ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT

Similar documents
PIP INSA1000 Acoustic Insulation Systems Specification

Addendum to Specifications

FIRE STATION 55 June 14, 2010

SECTION HVAC INSULATION

This specification describes the minimum requirements for industrial thermal insulation.

Design & Construction Standards, Revised January

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2

PROJ. NO SECTION HVAC DUCT INSULATION

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

ITW INSULATION SYSTEMS

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

APPLICATION INSTRUCTIONS FOR MUFFL-JAC ACOUSTICAL JACKETING ON HOT PIPE INSULATION

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

079 Quick Installation Guide

ITW INSULATION SYSTEMS

B. Refer to Section : Air Distribution for lined ductwork requirements.

INSTALLATION GUIDELINES FOR CHILL WATER PIPE INSULATION

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

SECTION (15081) - HVAC INSULATION

SPECIFICATION FOR COLD INSULATION

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

ITW INSULATION SYSTEMS

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

SECTION PIPING INSULATION

Installation Guidelines for ITW Insulation Systems Metal Jacketing Used on Insulated Pipe

INSTALLATION GUIDELINES FOR COLD/CRYOGENIC PIPE INSULATION

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER

SECTION PLUMBING INSULATION

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

Division 15 INSULATION Section 15100

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

MECHANICAL INSULATION

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

Addendum 1 Section THERMAL INSULATION FOR PIPING Burrow Avenue Pumping Station Upgrades Page 1 of 5

PIP INSC1000 Cold Service Insulation Materials and Installation Specification

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION MECHANICAL INSULATION

SPECIFICATION GUIDELINES FOR THE USE OF CRYOGEL Z ON COLD PIPING AND EQUIPMENT

INSTALLATION GUIDELINE FOR TRYMER INSULATION

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

Mechanical Insulation for Refrigeration Systems

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin

1 of 17. PO Box Bellevue Rd, Newark, DE V F

379 Quick Installation Guide

NCCER Progress Blvd, Alachua, Florida Tel: (888)

INSTALLATION GUIDELINE FOR TRYMER SUPERCEL PHENOLIC INSULATION

SECTION HVAC INSULATION

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

University of Delaware

TENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

SECTION MECHANICAL INSULATION

FOAMGLAS INSULATION SPECIFICATION

STANDARD SPECIFICATIONS. Followings have been covered in this section. The work is to be carried based on the standard specifications:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL-FIBER FIREPROOFING REPORT HOLDER: THERMAL CERAMICS, INC.

University of Houston Master Construction Specifications Insert Project Name

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

INSULATION SECTION 15250

SECTION HVAC PIPING INSULATION

INDUSTRIAL SYSTEMS. Application Manual for Piping Equipment. ARMASOUND INDUSTRIAL SYSTEMS - Application Manual for Piping Equipment

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

SECTION GYPSUM BOARD

A. Source Limitations: Obtain each type of building insulation through one source.

SECTION BUILT-UP BITUMINOUS WATERPROOFING

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

SECTION GYPSUM BOARD & SHEATHING SYSTEMS

K-FLEX K-FONIK INDUSTRIAL

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17

PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service

.1 The following is a list of standards which may be referenced in this Section:

Revision:C Pipework Insulation Issued:14/11/2012 PIPEWORK INSULATION CU14. 14/11/2012 Page 1 of 10 Pipework Insulation - RevC

PIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D

CFC & HCFC Free Thermal Insulation INSTALLATION AND SPECIFICATION GUIDE

Duct Wrap Flexible Wraps

SECTION DUCT INSULATION

National Master Specification (NMS) Section Publisher: Spex.ca Page 1. Approved: RELATED REQUIREMENTS.1 Section [ ].

State of Alaska Section State Office Building HVAC Fan Replacement MECHANICAL INSULATION

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

Recommended Installation and Repair Guide

Installation Manual PIPE AND EQUIPMENT INSULATION

Sept 30, 2004 Page 1

SECTION GYPSUM BOARD ASSEMBLIES

TENOCHCA HALL - PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

BuildingName The Description of the Project P DOCUMENTS

SECTION MECHANICAL SYSTEMS INSULATION

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

Transcription:

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT Specification for Acoustical Insulation (Lagging) for Piping and Equipment 1 of 5

TABLE OF CONTENTS 1.0SCOPE..... 3 2.0REFERENCED PUBLICATIONS... 3 3.0GENERAL... 3 4.0MATERIALS... 3 5.0ABSORPTIVE LAYER APPLICATION (INSULATION)... 4 6.0BARRIER LAYER APPLICATION... 4 7.0FINISH APPLICATION... 4 8.0IRREGULAR SURFACES... 5 9.0FLASHING... 5 Specification for Acoustical Insulation (Lagging) for Piping and Equipment 2 of 5

1.0 SCOPE 1.1 This specification describes the materials for and the application of acoustical insulation (lagging) for piping and equipment in hot and cold services. 2.0 REFERENCED PUBLICATIONS The following publications (latest editions) form part of this specification: COMPANY Engineering Specifications Cold Piping and Equipment Insulation Hot Piping and Equipment Insulation 3.0 GENERAL 3.1 This specification requires compliance with all applicable federal, state, and local laws and regulations. 3.2 Piping and equipment that is specified to receive acoustical insulation shall be insulated in accordance with this specification and any additional project requirements. 3.3 All equipment that is to be insulated will be listed on the equipment insulation schedule along with the insulation type, material, and thickness. 3.4 All piping that is to be insulated will be listed on the line schedule along with the insulation type, material, and thickness. 3.5 General insulation requirements are covered in COMPANY Engineering Specification IC 1.0.0 for cold service ( 225 F to +70 F) ( 143 C to +21C) installations and IH 1.0.0 for hot service (+70 F to +1200 F) (+21 C to +649 C) installations. All requirements of COMPANY Engineering Specifications shall apply except any exceptions or variations stated in this specification shall take precedence where acoustical insulation is specified. 3.6 Reusable pad type insulation covers may be used for the services specified in COMPANY Engineering Specification, provided they are supplied with a noise barrier layer. 3.7 Only lead free materials shall be used. 4.0 MATERIALS 4.1 All materials shall conform to the requirements of COMPANY Engineering Specifications except as modified by this specification. 4.2 Absorptive layer materials shall be one of the following: a. Glass fiber with a minimum density of 3 lb/ft 3 (48 kg/m 3 ) of specified thickness. b. Mineral fiber with a minimum density of 8 lb/ft 3 (128 kg/m 3 ) of specified thickness. 4.3 Barrier layer materials shall be one of the following: a. Loaded vinyl sheeting, such as Soundmat PB by Soundcoat Co. or equal, of specified surface weight. b. Loaded mastic, such as Acousti Lag by RPR Products Inc. or equal, of specified surface weight. c. Loaded vinyl metal laminated sheeting of specified surface weight. 4.4 Laminates providing combinations of absorptive, barrier, or finish layers shall be one of the following: a. Loaded vinyl sheeting laminated to aluminum or stainless steel jacketing, such as Acousti Jac Aluminum or Acousti Jac SS by RPR Products Inc. or equal, of specified surface weight. 4.5 All materials shall be asbestos free. Specification for Acoustical Insulation (Lagging) for Piping and Equipment 3 of 5

5.0 ABSORPTIVE LAYER APPLICATION (Insulation) 5.1 For cold service ( 225 F to +70 F) ( 143 C to +21 C) installations, the complete thermal system (basic insulation material, coverings and coatings, and sealers) shall be applied before any acoustical absorptive material is applied. A vapor barrier shall be installed between the acoustical insulation and the outer jacketing. 5.2 For hot service (+70 F to +1200 F) (+21 C to +649 C) installations, the acoustic absorptive material shall be applied directly to the piping or equipment. 5.3 For installations where thermal insulation already exists, the acoustic absorptive layer shall be applied directly over the existing insulation without modification to the thermal system. 5.4 All surfaces (including valve bodies, flanges, fittings, etc.) on the equipment or length of duct or piping that is to be acoustically insulated shall be covered with the absorptive material. Hangers and other supports shall also be covered. 5.5 Absorptive insulation shall be applied with a snug, tight fit at all joints, longitudinal and circumferential. If a thickness of more than 2 inches (50mm) is specified, the insulation shall be applied in multiple layers, staggering all joints. All openings shall be packed with loose insulation using elastomeric adhesives. Insulating cements shall not be used. 5.6 Insulation shall be secured on piping and equipment with wire or bands as required by COMPANY Engineering Specification IC 1.0.0 or IH 1.0.0. Pins and clips shall not be used to secure the insulation. 5.7 Elbows shall be covered with either preformed or field cut insulation of the same material and thickness as the pipe insulation. For other items like flanges in the system, the same treatment shall be applied in the most efficient manner. 6.0 BARRIER LAYER APPLICATION 6.1 Sheet barrier materials shall be applied in a watershed fashion, and all joints of barrier material and absorptive material shall be staggered. Circumferential and longitudinal joints of sheet barrier material shall be overlapped a minimum of 3 inches (76mm). On horizontal joints of sheet barrier material and loaded mastics, the sheet material shall be extended a minimum of 3 inches (76mm) over the mastic. On vertical joints, the mastic shall extend 3 inches (76mm) over the sheet material to provide proper watershed. All sheet barrier materials shall be applied in an airtight, gapless fashion. 6.2 The continuity of the barrier layer shall not be broken. Where it is impossible to fit the entire specified thickness of absorptive and barrier layers, the thickness of the absorptive layer shall be decreased to allow clearance. 6.3 On loaded vinyl sheet barrier materials where an additional finish is to be applied, bands, wire, tape, or adhesive bonding are all acceptable means of attachment. On vinyl sheet barrier material applications, when these materials will act as the finish surface, wire or tape shall not be used for attachment. To ensure gapless joints on vinyl sheet applications, all joints shall be adhesively bonded. Sheet metal screws shall not be used on plain vinyl sheet barrier layer materials. VENDORS should be consulted for specific instructions and limitations for their products. 7.0 FINISH APPLICATION 7.1 The final finish jacketing shall be secured with bands only. Screws or rivets shall not be used. 7.2 Prefabricated metal elbows and other fittings shall be used whenever possible. Specification for Acoustical Insulation (Lagging) for Piping and Equipment 4 of 5

7.3 All longitudinal and circumferential seams shall be caulked. Cuts and openings for projections shall be made as tight as possible. All openings and seams shall be caulked with a nonhardening, nonshrinking type caulking compound. 7.4 There shall be no direct or indirect metalto metal contact of equipment or pipe walls with outer jacketing materials. The use of weld studs, weld pins, peg rivets, or similar devices which could couple the jacketing material to the equipment or piping walls is prohibited. The use of the insulation system shown in COMPANY Engineering Specification IH 1.0.0, Figure 6, is prohibited for acoustical insulation systems since it couples the jacketing to the vessel. 7.5 The outer jacketing material shall form a total enclosure around the piping and equipment. There shall be no leaks, voids, or openings in the jacketing material. 8.0 IRREGULAR SURFACES 8.1 All irregular surfaces receiving acoustical insulation shall be completely covered with absorptive insulation. The insulation shall be cut and fitted together to avoid gaps. All openings shall be packed with loose insulation using elastomeric adhesives. Insulating cements shall not be used. 8.3 A tack coat of mastic (approximately half of the desired film thickness) shall be applied with sufficient pressure to assure impregnation of the absorptive layer. Reinforcing fabric shall be embedded in the wet tack coat, and then the final coat shall be applied to the specified wet film thickness. Adjacent pieces of reinforcement shall be lapped a minimum of 3 inches (76mm). The installed reinforcing shall be free of wrinkles and protruding edges. In multiple coat applications, the reinforcing fabric shall be applied to the middle coating. 8.4 If the acoustical coating is used in conjunction with metal jacketing, the coating shall be overlapped at least 3 inches (76mm) by the jacketing and banded and caulked at the extreme end of the overlapping jacketing. 9.0 FLASHING 9.1 A 1/4 inch (6mm) bead of flashing compound shall be applied to all possible points of acoustic leakage or moisture penetration. These shall include any interruptions of the finish or barrier layer at joints or between finish or barrier layers and protrusions such as valve bonnets, hangers, and instrument connections. All joints that are to be broken in removing a removable cover shall also be flashed. 8.2 Trowelable acoustical coatings, such as loaded mastic, shall be applied directly to the absorptive insulation and reinforced with glass cloth. The coating shall have a minimum dry film thickness of 0.07 inch (1.8mm) and a minimum surface weight of 0.72 lb/ft 2 (3.6 kg/m 2 ). The Noise Reduction Coefficient (NRC) of the loaded mastic is available from the VENDOR. Specification for Acoustical Insulation (Lagging) for Piping and Equipment 5 of 5