Post installed rebar connections

Similar documents
Post installed rebar connections

HILTI HY 150 REBAR DESIGN GUIDE

1 Basics of post installed rebar connections

Anchor Fastening Technology Manual 09 / 2012

How to calculate anchorage and lap lengths to Eurocode 2

RC Detailing to EC2 Webinar August RC Detailing to Eurocode 2. RC Detailing to Eurocode 2

Hilti HIT-RE 500 post-installed rebars

The nominal cover can be assessed as follows: C nom

Adhesive Anchors SECTION CONTENTS. General Information. Installation Information Design Information Material Information Ordering Information

HRA Rail anchor with Hilti HIT-RE 500 or HVU-G/EA glass capsule

Post-installed reinforcement bars in structural connections

Concrete Splitting for Post-Installed Reinforcing Bars According to AS-3600

European Technical Assessment ETA-16/0865 of 08/11/2016

E TA TECHNICAL REPORT. Evaluation of Anchorages in Concrete concerning Resistance to Fire. TR 020 Edition May 2004

DURABILITY AND SERVICEABILITY

General building approval

New ICC/ACI Design Concept for Post-Installed Reinforcement Bars Kelly Chua, B.Eng (Civil and Structural)

BS EN :2004 EN :2004 (E)

ANNEX 10. Special requirements recommended for structures subject to seismic actions. 1 Scope. 2 Basis of design. 2.1 Fundamental requirements

HIGH PERFORMANCE REINFORCEMENT PRODUCTS. Product Catalogue.

Eurocode 8 Timber and Masonry structures

Anchor Fastening Technology Manual. HIT-HY 170 mortar with rebar. Hilti HIT-HY 170 mortar with rebar (as post-installed conn.

ANCHORING WITH BONDED FASTENERS

Lecture Retaining Wall Week 12

Footings GENERAL CONSIDERATIONS 15.2 LOADS AND REACTIONS 15.4 MOMENT IN FOOTINGS

CEO s Note. Finally, I hope that this technical handbook will benefit all parties both in academic and industry. LOUIS HII The CEO of YKMW Groups

EN REINFORCED MASONRY DESIGN EXAMPLE 1 (NOTE: THIS USES THE UK NATIONAL ANNEX NDP VALUES)

European Technical Assessment. ETA 15/0226 of General Part TCM400PE, TCM600PE. Trade name of the construction product

7. SPECIFIC RULES FOR STEEL CONCRETE COMPOSITE BUILDINGS

The following excerpt are pages from the Hilti North America Post- Installed Reinforcing Bar Guide.

Seismic Behaviour of RC Shear Walls

> 0. 1 f, they are treated as beam-columns.

CHAPTER 10: GENERAL STRUCTURAL DETAILS

1 Input data. Profis Anchor Company: Specifier: Address: Phone I Fax: Page: Project: Sub-Project I Pos. No.

European Technical Assessment ETA-14/0453 of 11/12/2014

APPENDIX B ABC STRUCTURES DESIGN GUIDE

PRESTRESSED CONCRETE STRUCTURES. Amlan K. Sengupta, PhD PE Department of Civil Engineering Indian Institute of Technology Madras

REPORT No SIMPSON STRONG-TIE AT-HP

Design of Composite Bridges Use of BS 5400: Part 5: 1979

Lap Splices in Tension Between Headed Reinforcing Bars And Hooked Reinforcing Bars of Reinforced Concrete Beam

HIT-RE 500 V3 INJECTION MORTAR. Technical Datasheet Update: Dec-17

Hilti-HY 110 available in 330ml and 500ml foil packs. Static mixer HIT M1. Rebar BSt 500 S


Hilti HIT-ICE with rebar

English translation prepared by CSTB - Original version in French language. OUTIFIX 82, rue Saint Lazare Paris FRANCE

Hilti HIT-HY 200-R 500 ml foil pack (also available as 330 ml foil pack) Static mixer

Technical data No. 17/0002 of 22/05/2017

7.1 Transmission of Prestress (Part I)

TECHNICAL MANUAL. PSB Punching Reinforcement. Shear Reinforcement for Concrete Structures

Appendix M 2010 AASHTO Bridge Committee Agenda Item

This final draft of the fib MC2010 has not been published; it is intended only for the purpose of voting by the General Assembly.

CHAPTER 11: PRESTRESSED CONCRETE

HVU with HAS/HAS-E rod adhesive anchor system

REPORT No MRF /B

1 Input data. Profis Anchor Company: Specifier: Address: Phone I Fax: Obeikan Tensile Struct

Technical data No. 17/0001 of 25/04/2017

Hilti HVU-TZ foil capsule. HAS-TZ HAS-R-TZ HAS-HCR-TZ rod. Shock

Grout Filled Steel Pipe Integrated With Shear Key for Precast Concrete Connection

CHAPTER 2. Design Formulae for Bending

HRC T-Headed Bars Advantages for the user

Hilti HIT-HY 170 mortar with HIT-V rod. Anchor Fastening Technology Manual. Hilti HIT-HY 170 with HIT-V HIS-(R)N 03 / /

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures

5.4 Analysis for Torsion

SVM-PSC Polyester resin for use in concrete

HST Carbon steel. HST-R Stainless steel HST-HCR High corrosion resistance steel. Fire resistance

Slabs and Flat Slabs

English translation prepared by CSTB - Original version in French language

Masonry and Cold-Formed Steel Requirements

English translation prepared by CSTB - Original version in French language. SPIT EPCON C8 rebars

Hilti HIT-HY 70. Setting depth [mm] M6 M8 M10 M12 M8 M10 M12. Clay common (Dry pressed) f b b) 25 N/mm² L x H x B [mm] 230 x 110 x 76

R-Group Finland Oy. RTA, RWTL and RWTS Lifting anchors Design instructions

PRESTRESSED CONCRETE STRUCTURES. Amlan K. Sengupta, PhD PE Department of Civil Engineering Indian Institute of Technology Madras

BSF - DESIGN OF REINFORCEMENT, CANTILEVERED BEAM- BEAM

DESIGN OF RETAINING WALLS

Demountable Shear Connectors for Sustainable Composite Construction

Serviceability considerations

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE

In-plane testing of precast concrete wall panels with grouted sleeve

CHAPTER 11 Bar Cutoff

UHPC Connection of Precast Bridge Deck

R-Group Finland Oy. RLA Lifting Inserts Technical Manual According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved

3. Bond, Anchorage and Shear This chapter will discuss the following topics:

Recommendations for additional fire protection of structural elements

Schöck Isokorb type CV

Contents. Foreword 1 Introduction 1

1 Prepared By:Mr.A.Sathiyamoorthy, M.E., AP/Civil

Modelling of RC moment resisting frames with precast-prestressed flooring system

ST7008 PRESTRESSED CONCRETE

Hilti HIT-CT 1 with HIT-V

HKD Push-in anchor, Single anchor application

3.4.2 DESIGN CONSIDERATIONS

Schöck Isokorb Type CM

HDA-P HDA-PR HDA-PF Anchor for presetting. HDA-T HDA-TR HDA-TF Anchor for through-fasting. Nuclear power plant approval

Strength Design of Reinforced Concrete Structures

Schöck Isokorb type CVB Design

INFLUENCE OF PRSTRESS LEVEL ON SHEAR BEHAVIOR OF SEGMENTAL CONCRETE BEAMS WITH EXTERNAL TENDONS

Designated according to Article 29 of Regulation (EU) No 305/2011 and member of EOTA (European Organisation for Technical Assessment)

Schöck Isokorb Type CV

Structural Calculations for standard BALCONY 1 system handrail using 55mm diameter posts (48.3mm x 5mm CHS) & 150 x 150 x 15mm base plates

European Technical Assessment ETA-10/0422 of 08/01/2016

Transcription:

Post installed rebar connections Post installed rebar connections Basics of post installed rebar connections Hilti HIT-RE 500 post installed rebar Hilti HIT-HY 150 post installed rebar Hilti HIT- HY 150 MAX post installed rebar 1 / 2009 649

Basics of post installed rebar connections Basics of post installed rebar connections 1 Applications 1.1 Advantages of post-installed rebar connections With the use of the Hilti-HIT injection systems it is possible to connect new reinforcement to existing structures with maximum confidence and flexibility. design flexibility reliable like cast in horizontal, vertical and form work simplification defined load characteristics overhead simple, high confidence application 1.2 Application examples Post installed rebar connections are widely used within the construction industry in a wide range of applications, which vary from new construction projects, to structure upgrades and infrastructure requalifications. Post-installed rebar connections in new construction projects Diaphragm walls Slab connections Misplaced bars Vertical/horizontal connections 650 1 / 2009

Basics of post installed rebar connections Post-installed rebar connections in structure updgrades Wall strenghtening New slab constructions Joint strenghtening Cantilevers/balconies Post-installed rebar connections in infrastructure requalifications Slab widening Structural upgrade Slab strenghtening Side-walk upgrade 1 / 2009 651

Basics of post installed rebar connections 2 Rebar basics 2.1 Definition of rebar Rebar is standing for REinforcement BAR. At Hilti the word is used for a reinforcement bar inserted into a borehole filled with Hilti HIT in reinforced concrete structures, in other words for post-installed reinforcement. Post-installed reinforcement can be split up into four different main applications: Good detailing practice Shear studs Rebar as structural rebar Rebar as an anchor In the course of the Anchor FTM the focus will be on the last two types of applications. Chapter 3, Adhesive Anchoring Systems, deals with rebar as an anchor. The current chapter focuses on rebar as structural rebar, where the reinforcement is purely loaded in the longitudinal direction. l v l 0 l bd 2 / 3 l bd 10 d s Figure 2.1: Example of structural rebar application Structural rebar is characterized by very high loads. The reinforcement is often loaded up to steel yielding. The concrete structure (connection) shows a good serviceability. The deformations are small and due to this the crack width and therefore the influences by the environment (corrosion) are limited. The concrete connections behave as a monolithic structure or in other words as if the concrete was poured in one go. The high loads which can occur in either the anchorage or the splice can lead to an embedment length up to 15 till 80 times the diameter of the reinforcement. The design can be done according to two design concepts; Structural code, for instance EC2 EN 1992-1-1:2004 chapter 8.4 anchorage of longitudinal reinforcement, based on approvals (e.g. ETA according to EOTA TR023) See paragraph 4 of this chapter for an overview of the approvals Hilti HIT-Rebar design concept, based on the American Standard (ACI 318-08), where the allowable bond stress is controlled by splitting / spalling behaviour. For this type of connections an engineer is usually involved in the design. 652 1 / 2009

Basics of post installed rebar connections 2.2 Rebar as an anchor Rebar as an anchor is characterized by the fact it is not possible to splice the reinforcement (due to e.g. lack of useable reinforcement). The loads are typically smaller as in the case of structural rebar and the serviceability is slightly lower. The anchor failure modes like concrete cone failure or combined concrete cone and pull-out failure are considered in this application according to standard anchor design. For this type of connections an engineer is usually involved in the design. 2.3 Cast-in ribbed bars Generally, for load transfer in reinforced concrete only tensile or compressive forces in bars are considered. For ribbed bars, the load transfer in concrete is governed by the bearing of the ribs against the concrete (figure 2.3.a). The force reaction in the concrete is assumed to form a compressive strut in the direction of 45. For higher bond stress values, the concentrated bearing forces in front of the ribs cause the formation of cone-shaped cracks starting at the crest of the ribs. The resulting concrete keys between the ribs transfer the bearing forces into the surrounding concrete, but the wedging action of the ribs remains limited. In this stage the displacement of the bar with respect to the concrete (slip) consists of bending of the keys and crushing of the concrete in front of the ribs. The bearing forces, which are inclined with respect to the bar axis, can be decomposed into directions parallel and perpendicular to the bar axis. The sum of the parallel components equals the bond force, whereas the radial components induce circumferential tensile stresses in the surrounding concrete, which may result in longitudinal radial (splitting / spalling) cracks. Figure 2.3.a: Load transfer from ribbed bars into concrete Two failure modes can be considered: a) Bond failure (fig. 2.3.a): If the confinement (concrete cover, transverse reinforcement) is sufficient to prevent splitting of the concrete cover, bond failure is caused by pull-out of the bar. In that case the concrete keys are sheared off and a sliding plane around the bar is created. Thus, the force transfer mechanism changes from rib bearing to friction. The shear resistance of the keys can be considered as a criterion for this transition. It is attended by a considerable reduction of the bond stress. Under continued loading the sliding surface is smoothed due to wear and compaction, which will result in a further decrease of the bond stress, similar to the case of plain bars. 1 / 2009 653

Basics of post installed rebar connections b) Splitting failure (fig. 2.3.b): If the radial cracks propagate through the entire cover, bond splitting failure is decisive. In that case the maximum bond stress follows from the maximum concrete confinement, which is reached when the radial cracks have penetrated the cover for about 70%. Further crack propagation results in a decrease of the confining stresses. At reaching the outer surface these stresses are strongly reduced, which results in a sudden drop of the bond stress. Figure 2.3.b 2.4 Lapped bar splices 2.4.1 Model for load transfer at lapped bar splices The load transfer between bars is performed by means of compressive struts in the concrete (fig. 2.4.1). A 45 truss model is assumed. The resulting perpendicular forces act in a similar way as the splitting forces. The splitting forces normally are taken up by the transverse reinforcement. Small splitting forces are attributed to the tensile capacity of the concrete. The amount of the transverse or tie reinforcement necessary is specified in the design codes. Figure 2.4.1: Load transfer at lap splices 2.4.2 Influence of spacing and cover on splitting and spalling of concrete In most cases the reinforcement bars are placed close to the surface of the concrete member to achieve good crack distribution and economical bending capacity. For splices at wide spacing (normally in slabs, fig. 2.4.2a), the bearing capacity of the concrete depends only on the thickness of the concrete cover. At narrow spacing (normally in beams, fig. 2.4.2.b) the bearing capacity depends on the spacing and on the thickness of the cover. In the design codes the reduction of bearing capacity of the cover is taken into account by means of multiplying factors for the splice length. Figure 2.4.2.a Figure 2.4.2.b 2.4.3 Bond behaviour of post-installed ribbed bars The load transfer for post-installed bars is similar to cast in bars if the stiffness of the overall load transfer mechanism is similar to the cast-in system. The efficiency depends on the strength 654 1 / 2009

Basics of post installed rebar connections of the adhesive mortar against the concentrated load near the ribs and on the capacity of load transfer at the interface of the drilled hole. In many cases the bond values of post-installed bars are higher compared to cast in bars due to better performance of the adhesive mortar. But for small edge distance and/or narrow spacing splitting or spalling forces become decisive due to the low tensile capacity of the concrete. 3 Design basics 3.1 Rebar design methods Post-installed reinforcement connections can basically be designed in compliance with the national codes. Hilti is offering two design methods of which one is based on the Eurocode 2 (EC2 EN 1992-1-1:2004) and the other one on the American Standard (ACI 318-08). The most important characteristics will be explained in the following paragraphs. 3.2 Rebar design according to EC2/ETA approach The new technical report EOTA TR 023 (Assessment of post-installed rebar connections) establishes a common method to qualify chemical anchors in compliance with EC2. Chemical anchors must comply with a predefined step-diagram for the different concrete classes (Figure 3.2: Chemical anchors without limitations). In general it shall be shown by the tests as described in the TR 023 that the post-installed rebar systems can develop the same design values of bond resistance with the same safety margin as cast-in place rebars according to EC2. In EC2 no requirements for testing are given, but the values for fbd are published. These values are valid for worst case conditions, minimum concrete cover, minimum spacing and minimum transverse reinforcement. In Figure 3.2 a comparison is given which bond resistance in the tests and evaluation according TR 023 have to be reached (on y- axis) to show equivalence with the values f bd (on x- axis). A European Technical Approvals according to the EOTA TR023 allows a design according to EC2. However a design for fire resistance, fatigue, dynamic or seismic loading are excluded. The ETA for Rebar proves that approved systems are robust and durable. Influences of bad cleaning, wet holes, creep, freeze/thaw, durability, corrosion resistance, installation directions are tested within the approval. The post-installed rebar connections assessed according to TR 023 shall be designed as straight cast-in reinforcement according to EC2 using the values of the design bond resistance fbd for deformed bars. The definition of the bond region in EC2 is valid also for post-installed reinforcement. The conditions in EC2 concerning detailing (e.g. concrete cover in respect to bond and corrosion resistance, bar spacing, transverse reinforcement) shall be complied with. 1 / 2009 655

Basics of post installed rebar connections Figure 3.2: Chemical anchors without limitations from EOTA TR023 The following additional provisions have to be taken into account. To prevent damage of the concrete during drilling the following requirements have to be met: c min = 30 + 0,06l v 2d s (mm) for hammer drilled holes, with ds being the diameter of the rebar c min = 50 + 0,08l v 2d s (mm) for compressed air drilled holes The factors 0,06 and 0,08 take into account the possible deviations during the drilling process. This value might be smaller if special drilling aid devices are used. Minimum clear spacing between two post-installed rebars a = 40 mm 4d s To account for potentially different behaviour of post-installed and cast-in rebars in cracked concrete, in general, the minimum embedment length l b,min and l 0,min given in EC2 for anchorages and overlap splices shall be increased by a factor of 1,5. This increase may be neglected if it can be shown that the bond strength of the selected postinstalled rebars and cast-in rebars in cracked concrete (w = 0,3 mm) is similar. In this case the influence of cracks openings (crack movement tests) can be neglected because for rebar connections several rebars are present (redundant fastening) and not all of the rebars will be situated in a longitudinal crack. The transfer of shear forces between new and old concrete shall be designed according to EC2. See also paragraph 3.4 strut-and-tie model. The reader is referred to the paragraph 4 EC2 Design for more detail about this design concept. 656 1 / 2009

Basics of post installed rebar connections 3.3 Hilti HIT-Rebar design and ACI 318-08 approach The American Standard ACI (American Concrete Institute) 318-08 gives an explicit formula for the design of anchorages and splices that considers splitting and spalling as a function of concrete cover and bar spacing. This function is adapted and extended for post-installed reinforcement for the Hilti HIT-Rebar design concept. The embedment length of an anchorage or splice is defined as a function of concrete strength, the bar diameter, the minimum edge distance or spacing and a coefficient taking into account the transverse reinforcement. In figure 3.3 a typical design bond stress f bd curve as a function of the minimum edge distance/spacing distance, c d is shown for a concrete class C20/25 and for a rebar with a diameter of 12 mm (EC2/ETA approach). In this figure the equivalent design bond stresses resulting from the ACI and the EC2/ETA approaches are plotted to illustrate the two methods (the design bond stresses shown in the figure shall not be used for design purposes). The reduction of anchoring length allowed by ACI and EC2/ETA in specific conditions can be assimilated to an increase of the equivalent design bond stress if c d changes within certain limits. The equivalent design bond stress is defined by an inclined line and it increases with larger values of c d. The increase in the design bond stress is limited by the maximum pull-out bond stress, which is a value which is given by the standards in the case of a cast-in reinforcement. For post-installed reinforcement, the maximum design bond stress is a function of the bonding agent and not necessarily equals that of cast-in bars. Thus, the limitation for bond failure in the code has been replaced by the specific design bond stress of the bonding agent for the specific application conditions and the splitting function has been adapted according to the tests. fbd 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 0.0 6.9 N/mm 2 3.3 N/mm 2 0 10 20 30 40 50 60 70 80 90 100 110 c ACI 318-08 approach d,min c d C20/25, Ø = 12 mm EC2/ETA approach c d = min(a/2, c, c 1 ) Figure 3.3: equivalent design bond stress f bd as a function of c d., derived from reduction of anchoring lenght according to ACI 318-08 and EC2/ETA. 1 / 2009 657

Basics of post installed rebar connections Interaction of concrete cover and transverse reinforcement (splitting reinforcement) Tests show that transverse reinforcement improves the splitting capacity. Transverse reinforcement can be taken into account by adding a substitute value for the cover. The ACI 318-08 code explicitly takes into account the influence of transverse reinforcement able to prevent splitting by means of the transverse reinforcement index K tr. f bd = f ck c + K tr 4 φ ξ ; A tr f yt K tr = ; 10.34 s n c + K tr φ 2.5 for cast - in bars with: A tr total cross-sectional area of all transverse reinforcement that is within the spacing s and that crosses the potential plane of splitting through the reinforcement being developed [mm 2 ] f yt yield strength of transverse reinforcement [N/mm 2 ] s maximum spacing of transverse reinforcement within b, center to center [mm] n number of bars being developed along the plane of splitting [-] ξ substitute for various adjustment factors Hilti HIT-Rebar design concept c + K for tr 2. 5 (post-installed reinforcement and cast-in reinforcement): φ f bd f ck c + K = 4 γ φ tr for c + K tr > 2. 5 φ (bonded-in bars only): f bd = f ck c + K tr 2.5 + 0.75 2. 5 4 γ φ where: f bd design bond strength φ nominal bar size f ck characteristic concrete cylinder strength c = c d = min(a/2, c, c 1 ) K tr see above γ bar size factor For more detailed Information see: Kunz, J.; Münger, F.: Splitting- and bond failure of post-installed rebar splices and anchoring. ; Bond in Concrete from research to standards, Proceedings of the 3rd International Symposium held at the Budapest University of Technology and Economics, Budapest, Hungary, 20 to 22 November 2002, p.447-454. (Copy available from Hilti Technical Service) 658 1 / 2009

Basics of post installed rebar connections 3.4 Strut-and-tie model The tensile bearing capacity of concrete is very low compared to its compressive strength. For this reason tensile forces are attributed to the steel reinforcement of the concrete member. The reinforcement should be adequately anchored in the nodes {Clause 6.5.3(2), EC2: EN 1992-1- 1:2004}. Joint to be roughened Crack limitation Tension cord Figure 3.4: Strut-and-tie-model Compression cord and strut (concrete) Tension ties A strut-and-tie model is used to calculate the load path in reinforced concrete members. Where a non-linear strain distribution exists (e.g. supports) strut-and-tie models may be used {Clause 6.5.1(1), EC2: EN 1992-1-1:2004}. Strut-and-tie models consist of struts representing compressive stress fields, of ties representing the reinforcement and of the connecting nodes. The forces in the elements of a strut-and-tie model should be determined by maintaining the equilibrium with the applied loads in ultimate limit state. The ties of a strut-and-tie model should coincide in position and direction with the corresponding reinforcement {Clause 5.6.4, EC2: EN 1992-1-1:2004 Analysis with strut and tie models}. 3.5 Joint to be roughened The model of inclined compressive struts is used to transfer the shear forces through the construction joint at the interface between concrete cast at different times. Therefore a rough interface is required to provide sufficient cohesion in the construction joint {Clause 6.2.5(2), EC2: EN 1992-1-1:2004}. Rough means a surface with at least 3 mm roughness (R t > 3 mm), achieved by raking, exposing the aggregate or other methods giving an equivalent behaviour. 3.6 Anchorage of reinforcement The reinforcement has to be anchored at places where it is no longer needed. These situations may occur: when the load path of the tensile force has ended (e.g. support, figure 3.6.a) at curtailment of reinforcement (see figure 3.6.b) compression bar anchorage (see figure 3.6.c). 1 / 2009 659

Basics of post installed rebar connections Figure 3.6.a: Support, truss Figure 3.6.b: Tensile force has ended Figure 3.6.c: Compression 3.7 Lapped splice of reinforcement Lapped splices are used to achieve continuity in the tensile tie of the truss model at construction joints. The load from one bar to the other is transferred by means of compressive struts in the concrete. A 45 -truss model is assumed. The resulting splitting force (design bond stress) is limited to a value depending on the surface characteristics of the reinforcement, the tensile strength of the concrete and confinement of surrounding concrete. This depends on sufficient concrete cover, spacing of bar, transverse pressure and by the transverse reinforcement {Clause 6.6, EC2: EN 1992-1-1:2004}. Figure 3.7: Lapped splice 4 EC2 design 4.1 General The actual position of the reinforcement in the existing structure shall be determined on the basis of the construction documentation and taken into account when designing. The transfer of shear forces between new concrete and existing structure shall be designed according to EC2 EN 1992-1-1:2004. See also paragraph 3.4 Strut-and-tie model The joints for concreting must be roughened to at least such an extent that aggregate protrude. See also paragraph 3.5 Joint to be roughened. The design of post-installed rebar connections and determination of the internal section forces to be transferred in the construction joint shall be verified in accordance with EC2 EN 1992-1-1:2004. When ascertaining the tensile force in the rebar, allowance shall be made for the statically effective height of the bonded-in reinforcement. See also paragraph 5.2 Example with overlap joint 660 1 / 2009

Basics of post installed rebar connections 4.2 Determination of the basic anchorage length The calculation of the required anchorage length shall take into consideration the type of steel and bond properties of the reinforcement. The required basic anchorage length l b,rqd shall be determined in accordance with clause 8.4.3, EC2: EN1992-1-1:2004: l b,rqd = (d s / 4) (σ sd / f bd ) with: d s = diameter of the rebar σ sd = calculated design stress of the rebar f bd = design value of bond strength according to corresponding ETA, in consideration of the coefficient related to the quality of bond conditions and, of the coefficient related to the bar diameter and of the drilling technique. Refer to the relevant approval or technical data sheet for details. 4.3 Determination of the design anchorage length The required design anchorage length l bd shall be determined in accordance with clause 8.4.4, EC2: EN 1992-1- 1:2004: l bd = α 1 α 2 α 3 α 4 α 5 l b,rqd l b,min Where α 1, α 2, α 3, α 4 and α 5 are coefficients given in Table 4.1. α 1 is for the effect of the form of the bars assuming adequate cover (post-installed reinforcement is always straight) α 2 is for the effect of concrete minimum cover α2 = 1 0,15 ( c d d0 )/d0 straight bars; min ( a/2;c ;c) c d = 1 With no edge distance, α 2 = 0,7 if the spacing given in the table below are fulfilled: d s (mm) 8 10 12 14 16 18 20 22 24 25 26 28 30 32 34 36 40 Spacing (mm) 56 70 84 98 112 126 140 154 168 175 182 196 210 224 238 252 280 a (mm) 48 60 72 84 96 108 120 132 144 150 156 168 180 192 204 216 240 α 3 is for the effect of confinement by transverse reinforcement α 4 is for the influence of one or more welded transverse bars along the design anchorage length l bd. (no welded transverse reinforcement possible with postinstalled reinforcement) α 5 is for the effect of the pressure transverse to the plane of splitting along the design anchorage length. The product (α 2 α 3 α 5 ) 0,7 1 / 2009 661

Basics of post installed rebar connections l b,rqd = according to section 5.2 l b,min = minimum anchorage length according to clause 8.4.4, EC2: EN 1992-1-1:2004 = max {0.3 l b,rqd ; 10d s ; 100 mm} under tension = max {0.6 l b,rqd ; 10d s ; 100 mm} under compression (Please note that the minimum anchorage length may be increased by factor 1,5 according to EOTA TR023, 4.2. Refer to the relevant approval or technical data sheet for details.) Table 4.1: Values of α 1, α 2, α 3, α 4 and α 5 coefficients Influencing factor Type of anchorage Reinforcement bar In tension In compression Shape of bars Straight α 1 = 1.0 α 1 = 1.0 Concrete cover Straight α 2 = 1 0.15(c d α 2 = 1.0 ø)/ø 0.7 1.0 Confinement by Straight α 3 = 1 Kλ α 3 = 1.0 transverse reinforcement 0.7 1.0 Confinement by welded transverse Straight α 4 = 1.0 α 4 = 1.0 reinforcement Confinement by transverse pressure where: λ Straight α 5 = 1 0.04p 0.7 1.0 = (ΣA st - ΣA st,min )/ A s ΣA st cross-sectional area of the transverse reinforcement along the design anchorage length lbd ΣA st,min cross-sectional area of the minimum transverse reinforcement = 0.25 As for beams and 0 for slabs As area of a single anchored bar with maximum bar diameter K values shown in Figure 4.10 p transverse pressure [MPa] at ultimate limit state along lbd - Figure 4.3 : Values of K for beams and slabs 4.4 Overlap joints Forces are transmitted from one bar to another by lapping the bars. The detailing of laps between bars shall be such that: - the transmission of the forces from one bar to the next is assured - spalling of the concrete in the neighbourhood of the joints does not occur - large cracks which affect the performance of the structure do not occur 662 1 / 2009

Basics of post installed rebar connections Laps between bars should not be located in areas of high moments / forces (e.g. plastic hinges) and at any section normally be arranged symmetrically. The arrangement of lapped bars should comply with Figure 4.4. The clear distance between lapped bars should be 4ø and 50 mm, otherwise the lap length should be increased by a length equal to the clear space where it exceeds 4ø or 50 mm. 3ø Figure 4.4: Adjacent laps The required design lap length l 0 shall be determined in accordance with clause 8.7.3, EC2: EN 1992-1-1:2004: l 0 = α 1 α 2 α 3 α 5 α 6 l b,rqd l 0,min with: l b,rqd = according to section 4.2 l 0,min = minimum lap length = max {0.3α 6 l b,rqd ; 15d s ; 200 mm} (Please note that the minimum anchorage length may be increased by factor 1,5 according to EOTA TR023, 4.2. Refer to the relevant approval or technical data sheet for details.) Values of α 1, α 2, α 3 and α 5 may be taken from Table 4.1; however, for the calculation of α 3, ΣA st,min should be taken as 1,0 A s (σ sd /f yd ), with A s = area of one lapped bar. α 6 = (ρ 1 /25)0.5 but neither not exceeding 1,5 nor less than 1,0, where ρ 1 is the percentage of reinforcement lapped within 0.65l 0 from the centre of the lap length considered. Values of α 6 are given in Table 4.2. (Note: For postinstalled rebar applications α 6 = 1,5 for the majority of the cases) Table 4.2: Values of the coefficient α 6 Percentage of lapped bars < 25% 33% 50% > 50% relative to the total crosssection area α 6 1 1,15 1,4 1,5 4.5 Embedment depth for overlap joints Overlap joint for rebars: For calculation of the effective embedment depth of overlap joints the concrete cover at end-face of the postinstalled rebar c1 shall be considered: l v l 0 + c 1 with: l 0 = required lap length according to paragraph 4.4. c 1 = concrete cover at end-face of bonded-in rebar. See Figure 4.5 1 / 2009 663

Basics of post installed rebar connections Figure 4.5: Concrete cover c 1 If the clear distance between the overlapping bars is greater than 4d s the lap length shall be enlarged by the difference between the actual clear distance and 4d s. 4.6 Concrete cover The minimum concrete cover required for bonded-in rebars is shown in the ETA approvals in relation to the drilling method and the hole tolerance. Furthermore the minimum concrete cover given in clause 4.4.1.2, EC2: EN 1992-1- 1: 2004 shall be observed. 4.7 Transverse reinforcement The requirements of transverse reinforcement in the area of the post-installed rebar connection shall comply with clause 8.7.4, EC2: EN 1992-1-1:2004. 4.8 Connection joint In case of a carbonated surface of the existing concrete structure the carbonated layer shall be removed in the area of the post installed rebar connection with a diameter of d s + 60 mm prior to the installation of the new rebar. The depth of concrete to be removed shall correspond to at least the minimum concrete cover for the respective environmental conditions in accordance with EC2: EN 1992-1-1:2004. 664 1 / 2009

Basics of post installed rebar connections 5 Design examples 5.1 Anchorage: End support of slab, simply supported h = 300 d = 260 a 1 = 130 a l = 260 l n = 6,50 m h = 300 slab: l n = 6,50 m, Q k = 5 kn/m 2,h = 300 mm,d = 260 mm wall: h = 300 mm Concrete strength class: C20/25, dry concrete Properties of reinforcement: f yk = 500 N/mm2 Short-term/long-term temperature is 20 C Fire resistance: F90 (90 minutes) Loads: G d = 1,35 x 7,5 = 10,1 kn/m²; Q d = 1,5 x 5,0 = 7,5 kn/m² = 17,6 kn/m² Structural analysis (design forces) based on l eff : M Sd = 17,6 x 6,762 / 8 = 100,5 knm/m V Sd = 17,6 x (6,76 / 2) = 59,5 kn/m Bottom reinforcement required at mid span: A s,req = 100,5 x 1,15 / (0,26 x 0,9 x 0,5) = 988 mm²/m reinforcement provided: 16, s = 200 mm; A s,prov = 1010 mm²/m Bottom reinforcement at support: A s,min = 0,4 x 1 x 2,2 x 150 x 1000 / 500 = 264 mm²/m {Clause 7.3.2(2), EC2: EN 1992-1-1:2004} A s,min = 0,50 x 988 = 494 mm 2 /m {Clause 9.3.1.2(1), EC2: EN 1992-1-1:2004} {Clause 9.3.1.1(4), EC 2: EN 1992-1-1:2004} A s,min = 0,25 x 988 = 247 mm²/m {Clause 9.2.1.4(1), EC2: EN 1992-1-1:2004} A s,req = 59,5 x 1 / 0,9 x 1,15 / 0,5 = 152 mm 2 /m (al =d) {Clause 9.2.1.4(2), EC2: EN 1992-1-1:2004} Decisive is 494 mm²/m reinforcement provided: 12, s = 200 mm; A s,prov = 565 mm²/m a) Anchorage according to European Technical Approval (ETA) 08/0105, Post-installed rebar connections with Hilti injection mortar HIT-RE 500 Determination of the basic anchorage length The required basic anchorage length l b,rqd shall be determined in accordance with EC2: EN 1992-1-1:2004, section 8.4.3: l b,rqd = (d s / 4) x (σ sd / f bd ) with: d s = diameter of the rebar = 12 mm σ sd = calculated design stress of the rebar = (494 / 565) x (500 / 1,15) = 380 N/mm² f bd = design value of bond strength according to corresponding ETA = 2,3 N/mm² l b,rqd = (12 / 4) x (380 / 2,3) = 496 mm 1 / 2009 665

Basics of post installed rebar connections Determination of the design anchorage length The required design anchorage length l bd shall be determined in accordance with EC2: EN 1992-1-1:2004, section 8.4.4: l bd = α 1 α 2 α 3 α 4 α 5 l b,rqd l b,min with: l b,rqd as above α 1 = 1,0 for straight bars α 2 = 1 0,15(c d ø)/ø α 2 is for the effect of concrete minimum cover 0,7 1,0 a = 200 12 = 188 mm a/2 = 94 mm with c1 and c > 94 mm ø = 12 mm α 2 = 0,7 Straight bars, c d = min (a/2, c 1, c) α 3 = 1,0 because of no transverse reinforcement α 4 = 1,0 because of no welded transverse reinforcement α 5 = 1,0 influence of transverse pressure is neglected in this example l bd = 0,7 x 496 = 347 mm 2/3l bd = 231 mm 230 mm l b,min = minimum anchorage length {Clause 8.4.4(1), EC2: EN 1992-1-1:2004} = max {0,3 x 496; 10 x 12; 100} = 149 mm b) Anchorage according to Hilti HIT-Rebar design method (splitting): Reinforcement provided: 12, s = 200 mm; A s,prov = 565 mm²/m Mortar: Hilti HIT-RE 500 F Sd = 494 x 0,5 / 1,15 = 214,8 kn/m Steel: F Rd = 5 x (f yk x π x 2 x ¼) / у s = 245,9 kn/m > 214,8 kn/m ok Concrete (splitting) / Mortar (pull-out): Due to large edge distances in all directions (confined concrete) the failure mode splitting of concrete is not becoming decisive, but the pull out failure mode: f bd = 6.9 N/mm 2 F Rd = n(l bd x x π x f bd ) = 5(l bd x 12 x π x 6.9) = 214.8 kn/m l bd = 165 mm l b,min = 120 mm (10 x ) ok Fire resistance: Fire rating class F 90 (90 min.) (design table see paragraph 4.7): F st,req = 0,6 x 66,1 = 39,7 kn/m = 7,9 kn/bar {Clause 2.4.3 (4) and (5), EC2: ENV 1992-1-2:1995} Hilti HIT-RE 500: 12 l inst = 14,5 cm; F s,t = 6,02 kn l inst = 18 cm; F s,t = 15,0 kn 666 1 / 2009

Basics of post installed rebar connections Intermediate values may be interpolated linearly: l inst = 16,5 cm; F s,t = 11,2 kn/bar > 7,9 kn/bar l inst = 165 mm Top reinforcement 300 d = 260 a 1 = 130 a l = 260 l n = 6.50 m h = 300 Top reinforcement at support: Minimum reinforcement: 25% of bottom steel required at mid-span {Clause 9.3.1.2(2), EC2: EN 1992-1-1:2004} A s,req = 0,25 x 988 = 247 mm 2 /m A s,min = 0,4 x 1 x 2,2 x 150 x 1000 / 500 = 264 mm 2 /m {Clause 7.3.2(2), EC2: EN 1992-1-1:2004} Decisive is 264 mm²/m reinforcement provided: 12, s = 300 mm; A s,prov = 377 mm²/m a) Anchorage according to European Technical Approval (ETA) 08/0105, Post-installed rebar connections with Hilti injection mortar HIT-RE 500 Determination of the basic anchorage length The required basic anchorage length l b,rqd shall be determined in accordance with EC2: EN 1992-1-1:2004, section 8.4.3: l b,rqd = (d s / 4) x (σ sd / f bd) with: d s = diameter of the rebar = 12 mm σ sd = calculated design stress of the rebar = (264 / 377) x (500 / 1.15) = 304 N/mm² f bd = design value of bond strength according to corresponding ETA = 2,3 N/mm² l b,rqd = (12 / 4) x (304 / 2,3) = 397 mm Determination of the design anchorage length The required design anchorage length l bd shall be determined in accordance with EC2: EN 1992-1-1:2004, section 8.4.4: l bd = α 1 α 2 α 3 α 4 α 5 l b,rqd l b,min with: l b,rqd as above α 1 = 1,0 for straight bars α 2 = 1 0,15(c d ø)/ø α 2 is for the effect of concrete minimum cover 0,7 1,0 a = 300 12 = 288 mm a/2 = 144 mm with c1 and c > 144 mm ø = 12 mm 0,7 α 3 = 1,0 because of no transverse reinforcement α 4 = 1,0 because of no welded transverse reinforcement α 5 = 1,0 influence of transverse pressure is neglected in this example l bd = 0,7 x 397 = 278 mm 280 mm Can be critical with drilling! l b,min = minimum anchorage length {Clause 8.4.4(1), EC2: EN 1992-1-1:2004} = max {0.3 x 397; 10 x 12; 100} = 120 mm ok 1 / 2009 667

Basics of post installed rebar connections b) Anchorage according to Hilti HIT-Rebar design method (shear): Reinforcement provided: 12, s = 300 mm; A s,prov = 377 mm 2 /m Mortar: Hilti HIT-RE 500 F Sd = 264 x 0,5 / 1,15 = 114,8 kn/m Steel: F Rd = 3,33(f yk x π x 2 x ¼) / уs = 163,7 kn/m > 114,8 kn/m ok Mortar (pull-out): f bd = 6,9 N/mm 2 F Rd = n(l bd x x π x f bd ) = 3,33(l bd x 12 x π x 6,9) = 114,8 kn/m (if h ef < 18 ) l bd = 132 mm l b,min = 120 mm (10 x ) ok Concrete (shear): Uncracked concrete = rebar-cc method situation 1 s 18 ; c 9 ƒ AN = 1,0 (s = 300 mm > 216 mm; c > 108 mm) F Rd = F 0Rd x ƒ AN = 114,8 x 1.0 = 114,8 kn/m (with l bd = 132 mm) l bd = 135 mm 5.2 Example with overlap joint 30 l v l 0 c s = 50 d = 250 30 h = 300 Bending moment: M Sd = 120 knm/m slab: h = 300 mm; d = 250 mm, cs = 50 mm Concrete strength class: C25/30, Properties of reinforcement: f yk = 500 N/mm² Fire resistance: F60 (60 minutes), Light weight plaster for fire protection: 30 mm 10 top reinforcement: 16, s = 150 mm; A s,prov = 1340 mm²/m cover to face c 1 = 30 mm bottom reinforcement: 10, s = 200 mm; A s,prov = 393 mm²/m Note: reduced load in cast-in bar due to lever arm: η = 250 / 270 = 0,93 a) Overlap joints according to European Technical Approval (ETA) 08/0105, Post-installed rebar connections with Hilti injection mortar HIT-RE 500 Post-installed reinforcement The required design lap length l 0 shall be determined in accordance with EC2: EN 1992-1-1:2004, section 8.7.3: l 0 = α 1 α 2 α 3 α 5 α 6 l b,rqd l 0,min with: l b,rqd the basic anchorage length, l b,rqd = (d s / 4) x (σ sd / f bd ) d s = diameter of the rebar = 16 mm σ sd = calculated design stress of the rebar d = 250 mm, z 0,9 x 250 = 225 mm A s,req = 120 x 1,15 / (0,225 x 0,5) = 1227 mm 2 /m σ sd = (1227 / 1340) x (500 / 1,15) = 398 N/mm 2 f bd = design value of bond strength according to corresponding ETA = 2,7 N/mm 2 668 1 / 2009

Basics of post installed rebar connections l b,rqd = (16 / 4) x (398 / 2.7) = 590 mm α 1 = 1,0 for straight bars α 2 = 1 0,15(c d ø)/ø α 2 is for the effect of concrete minimum cover 0,7 1,0 c = 50-8 = 42 mm c d = 42 mm ø = 16 mm 0,76 α 3 = 1,0 because of no transverse reinforcement α 5 = 1,0 influence of transverse pressure is neglected in this example α 6 = 1,5 influence of percentage of lapped bars relative to the total cross-section area {Clause 8.7.3(1), EC2: EN 1992-1-1:2004} l 0 = 0,76 x 1,5 x 590 = 673 mm 675 mm l 0,min = minimum lap length {Clause 8.7.3(1), EC2: EN 1992-1-1:2004} = max{0.3 x 1.5 x 590; 15 x 16; 200} = 266 mm ok Cast-in reinforcement l 0 = α 1 α 2 α 3 α 5 α 6 l b,rqd l 0,min with: l b,rqd the basic anchorage length, l b,rqd = (d s / 4) x (σ sd / f bd ) d s = diameter of the rebar = 16 mm σ sd = calculated design stress of the rebar d = 270 mm, z 0,9 x 270 = 243 mm A s,req = 120 x 1,15 / (0,243 x 0,5) = 1136 mm 2 /m σ sd = (1136 / 1340) x (500 / 1,15) = 369 N/mm 2 f bd = design value of bond strength according to corresponding ETA = 2,7 N/mm 2 l b,rqd = (16 / 4) x (369 / 2.7) = 547 mm α 2 = 1 0,15(c d ø)/ø α 2 is for the effect of concrete minimum cover 0,7 1,0 c = 30-8 = 22 mm c d = 22 mm ø = 16 mm 0,94 l 0 = 0,94 x 1,5 x 547 = 771 mm 770 mm Cast-in reinforcement is decisive! l 0,min = minimum lap length {Clause 8.7.3(1), EC2: EN 1992-1-1:2004} = max{0,3 x 1,5 x 547; 15 x 16; 200} = 246 mm ok Embedment depth for overlap joints for rebars: l v l 0 + c 1 with: l 0 = required lap length = 770 mm (see above) c 1 = concrete cover at end face of cast-in rebar = 30 mm l v = 800 mm If the clear distance between the overlapping rebars is greater than 4d s (4 x 16 = 64 mm) the lap length shall be enlarged by the difference between the clear distance and 4d s. Most unfavorable case post-installed rebar is located right in the middle between the cast-in rebars. The clear distance between the overlap is: s 22 = (75 8)2 + (20 8)2 = 4633 s 2 = 68 mm 68 64 = 4 mm 5 mm l v = 800 + 5 = 805 mm 1 / 2009 669

Basics of post installed rebar connections b) Overlap joints according to Hilti HIT-Rebar design method (splitting): Post-installed reinforcement Reinforcement provided: 16, s = 150 mm; A s,prov = 1340 mm²/m Mortar: Hilti HIT-RE 500 F Sd = 1340 x 398 = 533,3 kn/m (see above) Steel: F Rd = 6,66(f yk x π x 2 x ¼) / уs = 582,2 kn/m > 533,3 kn/m ok Mortar (pull-out): f bd = 7,1 N/mm 2 ' tr f Concrete (splitting): c 2.5 + 0.75 2.5 (c + Ktr) / = 3.1 > 2.5 f bd is calculated φ f bd = according with: c = min{c, s/2} = 50 mm 4γ Ktr = 0 = 16 mm ' f c = compressive strength of concrete = 25 N/mm2 for C25/30 γ = reinforcement size factor = 0.8 for 18 f bd = 4,6 N/mm 2 Due to edge distances (c = 50 mm) and spacing (s = 150 mm) the failure mode splitting of concrete is decisive. α 6 = 1,5 f bd = 3,1 N/mm 2 {Clause 8.7.3(1), EC2: EN 1992-1-1:2004} F Rd = n(l 0 x x π x f bd ) = 6.66( 0 x 16 x π x 3,1) = 533,3 kn/m l 0 = 514 mm Cast-in reinforcement (as above) l 0 = 770 mm Cast-in reinforcement is decisive! Embedment depth for overlap joints for rebars: l v = 805 mm Fire resistance: Fire rating class F 60 (60 minutes) (design table see paragraph 4.7): Clear concrete cover including light weight plaster: c = 4 + 3 = 7 cm F st,req = 0.6 x 120 / 0,225 = 320 kn/m = 48 kn/bar {Clause 2.4.3 (4) und (5), EC2: ENV 1992-1-2:1995} τ T,req = 48000 / (16 x π x 770) = 1,2 N/mm 2 Hilti HIT-RE 500: τ T = 1,0 N/mm2 < 1,2 N/mm 2 increase plaster to 4 cm c = 8 cm, τ T = 1,4 N/mm 2 ok c + K 670 1 / 2009

Basics of post installed rebar connections 6 Corrosion behavior The Swiss Association for Protection against Corrosion (SGK) was given the assignment of evaluating the corrosion behavior of fastenings post-installed in concrete using the Hilti HIT-HY 150, Hilti HIT-HY 150 MAX and Hilti HIT-RE 500 injection systems. Corrosion tests were carried out. The behavior of the two systems had to be evaluated in relation to their use in field practice and compared with the behavior of cast-in reinforcement. The SGK can look back on extensive experience in this field, especially on expertise in the field of repair and maintenance work. The result can be summarized as follows: Hilti HIT-HY 150 + Hilti HIT-HY 150 MAX The Hilti HIT-HY 150 and Hilti HIT-HY 150 MAX systems in combination with reinforcing bars can be considered resistant to corrosion when they are used in sound, alkaline concrete. The alkalinity of the adhesive mortar safeguards the initial passivation of the steel. Owing to the porosity of the adhesive mortar, an exchange takes place with the alkaline pore solution of the concrete. If rebars are bonded-in into chloride-free concrete using this system, in the event of later chloride exposure, the rates of corrosion are about half those of rebars that are cast-in. In concrete containing chlorides, the corrosion behavior of the system corresponds to that of cast-in rebars. Consequently, the use of unprotected steel in concrete exposed to chlorides in the past or possibly in the future is not recommended because corrosion must be expected after only short exposure times. Hilti HIT-RE 500 If the Hilti HIT-RE 500 system is used in corrosive surroundings, a sufficiently thick coat of adhesive significantly increases the time before corrosion starts to attack the bonded-in steel. The HIT-RE 500 system may be described as resistant to corrosion, even in concrete that is carbonated and contains chlorides, if a coat thickness of at least 1 mm can be ensured. In this case, the unprotected steel in the concrete joint and in the new concrete is critical. If the coat thickness is not ensured, the HIT-RE 500 system may be used only in sound concrete. A rebar may then also be in contact with the wall of the drilled hole. At these points, the steel behaves as though it has a thin coating of epoxy resin. In none of the cases investigated did previously rusted steel (without chlorides) show signs of an attack by corrosion, even in concrete containing chlorides. Neither during this study an acceleration of corrosion was found at defective points in the adhesive nor was there any reference to this in literature. Even if a macro-element forms, the high resistance to it spreading inhibits a locally increased rate of corrosion. Information in reference data corresponds with the results of this study. 7 Fire design If passive fire prevention requirements have to be met, the suitability of rebar connections should be verified additionally to ULS cold design. Large-area building components (walls and floors) can be verified according to tables 1 and 2. The design tables are derived from tests at the University / IBMB Braunschweig following the Standard ISO 834 temperature/time curve. Design for fire resistance is carried out in line with several specific standards. On the following pages only the fire data for Standard according EC2 are given. Details to all available Standards and specific reports are named below the following tables. Note for the following tables 1 to 6: F s,t = force in bar when exposed to fire. Intermediate values may be interpolated linearly. Extrapolating is not permitted. 1 / 2009 671

Basics of post installed rebar connections Hilti HIT-HY 150 rebar Bar perpendicular to slab or wall surface exposed to fire Temperature time curve (acc. ISO 834) l inst Table 1: Maximum force in rebar in conjuction with HIT-HY 150 as a function of embedment depth for the fire resistance classes F30 to F180 (yield strength f yk = 500 N/mm²) according EC2 a) Bar Drill hole F30 F60 F90 F120 F180 [mm] [mm] 8 10 10 12 12 16 14 18 16 20 20 25 l inst [mm] F S,T [kn] l inst [mm] F S,T [kn] l inst [mm] F S,T [kn] l inst [mm] F S,T [kn] l inst [mm] F S,T [kn] 120 10,6 120 5,0 120 2,8 120 1,9 120 0,7 140 14,1 140 8,4 140 4,5 140 3,3 140 1,5 150 15,6 160 11,9 160 7,9 160 5,2 160 2,7 180 15,4 180 11,4 180 8,6 200 5,3 190 15,6 200 14,9 200 12,1 240 9,6 210 15,6 220 15,6 280 15,6 150 19,8 150 12,7 150 1,7 150 5,1 150 2,6 160 22,0 160 14,9 160 9,9 160 6,5 160 3,3 180 24,3 180 19,3 180 14,3 180 10,7 180 4,9 200 23,7 200 18,7 200 15,1 220 8,5 210 24,3 220 23,1 220 19,5 260 16,4 230 24,3 250 24,3 300 24,3 180 31,7 180 23,1 180 17,1 180 12,9 180 5,9 200 35,1 200 28,4 200 22,4 200 18,1 200 8,0 220 33,7 220 27,7 220 23,4 240 14.,4 230 35,1 240 32,9 240 28,7 280 24,9 250 35,1 270 35,1 320 35,1 210 46,2 210 36,2 210 29,2 210 24,2 210 10,6 220 47,7 220 39,3 220 32,2 220 27,3 220 11,9 240 45,4 240 38,4 240 33,5 240 16,8 250 47,7 260 44,6 260 39,6 280 29,1 270 47,7 280 45,8 320 41,4 290 47,7 350 47,7 240 62,3 240 51,9 240 43,9 240 38,3 240 19,2 260 59,0 260 51,0 260 45,3 280 33,2 270 62,3 280 58,0 280 52,3 320 47,3 300 62,3 300 59,4 360 61,4 310 62,3 370 62,3 300 97,4 300 91,3 300 81,3 300 74,3 300 50,3 320 97,4 320 90,1 320 83,0 320 59,1 340 97,4 340 91,8 360 76,7 360 97,4 400 94,3 410 97,4 672 1 / 2009

Basics of post installed rebar connections Bar Drill hole F30 F60 F90 F120 F180 [mm] [mm] 25 32 l inst [mm] F S,T [kn] l inst [mm] F S,T [kn] l inst [mm] F S,T [kn] l inst [mm] F S,T [kn] l inst [mm] F S,T [kn] 375 152,2 375 152,2 375 142,9 375 134,0 375 104,1 380 145,6 380 136,7 380 106,9 400 152,2 400 147,7 400 117,9 410 152,2 440 139,9 470 152,2 Remark: The minimum setting depth is related to l > 15 x d s a) For tables according British- and Singapore Standard (resistance class up to F240) see Warringtonfire report WF 166402 or/and IBMB Braunschweig report No 3162/6989 (including supplements). Hilti HIT-HY 150 rebar Bar connection parallel to slab or wall surface exposed to fire Max. bond stress, τ T, depending on actual clear concrete cover for classifying the fire resistance. It must be verified that the actual force in the bar during a fire, F s,t, can be taken up by the bar connection of the selected length, l inst. Note: Cold design for ULS is mandatory. F s, T (l inst c f ) π τ T where: (l inst c f ) l s ; l s = lap length = nominal diameter of bar l inst c f = selected overlap joint length; this must be at least l s, but may not be assumed to be more than 80 τ T = bond stress when exposed to fire Temperature time curve (acc. ISO 834) l inst c f c Table 2: Critical temperature-dependent bond stress, τ crit,t, concerning overlap joint for Hilti-HIT-HY 150 injection adhesive in relation to fire resistance class and required minimum concrete coverage c. Clear concrete cover c Max. bond stress, τ T [N/mm²] [mm] F30 F60 F90 F120 F180 20 0,7 0 30 1,4 0,2 0 0 40 1,9 0,7 0 50 2,4 1,2 0,4 60 2,8 1,7 0,7 0,3 70 4,9 2,2 1,2 0,7 1 / 2009 673

Basics of post installed rebar connections Clear concrete cover c Max. bond stress, τ T [N/mm²] [mm] F30 F60 F90 F120 F180 80 2,5 1,7 1,0 0,2 90 2,8 2,0 1,5 0,5 100 4,0 2,3 1,9 0,7 110 4,5 2,7 2,3 1,2 120 6,5 2,9 2,6 1,6 130 4,0 2,8 1,9 140 6,5 3,0 2,2 150 4,5 2,3 160 7,0 6,5 2,5 170 2,6 180 2,7 7,0 190 2,8 7,0 200 2,9 7,0 210 3,0 220 4,5 230 6,5 240 7,0 Hilti HIT-HY 150 MAX rebar Bar perpendicular to slab or wall surface exposed to fire Temperature time curve (acc. ISO 834) l inst Table 3: Maximum force in rebar in conjuction with HIT-HY 150 MAX as a function of embedment depth for the fire resistance classes F30 to F180 (yield strength f yk = 500 N/mm²) according EC2 a). Bar Drill hole Max. F s,t l inst F30 F60 F90 F120 F180 [mm] [mm] [kn] [mm] [kn] [kn] [kn] [kn] [kn] 80 2,18 0,73 0,24 0,05 0 120 8,21 2,90 1,44 0,82 0,18 170 16,2 9,95 5,99 3,69 1,35 8 12 16,2 210 16,2 13,01 9,52 3,6 230 16,2 13,04 5,74 250 16,2 9,26 300 16,2 100 5,87 1,95 0,84 0,4 0 150 16,86 8,06 4,45 2,82 0,96 190 25,3 16,83 11,86 7,65 2,91 10 14 25,3 230 25,3 20,66 16,29 7,18 260 25,3 22,89 13,77 280 25,3 18,17 320 25,3 674 1 / 2009

Basics of post installed rebar connections Bar Drill hole Max. F s,t l inst F30 F60 F90 F120 F180 [mm] [mm] [kn] [mm] [kn] [kn] [kn] [kn] [kn] 120 12,32 4,35 2,16 1,23 0,27 180 28,15 17,56 11,59 7,14 2,69 220 36,4 28,12 22,15 16,91 6,82 12 16 36,4 260 36,4 32,7 27,47 16,53 280 36,4 32,75 21,81 300 36,4 27,08 340 36,4 140 20,53 8,77 4,74 2,95 0,95 210 42,08 29,72 22,76 16,66 6,3 240 49,6 38,96 32,0 25,89 13,12 14 18 49,6 280 49,6 44,31 38,21 25,44 300 49,6 44,36 31,6 330 49,6 40,83 360 49,6 160 30,5 16,38 9,26 5,77 2,04 240 58,65 44,53 36,57 29,59 15,0 260 64,8 51,56 43,61 36,63 22,04 16 20 64,8 300 64,8 57,68 50,70 36,11 330 64,8 61,26 46,67 360 64,8 57,22 400 64,8 200 55,72 38,06 28,12 19,39 7,22 250 77,71 60,06 50,11 41,39 23,15 310 101,2 86,45 76,5 67,78 49,54 20 25 101,2 350 101,2 94,09 85,37 67,13 370 101,2 94,16 75,93 390 101,2 84,72 430 101,2 250 97,13 75,07 62,46 51,73 28,94 280 113,63 91,56 79,13 68,23 45,43 370 158,1 141,04 128,61 117,71 94,91 25 32 158,1 410 158,1 150,60 139,70 116,90 430 158,1 150,69 127,90 450 158,1 138,89 500 158,1 a) For HIT-HY 150 MAX rebar only the standard acc. EC2 is available (Data also in Warringtonfire report WF 166402 or/and IBMB Braunschweig report No 3884/8246-CM. Hilti HIT-HY 150 MAX rebar Bar connection parallel to slab or wall surface exposed to fire Max. bond stress, τ T, depending on actual clear concrete cover for classifying the fire resistance. It must be verified that the actual force in the bar during a fire, F s,t, can be taken up by the bar connection of the selected length, l inst. Note: Cold design for ULS is mandatory. F s, T (l inst c f ) π τ T where: (l inst c f ) l s ; l s = lap length = nominal diameter of bar l inst c f = selected overlap joint length; this must be at least l s, but may not be assumed to be more than 80 = bond stress when exposed to fire τ T 1 / 2009 675

Basics of post installed rebar connections Table 4: Critical temperature-dependent bond stress, τ crit,t, concerning overlap joint for Hilti-HIT-HY 150 MAX injection adhesive in relation to fire resistance class and required minimum concrete coverage c. Clear concrete cover c Max. bond stress, τ T [N/mm²] [mm] F30 F60 F90 F120 F180 30 0,46 35 0,56 0 40 0,69 45 0,84 0,37 0 50 1,04 0,45 55 1,22 0,53 0 60 1,47 0,62 65 1,85 0,73 0,38 0 70 0,87 0,46 75 1,02 0,52 80 1,21 0,59 0,37 85 1,35 0,67 0,43 90 1,52 0,78 0,52 95 1,74 0,91 0,58 100 2,02 1,07 0,66 105 1,21 0,77 0,38 110 1,39 0,91 0,44 115 1,61 1,05 0,48 120 1,89 1,21 0,53 125 2,12 1,37 0,61 130 2,20 1,57 0,69 135 1,82 0,75 140 2,13 0,81 145 0,89 2,20 150 0,88 155 0,97 160 2,20 1,08 165 1,22 2,20 170 1,40 175 1,62 180 1,90 185 2,05 190 2,20 Hilti HIT-RE 500 rebar Bar perpendicular to slab or wall surface exposed to fire Temperature time curve (acc. ISO 834) l inst 676 1 / 2009

Basics of post installed rebar connections Table 5: Maximum force in rebar in conjuction with HIT-RE 500 as a function of embedment depth for the fire resistance classes F30 to F240 (yield strength f yk = 500 N/mm²) according EC2 a). Bar Drill hole Max. F s,t l inst Fire resistance of bar in [kn] [mm] [mm] [kn] [mm] F30 F60 F90 F120 F180 F240 65 1,38 0,57 0,19 0,05 0 0 80 2,35 1,02 0,47 0,26 0 0 95 3,87 1,68 0,88 0,55 0,12 0 115 7,3 3,07 1,71 1,14 0,44 0,18 8 10 16,19 150 16,19 8,15 4,59 3,14 1,41 0,8 180 16,19 9,99 6,75 2,94 1,7 205 16,19 12,38 5,08 2,86 220 16,19 6,95 3,82 265 16,19 8,57 305 16,19 80 2,94 1,27 0,59 0,33 0 0 100 5,68 2,45 1,31 0,85 0,24 0 120 10,66 4,44 2,48 1,68 0,68 0,31 140 17,57 7,76 4,38 2,99 1,33 0,73 10 12 25,29 165 25,29 15,06 8,5 5,79 2,58 1,5 195 25,29 17,63 12,18 5,12 2,93 220 25,29 20,66 8,69 4,78 235 25,29 11,8 6,30 280 25,29 13,86 320 25,29 95 5,8 2,52 1,32 0,83 0,18 0 120 12,79 5,33 2,97 2,01 0,82 0,37 145 23,16 10,68 6,02 4,12 1,84 1,03 180 36,42 24,29 14,99 10,12 4,41 2,55 12 16 36,42 210 36,42 27,38 20,65 8,47 4,74 235 36,42 312,01 14,16 7,56 250 36,42 19,13 9,89 295 36,42 21,43 335 36,42 110 10,92 4,65 2,55 1,7 0,61 0,20 140 24,60 10,87 6,13 4,19 1,86 1,03 170 39,12 23,50 13,55 9,2 4,07 2,37 195 49.58 35,6 24,69 17,05 7,17 4,10 14 18 49.58 225 49.58 39,20 31,34 13,48 7,34 250 49.58 43,44 22,32 11,54 265 49.58 29,49 15,00 310 49.58 31,98 350 49.58 130 22,59 9,42 5,30 3,61 1,56 0,8 160 39,17 21,33 11,95 8,15 3,65 2,11 190 55,76 37,92 24,45 17,25 7,35 4,22 210 64,75 48,98 36,51 27,53 11,29 6,32 16 20 64,75 240 64,75 53,10 44,12 20,88 11,04 265 64,75 57,94 33,7 17,14 280 64,75 42,0 22,17 325 64,75 44,84 365 64,75 1 / 2009 677

Basics of post installed rebar connections Bar Drill hole Max. F s,t l inst Fire resistance of bar in [kn] [mm] [mm] [kn] [mm] F30 F60 F90 F120 F180 F240 160 48,97 26,67 14,93 10,18 4,56 2,64 200 76,61 54,31 38,73 27,5 11,42 6,48 240 101,18 81,96 66,37 55,15 26,10 13,8 20 25 101,18 270 101,18 87,11 75,88 45,58 23,36 295 101,18 93,16 62,86 35,72 310 101,18 73,23 45,69 355 101,18 76,79 395 101,18 200 95,77 67,89 48,41 34,37 14,27 8,10 250 138,96 111,09 91,60 77,51 39,86 20,61 275 158,09 132,69 113,2 99,17 61,30 31,81 25 30 158,09 305 158,09 139,12 125,09 87,22 52,79 330 158,09 146,69 108,82 74,39 345 158,09 121,77 87,34 390 158,09 126,22 430 158,09 255 183,40 147,72 122,78 104,82 56,35 28,80 275 205,52 169,84 144,90 126,94 78,46 40,71 325 259,02 225,13 200,19 182,23 133,75 89,68 32 40 259,02 368 259,02 238,89 220,93 172,46 128,39 380 259,02 243,05 194,58 150,51 395 259,02 211,16 167,09 440 259,02 216,86 480 259,02 290 249,87 209,73 181,67 161,46 106,93 59,1 325 293,41 253,27 225,21 205,01 150,47 100,89 355 327,82 290,59 262,54 242,33 187,80 138,22 36 44 327,82 385 327,82 299,86 279,65 225,12 175,54 410 327,82 310,75 256,22 206,64 425 327,82 274,88 225,30 470 327,82 281,28 510 327,82 320 319,10 274,50 243,33 220,87 160,28 105,19 355 367,48 322,88 291,71 269,25 208,66 153,57 385 404,71 364,35 333,18 310,72 250,13 195,04 40 47 404,71 415 404,71 374,64 352,19 291,60 236,51 440 404,71 386,75 326,16 271,07 455 404,71 346,89 291,80 500 404,71 354,01 540 404,71 a) For tables according the standards to DIN 1045-1988, NF-ENV 1991-2-2(EC2), Österreichische Norm B 4700-2000, British-, Singapore- and Australian Standards see Warringtonfire report WF 166402 or/and IBMB Braunschweig report No 3357/0550-5. Hilti HIT-RE 500 rebar Bar connection parallel to slab or wall surface exposed to fire Max. bond stress, τ T, depending on actual clear concrete cover for classifying the fire resistance. It must be verified that the actual force in the bar during a fire, F s,t, can be taken up by the bar connection of the selected length, l inst. Note: Cold design for ULS is mandatory. F s, T (l inst c f ) π τ T where: (l inst c f ) l s ; 678 1 / 2009

Basics of post installed rebar connections l s = lap length = nominal diameter of bar l inst c f = selected overlap joint length; this must be at least l s, but may not be assumed to be more than 80 τ T = bond stress when exposed to fire Table 6: Critical temperature-dependent bond stress, τ crit,t, concerning overlap joint for Hilti-HIT RE 500 injection adhesive in relation to fire resistance class and required minimum concrete coverage c. Clear concrete cover c Max. bond stress, τ T [N/mm²] [mm] F30 F60 F90 F120 F180 F240 10 0 20 0,494 0 30 0,665 0 0 40 0,897 0,481 0 50 1,209 0,623 0 60 1,630 0,806 0,513 70 2,197 1,043 0,655 0,487 80 2,962 1,351 0,835 0,614 90 3,992 1,748 1,065 0,775 0,457 100 5,382 2,263 1,358 0,977 0,553 110 7,255 2,930 1,733 1,233 0,669 0,469 120 9,780 3,792 2,210 1,556 0,810 0,551 130 4,909 2,818 1,963 0,980 0,647 140 6,355 3,594 2,477 1,185 0,759 150 8,226 4,584 3,125 1,434 0,829 160 10.649 5,846 3,943 1,735 1,047 170 7,456 4,974 2,099 1,230 180 9,510 6,276 2,540 1,445 190 7,918 3,037 1,697 200 9,990 3,718 1,993 210 4,498 2,341 220 11,00 5,442 2,749 230 6,584 3,228 240 11,00 7,966 3,792 250 11,00 9,639 4,453 260 11,00 5,230 270 6,143 280 7,214 11,00 290 8,473 300 9,951 310 11,00 1 / 2009 679

Basics of post installed rebar connections 8 Fatigue of bonded-in reinforcement for joints with predominantly cyclical imposed loading 8.1 General notes For loadbearing elements which are subjected to considerable cyclic stress the bonded-in connections should be designed for fatigue. In that case evidence for fatigue of reinforcing steel bars, concrete and bond should be provided separately. For simple cases it is reasonable to use simplified methods on the safe side. The partial safety factors for loads are specified in the code for reinforced concrete. The partial safety factors for material are specified in Table 4.3. Table 4.3: Partial safety factors for materials subjected to cyclic loading Evidence for concrete bond reinforcing bars (steel) Partial safety factor 1.5 1.8 1.15 8.2 Fatigue of reinforcing bars (steel) The resistance for fatigue of reinforcing bars (steel) is specified in the actual code for reinforced concrete. The behaviour of the steel of reinforcing bars bonded-in by means of Hilti HIT is at least as good as cast-in place reinforcement. 8.3 Fatigue of bond and concrete (simplified approach) As a simple and conservative approach on the safe side evidence for fatigue is proven if the following equation is valid: F Sd,fat N Rd f fat where: F Sd,fat N Rd Design value of the anchorage force for the ruling loading model for fatigue. Design resistance for static load of the anchorage (bond and concrete). f fat Reduction factor for fatigue for bond and concrete: f fat = 0.5 If max/min of cycles is known, reduction factors are shown in Figure 4.13. 1 0.9 0.8 Diagram for a simplified approach with 2 10 6 cycles (Weyrauch diagram) Sd,fat max / N Rd 0.7 0.6 F Sd,fat F Sd,fat max 0.5 0.4 0.3 0.2 0.1 0 0 0.2 0.4 0.6 0.8 1 Sd,fat min / N Rd 0 time F Sd,fat min Figure 4.13: Reduction factors for fatigue for bond and concrete Hilti design software for rebar connections does also the fatigue design. If the simplified method is not satisfying, additional information using the Woehler - lines is available. Ask Hilti Technical Service for the Hilti Guideline: TWU-TPF 06a/02 Hilti HIT-Rebar: Fatigue. 680 1 / 2009

Basics of post installed rebar connections 1 / 2009 681

Hilti HIT-RE 500 post installed rebars Hilti HIT-RE 500 post installed rebars Injection mortar system Benefits Hilti HIT-RE 500 330 ml foil pack (also available as 500 ml and 1400 ml foil pack) Static mixer Rebar - suitable for non-cracked concrete C 20/25 to C 50/60 - high loading capacity - suitable for dry and water saturated concrete - under water application - large diameter applications - high corrosion resistant - long working time at elevated temperatures - odourless epoxy - embedment depth range: from 40 160 mm for M8 to 120 600 mm for M30 Concrete Fire resistance Fatigue European Technical Approval DIBt approval Drinking water appoved Corossion tested Marque NF Hilti anchor design software Hilti rebar design software Service temperature range Temperature range: -40 C to +80 C (max. long term temperature +50 C, max. short term temperature +80 C). Approvals / certificates Description Authority / Laboratory No. / date of issue European technical approval a) DIBt, Berlin ETA-08/0105 / 2008-05-26 DIBt approval DIBt, Berlin Z-21.8-1790 / 2007-11-29 Fire test report IBMB Braunschweig 3357/0550-5 / 2002-07-30 Assessment report (fire) Warringtonfire WF 166402 / 2007-10-26 a) All data given in this section according ETA-08/0105, issue 2008-05-26. 682 1 / 2009

Hilti HIT-RE 500 post installed rebars Materials Reinforcmenent bars according to EC2 Annex C Table C.1 and C.2N. Properties of reinforcement Product form Bars and de-coiled rods Class B C Characteristic yield strength f yk or f 0,2k (MPa) 400 to 600 Minimum value of k = (f t /f y ) k 1,08 1,15 < 1,35 Characteristic strain at maximum force, ε uk (%) 5,0 7,5 Bendability Maximum deviation from nominal mass (individual bar) (%) Bond: Minimum relative rib area, f R,min Nominal bar size (mm) 8 > 8 Nominal bar size (mm) 8 to 12 > 12 Bend / Rebend test ± 6,0 ± 4,5 0,040 0,056 Setting details For detailed information on installation see instruction for use given with the package of the product. Curing time for general conditions Data according ETA-08/0105, issue 2008-05-26 Temperature of the base material Working time in which anchor can be inserted and adjusted t gel Initial curing time t cure,ini Curing time before anchor can be fully loaded t cure 5 C T BM < 10 C 2 h 18 h 72 h 10 C T BM < 15 C 90 min 12 h 48 h 15 C T BM < 20 C 30 min 9 h 24 h 20 C T BM < 25 C 20 min 6 h 12 h 25 C T BM < 30 C 20 min 5 h 12 h 30 C T BM < 40 C 12 min 4 h 8 h T BM = 40 C 12 min 4 h 4 h For dry concrete curing times may be reduced according to the following table. For installation temperatures below +5 C all load values have to be reduced according to the load reduction factors given below. Curing time for dry concrete Temperature of the base material Working time in which anchor can be inserted and adjusted t gel Additional Hilti technical data Initial curing time t cure,ini Reduced curing time before anchor can be fully loaded t cure Load reduction factor T BM = -5 C 4 h 36 h 72 h 0,6 T BM = 0 C 3 h 25 h 50 h 0,7 T BM = 5 C 2 ½ h 18 h 36 h 1 T BM = 10 C 2 h 12 h 24 h 1 T BM = 15 C 1 ½ h 9 h 18 h 1 T BM = 20 C 30 min 6 h 12 h 1 T BM = 30 C 20 min 4 h 8 h 1 T BM = 40 C 12 min 2 h 4 h 1 1 / 2009 683

Hilti HIT-RE 500 post installed rebars Dry and water-saturated concrete, hammer drilling a) a ) Note: Manual cleaning for element sizes d 16mm and embedment depth h ef 20 d only! 684 1 / 2009

Hilti HIT-RE 500 post installed rebars Dry and water-saturated concrete, diamond coring drilling; Hilti technical information only a) Note: Manual cleaning for element sizes d 16mm and embedment depth h ef 20 d only! Fitness for use Some creep tests have been conducted in accordance with ETAG guideline 001 part 5 and TR 023 in the following conditions : in dry environnement at 50 C during 90 days. These tests show an excellent behaviour of the post installed connection made with HIT-RE 500: low displacements with long term stability, failure load after exposure above reference load. 1 / 2009 685

Hilti HIT-RE 500 post installed rebars Resistance to chemical substances Categories Chemical substances resistant Alkaline products Acids Solvents Products from job site Environnement Drilling dust slurry ph = 12,6 Potassium hydroxide solution (10%) ph = 14 Acetic acid (10%) Nitric acid (10%) Hydrochloric acid (10%) Sulfuric acid (10%) Benzyl alcohol Ethanol Ethyl acetate Methyl ethyl keton (MEK) Trichlor ethylene Xylol (mixture) Concrete plasticizer Diesel Engine oil Petrol Oil for form work Sslt water De-mineralised water Sulphurous atmosphere (80 cycles) Non resistant Electrical Conductivity HIT-RE 500 in the hardened state is not conductive electrically. Its electric resistivity is 66 10 12 Ω.m (DIN IEC 93 12.93). It is adapted well to realize electrically insulating anchorings (ex: railway applications, subway). 686 1 / 2009

Hilti HIT-RE 500 post installed rebars Basic design data for rebar design according to ETA Bond strength Bond strength in N/mm² according to ETA for good bond conditions for hammer drilling, compressed air drilling, dry diamond core drilling Rebar (mm) Concrete class C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60 8 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 10 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 12 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 14 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 16 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 18 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 20 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 22 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 24 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 25 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 26 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 28 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 30 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 32 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 34 1,6 2,0 2,3 2,6 2,9 3,3 3,6 3,9 4,2 36 1,5 1,9 2,2 2,6 2,9 3,3 3,6 3,8 4,1 40 1,5 1,8 2,1 2,5 2,8 3,1 3,4 3,7 4,0 1 / 2009 687

Hilti HIT-RE 500 post installed rebars Bond strength in N/mm² according to ETA for good bond conditions for wet diamond core drilling Rebar (mm) Concrete class C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60 8 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 10 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 12 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 14 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 16 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 18 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 20 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 22 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 24 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 25 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3 26 1,6 2,0 2,3 2,7 2,7 2,7 2,7 2,7 2,7 28 1,6 2,0 2,3 2,7 2,7 2,7 2,7 2,7 2,7 30 1,6 2,0 2,3 2,7 2,7 2,7 2,7 2,7 2,7 32 1,6 2,0 2,3 2,7 2,7 2,7 2,7 2,7 2,7 34 1,6 2,0 2,3 2,6 2,6 2,6 2,6 2,6 2,6 36 1,5 1,9 2,2 2,6 2,6 2,6 2,6 2,6 2,6 40 1,5 1,8 2,1 2,5 2,5 2,5 2,5 2,5 2,5 Minimum anchorage length According to ETA-08/0105, issue 2008-05-26, the minimum anchorage length shall be increased by factor 1,5 for wet diamond core drilling. For all the other given drilling methods the factor is 1,0. 688 1 / 2009

Hilti HIT-RE 500 post installed rebars Minimum and maximum embedment depths and lap lengths for C20/25 according to ETA Diameter d s [mm] Rebar f y,k [N/mm²] Hammer drilling, Compressed air drilling, Dry diamond coring drilling l b,min * [mm] l 0,min * [mm] Wet diamond coring drilling l b,min * [mm] l 0,min * [mm] l max [mm] 8 500 113 200 170 300 1000 10 500 142 200 213 300 1000 12 500 170 200 255 300 1200 14 500 198 210 298 315 1400 16 500 227 240 340 360 1600 18 500 255 270 383 405 1800 20 500 284 300 425 450 2000 22 500 312 330 468 495 2200 24 500 340 360 510 540 2400 25 500 354 375 532 563 2500 26 500 369 390 553 585 2600 28 500 397 420 595 630 2800 30 500 425 450 638 675 3000 32 500 454 480 681 720 3200 34 500 492 510 738 765 3200 36 500 532 540 797 810 3200 40 500 616 621 925 932 3200 l b,min (8.6) and l 0,min (8.11) are calculated for good bond conditions with maximum utilisation of rebar yield strength f yk = 500 N/mm² and α 6 = 1,0 1 / 2009 689

Hilti HIT-RE 500 post installed rebars Precalculated values Example of pre-calculated values for anchoring Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions For all drilling procedures, excluding wet diamond core drilling (DD) Rebar Anchorage Design Mortar Anchorage Design Mortar length l bd value N Rd volume length l bd value N Rd volume [mm] [mm] [kn] [ml] [mm] [kn] [ml] α 1 =α 2 =α 3 =α 4 =α 5 =1.0 α 2 or α 5 = 0.7 α 1 = α 3 = α 4 = 1.0 100 6,79 8 100 9,70 8 8 160 10,86 12 160 15,52 12 200 13,58 15 - - - 322 21,87 24 225 21,87 17 121 10,24 11 121 14,63 11 200 16,96 18 200 24,22 18 10 250 21,20 23 250 30,28 23 300 25,43 27 - - - 403 34,13 36 282 34,13 25 145 14,74 15 145 21,06 15 240 24,41 25 240 34,87 25 12 300 30,51 32 300 43,59 32 360 36,61 38 - - - 483 49,13 51 338 49,13 36 169 20,09 20 169 28,70 20 280 33,26 34 280 47,52 34 14 350 41,58 42 350 59,40 42 480 57,02 58 - - - 564 66,96 68 395 66,96 48 193 26,22 26 193 37,45 26 320 43,42 43 320 62,02 43 16 400 54,27 54 400 77,53 54 480 65,12 65 - - - 644 87,39 87 451 87,39 61 217 36,86 46 217 52,66 46 360 61,04 76 360 87,20 76 18 450 76,30 95 450 109,00 95 540 91,56 115 - - - 725 122,87 154 507 122,87 108 242 40,96 51 242 58,51 51 400 67,82 85 400 96,89 85 20 500 84,78 106 500 121,11 106 600 101,74 127 - - - 805 136,52 171 564 136,52 120 266 49,57 56 266 70,81 56 440 82,08 93 440 117,26 93 22 550 102,60 117 550 146,58 117 660 123,12 140 - - - 886 165,22 188 620 165,22 131 * Values corresponding to the minimum anchorage length. The maximum permissible load is valid for good bond conditions as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of mortar correspond to the formula 1,2 (d 0 ²-d²) π lb/4 690 1 / 2009

Hilti HIT-RE 500 post installed rebars Example of pre-calculated values for anchoring Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions For all drilling procedures, excluding wet diamond core drilling (DD) Rebar Anchorage Design Mortar Anchorage Design Mortar length l bd value N Rd volume length l bd value N Rd volume [mm] [mm] [kn] [ml] [mm] [kn] [ml] α 1 =α 2 =α 3 =α 4 =α 5 =1.0 α 2 or α 5 = 0.7 α 1 = α 3 = α 4 = 1.0 290 58,97 61 290 84,24 61 480 97,65 102 480 139,51 102 24 600 122,07 127 600 174,38 127 720 146,48 153 - - - 966 196,57 205 676 196,57 143 302 64,04 114 302 91,49 114 500 106,06 188 500 151,51 188 25 625 132,57 235 625 189,39 235 750 159,08 282 - - - 1 006 213,48 378 705 213,48 265 314 69,26 67 314 98,94 67 520 114,70 110 520 163,85 110 26 650 143,37 138 650 204,81 138 780 172,04 165 - - - 1 047 230,87 222 733 230,87 155 338 80,35 72 338 114,78 72 600 142,56 127 600 203,66 127 28 700 166,32 148 700 237,60 148 840 199,59 178 - - - 1 127 267,83 239 789 267,83 167 362 92,22 160 362 131,74 160 600 152,71 265 600 218,16 265 30 750 190,89 332 750 272,70 332 900 229,07 398 - - - 1 418 360,91 627 845 307,39 374 386 104,87 210 386 149,81 210 640 173,66 347 640 248,09 347 32 800 217,08 434 800 310,11 434 960 260,50 521 - - - 1 288 349,57 699 902 349,57 490 426 118,43 90 426 169,19 90 680 188,86 144 680 269,81 144 34 850 236,08 180 850 337,26 180 1 020 283,30 216 - - - 1 421 394,78 301 995 394,78 211 452 132,78 96 452 189,69 96 720 211,74 153 720 302,49 153 36 900 264,68 191 900 378,11 191 1 080 317,61 229 - - - 1 505 442,60 319 1 054 442,60 223 522 163,96 701 522 234,22 701 800 251,40 1 074 800 359,14 1 074 40 1 000 314,25 1 343 1 000 448,93 1 343 1 200 377,10 1 612 - - - 1 739 546,52 2 336 1 217 546,52 1 635 * Values corresponding to the minimum anchorage length. The maximum permissible load is valid for good bond conditions as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of mortar correspond to the formula 1,2 (d 0 ²-d s ²) π lb/4 for hammer drilling 1 / 2009 691

Hilti HIT-RE 500 post installed rebars Example of pre-calculated values for overlap joints Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions For all drilling procedures, excluding diamond wet (DD) Rebar Anchorage Design Mortar Anchorage Design Mortar length l bd value N Rd volume length l bd value N Rd volume [mm] [mm] [kn] [ml] [mm] [kn] [ml] α 1 =α 2 =α 3 =α 5 =α 6 =1,0 α 2 or α 5 = 0,7 α 1 = α 3 = α 6 = 1,0 200 13,58 15 200 19,40 15 8 250 16,98 19 - - - 300 20,37 23 - - - 322 21,87 24 225 21,87 17 200 16,96 18 200 24,22 18 250 21,20 23 250 30,28 23 10 300 25,43 27 - - - 350 29,67 32 - - - 403 34,13 36 282 34,13 25 200 20,34 21 200 29,06 21 240 24,41 25 240 34,87 25 12 300 30,51 32 300 43,59 32 360 36,61 38 - - - 483 49,13 51 338 49,13 36 210 24,95 25 210 35,64 25 280 33,26 34 280 47,52 34 14 350 41,58 42 350 59,40 42 480 57,02 58 - - - 564 66,96 68 395 66,96 48 240 32,56 33 240 46,52 33 320 43,42 43 320 62,02 43 16 400 54,27 54 400 77,53 54 480 65,12 65 - - - 644 87,39 87 451 87,39 61 270 45,78 57 270 65,40 57 360 61,04 76 360 87,20 76 18 450 76,30 95 450 109,00 95 540 91,56 115 - - - 725 122,87 154 507 122,87 108 300 50,87 64 300 72,67 64 400 67,82 85 400 96,89 85 20 500 84,78 106 500 121,11 106 600 101,74 127 - - - 805 136,52 171 564 136,52 120 330 61,56 70 330 87,95 70 440 82,08 93 440 117,26 93 22 550 102,60 117 550 146,58 117 660 123,12 140 - - - 886 165,22 188 620 165,22 131 Values corresponding to the minimum anchorage length. The maximum permissible load is valid for good bond conditions as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of mortar correspond to the formula 1,2 (d 0 ²-d s ²) π lb/4 for hammer drilling 692 1 / 2009

Hilti HIT-RE 500 post installed rebars Example of pre-calculated values for overlap joints Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions For all drilling procedures, excluding diamond wet (DD) Rebar Anchorage Design Mortar Anchorage Design Mortar length l bd value N Rd volume length l bd value N Rd volume [mm] [mm] [kn] [ml] [mm] [kn] [ml] α 1 =α 2 =α 3 =α 4 =α 5 =1.0 α 2 or α 5 = 0.7 α 1 = α 3 = α 4 = 1.0 360 73,24 76 360 104,63 76 480 97,65 102 480 139,51 102 24 600 122,07 127 600 174,38 127 720 146,48 153 - - - 966 196,57 205 676 196,57 143 375 79,54 141 375 113,63 141 500 106,06 188 500 151,51 188 25 625 132,57 235 625 189,39 235 750 159,08 282 - - - 1 006 213,48 378 705 213,48 265 390 86,02 83 390 122,89 83 520 114,70 110 520 163,85 110 26 650 143,37 138 650 204,81 138 780 172,04 165 - - - 1 047 230,87 222 733 230,87 155 420 99,79 89 420 142,56 89 600 142,56 127 600 203,66 127 28 700 166,32 148 700 237,60 148 840 199,59 178 - - - 1 127 267,83 239 789 267,83 167 450 114,53 199 450 163,62 199 600 152,71 265 600 218,16 265 30 750 190,89 332 750 272,70 332 900 229,07 398 - - - 1 418 360,91 627 845 307,39 374 480 130,25 261 480 186,07 261 640 173,66 347 640 248,09 347 32 800 217,08 434 800 310,11 434 960 260,50 521 - - - 1 288 349,57 699 902 349,57 490 510 141,65 108 510 202,35 108 680 188,86 144 680 269,81 144 34 850 236,08 180 850 337,26 180 1 020 283,30 216 - - - 1 421 394,78 301 995 394,78 211 540 158,81 115 540 226,87 115 720 211,74 153 720 302,49 153 36 900 264,68 191 900 378,11 191 1 080 317,61 229 - - - 1 505 442,60 319 1 054 442,60 223 600 188,55 806 600 269,36 806 800 251,40 1 074 800 359,14 1 074 40 1 000 314,25 1 343 1 000 448,93 1 343 1 200 377,10 1 612 - - - 1 739 546,52 2 336 1 217 546,52 1 635 * Values corresponding to the minimum anchorage length. The maximum permissible load is valid for good bond conditions as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of mortar correspond to the formula 1,2 (d 0 ²-d s ²) π lb/4 for hammer drilling 1 / 2009 693

Hilti HIT-HY 150 post installed rebars Hilti HIT-HY 150 post installed rebars Injection mortar system Benefits Hilti HIT-HY 150 330 ml foil pack (also available as 500 ml and 1400 ml foil pack) Statik mixer Rebar - suitable for concrete C 12/15 to C 50/60 - high loading capacity and fast cure - suitable for dry and water saturated concrete - for rebar diameters up to 25 mm - non corrosive to rebar elements - good load capacity at elevated temperatures - hybrid chemistry - suitable for embedment length till 2000 mm - suitable for applications down to - 5 C Concrete Fire resistance Fatigue DIBt approval Drinking water appoved Corossion tested Hilti anchor design software Hilti rebar design software Service temperature range Temperature range: -40 C to +80 C (max. long term temperature +50 C, max. short term temperature +80 C). Approvals / certificates a) Description Authority / Laboratory No. / date of issue DIBt approval a) DIBt, Berlin Z-21.8-1648 / 2007-09-19 Fire test report IBMB Braunschweig 3162/6989 / 1999-07-16 Assessment report (fire) Warringtonfire WF 166402 / 2007-10-26 The data given in this section are derived from DIBt Z-21.8-1648 issue 2007-09-19 and adapted to fit EC2 design method. Materials Reinforcmenent bars according to EC2 Annex C Table C.1 and C.2N. 694 1 / 2009

Hilti HIT-HY 150 post installed rebars Properties of reinforcement Product form Bars and de-coiled rods Class B C Characteristic yield strength f yk or f 0,2k (MPa) 400 to 600 Minimum value of k = (f t /f y ) k 1,08 1,15 < 1,35 Characteristic strain at maximum force, ε uk (%) 5,0 7,5 Bendability Maximum deviation from nominal mass (individual bar) (%) Bond: Minimum relative rib area, f R,min Nominal bar size (mm) 8 > 8 Nominal bar size (mm) 8 to 12 > 12 Bend / Rebend test ± 6,0 ± 4,5 0,040 0,056 Setting details For detailed information on installation see instruction for use given with the package of the product. Working time, Curing time Temperature of the base material T BM Working time t gel Curing time t cure * -5 C T BM < 0 C 90 min 9 h 0 C T BM < 5 C 45 min 4,5 h 5 C T BM < 10 C 20 min 2 h 10 C T BM < 20 C 6 min 90 min 20 C T BM < 30 C 4 min 50 min 30 C T BM 40 C 2 min 40 min * The curing time data are valid for dry anchorage base only. For water saturated anchorage bases the curing times must be doubled. 1 / 2009 695

Hilti HIT-HY 150 post installed rebars Dry and water-saturated concrete, hammer drilling a) a) Note: Manual cleaning for element sizes d 16mm and embedment depth h ef 10 d only! 696 1 / 2009

Hilti HIT-HY 150 post installed rebars Fitness for use Creep behaviour Creep tests have been conducted in accordance with national standards in different conditions: in wet environnement at 23 C during 90 days in dry environnement at 43 C during 90 days. These tests show an excellent behaviour of the post installed connection made with HIT-HY 150: low displacements with long term stabilisation, failure load after exposure above reference load. Resistance to chemical products HIT-HY 150 has been tested to its resistance to chemical products and the results are given in the table below: Chemical product Concentration First effects Resistance (in % of weight) (in days) Acetic acid Pure 6 o 10 % + Hydrochloric Acid 20 % + Nitric Acid 40 % < 1 - Phosphoric Acid 40 % + Sulphuric acid 40 % + Ethyl acetate Pure 8 - Acetone Pure 1 - Ammoniac 5 % 21 - Diesel Pure + Gasoline Pure + Ethanol 96 % 30 o Machine oils Pure + Methanol Pure 2 - Peroxide of hydrogen 30% 3 o Solution of phenol Saturated < 1 - Silicate of sodium 50% ph=14! + Solution of chlorine saturated + Solution of hydrocarbons 60 % vol Toluene; 30 % vol + Xylene 10 % vol Naphtalene of methyl Salted solution (sodium 10 % + chloride) Suspension of cement Saturated + Carbon tetrachloride Pure + Xylene Pure + We can retain that HIT-HY 150 behaves well as alkaline middle and that it is very resistant: in aqueous solutions in elevated ph (ex: silicate of sodium): no risk of saponification under weathering in salty solutions (ex: sea water) in solutions saturated in chlorine (ex: applications in swimming pool). Electrical conductivity HIT-HY 150 in cured state shows low electrical conductivity. Its electric resistivity is 2.10 11 Ω.m (DIN VDE 0303T3). It suits well electrically insulating anchoring (ex: railway applications, subway). 1 / 2009 697

Hilti HIT-HY 150 post installed rebars Basic design data for rebar design Bond strength Bond strength in N/mm² according to EC2 for good bond conditions for all drilling methods Rebar (mm) Concrete class C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60 8 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 10 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 12 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 14 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 16 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 18 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 20 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 22 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 24 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 25 1,6 2,0 2,3 2,7 3,0 3,0 3,0 3,0 3,0 Minimum anchorage length The multiplication factor for minimum anchorage length shall be considered as 1,5 for all drilling methods. Minimum and maximum embedment depth and lap lengths Diameter d s [mm] Rebar f y,k [N/mm²] l b,min * [mm] Hammer drilling, Compressed air drilling l 0,min * [mm] lmax [mm] 8 500 170 300 1000 10 500 213 300 1000 12 500 255 300 1000 14 500 298 315 1000 16 500 340 360 1500 20 500 425 450 2000 25 500 532 563 2000 *l b,min (8.6) and l 0,min (8.11) are calculated for good bond conditions with maximum utilisation of rebar yield strength f yk = 500 N/mm² and α 6 = 1,0 698 1 / 2009

Hilti HIT-HY 150 post installed rebars Precalculated values Example of pre-calculated values for anchoring Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions Rebar Anchorage Design Mortar Anchorage Design Mortar length l bd value N Rd volume length l bd value N Rd volume [mm] [mm] [kn] [ml] [mm] [kn] [ml] α 1 =α 2 =α 3 =α 4 =α 5 =1.0 α 2 or α 5 = 0.7 α 1 = α 3 = α 4 = 1.0 170 9,84 13 113 9,37 9 8 200 11,57 15 200 16,53 15 320 18,51 24 - - - 378 21,87 29 265 21,87 20 213 15,36 19 213 21,94 19 250 18,06 23 250 18,06 23 10 300 21,67 27 300 30,95 27 400 28,89 36 - - - 473 34,13 43 331 34,13 30 255 22,11 27 255 31,58 27 300 25,99 32 300 37,13 32 12 360 31,19 38 360 44,55 38 480 41,58 51 567 49,13 60 397 49,13 42 298 30,13 36 298 43,04 36 400 40,48 48 400 57,83 48 14 420 42,50 51 420 60,72 51 560 56,67 68 - - - 662 66,96 80 463 66,96 56 340 39,33 46 340 56,18 46 400 40,48 54 400 66,04 54 16 480 55,48 65 480 79,25 65 640 73,97 87 - - - 756 87,39 103 529 87,39 72 425 61,43 90 425 87,76 90 500 72,22 106 500 103,17 106 20 600 86,66 127 600 123,81 127 800 115,55 170 - - - 945 136,52 200 662 136,52 140 532 96,07 200 532 137,24 200 600 108,41 226 600 154,88 226 25 750 135,52 282 750 193,59 282 1000 180,69 376 - - - 1181 213,48 444 827 213,48 311 * Values corresponding to the minimum anchorage length. The maximum permissible load is valid for good bond conditions as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of mortar correspond to the formula 1,2 (d 0 ²-d²) π lb/4 1 / 2009 699

Hilti HIT-HY 150 post installed rebars Example of pre-calculated values for overlap joints Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions Rebar Anchorage Design Mortar Anchorage Design Mortar length l bd value N Rd volume length l bd value N Rd volume [mm] [mm] [kn] [ml] [mm] [kn] [ml] α 1 =α 2 =α 3 =α 5 =α 6 =1,0 α 2 or α 5 = 0,7 α 1 = α 3 = α 6 = 1,0 300 17,35 23 300 21,85 23 8 310 17,93 23 - - - 320 18,51 24 - - - 378 21,87 29 - - - 300 21,67 27 300 30,95 27 320 23,11 29 320 33,01 29 10 350 25,28 32 - - - 400 28,89 36 - - - 473 34,13 43 331 34,15 30 300 25,99 32 300 37,13 32 320 27,72 34 320 33,01 29 12 350 30,32 37 350 43,32 37 480 41,58 51 - - - 567 49,12 60 397 49,13 42 315 31,88 38 315 45,54 38 350 35,42 42 350 50,60 42 14 420 42,50 51 420 60,72 51 560 56,67 68 - - - 662 66,99 80 463 66,94 56 460 53,16 62 460 75,95 62 470 54,32 64 470 77,60 64 16 480 55,48 65 480 79,25 65 640 73,97 87 - - - 756 87,37 103 529 87,34 72 450 65,00 95 450 92,85 95 500 72,22 106 500 103,17 106 20 600 86,66 127 600 123,81 127 800 115,55 170 - - - 945 136,50 200 662 136,60 140 563 101,73 212 563 145,32 212 600 108,41 226 600 154,88 226 25 750 135,52 282 750 193,59 282 1000 180,69 376 - - - 1181 213,39 444 827 213,47 311 * Values corresponding to the minimum anchorage length. The maximum permissible load is valid for good bond conditions as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of mortar correspond to the formula 1,2 (d 0 ²-d s ²) π lb/4 700 1 / 2009

Hilti HIT-HY 150 post installed rebars 1 / 2009 701

Hilti HIT-HY 150 MAX post installed rebars Hilti HIT-HY 150 MAX post installed rebars Injection mortar system Benefits Hilti HIT-HY 150 MAX 330 ml foil pack (also available as 500 ml and 1400 ml foil pack) Static mixer Rebar - suitable for concrete C 12/15 to C 50/60 - high loading capacity and fast cure - suitable for dry and water saturated concrete - for rebar diameters up to 25 mm - non corrosive to rebar elements - good load capacity at elevated temperatures - hybrid chemistry - multiplication factor for minimum anchoring and splice length 1.0 - suitable for embedment length till 2000 mm - suitable for applications down to - 10 C Concrete Fire resistance Fatigue European Technical Approval CE conformity Drinking water appoved Corossion tested Hilti anchor design software Hilti rebar design software Service temperature range Temperature range: -40 C to +80 C (max. long term temperature +50 C, max. short term temperature +80 C). Approvals / certificates a) Description Authority / Laboratory No. / date of issue European technical approval a) CSTB, France ETA-08/0202 / 2008-07-24 Fire test report IBMB Braunschweig 3884/8246 / 2007-05-24 Assessment report (fire) Warringtonfire WF 166402 / 2007-10-26 All data given in this section according ETA-08/0202, issue 2008-07-24. Materials Reinforcmenent bars according to EC2 Annex C Table C.1 and C.2N. 702 1 / 2009

Hilti HIT-HY 150 MAX post installed rebars Properties of reinforcement Product form Bars and de-coiled rods Class B C Characteristic yield strength f yk or f 0,2k (MPa) 400 to 600 Minimum value of k = (f t /f y ) k 1,08 1,15 < 1,35 Characteristic strain at maximum force, ε uk (%) 5,0 7,5 Bendability Maximum deviation from nominal mass (individual bar) (%) Bond: Minimum relative rib area, f R,min Nominal bar size (mm) 8 > 8 Nominal bar size (mm) 8 to 12 > 12 Bend / Rebend test ± 6,0 ± 4,5 0,040 0,056 Setting details For detailed information on installation see instruction for use given with the package of the product. Working time, Curing time Temperature of the base material T BM Working time t gel Curing time t cure -10 C T BM < -5 C 180 min 12 h -5 C T BM < -0 C 90 min 9 h 0 C T BM < 5 C 45 min 4,5 h 5 C T BM < 10 C 20 min 2 h 10 C T BM < 15 C 7 min 50 min 15 C T BM < 20 C 6 min 40 min 20 C T BM < 25 C 5 min 30 min 25 C T BM < 30 C 3 min 30 min 30 C T BM 40 C 2 min 30 min 1 / 2009 703

Hilti HIT-HY 150 MAX post installed rebars Dry and water-saturated concrete, hammer drilling a) a) Note: Manual cleaning for element sizes d 16mm and embedment depth h ef 10 d only! 704 1 / 2009