Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Similar documents
A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings

A FIELD STUDY OF AIRFLOW IN MID TO HIGH-RISE MULTI-UNIT RESIDENTIAL BUILDINGS

airflow in to, out of, and within buildings. These airflows are resisted by the airtightness of building elements including the exterior enclosure and

Airflow in Mid to High-rise Multi-Unit Residential Buildings

BUILDING CODE BULLETIN

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

Using Air Flow Modelling Software to Predict Airtightness Improvements in a High-Rise Residential Building: A Case Study

ASHRAE 62.2: What s New in 2016

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5)

ASHRAE 62.2: What s New in 2016

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

EVALUATING THE ENERGY SAVINGS OF HIGH PERFORMANCE BUILDING ENCLOSRE RETROFITS Brittany Hanam, MASc, P.Eng. Graham Finch, MASc, P.Eng.

Illinois Sustainable Technology Center, University of Illinois at Urbana-Champaign

Spending Through the Roof: Tall Building Energy Wasted Through Passive Vents. Building Energy 2017 A presentation by: Jamie Kleinberg & Robin Neri

Can you Believe Energy Savings Forecasts

7 AIR LEAKAGE TESTING OF INDIVIDUAL SUITES IN MULTI UNIT RESIDENTIAL BUILDINGS

Revisions to the Residential Standards and ACM Calculations. June 13, 2007 Bruce Wilcox, P.E.

Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA

12/20/2010. NIST Capabilities/Program Opportunities for Manufactured Housing what s up in Gaithersburg OUTLINE. NIST IAQ and Ventilation Group

Influence of Stack Effect on Ventilation in a High-rise Residential Building

A New Paradigm for the Design of Sustainable Buildings

Balancing the Control of Heat, Air, Moisture, and Competing Interests

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard.

Deep Energy Retrofit of a HighRise MURB

Reducing Air Leakage Through Envelope Retrofits: Does Your Building Suck?

Stack Pressure + Wind Pressure + Holes = Bigger Leak. Air Leakage in Commercial & Multi-Family Buildings. Contents. Stack Pressure + Holes = Leaks

Mark Lawton, P.Eng., FEC. Airtightness in Buildings A Canadian History June 2017

ACHIEVING HIGH-PERFORMANCE MULTI-UNIT RESIDENTIAL BUILDINGS: THE OPPORTUNITIES

VENTILATION STRATEGIES AND MEASUREMENT TECHNIQUES 6th AIC Conference, September , Netherlands

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

USE OF MULTI-ZONE AIR FLOW SIMULATIONS TO EVALUATE A HYBRID VENTILATION SYSTEM. Åke Blomsterberg 1, Tomas Johansson 1.

Passive House Northwest AIA CEU Provider

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont

Advanced Ventilation for Residential applications FBC Res 2010.

Adhered Veneers and Inward Vapor Drives: Significance, Problems and

Adhered Veneers and Inward Vapor Drives: Significance, Problems and

Good indoor air quality (IAQ) management has become paramount in the construction industry as study

Infiltration simulation in a detached house empirical model validation

The Importance of Slab Edge & Balcony Thermal Bridges

A, B, C, D VENTILATION SYSTEMS: COMPARISON

Insight. The Hollow Building. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE

Using Compartmentalization to Mitigate the Impacts of Stack Effect in Tall Residential Buildings

Controlling Air Leakage In Tall Buildings

Energy Efficiency Requirements 9.36

A Method for Modifying Ventilation Airflow Rates to Achieve Equivalent Occupant Exposure

Welcome to this continuing education seminar. This is the first of three parts of the Building Enclosure Fundamentals series.

E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings

A Performance Based ENERGY STAR Homes Program: The Wisconsin ENERGY STAR Homes Perspective

2012 Fiscal Impact International Mechanical Code

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

Airtightness Testing in Large Buildings by John Straube

Proposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality

CSC Victoria Air Barriers and Airtightness Testing for Large Buildings CSC VANCOUVER ISLAND CHAPTER, VICTORIA, BC

Chapter 8: Indoor Environmental Quality

MOISTURE BUFFERING AND VENTILATION STRATEGIES TO CONTROL INDOOR HUMIDITY IN A MARINE ENVIRONMENT: A FIELD EXPERIMENTAL STUDY

County of Yolo Development Services Building Inspection Division

Impact of airtightness on the heat demand of passive houses in central European climate

ASHRAE and Indoor Air Quality

Where,h(t)the indicial response of thermal flow rate, B 0 the

Informed Mechanical Design Through Tested Air Leakage Rates

EXPERIMENTAL AND NUMERICAL STUDY OF SMOKE CONDITIONS IN AN ATRIUM WITH MECHANICAL EXHAUST

WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia

BUILDING ENCLOSURE DESIGN GUIDE WOOD FRAME MULTI-UNIT RESIDENTIAL BUILDINGS. Summary. 1. Introduction

A PREDICTIVE METHOD TO DETERMINE THE LEAKAGE AREA NEEDED IN RESIDENCES FOR IAQ CONTROL BY INFILTRATION

How We Obtained LEED Certification pertaining to the Indoor Environmental Quality Category. Ron Fields, CAFS, NCT General Dynamics C4 Systems

2014 British Columbia Building Code Changes

Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial Buildings

Underf loor For Schools

Rehabbing/Restoring Vacant Buildings. Richard Reilly, LEED AP, BPI BA. EP & HHE, HES Assessor Energy Programs Manager

AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL

The Importance of Slab Edge & Balcony Thermal Bridges

The Palestra Building London, England

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Welcome to this continuing education seminar. This is the first of two parts of the High- Performance Building series.

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

INFLUENCE ANALYSIS OF STACK EFFECT ON ODOR DISPERSION FROM UNIT TO CORE IN THE HIGH-RISE RESIDENTIAL BUILDINGS. South Korea METHOD

Indoor Air Quality. Dr. Iain S. Walker NSF BEST Center National Workshop January 8, 2015

CASE STUDY. Two Dogs and Two Cats Insufficient Air Exchange with High CO2

Draft PDS-02. BSR/RESNET/ICC Addendum A-201x

Work Package 2: Performance of naturally ventilated buildings

ResVent ASHRAE and Application for the iphone, ipad, and ipod touch. R.J. Karg Associates

Water Bottling Facility

Validation of Numerical Modeling of Air Infiltration through Building Entrance Doors

Measured Change in Multifamily Unit Air Leakage and Airflow Due to Air Sealing and Ventilation Treatments

Work Package 2: Performance of naturally ventilated buildings

Overview of Presentation. Airflow Control: Why. Airflow Control: what kind?

Pinoleville Pomo Nation Sustainable Home: A case study of energy modeling on sustainable design

Analysis of Heat Gain in Computer Laboratory and Excellent Centre by using CLTD/CLF/SCL Method

Energy Modeling of Dedicated Outdoor Air Systems for a Small Commercial Pilot Project

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949)

Assessing the Impact of US Housing. Retrofits. Building Carbon Emissions. Building Energy Use. buildingscience.com

Improving the Effectiveness of In-Suite Ventilation Systems with Respect to Cross Contamination and Odour Transmission in MURBs

currently referenced throughout the

BUILDING ENCLOSURE AIR TIGHTNESS TESTING Course Number: BCLUNA018-01P

The Addition of Moisture Transport to the Air Leakage Energy Calculator. Andre Desjarlais Som Shrestha, PhD Oak Ridge National Laboratory

Mechanical Services in Tall Residential Buildings

Estimating the Concentrations of Soil Gas Pollutants in Housing

Building & Ductwork Airtightness Standards

Transcription:

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based ventilation systems are pervasively used to ventilate mid- to high-rise multi-unit residential buildings in North America. This paper provides a summary of a study evaluating the performance of these systems based on an experimental program conducted at a case study building which has undergone an energy efficient building enclosure retrofit. In particular, the efficiency and effectiveness of these systems at providing ventilation air to the zones of the building will be assessed, along with the interaction between the ventilation system and the exterior environment. The experimental program carried out at the case study building includes measurement of airflow rates provided by the make-up air unit, measurement of flow rates between zones of the building using perfluorocarbon tracer methods, and long-term monitoring of pressure differences. Exterior conditions including wind speed and direction, temperature, and relative humidity were monitored using a weather station installed on the roof of the building to allow for evaluation of the interaction between the building and the exterior environment. Pressure equalized airtightness testing was also performed on a sample of suites to measure the airtightness provided by both the exterior enclosure and interior compartmentalizing elements. The results of this extensive experimental program are presented and conclusions are drawn with regards to the interaction of the driving forces of airflow (wind, stack effect, and mechanical ventilation systems) with the physical building to create airflow patterns in mid- to high-rise multi-unit residential buildings. The performance of the corridor pressurization ventilation system is specifically evaluated including discussion of its limited potential for use moving forward due to generally poor measured performance and increasing energy efficiency and indoor air quality expectations. Overall, this study works to improve the understanding of corridor pressurization based ventilation system performance as well as the general understanding of airflow patterns in mid- to high-rise multi-unit residential buildings. This knowledge can then be applied to the design of improved ventilation systems and compartmentalization strategies for these buildings. Effort is made to extend the conclusions of the study to meaningful recommendations for industry. INTRODUCTION Corridor pressurization based ventilation systems are pervasively used to ventilate mid- to high-rise multi-unit residential buildings in North America. This system uses a make-up air unit (MAU), usually located on the roof of the building, to draw fresh air in with a large fan either continuously or on a pre-set schedule. Once the air is drawn into the building, it is distributed to each floor through a large vertical duct usually located in the building core. A grille is provided Lorne Ricketts is a Masters of Applied Science Candidate at the University of Waterloo, Ontario, and a Building Science Research Engineer at RDH Building Engineering Ltd., Vancouver, BC. Dr. John Straube is an Associate Professor at the University of Waterloo and a Principal at Building Science Consulting Inc. in Waterloo, Ontario.

in this duct at each floor to allow air to flow from the duct to the corridor. This flow of air into the corridor pressurizes the corridor relative to the surrounding spaces (thus giving the system its name) and this pressure is intended to force air through intentional gaps below the suite entrance doors and into the suites. Typically these ventilation systems are supplemented with intermittent occupant controlled point-source exhaust fans often located in bathrooms, kitchens, and incorporated into clothes dryers, to exhaust high concentrations of air contaminates. As well as providing ventilation air to the corridors and suites, the pressurization of the corridors relative to the surrounding suites is intended to prevent the flow of contaminates such as tobacco smoke and cooking odors from suites to the corridors and from one suite to another via the corridor. Despite its pervasive use, anecdotal accounts of poor performance and supporting research are common. This paper provides a summary of an ongoing study of the performance of the corridor pressurization based ventilation system at 13-storey multi-unit residential building in Vancouver, BC. The building was originally constructed in 1986, has a gross floor area of approximately 5, m² (54, ft²), and has 37 residential units with an average of 125 m² (1,34 ft²) each. The residents of the building are typically 55 years or older and many spend much of their time within their suites, unlike some condominiums which are occupied for fewer hours per day. The building is ventilated by an MAU on the roof of the building using a corridor pressurization based ventilation strategy. Overall, the case study building is archetypically representative of much of the existing mid- to high-rise multi-unit residential housing stock constructed from the 197 s through 199 s across North America. In the latter half of 213 the building underwent a significant building enclosure retrofit including over-cladding and window replacement. The potential impact of this retrofit on ventilation rates and airflow patterns is considered where appropriate. To evaluate the performance of the ventilation system and its interaction with other drivers of airflow at this case study building, an experimental program was developed and implemented. This program includes: Measurements of airflow between zones using perfluorocarbon tracer (PFT) gas testing Measurements of airflow rates in to the MAU and airflow rates supplied to each corridor Measurements of exterior enclosure and interior compartmentalizing element airtightness using pressure neutralized testing techniques Monitoring of pressure differences between building zones The methodology and results for each of these components of the experimental program are presented in the Experimental Program section of this paper. Conclusions are drawn at the end of the paper based on the compilation of the findings of each of the individual components of the experimental work. These conclusions are then extended to recommendations for the building industry with respect to multi-unit residential building ventilation system design. This paper provides a summary of this research work, and the complete airflow and ventilation component of this study is detailed in Ricketts 214. EXPERIMENTAL PROGRAM The subsequent sections of this paper present the methodology and results for each of the components of the experimental program. First, measurements of the actual airflow (i.e. ventilation) rates are presented, and then measurements of other factors which may impact airflow rates are presented as means of explanation. Perfluorocarbon Tracer Gas Testing Airflow rates between zones of the case study building were measured using the perfluorocarbon tracer gas (PFT) testing method developed by Brookhaven National Laboratory. (Heiser, & Sullivan, 22) (D Ottavio, Senum, & Dietz, 1988) This testing used 7 distinct PFT gasses to tag the air in various suites of the case study building. Because the source release rate is known, and assuming that these gasses are well mixed with the air within a given zone, measurement of the quantity of these gasses in the air of the tagged zones can provide a measurement of the air change rates of the tagged zones as well as of the airflow rates between zones. To measure the concentration of the PFTs in the selected zones,

capillary absorption tube samplers (CATS) were placed in each of the selected zones. These CATS absorb all of the PFT gasses simultaneously and when subsequently analyzed, they provide a time-averaged measurement of the concentration of each of the PFT gasses in the zone in which they were installed. For this testing, the sources and CATS were installed for a period of one week from April th to 17 th, 213 to capture typical occupancy patterns. For reference, the average exterior temperature during this period was 8 C and the average wind speed was 3.3 m/s. The total air flow rates into the suites as determined by the PFT testing are provided in Figure 1. Airflow [L/s] 9 8 7 6 5 4 3 2 5 22 13 31 Lowers ASHRAE 62.1 2 4L/s 5 32 12 33 23 42 33 3 27 11 Upper s Figure 1 Chart showing the total airflow rate from all sources into each of the measured suites (to convert from L/s to cfm multiply by 2.13) 73 12 91 13 57 123 This figure indicates that there is an order of magnitude variation in the ventilation rates of the suites at the case study building. Typically, upper suites are more ventilated than lower suites, and most suites are either over- or under-ventilated compared to modern ventilation standards. (ASHRAE 62.1-2) The cause of this variation is discussed in subsequent sections of this paper. Figure 2 and Figure 3 illustrate the airflow rates to and from adjacent zones for six suites at the case study building as measured as part of the PFT testing. Airflow Rate [L/s] 9 8 7 6 5 4 3 2 Flow to suites above and below only measured for 32 and 13. 31 32 33 11 12 13 Corridor to Right to Left Above Below Exterior Parking Garage *Some results manually corrected. Figure 2 Chart showing source of airflow into suites for six suites at the case study building (to convert from L/s to cfm multiply by 2.13)

Airflow Rate [L/s] 9 8 7 6 5 4 3 2 Flow to suites above and below only measured for 32 and 13. 31 32 33 11 12 13 Corridor to Right to Left Above Below Exterior Parking Garage *Some results manually corrected. Figure 3 Chart showing airflow out of suites for six suites at the case study building (to convert from L/s to cfm multiply by 2.13) Consistent with Figure 1, these figures also show significantly higher airflow rates into and out of the upper suites compared to the lower suites. Generally, this is due to higher airflow rates into the suite from the corridor (ventilation) and higher airflow rates out of the suites to the exterior. This finding is consistent with stack effect which would tend to cause exfiltration at the top of the building from the corridor through the suites to the exterior. This may also be caused by proximity to the make-up air unit and increased magnitude of wind on upper floors. It is also apparent that the lower suites ( 31, 32, and 33) receive a significant proportion of the airflow into the suites from the parking garage. Parking garages often have relatively high concentrations of harmful contaminates including particulates, carbon monoxide, and various hydrocarbons from vehicle exhaust; consequently, airflow from the parking garage to occupied spaces of the building is a significant health concern. Overall, the PFT testing at the case study building found that typically the upper suites are over-ventilated and the lower suites are under-ventilated compared to modern ventilation standards, and that there is an order of magnitude variation in the ventilation rates. These findings indicate that the corridor pressurization ventilation system at this building is not effectively or efficiently ventilating the suites. The cause of these airflow patterns is discussed in more detail in subsequent sections. Make-Up Air Unit Airflow Measurements The airflow patterns determined by the PFT testing may be as a result of improper operation of the MAU. To evaluate the performance of the MAU the intake airflow rate was measured using a custom made powered flow hood apparatus, and the airflow rates supplied to each corridor was measured using a balometer. The MAU flow measurement was correlated with a pitot tube pressure measurement and this pressure was monitored hourly and then converted to flow rate. Based on this monitoring, the flow rate of the MAU was found on average to be very similar to the rated flow rate of 1,56 L/s (3,3 cfm) at a static pressure of 25 Pa. Figure 4 provides the measurements of the airflow into the corridors from the MAU.

Floor Number 14 12 8 6 4 2 25 5 75 125 15 Flow Rate [L/s] Fire Damper noted to be closed on Floors 4, 8, & 12. Pre Retrofit (21 C) Total = 593 L/s Post Retrofit (6 C) Total = 559 L/s Post Retrofit (16 C) Total = 58 L/s Pre Retrofit (21 C) Post Retrofit (6 C) Post Retrofit (16 C) Figure 4 Graph showing measured airflow rates into each corridor through the MAU grilles (to convert from L/s to cfm multiply by 2.13) This figure shows that the MAU is delivering significantly more ventilation air to the upper floors than to the lower floors, which is consistent with previously discussed findings indicating that the suites on upper floors are more ventilated than the suites on lower floors. Also, the total airflow provided to the corridors is only approximately 37% of the intake airflow rate, so the remaining airflow must leak out of the MAU duct prior to being supplied to the corridors. This loss of air from the duct is a significant inefficiency in the system. Airtightness Testing Airtightness resists airflow and it is possible that the distribution of airtightness of the exterior enclosure and of interior compartmentalizing elements is impacting the airflow patterns at the case study building. To evaluate the role of airtightness in creating the measured airflow patterns, pressure-neutralized multi-point fan depressurization/pressurization testing was performed. This technique uses multiple fans to sequentially develop and neutralize pressure differences across the exterior enclosure and interior compartmentalizing elements thereby determining the airflow resistance characteristics (i.e. the flow coefficient (C), and the flow exponent (n)) of each of the zone boundaries. This type of testing was performed on 3 corridors (Corridors 3, 9, and 11). The airflow resistances of the corridor compartmentalizing elements were determined by sequentially sealing openings to the corridors (i.e. suite entrance doors, elevator doors, stairwell doors, etc.). The average result of the 3 corridor tests is presented in Figure 5.

Figure 5 Chart showing the average distribution of airtightness for the three tested corridors Figure 5 illustrates that when the corridor is equally pressurized relative to adjacent zones, only approximately 2% of the airflow paths are directly to the adjacent suites through the suite entrance door. As the pressurized corridor ventilation system relies on pressurization of the corridor to deliver ventilation air to the suites, this finding indicates a significant potential for loss of ventilation air to other adjacent spaces such as the stairwells and elevator shafts, and consequently a significant inefficiency in the system. Additionally, large flow paths to zones other than the adjacent suites make controlling pressure differences more difficult as the zones are less compartmentalized relative to each other. Pressure Monitoring A long-term monitoring program was implemented as part of the experimental program at the case study building. This monitoring included hourly measurements of pressure differences between various zones of the building as well as across the exterior enclosure at locations on each elevation near the top of the building and near the bottom of the building. As pressure differences drive airflows, these measured pressures provide an indication of the drivers that are creating the measured airflow patterns. Stack effect was found to have a relatively large impact on the building pressure regime despite the relatively moderate climate of Vancouver, BC. Literature commonly discusses stack effect across the exterior enclosure, and the airtightness testing indicates that approximately half of the stack effect pressures should act across the exterior enclosure post-retrofit because the exterior enclosure and suite entrance doors have similar airtightness. However, the pressure measurements indicate that approximately 69% of stack effect acts across the boundary between the corridors and the adjacent suites. This is thought to be due to the use of operable exterior windows which, when open, provide large airflow paths relative to the airflow paths through rest of the exterior enclosure. Figure 6 shows the average pressure difference from the corridor to the adjacent suites for three upper floors and three lower floors. (Positive indicates the corridor is pressurized relative to the adjacent suites.)

Pressure Difference [Pa] 2 15 5 5 25 2 15 5 5 Exterior Temperature [ C] Floor 2 Floor 3 Floor 4 Floor Floor 11 Floor 12 Temp WS' [ C] Figure 6 Graph showing the average pressure difference from the corridors to the adjacent suites for six floors at the case study building This figure clearly illustrates that on upper floors the pressure of the corridor increases relative to the adjacent suites during colder periods of the year; while on lower floors there is little to no fluctuation. This finding is consistent with stack effect. Importantly the variation in the pressure on upper floors is approximately to 15 Pa, and the MAU was determined to pressurize the corridor by approximately 5 to Pa. Because these pressure differences are of similar magnitude and acting in the same location, it is likely that stack effect significantly affects ventilation rates within the case study building and is likely a major cause of the measured ventilation patterns. Wind is another cause of pressure differences at buildings, and as one would expect, it was found to create the peak pressure difference across the building enclosure; however, typically these pressure acted for relatively short time periods. Wind also created the peak pressure differences across interior elements which could cause transfer of air contaminates between adjacent suites. Overall, pressures created by wind were found to be highly variable and difficult to predict. CONCLUSIONS & RECOMMENDATIONS A study was conducted at a case study building to evaluate the performance of the corridor pressurization based ventilation system. This study included measurements of airflow rates, airtightness, and pressure differences. Overall, the pressurized corridor based ventilation system at the case study building was found to unevenly distribute ventilation air to both the corridors and suites of the building with upper zones receiving significantly higher ventilation rates than lower zones, and most suites being significantly over- or under-ventilated. This poor performance is in part likely due to significant leakage of ventilation air along the ventilation flow path both from the duct (approximately 6% leakage) and from the corridor (approximately 8% of flow paths not directly to the suites). Effective distribution of ventilation air in the building is also significantly impacted by stack effect, and, on a shorter time-scale, by wind. These driving forces were measured to create pressure differences of similar (and frequently greater) magnitude as those created by the mechanical ventilation system. Furthermore, operable windows can significantly reduce the airtightness of the exterior enclosure such that pressures created by wind and stack effect frequently act across interior

compartmentalizing elements such as suite entrance doors. In the case of stack effect, approximately 69% of the theoretical stack effect pressure difference was measured across the suite entrance doors. Given that these driving forces of airflow frequently act across interior compartmentalizing elements and are of similar magnitude to mechanically induced pressure differences, there is significant potential for overwhelming of the mechanically induced pressures and consequently for alteration of airflow rates and direction. Changes in the flow rates and direction due to stack effect and wind can lead to the under- and over-ventilation that was measured and can also cause contaminate transfer between zones. As the elimination of operable windows and doors is not practical for residential buildings, these types of buildings should be designed to accommodate their operation. Consequently, interior compartmentalizing elements between suites and between the suites and the corridor should be relatively airtight such that the operation of windows in one suite does not significantly impact airflow and ventilation rates in other parts of the building. Additionally, floors and vertical shafts should be sealed to reduce the effective stack height and limit the development of associated pressure differences. If suites are to be compartmentalized relative to adjacent to zones, the corridor pressurization based ventilation system is no longer a feasible option for ventilation of the suites, and the ventilation air would need to be ducted directly to each suite or supplied by in-suite systems. A significantly smaller corridor pressurization system could potentially be used to ventilate the corridors and could also help control contaminate transfer by pressurizing the corridors. This system would require significantly less airflow and be more predictable due to the compartmentalized nature of the corridors. Overall, the case study building examined in this study is a typical multi-unit residential building, and many of the findings and conclusions are broadly applicable to multi-unit residential building ventilation system design. Based on the findings of this study, corridor pressurization based ventilation systems often do not appropriately or efficiently ventilate and control airflow in high-rise multi-unit residential buildings, and furthermore do not likely provide the potential to do so. Consequently, alternative ventilation designs should be used for these buildings and these systems would likely require compartmentalization of the suites and direct supply of ventilation air to each suite. ACKNOWLEDGMENTS This project was completed with the support of the following funding partners: Homeowner Protection Office (HPO) branch of BC Housing, BC Hydro, Fortis BC, NRCan, the City of New Westminster, the City of North Vancouver, the City of Richmond, the City of Surrey, Enbridge Gas, and the City of Vancouver. NOMENCLATURE IAQ = Indoor Air Quality MAU = Make-up Air Unit PFT = Perfluorocarbon Tracer REFERENCES ASHRAE. 2. ANSI/ASHRAE Standard 62.1-2: Ventilation for Acceptable Indoor Air Quality. Atlanta: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. D Ottavio, T., Senum, G., Dietz, R. 1988. Error Analysis Techniques for Perfluorocarbon Tracer Derived Multizone Ventilation Rates. Building and Environment Vol. 23, No. 3: 187-194. Heiser, J., and Sullivan, T. 22. The Brookhaven National Laboratory Perfluorocarbon Tracer Technology: A Proven and Cost-Effective Method to Verify Integrity and Monitor Long-term Performance of Walls, Floors, Capps, and Cover Systems. Upton: Brookhaven National Laboratory. Ricketts, L. 214. A Field Study of Airflow in a High-rise Multi-unit Residential Building. MASc Thesis at University of Waterloo.