T-joints, Elbows, and Couplings), Valves (Butterfly valve, Gate Valves) and friction losses (major & minor loss) in the pipes. i. Avg. water consumption: According to the average water consumption, the capacity of water storage tank (per hour basis) has to be defined. This depends upon the potential hazard that could be encountered: a. Light hazard ------- 30 mins. b. Ordinary hazard --------- 60 mins to 90 mins c. Extra-ordinary hazard ----------- 90 to 120 mins j. Spacing between 2 sprinklers: This depends on the coverage area of the sprinkler. Spacing is generally 18 www.ijeas.org

kept between 3 mtrs to 4 mtrs. There are mainly two types of spacing provided as per the design criteria as shown in figure 6. They are Triangular spacing and Rectangular spacing. It consists of the following components: Reservoir. Main (trunk) line Sub-mains Figure-6 : Spacing between sprinklers w.r.t. coverage k. Selection of material: Pipes that are mainly used in fire industries is 40 galvanised steel. But as per NFPA and IS codes CPVC piping can also be used (only for light hazards) l. Codes to be followed There are many codes/regulations that can be followed for designing the fire protection system. For example NFPA, FM, OSID, BIS, NBC, TAC or any other local codes. 3. Network Layout: - After the design criteria are determined, the next step is to choose a suitable pipe network layout and to estimate pipe sizes on the basis of water demand and local code requirements. The pipes are then drawn on a digital map (using AutoCAD, for example), starting from the water source (Figure 7). All the components i.e. pipes, valves, fire hydrants, etc. of the water network should be shown on the lines. These layouts are used by project executers (contractors) for implementation (installation). Figure-7: A screen-shot of piping in AutoCAD layout III. ANALYSIS AND DISCUSSION There are 3 types of piping layouts possible in fire protection designing. They are: A. Branching with dead end. (Tree system) B. Grid (Gridiron system) C. Grid with loop. (Circular or ring system) Figure-8 : Water flow in Tree-system Main line is the main source of water supply. There is no direct supply from the main trunk line, the water is first supplied to the consumers from the main line through the sub-mains, which are connected to the main line and they are laid along the main roads. From the sub-mains, the water then flows through the branches which are connected to the sub-mains and they are laid along the streets. From the branches, the water lastly flows through the service connections which are connected to the branches and thus the water is supplied to the consumers. It is a very simple layout for water distribution. Design calculations are easy and simple to do. The required dimensions of the pipes for this layout are small, thus it is economical and cheap. This layout requires comparatively less number of cut-off valves. However, this layout is not usually favoured in modern water works practice due to the following disadvantages. The area receiving water from a pipe under repair is without water until the work is completed. In this system, there are large numbers of dead ends where water does not circulate but remains static. Sediments accumulate due to stagnation of water at these dead ends and bacterial growth may occur at these points. To overcome this problem, drain valves are provided at dead ends and stagnant water is drained out by periodically opening these valves but a large amount of water is wasted. It is difficult to maintain chlorine residues at the dead ends of the pipe. Water available for fire-fighting will be limited since it is being supplied by only one water main. The pressure at the end of the line may become undesirably low as additional areas are connected to the water supply system. This problem is common in many lesser-developed countries, where this type of piping layout is common. A. Branching Pattern with Dead End This is the simplest type of piping layout. It is called a Branching as it looks similar to the branching of a tree (Figure 8). 19 www.ijeas.org

Piping layout for fire sprinkler system: An overview Figure-9 : Software generated report for tree system B. Grid Pattern In grid type layout, all the pipes are interconnected with no dead-ends (Figure 10). In such a system, water can reach any point from more than one direction. This system cannot be designed with pipe schedule method. It has to be done with hydraulically designed method. It consists of the following components: Reservoir Main line Figure-10: Water flow in Grid system Since water in the supply system is free to flow in more than one direction, stagnation does not occur as readily as in the branching piping layout. In case of repair or break down in a pipe, the area connected to that pipe will continue to receive water, as water will flow to that area from the other side. Water reaches all points with minimum head loss. At the time of fires, by manipulating the cut-off valves, plenty of supplied water can be diverted and be used for concentrated fire-fighting. Cost of laying the pipes is more because relatively longer pipes are required. More number of valves are required. The calculations of pipe sizes are more complicated. Figure-11: Software generated report for Grid system C. Grid Pattern with Loops: This type of pipe layout is a modified type of Grid layout (Figure 12). In this layout, loops are provided in a grid to improve water pressure in certain portions of a city (industrial, business and commercial areas). The loops should be strategically located so that as the city develops, the required water pressure should be sustained. It consists of the following components: Reservoir Main line The advantages and disadvantages of this are the same as those of the grid. Figure-12 : Water flow in Loop system Since water in the supply system is free to flow in more than one direction, stagnation does not occur as readily as in the branching. This system is balanced as water reaches all points with minimum time and minimum head loss. At the time of fires, by manipulating the cut-off valves, plenty of supplied water can be diverted and be used for concentrated fire-fighting. Designing of the system is much easier than grid system. Cost of laying the pipes is more because relatively longer pipes are required as in tree and grid system. More number of valves are required to isolate. This system cannot be designed with pipe schedule method. It has to be hydraulically designed. Figure-13: Software generated report for loop system 4. Hydraulic Analysis (Of Distribution Systems):- After the suitable type of pipe layout is chosen, the next and final step involves the analysis of the chosen layout. This involves calculating the flow rate, supplied water pressure, volume, losses, etc. The calculation process is done using hydraulic analysis software like SprinkCALC, PipeNET, SprinkCODE etc. These softwares are designed especially for calculations of piping for fire protection systems. 20 www.ijeas.org

V. CONCLUSIONS AND RECOMMENDATIONS The results obtained are software generated based on SprinkCALC (A TYCO product). From the above observations and studies, we can conclude that on the basis of certain properties, the three types of piping layouts and their uses can be summarized as follows: Figure-14: Friction losses in pipes. Friction Losses in Pipes Friction losses are a complex function of the system geometry, the fluid properties and the flow rate in the system. By observation, the head loss is roughly proportional to the square (Figure 14) of the flow rate in most engineering flows (fully developed, turbulent pipe flow). This observation leads to the Hazen Williams equation for head loss due to friction: Branching type In this type of layout, the pressure requirement is high, so the pump capacity increases. The flow i.e. water requirement is high, hence system volume is low i.e. the quantity of water flowing through the pipes will reduce. Total length of pipe (different size) required is minimum. Grid type In this type of layout, pressure requirement is lesser than Branching type, but higher than the Grid with loop type piping layout. Grid with loop type- In this type of layout, pressure requirement is low, so pump capacity reduces. At the same time, system volume is high i.e. the quantity of water the pipe will increase. Recommended for areas where the source pressure is low. Central feeding of water should be used for better distribution of water (flow, pressure, etc.) where: V is velocity k is a conversion factor for the unit system (k = 1.318 for US customary units, k = 0.849 for SI units) C is a roughness coefficient R is the hydraulic radius S is the slope of the energy line (head loss per length of pipe or h f /L VI. ACKNOWLEDGEMENT I would like to thank my parents for inspiring me for such research work. Special thanks to Mr. Sushant Tambadkar for his guidance and technical support. Last but not least I would like to give sincere thanks to Mr. Hemant Khadse and team of East Corp for providing me the possible infrastructure to complete this work. IV. RESULT On comparing all the three possible piping layouts, keeping few parameters constants, the following result is obtained through hydraulic analysis using SprinkCALC software. K= 80.3 Coverage = 9.3m 2 Total no. of sprinklers operated = 35 Calculation Mode Demand Hydraulic Model - Hazen-Williams Fluid Name - Water @ 60F (15.6C) Min. Density (l/min/m²) - 6.1 Type of System wet Result Table: Req. Pressure at source Max. velocity (m/s) Total Water Required (l/min) (Flow) Volume - Entire System Total length of pipe (m) Branching Grid Grid with Loop 2.5 1.85 1.61 8.1 7.31 7.21 2318.86 2091.77 2064.67 272.7 l 428.2 517.6 l 142.5 170.5 189.25 VII. REFERENCES [1] https://en.wikipedia.org/wiki/hydraulic_calculation [2] www.canutesoft.com/table/basic-hydraulic-calculation-for-fire-p rotection-enginee... [3] www.ence-pumps.ru/eng/truboprovody.php [4] www.sprinklerwarehouse.com [5] https://media.toro.com/documents/irrigation/sprinkler-pig.pdf [6] wiginton.net/pdf/wiginton-fire-protection.pdf [7] http://www.sfpe.org/pages/2012_q2_3 [8] Natural gas engineering and safety challenges by G.G Nasr, N.E.Connor, p127-p145 [9] http://law.resource.org/pub/bis/is15105(2002).pdf p5 p63. [10] http://www.nfpa.org/proposedtia998nfpa13.pdf [11] http://www.nfpa.org/assents/files/13commdraft6-0reduced-1.pd f p17-p25, p122-126 Kshitiz Vishnoi, possess a Bachelor s Degree in Mechanical Engineering from University of Mumbai. Professionally, working as a Design Engineer (MEP-Systems) in EAST-Corp, Mumbai. INDIA Contact No. +91 9869193090 21 www.ijeas.org