GUIDELINES FOR SUB-SYSTEM COMPLETION CERTIFICATES AND TEST RECORDS FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES

Similar documents
ETCI announces the following Amendment No. 2.3 to the National Rules for Electrical Installations ET 101:2008 incorporating Amendment No.

OPTIONS FOR SHOWING ELECTRICAL INSTALLATION COMPETENCE

Specification for UDC Electrical Testing

Assessment Route Summary

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN

Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations.

Installation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation.

Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations.

ROAD LIGHTING ELECTRICIAL INSTALLATION CERTIFICATE. (Requirements for Electrical Installations BS7671 (IET Wiring Regulations) (1) (See notes page 6)

INSTALLATION ELECTRICIAN / MAINTENANCE ELECTRICIAN APPRENTICESHIP ASSESSMENT PLAN

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200

NZQA unit standard version 1 Page 1 of 5

Technical Guideline for. Section 8. Inspection and Approval of Construction

TÜV SÜD BABT Production Quality Certification Scheme

SAFETY, HEALTH & WELFARE AT WORK (CONSTRUCTION) REGULATIONS Briefing Note 1 for Clients, Designers and Project Supervisor Design Process

Same As Client Address SPECIMEN. operational limitations. of the inspection and. agreed with):

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION EARTHING AND EARTH FAULT PROTECTION

Transnational Skill Standards Foreman Electrical Works (Construction)

UL TEST REPORT AND PROCEDURE

ELECTROMAGNETIC ENERGY

Candidate Self-Assessment Checklist

Same as Client Address. 40, Havelock Close. India Way. London. Postcode: W12 7NQ

Ensure no person makes contact with the steel pole streetlight or temporary earth electrode while the testing procedures are being undertaken.

Project Procedure 1.0 PURPOSE 2.0 SCOPE 3.0 REFERENCES. No.: P /19/2011 PAGE 1 OF 4 FACILITY LIGHTING SYSTEMS INSTALLATION

Candidate Self-Assessment Checklist

DoES-QW1 Suitability Assessment Questionnaire and Declaration

NAPIT Periodic Report on an existing Electrical Installation Requirements for Electrical Installations BS 7671 [IEE Wiring Regulations 17th Edition]

BS 7671:2018 MODEL FORMS

High voltage for apparatus under Safe Access Rules and statutory regulations is defined as being greater than 1000V ac or 1500V dc.

PERMANENT DOCUMENT CIG 023. Factory Inspection Report

ElECTrICAl INSTAllATION CONDITION

IECQ PUBLICATION IECQ IEC Quality Assessment System for Electronic Components (IECQ System)

Compiled by: Figure 2: Fire triangle. Successfully suppressing or separating one or more of these three components can avoid a fire or explosion.

SECTION GROUNDING

Specifications. Level 1 Essential Energy Works for the Warialda Truck Wash

HEALTH, SAFETY AND ENVIRONMENT MANAGEMENT SYSTEM

Microgeneration Installation Standard MIS 3006

IECEE OPERATIONAL DOCUMENT

WORK IN THE VICINITY OF UNDERGROUND ASSETS

Chapter 3 Other Stakeholders Duties

GN7 Amendment 3-5 Agricultural and horticultural premises

Preparation and Installation of the ENVIRO-SEAL I Rupture Disc

Deliverables list for Projects in the fertilizer industry

IECEx Certificate of Conformity

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION CODE

Electrical installations Marinas and boats

Article 10 - ADMINISTRATIVE SECTION

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

Sections through of Chapter 5 of the Victoria City Code are amended to read as follows: ARTICLE IX. NATIONAL ELECTRICAL CODE

Amendment A National Electric Code

TUV SUD BABT PRODUCTION QUALITY CERTIFICATION SCHEME

Microgeneration Installation Standard MIS 3006

ELECTRICAL BULLETIN

ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS (EEHA) MAINTENANCE STANDARD

Apply earths to and remove earths from electrical conductors, plant and equipment

ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS (EEHA) VERIFICATION DOSSIER STANDARD

POWER TRANSFORMER INSTALLATION

SERVICE LEVEL PROCEDURE

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

ExTAG Training Workshop Application ISO/IEC :2018

What to You Need to Know When Limited Production Certification is Your Hazardous Locations Compliance Strategy

IECEx OPERATIONAL DOCUMENT

DEFINITIONS: The following definitions apply to terms used in this document:

Grounding & Bounding. 1. Bonded Connected to establish electrical continuity and conductivity.

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

STATIC GROUNDING VERIFICATION SYSTEM

UL TEST REPORT AND PROCEDURE

ABENGOA INABENSA ABENGOA INABENSA. General Operating Procedure POG Page 2 of 9. Translation control table. Revision: 02

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

Certificate of Compliance

Microgeneration Installation Standard: MIS 3003

PIKES PEAK PARKING RESTORATION TABLE OF CONTENTS

Giza Cable Industries. Quality & Occupational Health and Safety Manual ISO 9001 : 2008 & OHSAS : 2007

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

WELMEC European cooperation in legal metrology

Level 3 in Electrotechnical Services Experienced Worker ( )

NPS/002/013 Technical Specification for Telephone and Pilot Cable Joints

pproval of rvc upplrsno. 2.9 APRIL 2013

ELECTRICITY SUPPLY - POWER QUALITY AND RELIABILITY Code of Practice

Association of American Railroads Quality Assurance System Evaluation (QASE) Checklist Rev. 1/12/2017

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

A. Section includes busway and fittings including plug-in units.

SECTION BUSWAYS

ISO 9001:2015 Readiness Review

AUDITING OF HIGH VOLTAGE INSTALLATIONS

ELEVATING DEVICES CODES REGULATION

SLIM lamp CEILING version

TABLE OF CONTENTS INTRODUCTION... 7 CHAPTER 1-GENERAL CHAPTER 2-WIRING AND PROTECTION CHAPTER 3-WIRING METHODS AND MATERIALS...

QUALITY MANUAL ECO# REVISION DATE MGR QA A 2/25/2008 R.Clement J.Haislip B 6/17/2008 T.Finneran J.Haislip

Prototype Integration Facility SUPPLIER QUALITY SYSTEM REQUIREMENTS

IECEx OPERATIONAL DOCUMENT

110.2 Training Requirements.

CORPORATE MANUAL OF INTEGRATED MANAGEMENT SYSTEM

Dated: April 16, 2002

SECTION LIGHTNING PROTECTION SYSTEM

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:

Ground Fault Circuit Interrupters (GFCI) & Assured Grounding Program

VERTICAL ASSESSMENT INSPECTION ISO/IEC 17020:2012

Transcription:

Sub-System Completion Certificate: Scope: In the case of new installations or modifications to existing installations, where part of the installation traverses hazardous areas, this Sub-system Completion Certificate must accompany the associated ETCI ET101:2008 Completion Certificate. The Sub-System Completion Certificate must be completed in its entirety whenever any part of the installation traverses a hazardous area, whether or not there are a number of contractors on a project. These guidelines do not propose to provide complete information on all aspects of testing and certification. These guidelines should be read in conjunction with the guidelines for completion certificates given in ET101:2008. See also the current edition of ET105:2011 & I.S.EN60079 series of standards This Sub-System Completion Certificate must be held in the project Safety File as required by the 2006 Safety Health & Welfare at Work (Construction) Regulations. Introduction: The client, designer, installer, constructor or inspector who signs the Sub-System Completion Certificate is making a formal declaration that, as far as that person can reasonably ascertain, the installation as installed, complies with all of the relevant National Rules for Electrical Installations and current relevant legislation and is ready for final connection/operation. The associated Explosion Protection Document (EPD) or Design Dossier must be made available, fully complied with where applicable and a reference copy held in the project Safety File as required by the2006 Safety Health & Welfare at Work (Construction) Regulations. Filling in the Sub-System Completion Certificate: The Test Records should be filled in as construction proceeds and should be completed (except in the case of new installations where power-on tests are required after connection to the supply), before filling-in the Sub-System Completion Certificate. Certificate Specifics: Page 1: This is available for purchase from ETCI and will contain a unique certificate reference number to be used on all subsequent attachments. The installation may require a tick in more than one box per line e.g. Zone 1 & Zone 2 Under Section 5 Nature of ignitable materials, the intention is to record the extent of the range of Zones, Groups and Classes and not just the worst case scenario. The designer therefore is requested to tick all applicable boxes pertaining to the installation associated with the certificate. Referred to in Section 5 is an EPD. An EPD is an explosion protection document which contains the findings of a risk assessment of any work activity involving flammable/or explosive atmospheres. It may be Page 1 of 5 ETCI Website: http://www.etci.ie July 2012

incorporated or at least referenced in the Safety Statement, be part of other risk assessment documentation or included in the Safety Report for those establishments subject to the European Communities (Control of Major Accident Hazards Involving Dangerous Substances) Regulations. Page 1, 2 & 4: If additional comments are required to substantiate any part of this certificate, then the use of a Comment Sheet shall be utilized. Page 2, 3 & 4: The definition of Affiliation includes Others to mean those suitably qualified, trained and experienced in this field with the authority to sign accordingly. Adequate support documentation shall be provided and filed with this certificate. Page 2 Design & Selection: the best of their abilities, to all associated DESIGN and SELECTION works. If the design and selection is divided between different parties it must be agreed before the commencement of the work and clearly indicated on this certificate. Page 3 Installation: the best of their abilities, to all associated ERECTION/CONSTRUCTION works. Page 4 Inspector: Page 4: the best of their abilities, to all associated installation INSPECTION works. The comments section allows for relevant comments which are not otherwise provided for in the certificate. Because the certificate is a completion certificate it is not acceptable to write not accessible or the like. N/A means not applicable and should only be used if the particular section does not apply. All the boxes must be filled in with a tick. Confirmation of satisfactory test values in accordance with ET101:2008 is confirmed by reference to the associated ETCI Completion Certificate. Confirmation of the remaining parts of this section is by reference to the Test Record Sheets for the installation. The Visual Confirmation section refers to the documentation for the sub-system. These documents must be made available to enable confirmation of the suitability of apparatus, cables & protective conductors and to verify the test measurements detailed in the Test Record Sheets. Diagrams, warning notices and signage must be verified in conjunction with the Client and confirmed in line with associated current legislation. Confirmation of current calibration certificates relates to test instruments used only for verification purposes and to confirm copies of the associated test instruments are attached to this certificate. Page 2 of 5 ETCI Website: http://www.etci.ie July 2012

Verification of documentation also assures the availability of documentation for future maintenance and periodic inspection and testing. Declarations of Conformity fulfill the statutory obligations of the plant operator in this respect. (NOTE: Declarations of Incorporation if not bridged to Conformity need to be viewed carefully and brought to the attention of the Designer for review). Verification of Classification of hazardous areas includes Temperature Class for all equipment types in every gas and/or dust group present in the area. Verification of inspection schedules of ET105:2011 Annex J provides an accommodation for any detailed inspections not otherwise covered in the Test Record Sheets for the particular installation e.g. gas pressures, flow indicators etc. at EEx p installations. Test Record Sheet: ETCI Test Record Sheets are available for Power circuits and EExi device records. The effectiveness of earthing systems is verified by tests which assure a resistance to the general mass of earth which can be reliably sustained and is compatible with other earth electrodes in the installation, e.g. lightning protection electrodes at vertical storage tanks where the maximum acceptable combined value is 10 Ohms. In verifying the effectiveness of protection devices, account should be taken of the change-over time setting at star/delta starters of rotating electric machines. Note also that special conditions apply in the case of variable frequency drives. Insulation resistance is verified by tests between each current carrying conductor (including neutrals), which give a value in excess of 10 Mega-ohms. Verification of EExi circuits is satisfactory when the test values of the EExi Test Record Sheet are in accordance with the system documentation. Note that additional tests shall be required as specified in the design documentation of uncertified systems. (SI 732 of 2007) Regulation 89: Certification After the installation has been tested and found to be in compliance, the contractor or other person responsible for the construction of the installation, or a person duly authorized to act on his or her behalf, must sign a statement to that effect. In addition to the certificate, the employer must retain Test Record Sheets containing the results of tests carried out. The certificate must be completed by an authorized person having adequate qualifications, training, technical knowledge and experience. The installation shall be tested by an appropriate person from time to time having regard for the nature, location and use of the installation or at any time if an inspector so requires. Distribution of Certificates: Page 3 of 5 ETCI Website: http://www.etci.ie July 2012

The original Sub-System Completion Certificate and Test Record Sheets must be handed over and held in the Project Safety File as required by the 2006 Safety Health & Welfare at Work (Construction) Regulations. Working copies of both documents must be held by the Plant Manager and the Tester to facilitate periodic inspection, testing and maintenance. Technical Notes: Effectiveness of phase-earth fault impedance is confirmed by test values which satisfy the requirements of Chapter 43 of ET101:2008 and which allow minimum prospective fault currents which satisfy the formula: I 2 t = k 2 S 2, so that under fault conditions (not exceeding 5 seconds), temperatures will be lower than the ignition temperature of the explosive atmosphere and the short time temperature rating of the cable. ( t is the operating time of the disconnecting device, S is the cross sectional area of the conductor in mm 2, and k is a factor dependent on the conductor initial and final temperature). Phase to Phase impedance tests are required to determine the prospective fault current value. In a three phase system the phase to phase short-circuit fault current will always be higher than the phase to earth fault current. The measured values will be required in the selection verification for the operating characteristics and to ensure the correct breaking capacity of the protective device. Insulation resistance testing of circuits is required to verify that, for compliance with ET101:2008, the insulation of conductors and electrical accessories and equipment is satisfactory and that live conductors or protective conductors are not short-circuited or do not show a low insulation resistance. Conductivity of protective conductors is confirmed by test values which satisfy the I 2 t formula (*above). Conductivity of bonding conductors is confirmed by test values which confirm continuity from the main earth terminal to frameworks and enclosures. Equipotential and supplementary bonding is confirmed by test values which satisfy the formula: R Ia 50 Volts, where R is the resistance in ohms and Ia is the operating current in amperes of the protective device. In addition, in Zone 0, and Zone 1 areas, the test values should confirm that the resistance in ohms between any two simultaneously accessible parts does not exceed the value of R in the formula: R = 12 Z / U, where Z is the phase-earth loop impedance and U is phase/earth voltage (reference to ET 101:2008 sub-clause 613.6.5). Insulation testing of EExi circuits is necessary to confirm that they are earthed or insulated from earth throughout in accordance with ET105:2011. Note: systems which are isolated from earth may have electrostatic discharge protection via an earth connection of 0.2 to 1.0 MΩ. Insulation of screens is confirmed when the screens are disconnected at the point specified in the documentation, for the duration of the tests, and the screens are then confirmed to be clear of earth. The integrity of non-isolated EExi earth connections is confirmed by measurement of the resistance of the earth connection between the EExi circuits and the earth point (per system documentation). Electrical parameters of EExi circuits are confirmed by measurement and by reference to the maximum permissible values ascertained from the associated apparatus, documentation and marking plates. Page 4 of 5 ETCI Website: http://www.etci.ie July 2012

Details required on the Descriptive System Document of Intrinsically Safe or other Energy Limiting Systems include: IS System Design Details required on the Descriptive System Document of Intrinsically Safe or other Energy Limiting Systems. Tag No. Description Make Model No. EC Cert No. Marking Electrical Parameters Field Equipment Cables/Leads Associated Conditions of Intrinsic IS System Status Ui * Vdc Uo * Vdc Ui >= * Uo * Vdc >= * Vdc Ii * ma Io * ma Ii >= * Io * ma >= * ma Pi * W Po * W Pi >= * Po * W >= * W Li Lc Lo Li + Lc <= * Lo <= Ci Cc Co Ci + Cc <= * Co <= L/Ri * L/Rc * L/Ro In accordance uf/ohm with I.S. EN60079-14 uh/ohm & 25 /ohm L/Ri + L/Rc <= * L/Ro *mh/ohm <= *mh/ohm General Notes: The Sub-System Completion Certificates and Test Record Sheets are issued and signed by the person responsible for the design, selection, construction, inspection and/or testing of the installation or a person duly authorized to act on his or her behalf. The Sub-System Completion Certificates and the associated Test Record Sheets must be submitted to the Project Supervisor (Construction) Stage (PSCS) and included in the project safety manual. Electrical installations should be inspected and tested periodically to comply with relevant statutes and standards. Further information can be found on the ETCI website. http://www.etci.ie The Electro-Technical Council of Ireland is not responsible for the electrical installation or for the accuracy of the information given on the Sub-System Completion Certificates and Test Record Sheets. Page 5 of 5 ETCI Website: http://www.etci.ie July 2012