Comparative evaluation of the predictions of two established mould growth models

Similar documents
Development of an improved model for mould growth: Modelling

Mould growth in building materials Experiments & Modelling

Analysis of the suitability of mould growth models for the risk assessment of woodfibre internal wall insulation

A NEW MODEL FOR PREDICTION AND ITS APPLICATION IN PRACTICE

Mould growth in building materials in laboratory and field experiments

A MATHEMATICAL MODELING OF MOISTURE BEHAVIOUR AND MOULD GROWTH IN BUILDING ENVELOPES

Design of Mineral Fibre Durability Test Based on Hygrothermal Loads in Flat Roofs.

Proceedings Cold Climate HVAC Sisimiut, Greenland, March 2009

INVESTIGATIONS OF GYPSUM BOARDS WITH REGARD TO THE MOISTURE-BUFFERING-EFFECTS

Condensation Problems in Cool Roofs

COMBINED EFFECT OF TEMPERATURE AND HUMIDITY ON THE DETORIATION PROCESS OF INSULATION MATIRIALS IN ETICS

Seasonal mould growth probability in building envelope insulation

Control of Moisture Safety Design by Comparison between Calculations and Measurements in Passive House Walls Made of Wood

Hygrothermal Calculations applied to water-repellent surfaces - Validation and Application -

Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood

SUPPLY AND EXHAUST VENTILATION SYSTEM WITH HEAT RECOVERY IN COMPARISON TO A DEMAND-BASED (MOISTURE-CONTROLLED) EXHAUST VENTILATION SYSTEM

Hygrothermal Evaluation of Icynene Spray Foam Insulation Installed Between Roof Rafters on Pitched Roofs

Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood

Hygrothermal Performance of Flat Roofs with Construction Moisture

Defacement of ETICS Cladding Due to Hygrothermal Behaviour

Evaluation of the hygrothermal performance of a concrete wall construction with Icynene open cell insulation

Hygrothermal simulation of green roofs new models and practical application

Energy Efficient Buildings in Germany An Introduction

Field Performance of Spray Polyurethane Foam: The Role of Vapour Diffusion Control

Thermal Performance Degradation of Foam Insulation in Inverted Roofs Due to Moisture Accumulation

Flexible Vapor Control Solves Moisture Problems of Building Assemblies - Smart Retarder to Replace the Conventional PE-Film

Table 2 Independent lab test results for Conventional 2x6 Wall U-factor 0F to 70F (28.7% framing)

A SYSTEMATIC APPROACH TO HYGROTHERMAL MODELING AND COMPLIANCE WITH FAILURE CRITERIA USING WUFI

Application of a Computer Model for Integrated Hygrothermal Building Analysis

PH-CALCULATION Dynamic simulation with WUFI

Buildings XI Conference Workshop 2: Thermal Mass IV Assessing Thermal and Moisture Control Benefits of PCM Components by Hygrothermal Simulation

Moisture conditions in highly insulated outdoor ventilated crawl spaces in cold climates

WUFI: Moisture Engineering in the 21 st Century (and Beyond)

LIGHTWEIGHT WOOD-BASED WALLS WITH VARIOUS THERMAL INSULATIONS: LONG-TIME MEASUREMENT AND SUBSEQUENT COMPARISON WITH HAM SIMULATION

Moisture risks of passive retrofitting one town house for the adjacent conventional neighboring structures

SUSREF. Sustainable Refurbishment of Building Facades and External Walls 1 (57) Deliverable: D2.2

On the hygrothermal performance of straw bale wall elements in Belgium

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Assessment of the Risk for Mold Growth in a Wall Retrofitted with Vacuum Insulation Panels

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

Adapted vapour control for durable building enclosures

Performance of internal wall insulation systems - experimental test for the validation of a hygrothermal simulation tool

Hygrothermal behaviour of timber frame walls finished with a brick veneer cladding

RESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS

Conditions for mould growth on typical interior surfaces

Moisture conditions and energy consumption in heated crawl spaces in cold climates

IBP. akustik Hygrothermics

building renovation projects

Ongoing R&D projects in COST member countries Finland

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Moisture supply Set Point for avoidance of moisture damage in Swedish multifamily houses

Moisture convection performance on the joint of external wall and attic floor - laboratory tests and two-dimensional simulation model validation

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Impact on indoor climate depending on the moisture buffering of building materials

Accuracy of simplified indoor humidity simulation

Controlling the indoor environment using wood

Hygrothermal modelling of a sustainable retrofit taking into account the urban microclimate. Case study of the medieval city center of Cahors (France)

Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001

Validation of a 1D transient heat and moisture calculation tool under real conditions

WUFI COMPUTER MODELING WORKSHOP FOR WALL DESIGN AND PERFORMANCE (HEAT AND MOISTURE TRANSFER IN BUILDING ENVELOPES) Boston, MA - October 11-12, 2016

Comparison between uniform rain loads and point sources to simulate rainwater leakage with commercial HAM-models

Air leakage and hygrothermal performance of an internally insulated log house

The Rijksmuseum Amsterdam - Hygrothermal analysis and dimensioning of thermal insulation

Moisture Risks in Multi-layered Walls - Comparison of COMSOL Multiphysics and WUFI PLUS Models with Experimental Results

A well-planned building envelope is a requirement for achieving high user comfort and low energy costs.

Mould resistance assessment of building materials Material specific isopleth-systems for practical application

Internationell och nationell FoU-samverkan. Riskbedömningar vid renoveringar för att energieffektivisera bostadshus

See how to use WUFI in conjunction with ASHRAE s New Standard 160, Design Criteria for Moisture Control in Buildings.

A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J.

A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J.

Thermostat setback effect in whole building performance NRCC Tariku, F.; Kumaran, M.K.; Fazio, P.

Breathability of building elements

THE HYGROTHERMAL BEHAVIOUR OF ROOMS: COMBINING THERMAL BUILDING SIMULATION AND HYGROTHERMAL ENVELOPE CALCULATION

See how to use WUFI in conjunction with ASHRAE s New Standard 160, Design Criteria for Moisture Control in Buildings.

The Thermal Performance of Tradical Hemcrete.

Effect of energy renovation on thermal sensation and comfort

ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES. Civil Engineer, PhD, Assistant Professor, Civil Engineering Department (3)

Optimizimg energy-efficiency of late 19th century ( Gründerzeit ) buildings

SELECTION TOOL FOR WATER-RESISTIVE BARRIERS WITH SUITABLE VAPOUR PERMEABILITY

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

Studies energy efficiency of the renewable sources use considering climate in Latvia

Simulink modelling tool for HAM-system analyses in building physics

NORDTEST PROJECT ON MOISTURE BUFFER VALUE OF MATERIALS

Infiltration simulation in a detached house empirical model validation

Modelling of service life and durability of wooden structures

The comparative in situ hygrothermal performance of. Hemp and Stone Wool insulations in vapour open timber

Numerical Simulation of a Building Envelope with High Performance Materials

Quantifying the Influence of Hygroscopic Materials in the Fluctuation of Relative Humidity in Museums Housed in Old Buildings

Is the moisture buffer value a reliable material property to characterise the hygric buffering capacities of building materials?

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Improving the Energy Performance of Museum Buildings Development and Evaluation of Sustainable Refurbishment Strategies

Hygrothermal performance of sarking roof structure

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

USE OF MULTI-ZONE AIR FLOW SIMULATIONS TO EVALUATE A HYBRID VENTILATION SYSTEM. Åke Blomsterberg 1, Tomas Johansson 1.

Condensation - Prevention and Control

Publisher Rights CC BY-NC-ND Published version available via:

VALIDATED DENSITY FUNCTION RELATED TO CERTAIN BUILDING USE CASES FOR NON-RESIDENTIAL BUILDINGS TO RUN A COMPREHENSIVE URBAN SIMULATION ENVIRONMENT

IEA Annex 41 MOIST-ENG Whole Building Heat, Air and Moisture Response Comparison of measured and simulated moisture buffering results

Moisture transfer in internally insulated buildings

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager

Impact of airtightness on the heat demand of passive houses in central European climate

Transcription:

2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE s prior written permission. 2010 ASHRAE. THIS PREPRINT MAY NOT BE DISTRIBUTED IN PAPER OR DIGITAL FORM IN WHOLE OR IN PART. IT IS FOR DISCUSSION PURPOSES ONLYAT THE 2010 ASHRAE ANNUAL CONFERENCE. The archival version of this paper will be published in ASHRAE Transactions, Volume 116, Part 2. Comparative evaluation of the predictions of two established mould growth models Martin Krus, Dr.-Ing. Michael Seidler Klaus Sedlbauer, Prof. Dr.-Ing. ABSTRACT Calculation models for the prediction of mould growth can are an essential contribution to avoid mould growth and to assess renovation measures. There are primarily two well-known and widely used models, the VTT model and biohygrothermal model. While the VTT model is an empirical model the biohygrothermal method is based on a physically founded model and considers transient ambient conditions. The result is mould growth in mm, which is, however, not intelligible to all. The Scandinavian countries in particular established a very clear six-step evaluation model, the so-called mould index. By combining the results of the biohygrothermal model and the mould index of the Viitanen model it is possible to use a primarily clear and acknowledged rating measure. A conversion function was developed allowing the transfer of the calculated growth into the mould index with very good correlation. INTRODUCTION Numerous damage cases in residential and non-residential buildings can be directly or indirectly attributed to the impact of moisture. Besides reducing potential damage risks the renovation of existing buildings should be aimed at improving the energetic performance. This may result in the reduction of already existing problems with moisture e.g. mould growth caused by temperatures on the internal surfaces, which are too low but will probably also generate new moisture problems. Therefore, mould growth, particularly on internal surfaces of external building envelope components but also in other areas on or inside building assemblies, has become an essential point of discussion in recent times. To remove or avoid mould growth causes considerable costs. Mould growth may pose a health risk for residents [Mücke W. 1999]. Any case of damage in connection with these micro-organisms arises the question anew, whether the building construction is the cause of it and thus finally the owner is responsible or whether the cause is incorrect user behaviour in the sense of insufficient ventilation. To clarify these questions measurements as well as modern hygrothermal calculation methods are Author A is a professor in the Department of Mechanical Engineering, Accredited State University, City, State. Author B is a research at Commercial Company, City, State. 1

applied to provide information on the existing transient moisture conditions and to assess the risk of mould growth. The biohygrothermal model described in [Sedlbauer K. 2001] is an established calculation method predicting the risk of mould growth on internal surfaces for transient boundary conditions. It is based on measured mould growth isopleths and on the calculation of the transient water content of a model spore. The result is growth in mm, which is, however, not intelligible to all. Primarily the Scandinavian countries established a six-step assessment model in the meantime, the so-called Mould Index, introduced by Viitanen and based on a description of the mould growth situation and the percentage of the envelope surface covered. Since the Mould Index is more generally understandable, the results of both models are compared and the integral growth rate form the bio-hygrothermal model is converted into the Mould Index of Viitanen. Description of the two Models Biohygrothermal Model WUFI -Bio The assessment of the risk of mould growth on building surfaces and internal building components is of special importance for building practice. Since temperature and moisture conditions are essential influencing factors of mould growth, knowledge of transient hygrothermal conditions may provide information on spore germination and mycelium growth of mould fungi. Isopleth systems describe the dependence of spore germination or mycelium growth on the surface temperature and humidity. In order to regard the influence of the substrate, that is the building materials or possible soiling, on the formation of mould, Isopleth systems for 4 categories of substrates were suggested that could be derived from experimental examinations: Substrate category 0: Optimal culture medium; Substrate category I: biodegradable building materials; Substrate category II: building materials containing some biodegradable compounds Substrate category III: non-biodegradable building materials without nutrients. For the substrate category III no Isopleth system is given since it can be assumed that formation of mould fungi is not possible without soiling. In case of considerable soiling, substrate category I always has to be assumed (Fig. 1 left). Persistent building materials with high open porosity mostly belong to substrate category II. In 2001 a biohygrothermal model has been developed to describe the mode of action for the fundamental means of influence on the germination of spores, i.e. the humidity available at certain temperatures in a correct way from the physical point of view. This model allows the calculation of the moisture content in a spore in dependence of transient boundary conditions, i.e. it is also possible to consider intermediate drying of the fungus spores. Fig. 1 shows a schematic diagram 2

of the model spore which is the basis of the biohygrothermal method WUFI -Bio. Figure 1: Schematic diagram of the Biohygrothermal Model [2]. The real relation of spore diameter and wall thickness (30 cm) amounts to approx. 1:100.000. If the specific water content (critical water content) is achieved inside the spore, germination can be regarded as completed and mould growth will begin. This critical water content is defined by means of the isopleth systems for spore germination. Further detailed information on this model which was already successfully applied in several cases to assess mould growth is to be found in [Sedlbauer K. 2003]. Fig. 2 presents characteristic results of this program. Fig. 2: Results of a calculation by means of the current Biohygrothermal model. The Model of Viitanen (VTT-model) The fundamentals of the mould growth model were developed by Viitanen and Ritschkoff in [Viitanen H. 1991] under laboratory conditions. The objective of this 3

work was the determination of the times for germination and the mould growth on pine and spruce wood as well as their deterioration under defined humidities and temperatures to get the essential data for modelling. On the basis of numerous laboratory experiments with various constant temperature and humidity conditions the mathematical modelling was developed. Related studies were exclusively performed in the laboratory, since the interaction of surface humidity, material moisture content, temperature, time and microbial growth in buildings was difficult to simulate and analyze. In the model, constant and periodically changing climate conditions as well as the type of wood and the surface qualities can be selected as boundary conditions. These models have undergone continuous developments (see e.g. [Viitanen H 2007, Viitanen H. 2005-2009, Viitanen H. 2005-2009]), including the decrease of mould growth due to fluctuating moisture conditions as well as mineral materials. The results are presented in the Mould Index described in the following. 4

Mould Index (Wood based material) 0 = no growth 1 = some growth (microscopy) 2 = moderate growth (microscopy) coverage > 10% 3 = some visually detected growth (thin hyphae found under microscopy) 4 = visual coverage > 10% (growth found under microscopy) 5 = coverage > 50% 6 = dense coverage 100% The results for mineral materials are presented according to [7] in the latest VTT model with a separate definition of the mould index. Thus the same mould index means a quite different growth according to the respective substrate materials. Mould-Index (Stone-based material) 0 = no growth 1 = some growth 2 = moderate growth (coverage > 10%) 3 = coverage > 50% 4 = coverage < 100% 5 = coverage 100% A different intensity in growth with the same mould index (according to the respective selection of the substrate) is hardly practice-oriented or clear. Therefore, the development of a transfer function is exclusively based on the mould index defined by Viitanen for wood. Basic Differences of the two Models The two models, the biohygrothermal model and the VTT model, are quite different. The VTT model is an empirical model exclusively based on laboratory investigations. In contrast, the transient biohygrothermal model is based on a physically founded model. The biohygrothermal model allows the selection between various substrate categories which can also be extended by specific measured material substrate categories. The Viitanen model only allows the differentiation between two different wood types or a mineral substrate. Growth calculated under conditions unfavourable for mould growth can be retrogressive in case of the Viitanen model in contrast to the biohygrothermal model which shows zero growth at these times. Even at temperatures below 0 C the biohygrothermal model shows a slight growth in contrast to the Viitanen model. The most essential difference, however, is that the Viitanen model does not allow any increase of predicted mould growth beyond a limit value which is dependent on the respective climate boundary conditions, whereas the WUFI-Bio model allows growth as long as it is possible according to boundary conditions. TRANSFER OF CALCULATED GROWTH INTO THE MOULD INDEX 5

Using all the results of the laboratory investigations of Viitanen, which are the basis of all his calculations, with the biohygrothermal model are not targetoriented. For these experiments the documented boundary conditions applicable for the biohygrothermal model. Therefore the transfer is carried out on the basis of numerous calculations by means of both models. The advantage of this method is the fact that real and transient boundary conditions, which occur on the internal surfaces, may serve as a basis allowing a variety of parameter variations. Calculations are carried out by the one-dimensional hygrothermal simulation method WUFI [8-12] which was developed by the IBP and validated in many cases to investigate coupled processes of heat and moisture transfer. The resulting surface conditions serve as input parameter for the biohygrothermal model as well as for the VTT model which was made available by Viitanen for these investigations. Parameter Variations Possible variations for the investigations are location (exterior climate), construction type, indoor climate and thus the moisture load. As concerns the location selection special emphasis is placed on a large scope. Besides locations with very cold winters in Northern Europe, North America and the Alps other locations with high driving rain loads on the North and Baltic Sea are selected. Locations with continental climate in Eastern Europe and moderate climate in Central Europe but also with Mediterranean climate in Italy and Spain are taken into consideration resulting in a total number of 32 different locations. Indoor climate conditions derived from the outdoor climate according to EN 15026 or ASHRAE Standard 160 serve as a basis. Approaches with slightly or strongly increased moisture loads are selected. With regard to indoor temperatures numerous variations from 19 C ± 3 C to 24 C ± 2 C are calculated. This variety of 14 indoor climates is intended to simulate as many user habits as possible, also in the negative sense. As a matter of fact microbial growth primarily occurs due to the malpractice of users as concerns heating and ventilation or obstruction of free convection of indoor air to external wall surfaces by furniture or curtains. Variations with a U-value from 0.3 to 1.9 W/(m²K) are used for the selected external wall assemblies. External walls with insufficient insulation find disproportionately high consideration, as they are especially susceptible to microbial growth. The extremely high U-values are intended to simulate the surface areas of thermal bridges. Monolithic constructions made of various materials as well as lightweight constructions are investigated. Development of the Conversion Function All in all approx. 350 calculations are carried out in this way serving as a basis to develop the conversion function. The evaluation of results is performed by comparing the respective maximum values (mould index and growth in mm) during the calculated period of 365 days. Calculations are started at the beginning and in the middle of the year. A deadline is deliberately avoided, since both methods show different intensities of mould growth under particular climate boundary conditions and at different times. Fig. 3 shows the results of this method. A regression line by means of a polynomial function is added as a red line in the diagram. 6

This method already presents an acceptable result. But there is obviously a large scope of variations within the range of mould index 6. Some upward deviations but almost no downward occur at a lower mould index. These deviations occur due to the specific differences of the models. Whereas the VTT model shows a maximum value (MI 6), extremely high values under favourable growth conditions can be the result as concerns the biohygrothermal model. Upward deviations at a lower mould index always occur, if mould growth is reduced during periods of unfavourable boundary conditions in the Viitanen model, whereas a reduction in growth cannot occur in case of the current biohygrothermal model. Fig. 3: Comparison of the results calculated by both models for the different variations over a period of one year. A regression line by means of a polynomial function is added as a red line in the diagram. As a consequence two modifications are carried out. If MI 6 is reached in the Viitanen model at a certain time, calculation will only be carried out up to this point of time in the biohygrothermal model. Moreover, in all variations where reductions in growth occur according to the VTT model, the result will be corrected by the sum of reductions. If the new results of both models are listed in a diagram (Fig. 4), an even better correlation in the lower range will be the result. A BET adsorption curve serves as a regression curve in this case, since the curves are similar to a characteristic sorption curve. The function given as a red line correlates well with the results over the total range thus representing an appropriate transfer function. 7

Fig.4: Comparison of the results calculated by both models for the different variations after to the modifications described. A regression line by means of a BET-function is added as a red line in the diagram SUMMARY Although the energetic standard of buildings was considerably improved in the last decades, there are consistent reports on building damage caused by mould growth. Microbial growth, however, may pose a health risk for residents. The application of biocides, can avoid mould growth for only a limited period of time in most cases. Therefore mould growth on the surfaces of building components should be avoided by consequent measures. In this context, a preventive strategy should be applied which prevents boundary conditions favourable for mould growth by investigating the transient hygrothermal processes in buildings. Calculation models to predict mould growth can deliver an essential contribution to avoid mould growth and to assess renovation measures. There are primarily two models which are well-known and widely used in the meantime, the VTT model and biohygrothermal model. While the VTT model is an empirical model exclusively based on laboratory investigations, the biohygrothermal method is based on a physically founded model and considers transient ambient conditions. The result is mould growth in mm, which is, however, not intelligible to all. The Scandinavian countries in particular established a very clear six-step evaluation model in the meantime, the so-called mould index implemented in the VTT model based on coverage by percentage and completed by description. By combining the results of the biohygrothermal model and the mould index of the Viitanen model it is possible to use a primarily clear and acknowledged rating measure. A conversion function was developed allowing the transfer of the calculated growth into the mould index with very good correlation. This conversion function as well as the respective diagram will be implemented in the calculation tool in the near future. Since both methods of prediction (VTT model and biohygrothermal model) are widely used and will continue to for some time due to 8

their respective advantages or restrictions, it is important to allow the direct comparison of the results of both methods by the conversion function. This will promote further development of both models and encourage more wide-spread application of mould growth prediction methods in building practice. REFERENCES Mücke, W.; Lemmen, C. (1999): Schimmelpilze. ecomed-verlag, Landsberg am Lech. Sedlbauer, K. (2001): Prediction of mould fungus formation on the surface of and inside building components.. Dissertation Universität Stuttgart. Sedlbauer, K., Krus, M. (2003): Schimmelpilze in Gebäuden Biohygrothermische Berechnungen und Gegenmaßnahmen. Berlin : Ernst und Sohn Verlag S. 435-531, Bauphysik-Kalender 2003. Viitanen H., Ritschkoff A. (1991): Mould growth in pine and spruce sapwood in relation to air humidity and temperature. Uppsala : Swedish University of Agriculture Sciences, Department of Forrest Products. Viitanen, H. und Ojanen, T. Improved Model Predict Mould Growth in Building Materials. Espoo : VTT Technical Research Centre of Finland, 2007. Viitanen, H. Mathematical modelling of moisture behaviour and mould growth in building envelopes. Espoo Finnland : VTT/TTY, 2005-2009. Viitanen, H.: Mathematical modelling of moisture behaviour and mould growth in building envelopes. Espoo Finnland : VTT/TTY, 2005-2009. Künzel, H.M., Kießl, K., Krus, M.: Moisture in exposed building components. International Symposium on Moisture Problems in Building Walls, Porto, 11.-13. Sept. 1995, Proceedings S. 258-266. Hens, H., Ojanen, T., Künzel, H.M., Dow, G., Rode, C., Hagentoft, C.-E.: Summary reports of common exercises in modelling. IEA-Annex 24 final report, Vol. 1, Leuven 1996. Krus, M., Künzel, H.M., Kießl, K.: Use of advanced measuring and calculative procedures for moisture assessment of building elements. Trends in Heat, Mass & Momentum Transfer", Trivandrum/India, Vol. 5 (1999), pp. 1-17. Krus, M., Künzel, H.M., Kießl, K.: Use of advanced measuring and calculative procedures for moisture assessment of building elements. Trends in Heat, Mass & Momentum Transfer", Trivandrum/India, Vol. 5 (1999), pp. 1-17. Künzel, H.M., Schmidt, Th., Holm, A.: Exterior Surface Temperature of Different Wall Constructions - Comparison of Numerical Simulation and Experiment. Proceedings 11th Symposium for Building Physics, TU Dresden, Sept. 2002, pp. 441-449. 9