S T R U C T U R. Practical Solutions. magazine. Supplemental Damping and Using Tuned Sloshing Dampers. Tuned Sloshing Dampers

Similar documents
Vibration Control by Tuned Liquid Dampers

Fluid Viscous Dampers to reduce Wind-induced Vibrations in Tall Buildings

Analysis of Lateral Loads for a Framed Model with Tuned Liquid Damper

BUILDING MOTION CONTROL: SUPPLEMENTARY DAMPING SYSTEMS FOR TALL & SLENDER BUILDINGS

Seismic Behavior Of Reinforced Concrete Buildings Under Varying Frequency Contents

Response Behaviour of a Three Storied Framed Structure with Tuned Liquid Damper

Parametric Studies on Tuned Liquid Damper by Horizontal Shake Table Experiments

Torsional and Seismic Behavior of Shear Wall Dominant Flat Plate Buildings

Recent Applications of Damping Systems for Wind Response

SEISMIC ANALYSIS OF BUILDING USING TWO TYPES OF PASSIVE ENERGY DISSIPATION DEVICES

Experimental Study on the Outrigger Damping System for High-Rise Building

SUPPLEMENTARY DAMPING SYSTEMS

Wind Tunnel Applications for Buildings

SEISMIC DESIGN OF STRUCTURE

Studies on the Application of Tuned Liquid Dampers (TLD) to Up-Grade the Seismic Resistance of Structures

Effectiveness of Tuned Liquid Column Dampers on Vibration Behavior of One-story Steel Structure under Harmonic Force and an Earthquake Record

THE APPLICATION OF RESPONSE CONTROL DESIGN USING MIDDLE-STORY ISOLATION SYSTEM TO HIGH-RISE BUILDING

An Experimental Investigation on Dynamic Response Control of Structures using Tuned Liquid Column Damper

Wind Tunnel Applications for Buildings

Tuned Liquid Sloshing Water Damper: A Robust Device for Seismic Retrofitting

0306 SEISMIC LOADS GENERAL

Analysis of a Multi-Tower Frame Structure connected at different levels using ETABS

DYNAMIC TESTING OF FULL-SCALE 11-STORY RC BUILDING AND ITS 3-STORY STRUCTURAL PART: COMPARISON OF THE RESULTS AND SEISMIC RESISTANCE ESTIMATION

R. J. McNamara, S.E.

The Effect of Frame Geometry on the Seismic Response of Self-Centering Concentrically- Braced Frames

Engr. Thaung Htut Aung M. Eng. Asian Institute of Technology Deputy Project Director, AIT Consulting

OPTIMUM DAMPING IN ISOLATION SYSTEM

S. Gandhi *1, Syed Rizwan 2

RESPONSE OF GROUND SUPPORTED CYLINDRICAL TANKS TO HARMONIC LOADING

Study of seismic effect on buildings modified with shear wall

Department of Civil Engineering, SKP Engg. College, Tiruvanamalai, TN, India

Vibration control of a building model with base isolation

Seismic Evaluation of the Historic East-Memorial Building Retrofitted with Friction Dampers, Ottawa, Canada

Introduction of an innovative base isolation system for seismic protection of HV components based on a combination of wire ropes and viscous dampers

Dynamic optimization for the wind-induced response of a tall building

DESIGN OF OPTIMUM PARAMETERS OF TUNED MASS DAMPER FOR A G+8 STORY RESIDENTIAL BUILDING

Application of Isolation Technology in High-voltage Electrical Equipments

"Impact of New IS 1893 & Related Codes on Design of tall Buildings, Including Trend Setting Structures

Seismic Performance of Combined Isolation System for Asymmetric Buildings Using Non- Linear Time History Analysis

FULL-SCALE VERIFICATION TEST OF DYNAMIC RESPONSE CONTOROL TECHNIQUES FOR STRONG EARTHQUAKES

ACCURATE LINEAR AND NONLINEAR SEISMIC SSI ANALYSIS BASED ON ANSYS FE MODELING USING EXTENDED SASSI METHODOLOGY

Dynamic Stability of Elastomeric Bearings at Large Displacement

This point intends to acquaint the reader with some of the basic concepts of the earthquake engineer:

Forced vibration testing of a thirteen storey concrete building

On the Vibration Mechanism of Historical Menar-Jonban Monument in Iran

Research on seismic behavior of Wood-Concrete Hybrid Structure

AC : EXPERIMENTAL EXPLORATION OF COMMON MODEL- ING ASSUMPTIONS

MID-STORY SEISMIC ISOLATION FOR STRENGTHENING OF A MULTI-STORY BUILDING

Nonlinear Dynamic Analysis a Step Advance

PERIODS OF REINFORCED CONCRETE FRAMES DURING NONLINEAR EARTHQUAKE RESPONSE

Chapter 13 SEISMICALLY ISOLATED STRUCTURE DESIGN REQUIREMENTS

CONTROL EFFECT OF LARGE TUNED MASS DAMPER APPLIED TO EXISTING HIGH-RISE BUILDING FOR SEISMIC RETROFIT

Seismic behavior of concrete structures equipped with ADAS devices

Xyston Inn. NY. Proposal. Xiaodong Jiang. Structure Option. Advisor: Dr. Linda Hanagan

COMPUTER AIDED DESIGN AND ANALYSIS OF RC FRAME BUILDINGS SUBJECTED TO EARTHQUAKES

Xyston Inn. NY. Proposal. Xiaodong Jiang. Structure Option. Advisor: Dr. Linda Hanagan

The influence of vertical seismic ground motion on structures with uplift

Concept of Earthquake Resistant Design

Megacities Building Sway Considerations in Elevators Design for Mega Tall Buildings

Seismic Analysis of Elevated Water Tank

TEMPERING. Tremors. San Bernardino s new courthouse features a comprehensive seismic design that minimizes life-cycle costs.

Chinmoy Kolay Research Engineer

Shaking table experimental study on the base isolation system made of polymer bearings

Hybrid Shake Table for the Testing of Midlevel Seismic Isolation Systems

Seismic Rehabilitation of Selby Condominium Complex, Montreal (Quebec), Canada

Shake table test a structure retrofitted using 2-4 Direction Displacement Dependent (D3) viscous dampers

Pushover Analysis of Reinforced Concrete Structures with Coupled Shear Wall and Moment Frame. *Yungon Kim 1)

CE 6071 Structural Dynamics and Earthquake Engineering UNIT -5 2 MARKS

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

Floating Type Isolation System Using Earthquake Early Warning

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

CHAPTER 3 IMPROVEMENT OF DYNAMIC CHARACTERISTICS OF CUTTING TOOL SYSTEM USING VISCOELASTIC DAMPER

COMPARATIVE ANALYSIS OF SEISMIC ISOLATED SYSTEMS IN BRIDGES

WIND TUNNEL STUDIES AND THEIR VALIDATIONS WITH FIELD MEASUREMENTS FOR A SUPER-TALL BUILDING

SEISMIC DESIGN CHARACTERISTICS OF THE NEW BUILDING FOR DIGITAL AUTOMATION EQUIPMENT FOR LOVIISA NUCLEAR POWER PLANT

STRUCTURAL DAMAGE DETECTION THROUGH FORCED VIBRATION TESTING

Dynamic Analysis of Large Steel Tanks

Lecture 5 Building Irregularities

An experimental study of structural plastic hinge development and nonlinear soil deformation

Title. Author(s)M. OHSAKI; S. TSUDA; N. SUGIYAMA. Issue Date Doc URL. Type. Note. File Information DIRECTIONAL SEISMIC VIBRATION CONTROL

Study of Shear Walls in Different Locations of Multistoried Building with Uniform Thickness in Seismic Zone III

Full-scale dynamic testing of an 11-story RC building and interpretation of the results from the seismic-resistance viewpoint

Seismic analysis of vertically geometric irregular structures

COMPARISON OF SEISMIC PERFORMANCE OF BASE-ISOLATED HOUSE WITH VARIOUS DEVICES

Using friction dampers for improving earthquake response of self-variable stiffness RC framed buildings

Dynamic Time History Analysis of Plane Frame with Tuned Mass Considering Soil-Structure Interaction

sixteen seismic design Earthquake Design Earthquake Design Earthquake Design dynamic vs. static loading hazard types hazard types: ground shaking

RISK-BASED DECISION ANALYSIS FOR BUILDING SERVICEABILITY

Seismic Behaviour Of A Soft Storey Building With & Without Viscous Dampers

DESIGN OF SHEAR WALLS IN RESPONSE SPECTRUM METHOD USING ETABS

Literature Review of Wood-frame Structure Tests

Case Study: Challenges of a Single-layer Reticulated Dome

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

Seismic Devices. Connection Isolation Dissipation

CHAPTER 4. 1:6-Scale Frame: Stiffness and Modal Testing 4.1 OVERVIEW

Pushover Analysis of Structures with Plan Irregularity

Study On Performance Of Regular And Vertically Irregular Structure With Dampers, Shear Wall And Infill Wall

N.Nageswarao Department of Civil Engineering, Amara Institute of Engineering and Technology.

Transcription:

Practical Solutions solutions for the practicing structural engineer Supplemental Damping and Using Tuned Sloshing Dampers By Jamieson K. Robinson P.Eng., Scott L. Gamble P.Eng., and Bujar M. Myslimaj Ph.D., P.Eng. Dynamic Loading and Structural Performance We tend to think of the structures that we build as solid immovable objects. Much of the standard design approach is based on the application of equivalent static load distributions, which reinforces this notion. However, buildings, bridges, spires, roofs, and other slender or flexible structures move when subjected to environmental forces like wind and earthquakes, or moving loads like cars and pedestrians in the case of bridges. Under certain conditions, these motions can cause undesirable increases in structural loads due to the inertia of the large masses involved, and occupant motion sensitivity, motion sickness, or fatigue of the structural materials used. A significant effort is typically expended by the project design team to select and optimize a structural and architectural scheme that is functional, and costefficient. For dynamically sensitive structures, the results of this effort (in terms of structural dynamic performance) can be highly dependant upon the initial assumption about the inherent (natural) damping in the structure. This energy absorption and dissipation characteristic is key to reducing dynamic effects as it increases the structure s ability to absorb the energy imparted to it from external excitations. Damping of real structures is generally expressed as a ratio to critical damping, the energy absorption value which would cause the structure to simply return to center without oscillating if pulled to one side and released. A dynamically-sensitive structure is defined by the National Building Code of Canada (NBCC) 2, to be higher than 12 meters, or having a height/ width ratio of 4 or greater, or being susceptible to vibrations. ASCE 7 code is not as specific as NBCC 2 to define these parameters. ASCE 7 does however recognize that dynamic effects for irregular-shaped buildings or those prone to complex wind loads must be accounted for by using analytical procedures and/or wind tunnel testing. Many engineers refer to the procedures outlined in NBCC 2, as this code is regarded as a leading reference for wind-induced loading. In common structural design practice, the inherent damping value is chosen based on average values recommended in technical literature, codes, and standards, for steel, concrete or composite structural systems. These values typically are assumed to be in the range of 1% to 2% of critical for buildings, and less for simpler structures. However, since each structure is unique, the actual inherent damping exhibited by the finished structure is also unique due to specific architectural and structural system layout, structural detailing and cladding. Changes of only.% of critical or less in the assumed level of damping can have a significant impact on wind-induced loads and motions of a structure. One proven way to achieve a specific overall damping level is to incorporate a Supplemental Damping System (SDS) into the structure. Over the past few years, there has been a noticeable increase in the implementation of supplementary damping in various types of structures such as buildings, bridges, spires, floors, roofs, and grandstands. An SDS is essentially a supplemental energy dissipation system that is optimally designed to absorb vibration energy from a structure, thereby reducing energy dissipation demand on the structure. There are many ways to add energy absorption to a structural system. Technologies in common use today can be broadly classed as distributed, impact, active mass, semi-active mass, mechanical passive tuned mass, and liquid-based passive tuned mass. The trend has been to use passive damping systems, as these systems need no control electronics or powered drive mechanisms and can be counted on to absorb energy when needed most, even during storms when power outages are most likely to occur. The remainder of this article will focus on the application of one passive SDS technology to high-rise buildings. Liquid tuned mass dampers typically have one of two forms, Tuned Liquid Column Dampers (TLCD) or Tuned Sloshing Dampers (). The focus will be on Tuned Sloshing Dampers due to their attractive qualities of simplicity, low cost and dependability with little or no maintenance. Tuned Sloshing Dampers A Tuned Sloshing Damper () is an example of an SDS that utilizes liquid waves to absorb energy from vibrating structures through wave travel and viscous action in a partially filled tank of liquid. The tank is designed so that the liquid surface wave has a frequency tuned to be near the fundamental frequency of the building. The frequency of the liquid is determined by the density, length, width and depth of the liquid. Figure 1: How it works. 1 2 3 4 14 June 27

Sloshing frequency (Hz)..4.4.3.3.2.2.1.1...2.4.6.8 1 1.2 1.4 1.6 1.8 2 Liquid depth (m) Figure 1 depicts the basic principle of the fluid motion in the : Frame 1: Wind event not started. Structure not moving. Fluid at rest position. Frames 2 to 4: Wind event starts. Structure begins to oscillate due to wind. Wave in fluid moves in opposite direction of structure due to fluid inertia from gravity. Fluid motion is damped due to turbulence caused by flow restrictions (screens, posts, or louvers). Oscillation of structure is reduced. This cycle repeats for the duration of the wind event. Frame : Wind event completed. When the structure begins to move under wind forces, the liquid resonates out of phase with the structure and energy is dissipated from the liquid by flow-damping devices such as screens, louvers, or posts in the tank that resist the wave action. Different shapes of tanks, such as rectangular or circular, can be used in implementations to achieve certain goals. A rectangular tank can be tuned to two different frequencies in two orthogonal directions. Implementing Tuned Sloshing Dampers Design and Performance Testing The process for implementing an SDS into a building design is one where the Structural Motion Consultant, who has the expertise and experience to ensure optimum SDS performance, works closely with the design team to help balance energy absorption goals with structural performance and architectural design goals. Examples of this process are 3m 4m m 6m 7m 8m 9m 1m 11m Characteristic length of tank Minimum Water Depth Figure 2: A design chart indicating the minimal water depth (for a range of tank depths and sloshing frequencies) below which the liquid behavior will become highly non-linear. Elevation (floor) Y 7 6 4 3 2 1 1 - -1 presented for two residential building projects (each between and 6 stories tall) currently under construction in New York City. For these projects, additional damping was deemed more effective and beneficial than traditional methods of increasing mass and/or stiffness to reduce building motions to acceptable levels for serviceability. At the early design stage of the building, a technology feasibility study identified that water tank s were most suitable for the projects since adequate floor space could be made available at the top of the building. Initially, the space requirement was based on simplified analysis to allow the engineer and architect to reserve adequate space. A number of possible configurations were investigated, including both deep tank and shallow tank types. The decision regarding the optimal type and size of was made based upon weighting the relative importance of space availability for the on the mechanical floor, performance targets (in terms of reduction of building motions), construction costs, and the immediate and longer term cost benefits of minimizing structure while maintaining building motion serviceability targets. As the projects progressed into Detailed Design and Construction Documents, more comprehensive time-domain simulations of building and motions and scale models of the tanks were developed and tested to fine-tune the damper and to ensure optimal performance at the specified return period. continued on next page -Year Wind Response with TLCDs, 22 deg X axis Y axis X TLCD COM Y TLCD COM -.. X Force (MN) Force (kn) Force (kn) -. -.. -. 2 1-1 X Shear Y Shear 1 2 3 4 6 7 8 Floor 6 X Floor 6 Y 1 2 3 X TLCD COM Y TLCD COM 1 2 3 X TLCD, X axis Y TLCD, Y axis -2 1 2 3 2 1-1 X TLCD, X axis Y TLCD, Y axis -2 1 2 3 4 6 7 8 4 6 7 8 4 6 7 8 4 6 7 8 Time (s) Figure 3: Time-domain simulation animation graphics output. Using the wind tunnel test data for the project provided by the wind tunnel consultant as an input, analytical simulations investigate the performance of the damping system for the 1-year, -year, 1-year, and -year return wind storms. 1 June 27

Time Domain Analysis Simulations As wind action fluctuates with time, so does the behavior of the structure. The time domain simulations are an important part of the design process, since wind forces, building responses, and damping system motions are not constant with time. Referring to the chart in Figure 2 (see page 1), the red line indicates a threshold, below which the liquid behavior in a can become highly non-linear. It is important to account for the non-linear behavior of the during the design stage by using advanced time domain analysis techniques. Figure 4: Single-Axis Scale Model Performance Test: For fine-tuning design parameters; ensuring maximum possible damping is achieved in one direction. Time domain simulations are performed predicting the actual non-linear interaction between the moving structure under fluctuating wind loads and the moving mass (the sloshing water) in the damping system. Using the wind tunnel test data for the project provided by the wind tunnel consultant as an input, analytical simulations were used to investigate the performance of Tuned Sloshing Damper for the 1-year, -year, 1- year, and -year return wind storms. This ensured that the peak loads on the tank walls and screens, as well as peak water wave amplitudes and damping levels were accurately predicted for design purposes. This approach can also be used to predict the Ultimate State Design loading for the damper/structure interface where non-linearity at higher excitation levels requires better assessment of appropriate load factors. This makes sense when considering that the has several hundred tons of moving mass positioned at the top of the building. Visual animation-style time domain a- nalysis results can be provided. These graphics are often helpful to the design team to visualize and understand the building time response and damping system action. Figure 3 (see page 1) is from a project where such animations were provided. Figure : Dual-Axis Scale Model Shake-Table Performance Test: For fine-tuning design parameters; ensuring maximum possible damping is achieved in two directions simultaneously. Scale Model Performance Tests As the New York projects progressed into Detailed Design and Construction Documents, scale models of the tanks were developed and tested to fine-tune the damper and to ensure optimal performance at the specified return period. The tests were performed on a shaketable that simulated the wind-induced motions of the structures in which the s were to be installed. Figures 4 and show scale models test for two types of s. Figure 4 is for a singleaxis. This type of is designed so that the sloshing action of the liquid is tuned in only one direction, so that effective supplementary damping can enhance building performance for a singular direction of motion. This is useful when building responses acting in one principal direction are the highest contributor to overall building motions. In this case, the used static screen elements installed within the moving water to generate turbulence, and thus a means for energy dissipation (damping) within the. Figure is of a dual-axis scale model. In contrast to the one-directional, the dual-axis can enhance the damping performance in two directions simultaneously. Full Scale Model Scale 1:9 Parameter Imperial Metric Imperial Metric Length (L v ) 26.247 ft 8. m 2.916 ft.889 m Width (L x ) 23.186 ft 7.67 m 2.76 ft.78 m Nominal Water Depth 3.2 ft.93 m.339 ft.13 m Tank Depth 14. ft 4.267 m 1.6 ft.474 m Nominal fy Frequency.18 Hz.18 Hz.6 Hz.6 Hz Nominal fx Frequency.28 Hz.28 Hz.62 Hz.62 Hz Upper Sweep Frequency.344 Hz.344 Hz 1.31 Hz 1.31 Hz Lower Sweep Frequency.83 Hz.83 Hz.2 Hz.2 Hz Minimum Floor/ Table Amplitude Maximum Floor/ Table Amplitude Low Frequency Low Amplitude Peak Force Low Frequency Low Amplitude Peak Force Summary of Test Parameters: Full-Scale and Model-Scale In geographic regions where seismic design is also required, the time domain simulations using earthquake ground motions are used to check the performance of damping system and to determine the loading produced between the and the structure. For this purpose, many modes of structural vibration need to be examined. The bi-directional on this project used cruciform-shaped, static posts suspended into the moving water as the means to generate turbulence, and thus energy dissipation (damping)..7 ft.23 m.8 ft.3 m.86 ft.246 m.9 ft.27 m 481 lbf 218 N 7 lbf 3 N 3282 lbf 1347 N 42 lbf 18 N Table 1: Test parameters comparing characteristics of a full-scale in the building to the model-scale tested in the laboratory. 16 June 27

Figure 6: Close-up view of scale model damping screens. Load cells are used to measure shear forces and drag loads on the screens from the moving waves. The shake-table test was arranged to impose horizontal motions on the scale model. The motions imposed on the were sinusoidal, with control over the amplitude and frequency of the oscillations. For the New York projects performed by Motioneering, the total full-scale mass of the s are about 17, kg or 19 tons (with a length of 13.7 meters and width of. meters) for one project, and about 66, kg or 73 tons (with a length of 8. meters and a width of 7.1 meters) for the other project. The model scale required for the shake-table tests was 1:9. This translated to a model dimension of 1. meters in the long-axis (primary testing) direction for one project and.9 meters in the long-axis for the other. The full-scale and model-scale test parameters are summarized in Table 1. The scale model was mounted on a platform suspended by four steel bars from a rigid frame. The purpose of these bars was to carry the vertical load of the tank, while the shear forces were measured with load cells at the joints between the frame and the platform. The vertical displacement of the fluid at the Figure 7: Constructing the atop a new 6 floor residential building in New York City. The tank walls were constructed with cast-in-place poured concrete, since the material and labor to install was easily obtainable. ADVERTISEMENT For Advertiser Information, visit www.mag.org end walls of the tank was recorded, as well as the horizontal displacement of the shake-table to verify the input. The horizontal accelerations of the shake-table were also recorded. Each test consisted of a frequency sweep, where lower and upper bounds, the amplitude of excitation, and number of cycles and time interval at each frequency were specified. At each frequency, the maximum vertical,. 17 June 27

displacement of the fluid surface at the end walls of the tank was recorded. The resulting maximum amplitude versus frequency plot was used to establish the natural frequency of the system (see Figure 6, page 17). The tests were an important part of the design process. Necessary information was obtained for the detailed design of the tank, such as hydrostatic and hydrodynamic forces on the tank walls and ceiling during serviceability and design wind events. The tests also Figure 8: Damping Screen installation inside a provided valuable information to: Tank. Screen geometry is designed for ease of fabrication (a) optimize the porosity of the and installation. screens that are used to create local flow damping and energy dissipation, (b) only means for water loss is through evaporation (which is minimal in an enclosed tank). refine the predictions of wave amplitudes that generate shear forces and screen drag loads, At the time of writing this article, and (c) optimize screen or vane selection. construction for the two residential projects This ensured that the design of the tank and in New York was ongoing. Figures 7 (page 17), screens was safe and the performance objectives were 8 and 9 show some of the construction work. achieved. Construction The General Contractor team performed construction of the s. The tank walls were constructed with cast-in-place poured concrete, since the material and labor to install was easily obtainable. A waterproofing membrane was used to seal the tank walls. Since the top of the tank is usually dry, the damping louvers or screens were anchored to the tank roof and suspended into the water in the tank. Automatic water level monitoring was provided using a standard float-type sensor and water supply make-up solenoid valve. The need for water level replenishment is generally infrequent, since the Figure 9: Damping Screens are fastened to the tank roof, avoiding piercing of the waterproofing membrane. Commissioning Once the construction of the s is completed and the site is ready for commissioning, then final building motions (using accelerometers) are measured using our portable data acquisition equipment. The fundamental building frequencies are determined using FFT analysis of the acceleration data. Final adjustment of the water level is performed to tune the tank to the optimal frequency, thus matching the building frequencies for best possible damping performance. As with any building system, periodic visual inspections are recommended as part of a routine maintenance plan. Summary A range of different types of Supplementary Damping Systems (SDS) can be used to enhance the damping capabilities of a structure. This article has focused upon the design and implementation of one type of passive damping system the Tuned Sloshing Damper (). These types of damping systems are an effective means to reduce dynamic effects by increasing the structure s ability to absorb the energy imparted to it from external excitations. A is an efficient SDS option for structures with a moderate need for additional damping. For a typical mid-rise to high-rise structure, total effective damping levels of 3% to 4% of critical can often be achieved. s are attractive due to their qualities of simplicity, low cost and dependability with little or no maintenance. Other alternative and very effective damping options also exist, some of which will be discussed in future articles in. Scott Gamble, P.Eng., joined Motioneering in 24 as Vice President. Before coming to Motioneering, Scott gained 23 years of experience with Motioneering s sister company, RWDI, providing consulting services for clients. Mr. Gamble was awarded the Gzowski Gold Medal for Best Technical Paper, 199 by the Canadian Journal of Civil Engineering, and has contributed to the National Building Code of Canada provisions for snow loading of large roofs and arched roofs. He can be reached via email at scott.gamble@motioneering.ca. Jamieson K. Robinson, P.Eng., is a Senior Specialist for Business Development and Project Management for Motioneering and RWDI. His experience has taken him through managing many of the major damping system design and implementation projects for the firm. He can be reached via email at jamieson.robinson@motioneering.ca. Bujar Myslimaj, Ph.D., P.Eng., is a Senior Specialist at RWDI Inc., Guelph, Ontario, Canada. His experience includes research and consulting in earthquake engineering, nonlinear response of structures, windinduced loading and structural response control. He published and presented several research and technical papers in European, Japanese and International journals and conferences. He can be reached via email at bujar.myslimaj@rwdi.com. 18 June 27