DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE-CAST CONCRETE

Similar documents
DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW BUILDEX 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: TENDON SYSTEMS, LLC

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: BOSTITCH FASTENING SYSTEMS

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 100 PLANO, TEXAS 75024

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

Trusted ICC ES HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: MITEK USA, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: PLASTIC DECKING REPORT HOLDER: SILCA SYSTEM

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS LLC

DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: CPG INTERNATIONAL LLC DBA THE AZEK COMPANY LLC EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS REPORT HOLDER: HB&G BUILDING PRODUCTS, INC.

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A DIVISION OF MITEK

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

DIVISION: OPENINGS SECTION: VENTS/FOUNDATION FLOOD VENTS REPORT HOLDER: FLOOD FLAPS, LLC

DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: ULTRALOX 2955 LONE OAK DRIVE, SUITE 180 EAGAN, MINNESOTA 55121

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: PASLODE, AN ILLINOIS TOOL WORKS COMPANY

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015.

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC. EVALUATION SUBJECT: GRABBER FASTENERS FOR USG STRUCTURAL PANELS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: OPENINGS SECTION: VENTS/FOUNDATION FLOOD VENTS REPORT HOLDER: FLOOD FLAPS, LLC EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A DIVISION OF MITEK

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-FABRICATED WOOD TRUSSES REPORT HOLDER: EAGLE METAL PRODUCTS

DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: ULTRALOX EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: SRL INDUSTRIES LTD.

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC.

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: HY-TEK FASTENERS INC. EVALUATION SUBJECT: HY-TEK NAILS

DIVISION: OPENINGS SECTION: VENTS/FOUNDATION FLOOD VENTS REPORT HOLDER: SMARTVENT PRODUCTS, INC.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: ispan SYSTEMS LP 70 BRENTWOOD DRIVE PRINCETON, ONTARIO N0J 1V0 CANADA EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: TEJAS BORJA USA EVALUATION SUBJECT:

Trusted ICC ES MILAN ITALY SYSTEMS. Look. Conformity! Evaluation. ICC-ES Evaluation

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

DIVISION: MASONRY SECTION: MANUFACTURED BRICK MASONRY SECTION: MANUFACTURED STONE MASONRY REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS SECTION: PLASTIC DECKING REPORT HOLDER:

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: GRABBER NAILS FOR GYPSUM WALLBOARD INSTALLATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PEIKKO GROUP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: NCFI POLYURETHANES

DIVISION: CONCRETE SECTION: CAST-IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CONCRETE ROOF TILES REPORT HOLDER: BARTILE ROOFS, INC. EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PJ S REBAR INC.

Joint Evaluation Report

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: FLAMEOFF COATINGS, INC. EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: NCFI POLYURETHANES EVALUATION SUBJECT:

ESR ICC Evaluation Service, Inc. Issued March 1, 2006 This report is subject to re-examination in one year.

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY

To: Firm: Project: Product Specified: Specified Location:

DIVISION: METALS SECTION: METAL FASTENINGS DIVISION: FINISHES SECTION: FASTENERS REPORT HOLDER: HILTI, INC.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A MITEK COMPANY

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: GEOTECH ENTERPRISES, INC.

Joint Evaluation Report

Transcription:

0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3820 Issued 09/2017 This report is subject to renewal 09/2018. DIVISION: 03 00 00 CONCRETE SECTION: 03 16 00 CONCRETE ANCHORS SECTION: 03 41 00 PRECAST STRUCTURAL CONCRETE SECTION: 03 47 00 SITE-CAST CONCRETE REPORT HOLDER: MAGMATECH LTD 110 GLOUCESTER AVENUE LONDON NW1 8HK UNITED KINGDOM EVALUATION SUBJECT: MAGMATECH YETI-ANCHOR FIBER-REINFORCED WYTHE CONNECTORS FOR INTEGRALLY INSULATED WALL PANELS Look for the trusted marks of Conformity! 2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2017 ICC Evaluation Service, LLC. All rights reserved.

ICC-ES Evaluation Report ESR-3820 Issued October 2017 This report is subject to renewal October 2018. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION: 03 00 00 CONCRETE Section: 03 16 00 Concrete Anchors Section: 03 41 00 Precast Structural Concrete Section: 03 47 00 Site-cast Concrete REPORT HOLDER: MAGMATECH LTD 110 GLOUCESTER AVENUE LONDON NW1 8HX UNITED KINGDOM www.magmatech.co.uk EVALUATION SUBJECT: MAGMATECH YETI-ANCHOR FIBER-REINFORCED WYTHE CONNECTORS FOR INTEGRALLY INSULATED WALL PANELS 1.0 EVALUATION SCOPE Compliance with the following codes: 2015, 2012 and 2009 International Building Code (IBC) Property evaluated: Structural Environmental Physical and Mechanical 2.0 USES Yeti-Anchor connectors (40H, 40D, 50H and 50D) are used as panel connections in integrally insulated concrete walls (commonly known as sandwich walls) to resist static and transient tension (40H, 40D, 50H and 50D) and shear loads (40H and 50H) in uncracked, normal-weight concrete having a specified strength, f'c, of 2,500 psi to 6,000 psi. The connectors are alternatives to cast-in-place steel anchors described in Section 1901.3 of the 2015 IBC, Sections 1908 and 1909 of the 2012 IBC, or Sections 1911 and 1912 of the 2009 IBC. 3.0 DESCRIPTION 3.1 Connectors: Yeti-Anchor connectors (40H, 40D, 50H and 50D) refered to as connectors in this report are fiber-reinforced composite connectors with dove-tail anchors at both ends for anchorage into wet concrete with a plastic stopper in the middle of the connector. The connectors are illustrated in Figures 1 and 2. The connectors are produced by a pultrusion process from a polymer composite consisting of glass fiber reinforced epoxy vinylester. The stopper component is injectionmolded from acrylonitrile butadiene styrene (ABS). Yeti- Anchor connectors measure 0.315 inch (8 mm) diameter. 3.2 Concrete: Normal-weight concrete must conform to Section 1903 of the 2015 and 2012 IBC, or Section 1905 of the 2009 IBC, as applicable, and comply with the compressive strength requirements in Tables 3 and 4. 4.0 DESIGN AND INSTALLATION 4.1 Physical and Material Properties of the Connectors: Design must be based on the physical and mechanical properties described in Tables 1 and 2. 4.2 Design for and Shear: Design must be performed using the applicable sections of the applicable codes with the allowable loads as noted in Tables 3 and 4. Allowable loads for Yeti-Anchor connectors subjected to interaction of shear and tension forces must be determined by the following equation: where: PP 5/3 ss + VV 5/3 ss 1 PP tt VV tt PP ss = AAAAAAAAAAAAAA SSSSSSSSSSSSSS TTTTTTTTTTTTTT LLLLLLLL (llllll oooo NN) PP tt = SSSSSSSSSSSSSS TTTTTTTTTTTTTT LLLLLLLL (llllll oooo NN) VV ss = AAAAAAAAAAAAAA SSSSSSSSSSSSSS SSheeeeee LLLLLLLL (llllll oooo NN) VV ss = SSSSSSSSSSSSSS SSheeeeee LLLLLLLL (llllll oooo NN) 4.3 Displacement of the Connectors: The displacement due to gravity loads must be limited to 0.1 inch (2.54 mm). When the connector displacement exceeds the limiting value of 0.1 inch (2.54 mm) due to the gravity loads, the free end of the connector must be supported to maintain fixity by other means. The displacement must be calculated as follows (neglecting any contribution from the insulation in the intended application): where: gg = 3 QQ gg dd AA 12 EE AAAA II AA ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2017 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 6

ESR-3820 Most Widely Accepted and Trusted Page 2 of 6 gg = DDDDDDDDDDDDDDDDDDDDDDDD dddddd DDTT gggggggggggggg AATTLLAA (AATTSSh TTSS mmmm) QQ gg = GGGGGGGGGGGGGG AATTLLAA TTTT tthee SSTTTTTTAASSDDTTSS, DDggAAAASSLLAAAAgg tthee wwwwwwwwhtt oooo tthee llllttssaall AALLggAASS TTll tthee DDSSAAllddDDLLSSgg LLSSAALL llttss tthee SSTTTTTTAASSDDTTSS (llllll TTSS kkkk), QQ gg = tt aa bb yy, wwheeeeee: tt = tthaasskkttaatttt TTll tthee llllttssaall AALLggAASS (AATTSSh TTSS mmmm); aa = httssaaoottttddllaa TTAALLSSAATTgg TTll tthee SSTTTTTTAASSDDTTSS (ffffffff TTSS mmmm); bb = SSAASSDDAASSLLAA TTAALLSSAATTgg TTll tthee SSTTTTTTAASSDDTTSS (ffffffff TTSS mmmm); yy = ddaattttaaddgg TTll SSTTTTSSSSAADDAA (llll ffff 3 TTSS kkkk mm 3 ). dd AA = dd dd + 2h vv 3 1 1 1 + h vv dd dd dd AA = CCCCCCCCCCCCCCCCCC llaattaaaattgg AAAATTggDDh, aa llddttssddaatttt TTll AATTTTddAALLDDAATTTT tthaasskkttaatttt LLTTAA AADDllAAAADDAATTDD (AATTSSh TTSS mmmm). dd dd = IIIIIIIIIIIIIIIIIIII tthaasskkttaatttt (AATTSSh TTSS mmmm). h vv = EEDDllAAAADDAATTDD AAAATTggDDh TTll tthee SSTTTTTTAASSDDTTSS iiii SSTTTTSSSSAADDAA. EE AAAA = 0.95 DDAADDAATT tthee ffffffffddssllaa DDTTAAddAAddTT TTll AAAALLTTDDAASSAADDgg aaaa gggggggggg iiii DDLLllAAAA 1 (pppppp TTSS MMMMMM). II AA = MMTTDDAATTDD TTll AATTAASSDDAALL TTll tthee SSTTTTTTAASSDDTTSS aaaa gggggggggg iiii DDLLllAAAA 1 (iiii 4 oooo mmmm 4 ). The deflection of the connector may be decreased by reducing the connector spacing, but not less than 8 inches (203 mm) on center each way. 4.4 Installation: Connector orientations and locations must comply with the plans and specifications approved by the code official. Yeti-Anchor connectors must be installed in accordance with the instructions provided by MagmaTech Ltd. The instructions are provided with each shipment of the connectors. The minimum embedment, critical edge distance, and critical spacings must comply with Table 2 of this report. The minimum concrete thickness must comply with the applicable code requirements or Table 2, whichever is greater. Within 20 minutes after the bottom layer of concrete is placed, code-complying rigid insulation board with holes sized to accept the connectors must be placed over the concrete while it is in the plastic state. The connectors, sized to match the insulation board thickness, are inserted through the holes in the insulation board into the bottom layer of concrete, until the prescribed embedment is reached. Concrete consolidation around the connectors must be conducted in accordance with the applicable code and MagmaTech Ltd s published installation instructions. The top layer of concrete is then placed over the insulation board, engaging the connectors and consolidated. Panels must cure in accordance with the applicable code. 4.5 Special Inspection: Installations must be made under special inspection in accordance with Section 1705.1.1 and Table 1705.3 of the 2015 and 2012 IBC, or Section 1704.15 and Table 1704.4 of the 2009 IBC. The special inspector must be on the jobsite continuously during connector installation to verify connector type, connector dimensions, and cleanliness, embedment depth, concrete type, concrete compressive strength, edge distance(s), connector spacing(s), concrete thickness, concrete consolidation and concrete curing. 5.0 CONDITIONS OF USE The Yeti-Anchor connectors described in this report complies with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 Connector sizes, dimensions, and installation must comply with the information in this report and MagmaTech Ltd s published installation instructions. In case of a conflict between this report and any other documentation, this report governs. 5.2 Allowable tension and shear loads must be used as noted in Table 3 & 4. 5.3 Calculations and details demonstrating compliance with this report must be submitted to the code official for approval. The calculations and details must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 5.4 Design and installation of concrete wall panels, except as specifically noted in this report, is outside the scope of this report and must comply with the applicable code. 5.5 Connectors may be recognized for interior exposure, exterior exposure or damp environments. 5.6 Connectors must not be permitted in contact with preservative-treated and fire-retardant-treated wood. 5.7 Special inspection must be provided in accordance with Section 4.5 of this report. 5.8 Since ICC-ES acceptance criteria for evaluating data to determine the performance of connectors subjected to fatigue or shock loading is unavailable at this time, the use of these connectors under these conditions is beyond the scope of this statement. 5.9 Since an ICC-ES acceptance criteria for evaluating data to determine the performance of fiber-reinforced connectors in cracked concrete is unavailable at this time, the use of these connectors must be limited to installation in uncracked, normal-weight concrete. Cracking occurs when f t > f r due to service loads or deformations. 5.10 Connectors must not be permitted for use in conjunction with fire-resistant-rated construction, except when connectors resist wind loading only, or for other than wind loading, special consideration is given to fire exposure conditions. 5.11 Use of the connectors to resist seismic loads is beyond the scope of this report. 5.12 Connectors are manufactured by MagmaTech Ltd, under a quality control program with inspections conducted by ICC-ES. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Fiber-reinforced Composite Connectors Anchored in Concrete (AC320), dated October 2015, including creep tests. 7.0 IDENTIFICATION The connectors must be identified in the field by dimensional characteristics and packaging. The packaging label indicates the MagmaTech Ltd name and address, and the ICC-ES report number (ESR-3820).

ESR-3820 Most Widely Accepted and Trusted Page 3 of 6 DESCRIPTION TABLE 1 PHYSICAL AND MECHANICAL PROPERTIES Yeti 40 H AND 40 D Yeti 50 H AND 40 D Customary Units SI Units Customary Units SI Units Cross-sectional area 0.078 in 2 50.3 mm 2 0.078 in 2 50.3 mm 2 Moment of inertia 0.000483 in 4 201 mm 4 0.000483 in 4 201 mm 4 Embedment Depth (H - horizontal configuration) Embedment depth (D - diagonal configuration perpendicular to Embedment Depth (D - Diagonal Configuration) Bending elastic modulus (flexural modulus) 1.60 inches 40 mm 2.00 inches 50 mm 1.50 inches 38 mm 1.8 inches 47 mm 2.10 inches 54 mm 2.60 inches 67 mm 7,291,448 psi 50,272 MPa 7,291,448 psi 50,272 MPa TABLE 2 INSTALLATION PARAMETERS DESCRIPTION Yeti 40 H 2 Yeti 40 D 3 Yeti 50 H 2 Yeti 50 D 3 Embedment Depth 1 1.60 inches 2.10 inches 2.00 inches 2.60 inches Critical Edge Distance 4.00 inches 4.00 inches 4.00 inches 4.00 inches Critical Spacing 8.00 inches 8.00 inches 8.00 inches 8.00 inches Minimum Concrete Depth 2.00 inches 2.00 inches 3.00 inches 3.00 inches For SI: 1 inch = 25.4 mm. 1 According to Figure 3 of this report. 2 Horizontal configuration. 3 Diagonal configuration. TABLE 3 ALLOWABLE TENSION AND SHEAR VALUES IN NORMAL-WEIGHT CONCRETE 1.6-INCH EMBEDMENT DEPTH 1 CONCRETE COMPRESSIVE STRENGTH 2,500psi (17MPa) 3,000psi 2 (21MPa) 3,500psi 2 (24MPa) 4,000psi (28MPa) 4,500psi 2 (31MPa) 5,000psi 2 (34MPa) 5,500psi 2 (38MPa) 6,000psi (41MPa) Yeti 40 H Static (90 degrees to Yeti 40 D Static (45 degrees to 305 lb (1.4 kn) 351 lb (1.6 kn) 396 lb (1.8 kn) - - - 442 lb (2.0 kn) 355 lb (1.6 kn) 463 lb (2.1 kn) 453 lb (2.0) 485 lb (2.2 kn) 552 lb (2.5) 506 lb (2.2 kn) 650 lb (2.9) 527 lb (2.3 kn) 748 lb (3.3 kn) Yeti 40 H Static Shear (90 degrees to 1 Allowable loads have been determined by applying a factor of safety of 4 to the test results. TABLE 4 ALLOWABLE TENSION AND SHEAR VALUES IN NORMAL-WEIGHT CONCRETE 2-INCH EMBEDMENT DEPTH 1 CONCRETE COMPRESSSIVE STRENGTH 2,500psi (17MPa) 3,000psi (21MPa) 3,500psi (24MPa) 4,000psi (28MPa) 4,500psi (31MPa) 5,000psi (34MPa) 5,500psi (38MPa) 6,000psi (41MPa) Yeti 50 H Static (90 degrees to 461 lb (2.1 kn) 595 lb (2.6 kn) 730 lb (3.2 kn) 864 lb (3.8 kn) 866 lb 869 lb 871 lb 873 lb Yeti 50 D Static (45 degrees to Yeti 50 H Static Shear (90 degrees to - - - (1.0 kn ) (1.0 kn ) 600 lb (2.7 kn) 1 Allowable loads have been determined by applying a factor of safety of 4 to the test results. 670 lb (3.0 kn 739 lb (3.3 kn) 809 lb (3.6 kn) 878 lb

ESR-3820 Most Widely Accepted and Trusted Page 4 of 6 YETI 40 H YETI 40 D FIGURE 1 YETI 40 HORIZONTAL (H) AND DIAGONAL (D) CONFIGURATIONS YETI 50 H YETI 50 D FIGURE 2 YETI 50 HORIZONTAL (H) AND DIAGONAL (D) CONFIGURATIONS

ESR-3820 Most Widely Accepted and Trusted Page 5 of 6 FIGURE 3 EMBEDMENT DETAIL OF YETI H AND YETI D

ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3820 FBC Supplement Issued October 2017 This report is subject to renewal October 2018. A Subsidiary of the International Code Council DIVISION: 03 00 00 CONCRETE Section: 03 16 00 Concrete Anchors Section: 03 41 00 Precast Structural Concrete Section: 03 47 00 Site-cast Concrete REPORT HOLDER: MAGMATECH LTD 110 GLOUCESTER AVENUE LONDON NW1 8HX UNITED KINGDOM www.magmatech.co.uk EVALUATION SUBJECT: MAGMATECH YETI-ANCHOR FIBERREINFORCED WYTHE CONNECTORS FOR INTEGRALLY INSULATED WALL PANELS 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that the Magmatech Yeti-Anchor Fiber-Reinforced Wythe Connectors for Integrally Insulated Wall Panels, recognized in ICC-ES master evaluation report ESR-3820, have also been evaluated for compliance with the codes noted below. Applicable code editions: 2014 Florida Building Code Building 2014 Florida Building Code Residential 2.0 CONCLUSIONS The Magmatech Yeti-Anchor Fiber-Reinforced Wythe Connectors for Integrally Insulated Wall Panels, described in master evaluation report ESR-3820, comply with the Florida Building Code Building and the Florida Building Code Residential, when designed and installed in accordance with the 2012 International Building Code provisions noted in the master report. Use of the Magmatech Yeti-Anchor Fiber-Reinforced Wythe Connectors for Integrally Insulated Wall Panels for compliance with the High-Velocity Hurricane Zone Provisions of the Florida Building Code Building and the Florida Building Code Residential has not been evaluated and is outside the scope of this supplement. For products falling under Florida Rule 9N-3, verification that the report holder s quality-assurance program is audited by a quality-assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, issued October 2017. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2017 ICC Evaluation Service, LLC. All rights reserved. Page 6 of 6