Building Energy Management through a Distributed Fuzzy Inference System

Similar documents
Smart control of Air conditioning system for thermal comfort

Indoor Building Fuzzy Control of Energy and Comfort Management

DESIGN AND SIMULATION OF INTELLIGENT GREENHOUSE CLIMATE CONTROLLER

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES

Design of A hierarchical Sugeno Fuzzy Controller for HVAC in Large Buildings

Fuzzy Logic based Short-Term Electricity Demand Forecast

Control System Design for HVAC System and Lighting System using PID and MPC Controller

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Simulation and Design of Fuzzy Temperature Control for Heating and Cooling Water System

Greenhouse Air-Temperature Modelling and Fuzzy Logic Control

An Intelligent Approach of Achieving Demand Response by Fuzzy Logic based Domestic Load Management

intelligent Building Energy Management System (ibems) Stefano Mangili Schneider Electric Spa 25/05/2016

SIMALATION AND CONTROL SYSTEM DESIGN OF THERMAL CONDITIONS IN BUILDING USING ACTIVE AND PASSIVE RESOURCES

A DEVELOPMENT OF A LIGHTING CONTROLLER USING SMART SENSORS

3rd International Conference on Machinery, Materials and Information Technology Applications (ICMMITA 2015)

ICMIEE-PI A Case Study of Appropriate Supplier Selection of RFL industry by using Fuzzy Inference System (FIS)

A Comparison of Perturb & Observe and Fuzzy-Logic Based MPPT Methods for Uniform Environment Conditions

A framework of fuzzy control-based intelligent control system for greenhouse

A systematic approach of integrated building control for optimization of energy and cost

The energy benefits of View Dynamic Glass

A MODEL-BASED METHOD FOR THE INTEGRATION OF NATURAL VENTILATION IN INDOOR CLIMATE SYSTEMS OPERATION

NEURO-FUZZY CONTROLLER ALGORITHM FOR OBTAINING MAXIMUM POWER POINT TRACKING OF PHOTOVOLTAIC SYSTEM FOR DYNAMIC ENVIRONMENTAL CONDITIONS

Occupancy-Based Control of Indoor Air Ventilation: A Theoretical and Experimental Study

INFLUENCES OF LIGHTING CONTROL AND NATURAL VENTILATION ON ENERGY USE AND OVERHEATING FOR A DAY-LIT INDUSTRIAL BUILDING

Integration of BIPV systems and load management. Citation The International Conference on Electrical Engineering 2009.

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

Emulation of a Wind Turbine with a DC Motor controlled by Fuzzy Logic controller

Web Objects Based Energy Efficiency for Smart Home IoT Service Provisioning

ADAPTIVE NEURO FUZZY INFERENCE SYSTEM FOR MONTHLY GROUNDWATER LEVEL PREDICTION IN AMARAVATHI RIVER MINOR BASIN

FUZZY MODELING OF RECAST LAYER FORMATION IN LASER TREPAN DRILLING OF SUPERALLOY SHEET

FIS Based Speed Scheduling System of Autonomous Railway Vehicle

CASE STUDY OF APPLYING DIFFERENT ENERGY USE MODELING METHODS TO AN EXISTING BUILDING

DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing Quality of Power Transformer Insulation Oil

Daylight Savings Calculation Technique for Smart Buildings

SMART CONTROL FOR NATURAL VENTILATION HOUSE

ENERGY CONSERVATION IN BUILDINGS AND COMMUNITY SYSTEMS. Technical Report. P. Michel & M. El Mankibi ENTPE DGCB LASH France

Procedia - Social and Behavioral Sciences 109 ( 2014 )

Testing of a Tracer Gas Based Measurement Procedure to Assess Air Change Rates in Buildings

Analysis of Boiler Operational Variables Prior to Tube Leakage Fault by Artificial Intelligent System

Design of integrated control system for indoor environment*

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Building power control and comfort management using genetic programming and fuzzy logic

FACILITIES' CLOSENESS RELATIONSHIPS. The objective function in site layout planning is to minimize the total travel distance

Leveraging Smart Meter Data & Expanding Services BY ELLEN FRANCONI, PH.D., BEMP, MEMBER ASHRAE; DAVID JUMP, PH.D., P.E.

The effect of shading design and control on building cooling demand

Development of integrated building control systems for energy and comfort management in intelligent buildings

Thermal, Visual and Energy Performance in LEED buildings: Two Case Studies

additional cooling energy consumption. Because the thermal resistance of windows has always been a weak point, even with vacuum glass or low-e glass,

SECTION DESIGN REQUIREMENTS BASIS OF DESIGN GENERAL INFORMATION

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

Model Home 2020 project i CarbonLight Homes

An Assessment of Thermal Comfort in Hot and Dry Season (A Case Study of 4 Theaters at Bayero University Kano)

NORTH PROJECT AQABA, JORDAN. Recommended Energy Efficiency and Renewable Energy Measures for the Premium Villa

ScienceDirect. Simulation based mixed mode building design

TOWARDS SEAMLESS INTEGRATION OF MODEL-BASED ENERGY PERFORMANCE SIMULATION AND MULTI-OBJECTIVE OPTIMIZATION TOOLS

Energy Center Structure Optimization by using Smart Technologies in Process Control System

ENERGY EFFICIENCY IN BUILDINGS AND COMMUNITIES

Indoor Thermal Environment in Residential Buildings at Different Micro-Climates in Malaysia

Assessment of Indoor Climate: Learning from Buildings

A FUZZY-BASED MODEL TO DETERMINE CUI CORROSION RATE FOR CARBON STEEL PIPING SYSTEMS

Design of Fuzzy Logic based Controller for Energy Efficient Operation in Smart Buildings

HEATING LOAD PREDICTIONS USING THE STATIC NEURAL NETWORKS METHOD. S.Sholahudin 1, Hwataik Han 2*

Knowledge-Based Holistic Energy Management of Public Buildings

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

Giuseppe Giordano Founder & CEO

10 tips from your Architect

Building Energy Modeling Using Artificial Neural Networks

University of Reading

Comparative Performance of Internal Venetian Blind and Roller Blind with Respects to Indoor Illumination Levels

Temperature Policy Bentley University Academic Year 2016/2017 0

Fuzzy Logic Approach in Controlling the Grid Interactive Inverters of Wind Turbines

Great Ocean Rd Ice Creamery

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

BUILDING INTEGRATED VENTILATION SYSTEMS MODELLING AND DESIGN CHALLENGES

Daylight has been a primary source of lighting in buildings. Daylighting improve indoor environmental quality and visual comfort. Moreover, it reduces

FUZZY LOGIC CONTROLLER DEPLOYED FOR INDOOR AIR QUALITY CONTROL IN NATURALLY VENTILATED ENVIRONMENTS

Key Technologies of Intelligent Control of Agricultural Greenhouse

METHOD FOR VALIDATION OF STATISTICAL ENERGY MODELS. Department of Mechanical Engineering, Dalhousie University Halifax.

DEVELOPMENT OF AN INNOVATIVE ENERGY MANAGEMENT SYSTEM FOR UNIVERSITY CAMPUSES

Precision energy management for perfected built environments

Estimating Industrial Building Energy Savings using Inverse Simulation

A Building Commissioning Overview. Presented by: Goetting & Associates Commissioning

ASHRAE/USGBC/IES Standard What Does It Mean for Commissioning Providers?

Paul Ehrlich, PE Ira Goldschmidt, PE

Average Span & Comment Ratio for Maintenance of Model Using Fuzzy Technique

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

RFID, Web-Based, and Artificial Intelligence Integration in Facilities Management

DEVELOPMENT OF A COMPARISON-BASED CONTROL STRATEGY OF ELECTROCHROMIC GLAZING FOR THE MANAGEMENT OF INDOOR LIGHTING AND ENERGY EFFICIENCY

Verified net Zero Energy Building with air source heat pumps for SME

An Experimental Study for the Evaluation of the Environmental Performance by the Application of the Automated Venetian Blind

LEED LEED LEED. Earth Tech, Inc. Earth Tech, Inc. A Firm With Experience. A Firm With Experience. Operational Efficiencies & Resources Preservation

SAGEGLASS VARIABLE TINTED GLAZING INPUT SHEET FOR DIAL+ SOFTWARE

About the editors... List of contributors... Preface... Foreword... Acknowledgments...

Model Predictive Prior Reinforcement Learning for a Heat Pump Thermostat

DIRECTIVE 15H-9 Issue date: October 2018 COMMISSIONING

Artificial Neural Network Modeling of an Inverse Fluidized Bed Bioreactor *RAJASIMMAN, M, GOVINDARAJAN, L, KARTHIKEYAN, C

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT

Fuzzy Logic Driven Expert System for the Assessment of Software Projects Risk

Assessments of indoor environmental quality on occupant satisfaction and physical parameters in office buildings

Transcription:

Building Energy Management through a Distributed Fuzzy Inference System Pervez Hameed Shaikh #1, Nursyarizal Bin Mohd Nor #1, Perumal Nallagownden #1, Irraivan Elamvazuthi #1 # Universiti Teknologi Petronas, Bandar Seri Iskandar 31750, Perak, Malaysia 1 engr.pervezhameed@gmail.com Abstract Buildings consume significant world s energy resources, approximately 32% of the total primary energy. The rapid depletion of energy resources, has imparted researchers to focus on energy conservation and wastage. The next generation of smart buildings is becoming a trend to cope with the needs of energy and environmental ease in buildings. This advances the intelligent control of building to fulfill the occupants need. Intelligent system control for sustainable buildings is dynamic and highly complex. Building information accuracy with an effective controller scheme is a challenging task. This paper presents the fuzzy control system architecture (FCSA) for resolving the conflict of maintaining the inhabitants comfort index and the energy consumption in buildings. It also infers the graphical relationship between energy consumption and comfort parameters. With a distributed fuzzy inference system (FIS), control has been developed for temperature, air quality and artificial lighting comfort parameters. Model simulation has been carried out and control factors have been discussed. The FIS models have also been validated with implication of change function. The presented control system is capable of achieving energy conservation in the buildings. Keyword-Fuzzy control, Energy management, Comfort management, Energy consumption, Sustainable buildings I. INTRODUCTION The alarming environmental threats and the depletion of fossil resources have increased the awareness of the need to decrease energy consumption for sustainable energy development [1]. Energy efficiency, thus, has become a requirement inside buildings for both climate preservation and economic stability. Around 80-90 % of inhabitants spend their utmost time in buildings [2]. Therefore, an occupant s satisfaction is highly dependent on the indoor ambient comfort. The building energy management is primarily concerned in attaining the maximum indoor environment comfort in contrast tp the least energy consumption. Attainment of indoor comfort, keeping in view the consumer s preferences, is an important aspect. This will certainly influence the efficiency of the occupants and ultimately energy consumption. For reduction of power consumption and waste in buildings, an intelligent control system is needed, since energy consumption has been directly related to comfort and ultimately to operational costs. A building s indoor environmental primary comfort factors, according to the consumers preferences are thermal, visual and indoor air quality [3]. Therefore, satisfaction of energy prerequisites in efficient buildings has been focused on by assuring operational requirements with the least possible energy cost and the most environmental protection. An indoor building environment is quite sensitive to variations and will closely follow the change. The nonlinear fuzzy linguistic mapping model of an input data set to a scalar output data will overcome this. A FIS contains four basic blocks: fuzzifier, rule sets, inference engine and defuzzifier. The general architecture is shown in Fig. 1. Initially, an input set of crisp data is accumulated and turned into a fuzzy set utilizing fuzzy linguistic variables and membership functions called fuzzification. An inference is developed based on the rule set and finally, the fuzzy output is mapped to crisp values using the membership function called defuzzification [4]. The study presents the implementation of fuzzy control system architecture (FCSA) using a fuzzy inference system. The control functions employed for attaining energy conservation and improved level of comfort included thermal, visual and air quality as parameters. In a building envelope, the indoor thermal is the temperature [3], visual means the brightness level and the CO 2 concentration represents the air quality; these are regarded to be the main comfort parameters [5]. The user s preferences need to be considered in the design of the controller. This research is primarily focused on building towards the inhabitant s comforts and energy efficiency through actuator control. ISSN : 0975-4024 Vol 5 No 4 Aug-Sep 2013 3236

Crisp Input Rule Base Crisp Output Fuzzifier Defuzzifier Inference Fig. 1. Fuzzy Inference System II. RELATED LITERATURE An easy way to comply with the conference paper formatting requirements is to use this document as a template and simply type your text into it. Primarily, building energy systems have been introduced for the monitoring and control of indoor environmental parameters to abate energy usage and cost. Buildings utilize substantial amounts of energy, predominantly electrical, and emit greenhouse gases (GHG) [6, 7]. Various decision support analysis techniques have been presented comprising optimum choices involving energy, environment, social and financial constraints [8, 9]. A framework for a building energy management system (BEMS) has been anticipated in [6, 10]. The authors considered the targets of enhanced energy efficiency, effective energy cost and the least amount of fossil fuel dependency with reduced emissions. Energy consumption, and a prediction method for data collection of inhabitants activities and their movements along with their frequency was proposed. Furthermore, energy utilization of similar buildings in the same geographic neighborhood was explored in [11]. In [12], fuzzy logic control (FLC) has been developed for visual comfort. An illumination control system has been evaluated in the presence of daylight [13]. Whereas, [14] presented an airflow rate robust control approach. A building s air quality control has been employed with a fuzzy reasoning machine. A 3-D fuzzy model [15] has been deployed to represent overall comfort. The user decision-making model approach has been provided but has not been appropriately combined with comfort preferences. Several complicated control issues have been identified, whereas, real time control systems involve a network of controllers instead of a single unit. The proposed system employs a fuzzy expert system of local control to achieve the overall maximized comfort with less energy usage and waste. The distributed fuzzy controller system has been implemented in a general framework based on agents. Each FIS controller agent is regulated as a function of various sensors. The goal of consumer needs for building environmental comfort and custom adjustment of actuator devices releasing the tension of the manual control task was attained. III. PROBLEM FORMULATION AND METHOD The study aimed at providing an expert control system architecture for automated buildings which requires supply and control of energy keeping in view the interactions between the indoor environment and its residents. To cope with the energy demand of the building, the fuzzy expert system has been employed at an individual control level for sustainability and energy efficiency. The individual controls for each controlled parameter included temperature, illumination and CO 2 concentration. The input for the expert system is the standard comfort range, in which the consumer has the authority to set the desired comfort value. The instantaneous parameter value has been measured with sensors and has been fed back to the expert system for the desired amount of energy required to maintain the comfort. The proposed expert control architecture flow block is depicted in Fig. 2. Inputs (Sensor Values) + Fuzzy Inference _ Model Building Actuator Power Required Sensor (Indoor Environmental Sensor Parameter Measurement) Fig.2. Automated building design structure ISSN : 0975-4024 Vol 5 No 4 Aug-Sep 2013 3237

IV. CONTROL SYSTEM ARCHITECTURE WITH FUZZY A. Heating Ventilation and Air Conditioning Control In maintaining the inhabitants working efficiency and gratification, thermal comfort plays an important role and possesses a high impact. Due to the subjectivity of thermal comfort, it is difficult to a state environmental and personal factor range. This is why the comfort index for thermal, commonly termed as Predictive Mean Vote (PMV), has been majorly established on heating, ventilation and air conditioning (HVAC) schemes. The index has been devised as a user s normal body consciousness. The mean temperature radiance, speed of air, outfit elements and humidity are in direct proportion to the temperature [14]. The PMV index prevails within the range of -3 to +3. This has a variation occurrence in between -0.5 and +0.5, and thus satisfies around 90% of the building dwellers [12]. The thermal comfort index has already been a prime feature in PMV index computation and the building s temperature has generally been specified with [5]. Both heating and cooling techniques are associated with a one unit system actuator. The fuzzy control knowledge base inference consists of two set strategies, one is comfort optimization and the second is energy consumption minimization. The input and output membership functions are depicted in Fig. 3; whereas, the 3-D expert control plot is depicted in Fig. 4. The knowledge base of the FIS system is shown in Table I. ETemp EDTemp PTemp Fig.3. Fuzzy membership input and output functions for temperature. TABLE I Knowledge Base for FIS Temperature Controller E Temp Power Required NL NA NS NE PS PA PL NL NL NS PS PL PL PL PA NA NL NA NE PA PA PL PA NS NL NA NS PS PA PL PA ED Temp NE NL NA NS NE PS PA PA PS NL NL NA NS PS PA PA PA NL NL NA NA NE PA PA PL NL NL NL NL NS PS PA ISSN : 0975-4024 Vol 5 No 4 Aug-Sep 2013 3238

PTemp EDTemp ETemp Fig.4. Fuzzy control surface control plot for temperature. B. Artificial Illumination Control Indoor building envelopes utilise 20-30 % energy in artificial electrical lighting. An attractive dynamic load management potential exists in controlling artificial lighting loads. The measure of the radiance level specifies the interior visual comfort [16]. Therefore, visual comfort provides luminance control in the lighting fixtures [17] measured in Lux. The measurement of glare, wall colour etc. are subjective and challenging parameters. The input and output membership functions are depicted in Fig. 5; whereas, the expert control plot is depicted in Fig. 6. The knowledge base of the FIS system is shown in Table II. TABLE II Knowledge Base for FIS Illumination Controller P required Lighting Small SS BS OK SB Big OFF S REG SB BB ON EL PL Fig.5. Fuzzy membership input and output functions for illumination. ISSN : 0975-4024 Vol 5 No 4 Aug-Sep 2013 3239

C. Ventilation Control Fig.6. Fuzzy control plot for illumination. Air quality control space has been specified with level of CO2 concentration and is predominantly subjective to the concentration of pollutants in the indoor environment [18]. This verily signifies various sources of pollution the existence of the dwellers in the building. Thus, in parts per million (ppm) CO2 concentrations is measured and has been represented as level index for air quality. The computation of power demand for ventilation or an exhaust fan system was done with the fuzzy inference system controller. The computed power then applied to the slave controller, air quality subsystem. In the local fuzzy controller, input is the error of the outdoor natural concentration and the internal set point through the consumer. Thus, the output is utilized for ventilation actuator control with the required electrical power. The input and output membership functions are depicted in Fig. 7, whereas the expert control plot is depicted in Fig. 7. The knowledge base of an FIS system is shown in Table III. TABLE III Knowledge Base for FIS Air-quality Controller CO 2 Concentration LOW SL OK SH BH High P required OFF S REG SB BB ON EAQ PAQ Fig.7. Fuzzy membership input and output functions for air quality. ISSN : 0975-4024 Vol 5 No 4 Aug-Sep 2013 3240

Fig.7. Fuzzy control plot for air quality. V. DISCUSSION OF RESULTS The three distributed fuzzy controllers for temperature, illumination and air quality describe the control output surface. The 3-D plot of temperature in Fig. 3 depicts the actuator power requirement for both the heating and cooling systems combined. When the demand has moved in the positive direction, the cooling system is actuated, whereas, a negative demand activates the heating system to come into operation. The error (E Temp ) displays the direct proportion of the power requirement for both the cooling and the heating systems. Whereas, the error difference (ED Temp ) depicts an inverse proportional relation to the actuator power demand. The developed FIS model for thermal comfort has been validated employing trapezoidal and generalized polynomial based pi functions. The statistical data variance has been observed in Table IV. The deviation of trapezoidal and pi function has been obtained 0.7 and 0.23, whereas, the mean absolute percentage error contained is 6% and 2% respectively. Parameter TABLE 4 FIS validation of thermal comfort Trapezoidal Function Generalized Polynomial Based Pie Function Sum of Squared Error (SSE) 12.29 1.32 Mean Squared Error (MSE) 0.49 0.05 Root Mean Square Error (RMSE) 0.70 0.23 Mean Absolute Percentage Error (MAPE) 0.06 0.02 The actuator power requirement of the lighting fixture shown in Fig. 6 provides a linear pattern of the control system. With a large error range, a steady high actuator power requirement occurs and vice versa with a decreasing error. The developed FIS model for visual comfort has been verified using trapezoidal and difference between two sigmoidal (dsig) functions. The statistical data discrepancy has been observed in Table V. The deviation of trapezoidal and dsig function has been obtained 0.02 and 0.20, whereas, the mean absolute percentage error contained is 7% and 3.7% respectively. Parameter TABLE V FIS validation of visual comfort Trapezoidal Function Difference between two sigmoidal, Function Sum of Squared Error (SSE) 0.01 0.84 Mean Squared Error (MSE) 0.00 0.04 Root Mean Square Error (RMSE) 0.02 0.20 Mean Absolute Percentage Error (MAPE) 0.07 0.37 While for ventilation, as shown in Fig. 7, the actuator requires a low steady power demand with a limited concentration of CO 2 occurrence. Whereas, as the concentration increases, power demand rapidly increases with the minute rise in the concentration. The developed FIS model for air quality comfort has been verified using trapezoidal and generalized bell functions. The statistical data discrepancy has been observed in Table VI. The deviation of trapezoidal and bell function has been obtained 0.04 and 0.08, whereas, the mean absolute percentage error is limited to 3% each. ISSN : 0975-4024 Vol 5 No 4 Aug-Sep 2013 3241

TABLE VI FIS validation of air quality comfort Trapezoidal Generalized Bell Parameter Function Shaped Function Sum of Squared Error (SSE) 0.03 0.11 Mean Squared Error (MSE) 0.00 0.01 Root Mean Square Error (RMSE) 0.04 0.08 Mean Absolute Percentage Error (MAPE) 0.03 0.03 VI. CONCLUSION The comfort index of the inhabitants with regard to the power consumption in order to make a wise decision for energy management within a distributed control level has been shown in this study. An intelligent building control system utilizing fuzzy controller agents has been coordinated with intelligent coordinators. The intelligent FCSA provides an actuator sensor network for decision-making to maintain a balance between the occupant s comfort and the total power usage. The aims of learning and the weighted decision-making of consumer comfort preferences have been achieved to some extent. This will make consumers properly aware to take wise actions for energy consumption. The unforeseen behavioral relation with the used power and comfort has been inferred with the implication of the FIS control system. The inference models for each agent have also been validated with the implication of different membership function. The future work will be carried out on the system optimization, for the grid connected, constrained power supply and the inhabitant s interior environment comfort. ACKNOWLEDGMENT The authors thank and acknowledge Universiti Teknologi PETRONAS for carrying out this extensive research work. REFERENCES [1] Y. Kamiyoshi, T. Nakabe, G. Mine, and H. Nishi, "Construction of energy measuring system in a University for Cluster Energy Management System," in IECON 2010-36th Annual Conference on IEEE Industrial Electronics Society, pp. 2423-2429, 2010. [2] J. Kun, L. Yan and S. Zhen, Y. Yuebin, Energy Management Control Framework of Optimization Control and Operation for Energy Efficient Buildings in ACEEE Summer Study on Energy Efficiency in Buildings, 2012. [3] Z. Wang,, L. Wang, A.I. Dounis, & R. Yang, "Multi-agent control system with information fusion based comfort model for smart buildings," Applied Energy, vol. 99, pp. 247-254, 2012. [4] J. Vernon, Fuzzy Logic Systems, control-systems-princiles.co.uk/pdf. accessed on dated:03-05-2013. [5] A.I. Dounis, C. Caraiscos, Advanced control systems engineering for energy and comfort management in a building environment a review, Renewable Sustainable Energy Review, vol-13, pp.1246 1261, 2009. [6] Z. Peng, S. Suryanarayanan, X. Simo, and M. G. es., "An Energy Management System for Building Structures Using a Multi-Agent Decision-Making Control Methodology," in Industry Applications Society Annual Meeting (IAS), 2010 IEEE, pp. 1-8, 2010. [7] G.U. Fehmi, Y. Ergun, A linear programming approach to household energy conservation: Efficient allocation of budget, Energy and Buildings, vol 49, pp.200 208, 2012. [8] D. Kolokotsa, C. Diakaki, E. Grigoroudis, G. Stavrakakis, K. Kalaitzakis, Decision support methodologies on the energy efficiency and energy management in buildings, Advances in Building Energy Research, vol. 3, pp. 121 146, 2009. [9] P. Zhao, M. G. Simoes, S. Suryanarayanan, "A conceptual scheme for cyber-physical systems based energy management in building structures," 9th IEEE/IAS International Conference on Industry Applications, Nov. 2010. [10] L. Bei, G. Siddharth, C. Samuel and K.V. Pramode, Predicting User Comfort Level using Machine Learning for Smart Grid Environments, IEEE proceedings, 2011. [11] D. Holcomb, L. Wenchao, and S. S. A., Algorithms for green buildings: Learning-Based techniques for energy prediction and fault diagnosis, Electrical Engineering and Computer Sciences, Electrical Engineering and Computer Sciences, Tech. Rep. UCB/EECS, Oct. 2009. [12] A.I. Dounis, M. Santamouris, C.C. Lefas, Building visual comfort control with fuzzy reasoning, Energy Conversion Management, vol - 34, pp. 17 28, 1993. [13] D.H.W. Li,J.C. Lam, An analysis of lighting energy savings and switching frequency for a daylight corridor under various indoor design luminance levels, Applied Energy, vol-76, pp. 363 738, 2003. [14] S. Wang, X. Xu, Optimal and robust control of outdoor ventilation airflow rate for improving energy efficiency and IAQ, Building Environment, vol-39, pp. 763 773, 2004. [15] A. I. Dounis, C. Caraiscos, Intelligent coordinator of fuzzy controller-agents for indoor environment control in buildings using 3-D fuzzy comforter sets In: IEEE International Fuzzy System Conference, London, UK; pp. 1 6, 2007. [16] H. Sri Andari, P. Ashish, T. Ludo, W. Ying, Z. Meng, Lighting systems control for Demand Response, IEEE PES Innovative Smart Grid Technologies, vol-5, pp. 1-6, 2011. [17] A.I. Dounis and C. Caraiscos, Advanced control systems engineering for energy management and comfort in a building environment A review, Renewable and Sustainable Energy Reviews, vol- 13, pp. 1246-1261, 2009. [18] S. J. Emmerich and A. K. Persily, State-of-the-art review of CO 2 demand controlled ventilation technology and application, National Institute of Standards and Technology, Technology Administration, US. Department of Commerce. Pp. 1 43, 2001. ISSN : 0975-4024 Vol 5 No 4 Aug-Sep 2013 3242