Polymer Cutout Testing Recommendations

Similar documents
Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R

Polymer Cutout Evaluation NEETRAC

UNS 5kA Arrester. Certified Test Report IEC

UHS 10kA Arrester. Certified Test Report IEC

INTERNATIONAL STANDARD

DESIGN TEST REPORT. GAMMA Insulators 6184R-70 ANSI Class 55-3 Pin Type Insulator..

DESIGN TEST REPORT. GAMMA Insulators 7061R-70 ANSI Class 55-5 Pin Type Insulator.

DESIGN TEST REPORT. GAMMA Insulators 6183R-70 ANSI Class 55-4 Pin Type Insulator.

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

Draft. Not yet Approved. American Railway Engineering and Maintenance of Way Association Letter Ballot

DESIGN OF ROTATING WHEEL DIP TEST SYSTEM FOR STANDARD TRACKING AND EROSION TESTING OF POLYMERIC INSULATORS

6C-001 High-Voltage Pin-Type Insulator

Evaluation Test Procedures for Distribution Crossarms. Southeastern Electric Exchange November, 2018

Composite Insulator Components

TEMPERED GLASS INSULATORS

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES

GROUP A. Polymeric Insulators.

ENGINEERING SPECIFICATION EE SPEC

WESTERN UNDERGROUND COMMITTEE GUIDE 2.15 (2.15/00/0588)

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

CONTENTS. Section Title Page 1.0 SUMMARY TEST SPECIMENS TEST PROGRAM Pretest Inspection Thermal Aging 3

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

General Requirements. Technical Specifications for Insulators of Transmission Lines

needed for the SOFC electrolyte membrane application. Few directed vapor deposition

STANDARDS UPDATE NOTICE (SUN) ISSUED: August 16, 2018

Polluted Outdoor Insulators Maintenance and Washing

1/2W, 0805 Low Resistance Chip Resistor (Lead / Halogen free)

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test

Polymer Suspension Insulators 69kV to 765kV

ISO 6722 INTERNATIONAL STANDARD. Road vehicles 60 V and 600 V single-core cables Dimensions, test methods and requirements

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS

SPECIALTY POLYMER COATINGS, INC.

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

TEST PROCEDURE SUMMARY

TYPICAL PHYSICAL STRENGTH PROPERTIES OF PRO TILE

Standard Test Method for Measuring Compressive Properties of Thermal Insulations 1

Product Specification JUL 14 Rev. A1

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

MAY-16 REV B2

SPECIFICATION FOR DISC INSULATORS (Standard Type)

Protection Effectiveness of Vapor Corrosion Inhibitor VpCI 619 for Corrosion Under Insulation at Elevated Temperatures

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

Dec05 Rev A

THERMOFIT RT-218 TUBING Modified Polyvinylidene Fluoride, Low Outgassing, Heat-Shrinkable

S. C. Electric Cooperative s Specification for a Single-Phase, Two Bushing Overhead Distribution Transformer (Revised 10/2013)

NEW! PUPI Fiberglass Transmission & H-frame Products

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Master Wall Inc. continuously tests our products and systems to meet the most current building codes.

ME 280 Lab #1. Lüders Strain Evaluation of Stress Concentration and Electrochemical Embrittlement of Spring Steel

Mar11 Rev C

660 Volts 630 & 800AMP

GR-771-CORE Generic Requirements for Fiber Optic Splice Closures Issue 2, July 2008 Performance Requirements and Objectives

1. SCOPE 2. REFERENCED DOCUMENTS

Water Dispensers. Pure water type Daily capacity: 50 G Voltage: 220V Size: 37 x 21 x 48 cm Function: meet standard drinking water quality requirement

Application Note FS Series PV Module Mounting

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

EQUIPMENT AND SYSTEM FOR VACUUM COATING METALLIZING, SPUTTERING, PLASMA and PECVD. Hybrid system KOLZER DGK 36

ASSE International Product (Seal) Listing Program. ASSE Outdoor Enclosures for Fluid Conveying Components

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR GLASS LAVATORIES, SINKS AND COUNTER TOPS IAPMO IGC

PRODUCT SPECIFICATION th JAN. 18 Rev. A3

CEG-200. Industrial X-Ray Tube

DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 101, SALT ATMOSPHERE (CORROSION)

Comparison of BS and BS EN for steel materials

SECTION TERRA COTTA CLAY TILE RAINSCREEN SYSTEM

TEST REPORT (Self-Tested Data)

Polymer Post Insulators for 46 to 500kV Applications

Energy Division Insulators

Innovation in carbon-ammonia adsorption heat pump technology: a case study

Sep10 Rev C

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination

Electron Microscopy (EM) Grid

MECHANICAL AND PHYSICAL PROPRIETIES

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

Transmission Silicone Insulators Line Post 69 kv to 230 kv

FrelTec GmbH. Cement Fixed Resistors

RB 107 Specification DuraSeal Splices

NORDTEST METHOD NT BUILD NT BUILD

1 Exam Prep Guide to Shotcrete Questions

RELIABILITY TEST RESULTS

(Issued 1 Dec. 1988) CRD-C STANDARD METHODS OF TESTING JOINT SEALANTS, COLD-APPLIED, NON-JET-FUEL-RESISTANT, FOR RIGID AND FLEXIBLE PAVEMENTS

Sn-Pb plating or Tin plating

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Mar11 Rev B

SECTION ALUMINUM HANDRAIL SYSTEMS

CATHODIC PROTECTION SPECIFICATION

TESTING APPLICATION STANDARD (TAS) STANDARD REQUIREMENTS FOR THERMOPLASTIC OLEFIN ELASTOMER BASED SHEET USED IN SINGLE-PLY ROOF MEMBRANE

Design Objective

The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1.

SOLARLOK BREEZE Junction Box

Proudly Made in the U.S.A. 5-Year Warranty. Wayfinding Products

Surface Micromachining

IPC-TM-650 TEST METHODS MANUAL

SECTION HANGERS AND SUPPORTS FOR PLUMBING

Diffused Aeration Piping Equipment

Test of Abnormal Heat in Hydrogen Loaded Metal

Transcription:

1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert

Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3) 3. Interruption Test Series 1 (+50 C and at 50 C ) 4. Long Term Deformation 5. Insulation Test 6. Weathering UV Aging 7. Tracking & Erosion

1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 7.3 Water diffusion test 7.3.1 General This test is intended to check the resistance of the core material to water attack. 732S 7.3.2 Samples Four samples shall be cut from a production line insulator. The cuts shall be made approximately 90 to the long axis of the insulator with a diamond-coated circular saw blade under cold running water. The length of the samples shall be 30 mm ± 0.5 mm (1.1818 in ± 0.0202 in). The cut surfaces shall be smoothed by means of a fine abrasive cloth (grain size 180). The cut ends shall be clean and parallel.

1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 733P 7.3.3 Pre-stressing The surfaces of the samples shall be cleaned with isopropyl alcohol and filter paper p immediately before boiling. The samples shall be boiled in a suitable container (e.g., made of glass or stainless steel) for a minimum 100 h ± 0.5 h in deionized water with 0.1% by weight of NaCl. Samples of only one core material shall be boiled together in the same container (see Figure 1 for an example of such a container). After boiling, the samples shall be removed from the boiling container and placed in another container (e.g., made of glass or stainless steel) filled with tap water at ambient temperature for at least 15 min. The voltage test shall be carried out within 3 h of the samples being removed from the boiling container.

1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 734A 7.3.4 Applied voltage The voltage shall be applied using the assembly shown in Figure 2. Immediately before the voltage is applied, the samples shall be removed from the tap water container and their surfaces dried with filter paper. Each sample shall then be put between the electrodes. The voltage shall be increased at approximately 1 kv/s, up to 12 kv. The voltage shall be kept constant at 12 kv for 1 min and then decreased to zero. 7.3.5 Acceptance criteria During the application of the voltage, no puncture or surface flashover shall occur. The current during application of the voltage shall not exceed 1 ma (rms).

1. Water Diffusion Tests Figure 2

2. Dye Penetration (ANSI C29.13 Section 7.3) 7.3 Dye penetration test 7.3.1 Test specimens Ten samples shall be cut from an insulator. The length of the samples shall be 10 mm ± 0.5 mm. They shall be cut 90 degrees to the axis of the core with a diamond coated circular saw blade under cool running water. The cut surfaces shall be smoothed with a 180-grit abrasive cloth. The cut ends shall be clean and parallel.

2. Dye Penetration (ANSI C29.13 Section 7.3) 7.3.2 Test The samples shall be placed on a layer of steel or glass balls in a glass vessel with the fiber vertical. The balls shall be of the same diameter and in the range of 1 mm to 2 mm. The dye, composed of 1 gram of fuchsin in 100 grams of methanol, is poured into the vessel until its level is 2mm to 3mm above the top of the balls. 7.3.3 Evaluation The time for the dye to rise through the samples by capillarity shall be more than 15 minutes.

3. Interruption Tests Interruption Tests as required in C37.41, Section 6.4, Test Series 1 should be performed at +50 C (three samples) and at -50 C C (three samples) using a rigid mounting. Testing at ambient is not required. Pretests Install thermocouples in cutout rod and precondition three Attempts samples at will +50 be C made and to three measure impact energy for use samples in Thermal at -50 C Mechanical for a minimum test. tof 8 hours. Remove units from chamber and determine average time to cool down to +45 C and timetowarmupto-35 to to C.

3. Interruption Tests Perform Test Series 1 Precondition three samples at +50 C and three samples at -50 C for a minimum of 8 hours. Remove each sample from chamber in insulated container, transport to test cell, setup and test within the average time measured in the cool down / warm up pretests. Perform dye penetration test (ANSI C29.13 Section 7.3) on all samples after Test Series 1.

4. Long Term Deformation Apply static load d( (3 to 4X normal spring loading) to three cutout samples for a total of 8 weeks. Remove samples from loading frameand and perform Temperature rise test to determine if any permanent deformation has occurred which would cause over heating problems.

5. Insulation Test Test Description Pass/Fail Criteria i Hardness test ASTM D2240 100 hour boiling water test - in water having 0.1% by weight of NaCl Hardness test ASTM D2240 Steep-front impulse voltage test - min 1000 kv / µs, max 3000 kv / µs (10 positive & 10 negative) * OPTIONAL BANDS Low-frequency flashover test Elevated AC withstand test @ 80% of reference flashover voltage for 30 minutes. N/A N/A Samples must cool to within 5 C of the temperature where the initial measurement was made. Hardness must not change from the pre-boiled specimen by more than 20% All impulses must cause external flashover. Punctures that expose the insulating rod must not occur. Shall equal or exceed 90% of reference flashover value The maximum temperature rise of each cutout housing, between the sheds with respect to the temperature of the reference sample, shall be less than 10 C.

5. Insulation Test OPTIONAL A copper band d( (max. 20 mm wide and dless than 1 mm thick) may be attached around the cutout and connected to the mounting gpin for the steep front impulse tests. The band shall be in the plane of the mounting pin and perpendicular to the cutout axis. Optional Copper Band

5. Insulation Test Test Configuration without copper band

6. UV Aging One sample of each insulator design will be placed in an environmental aging chamber and aged using UVA 340 bulbs and the following cycle for 3,000 hours: 8 h UV at 60 (± 3) C Black Panel Temperature; 025h 0.25 water spray (no light), temperature not controlled; and 3.75 h condensation at 50 (±3) C Black Panel Temperature. Options for 5,000 hour Multi Stress Test from IEC 61109 and UVB aging should be considered by the Working Group.

7. Tracking & Erosion Samples three new samples The applied voltage during the energized period will be the maximum single phase to ground value listed in Table 2, Col 2 of C37.42.

7. Tracking & Erosion Each sample must complete 30,000 cycles lasting 200 seconds ±25 seconds each with the samples stationary no less than 80 % of the cycle time. Each cycle consists of the sample going through the four positions with approximately an equal period of time at each position. The saline solution in the tank will consist of de ionized water with 1.40 ±0.06 g/l of NaCl. After every four days of testing, the samples will be given a 24 hour recovery period. During this period, the test procedure will be the same except the dip tank will be empty.

Tracking Wheel 7. Tracking & Erosion

7. Tracking & Erosion Within 48 hours of completion of 30,000 cycles: Rinse with de ionized water and take resistance measurements from top to bottom, top to center and bottom to center. Compare these values to resistance of new units. If the after test resistances are less than 80% of the new, the units have failed. 80% AC withstand dry 80% BIL dry Thorough rinse with de ionized water to remove all salt deposits followed by 80% AC withstand wet

Comments / Contact Info Frank C. Lambert Georgia Tech / NEETRAC 404 675 1855 frank.lambert@neetrac.gatech.edu