AN APPLICATION OF BUILDING SIMULATION TECHNIQUES TO THE ASSESSMENT OF NATURAL VENTILATION IN OFFICE WITH DOUBLE SKIN FACADE

Similar documents
MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

APPLICATION OF COMPLEX ENERGY SIMULATION IN COMPETITION DESIGN OF CZECH EMBASSY IN OTTAWA

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS

This version was downloaded from Northumbria Research Link:

Air flow modeling approach for a double-skin facade system Hensen, J.L.M.; Bartak, M.; Drkal, F.

The effect of shading design and control on building cooling demand

USE OF BUILDING THERMAL AND CFD SIMULATION IN THE DESIGN OF A LARGE OFFICE BUILDING IN LISBON

Cost-Benefit Analysis of Dwelling Retrofit Options

Daylight has been a primary source of lighting in buildings. Daylighting improve indoor environmental quality and visual comfort. Moreover, it reduces

Investigation of indoor climate in a naturally ventilated building

User Interactions with Environmental Control Systems in Buildings

AN EXPERIMENTAL STUDY AND SIMULATIONS OF PHASE CHANGE MATERIALS IN AN OFFICE THERMAL ENVIRONMENT

Assessment of thermal comfort near a glazed exterior wall

Energy and indoor temperature consequences of adaptive thermal comfort standards

CFD ASSESSMENTS WITHIN STRONGLY TRANSIENT DOMAINS. Aizaz Samuel, Jon Hand Energy Systems Research Unit University of Strathclyde, Glasgow, Scotland

PERFORMANCE EVALUATION OF PV VENTILATED GLAZING

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Thermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone

New Generation Office Building

Passive Thermal Control for Window Insulation

CONTROLITE. Intelligent Daylighting System FACADE SKYLIGHT

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

Teaching building performance simulation - some quality assurance issues and experiences

ESP-r: INTEGRATED SIMULATION TOOL FOR DESIGN OF BUILDINGS AND SYSTEMS

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

125BEPM - Building energy performance modeling. Lecture handouts

Controlling ventilated façades

Slab cooling system design using computer simulation

Tage Møller Architect office building

ENERGY EFFICIENT TECHNIQUES AND SIMULATION OF ENERGY CONSUMPTION FOR THE SHANGHAI ECOLOGICAL BUILDING

Integrating Ventilated Façades in Hot and Humid Climates

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD

ScienceDirect. Simulation based mixed mode building design

DEVELOPMENT OF A GUIDELINE FOR SELECTING A SIMULATION TOOL FOR AIRLOW PREDICTION. E. Djunaedy, J.L.M. Hensen, M.G.L.C. Loomans

THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY

546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran

FORMAL CALIBRATION METHODOLOGY FOR A CFD MODEL OF A NATURALLY VENTILATED ROOM. Corresponding author:

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

IEA Annex 58: Full-scale Empirical Validation of Detailed Thermal Simulation Programs

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Work Package 2: Performance of naturally ventilated buildings

ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY

Effect of energy renovation on thermal sensation and comfort

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

OFSETTING THE NATURE

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing

Beyond Arrows: Natural Ventilation in a High-Rise Building with Double Skin Façade

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

The feasibility of natural ventilation in plus energy houses in Germany

COMFORT DRIVEN ADAPTIVE WINDOW OPENING BEHAVIOR AND THE INFLUENCE OF BUILDING DESIGN

Integrated Building Simulation: State-of-the-Art

BRF Kredit headquarters

ADAPTIVE LOW-E DOUBLE GLAZING WINDOW

Appraising the effects of window opening behaviour in an office building in different climates

Thermal and Energy Performance of Double Skin Facades in Different Climate Types

External Environment and Indoor Microclimate

Smoke Control using a Double-skin Facade

HEADQUARTERS OF THE COMISIÓN NACIONAL DEL MERCADO DE VALORES. DOUBLE FAÇADE SIMULATION STUDY. Barcelona, Spain.

Solar Energy for Hospitals

Available online at ScienceDirect. Energy Procedia 57 (2014 )

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

RECENT CZECH BUILDING ENERGY SIMULATION CASE STUDIES

LIGHT EXTERNAL WALLS AND THERMAL STABILITY OF ROOM

The Centre for Sustainable Building (ZUB) * A Case Study

! #! %%%%&%%% &( &% )) + # +,% #.!. # 0! 1 2! ,%,% 0 # 0! 1 2! ,4&,) 5,%

ENERGY PERFORMANCE OF DIFFERENT TYPES OF DOUBLE SKIN FACADES IN VARIOUS CLIMATES

Evaluation methodology and implementation for natural ventilation control strategies

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

Commissioning of a Coupled Earth Tube and Natural Ventilation System at the Post-Acceptance Step

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

An approach for energy conscious renovation of residential buildings in Istanbul by Trombe wall system

THE EFFECT OF SUSPENDED CEILINGS ON THERMAL MASS TO REDUCE OVERHEATING

Thermal comfort study of a hawker center in Singapore

DESIGN, MONITORING AND EVALUATION OF A LOW ENERGY OFFICE BUILDING WITH PASSIVE COOLING BY NIGHT VENTILATION

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

GENERALIZED CRITERIA OF ENERGY PERFORMANCE EVALUATION IN EARLY DESIGN STAGES OF NEARLY ZERO-ENERGY BUILDINGS

Effect of Building Orientation and Window Glazing on the Energy Consumption of HVAC System of an Office Building for Different Climate Zones

ENERGY CONSERVATION VS HEALTH. THE AIR QUALITY PICTURE. Aizaz Samuel Energy Systems Research Unit University of Strathclyde, Glasgow, Scotland

ScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings

Sustainable Facades for Indian Tropical Climate Case for External Movable Shading Systems

Deakin Research Online

Comparison of the Intensity of Ventilation at Windows Exchange in the Room - Case Study

CONTROLITE. Intelligent Daylighting System FACADE SKYLIGHT

Thermal Performance Analysis to Assess Inhabitant Comfort inside LIG houses in Chhattisgarh

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

Intelligent tall building envelope technologies and design alternatives for comfort and energy efficiency in hot, arid climate

Efficient and smart climate shell. refurbishment of residential buildings PART OF SMART SOLUTION 1: EFFICIENT AND SMART CLIMATE SHELL REFURBISHMENT

BUILDING INTEGRATED VENTILATION SYSTEMS MODELLING AND DESIGN CHALLENGES

Published in: CleanTech for Sustainable Buildings: From Nano to Urban Scale (CISBAT), Lausanne, September 2011

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Comparison of the Effects of Various Countermeasures on Energy Consumption in a Residential Building

Numerical analysis of indoor thermal comfort in a cross-ventilated space with top-hung windows

DYNAMICMODELLINGOFSHIPENVIRONMENTSWITHESP-R Andrew Pennycott 1, Aizaz Samuel 2

Evaluation methods for indoor environmental quality assessment according to EN15251

Phase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing

Transcription:

Third German-Austrian IBPSA Conference AN APPLICATION OF BUILDING SIMULATION TECHNIQUES TO THE ASSESSMENT OF NATURAL VENTILATION IN OFFICE WITH DOUBLE SKIN FACADE Milan Janak, Katarina Moravcikova Slovak University of Technology, Civil Engineering Faculty, Department of Building Constructions, Bratislava, Slovakia ABSTRACT In our paper we describe an application of the building simulation techniques to the assessment of an energy, thermal comfort and natural ventilation effectiveness in the office with a double skin facade. Two distinct building simulation techniques are applied. Firstly, it is a Computational Fluid Dynamics (CFD) technique to assess wind effects on a building façade and to carry out detailed simulation of natural ventilation of an office. Secondly, it is a dynamic building energy simulation coupled with an air flow network model to predict annual performance related to the energy, thermal comfort and natural ventilation. Results of this application simulation study clearly show that a particular design of a double skin façade has a significant negative effect on natural ventilation when compared to the typical operable window. On the other hand results show that with the aid of simulation approach it is possible to identify a construction measures to optimise façade performance. Secondly, it is a dynamic building energy simulation coupled with an air flow network model to predict annual statistics of natural ventilation effectiveness such as time distribution of CO2 concentrations and thermal comfort parameter such as time distribution of the operative room temperatures. An application of these simulation techniques is demonstrated on a case study project of a retrofit of northeast and southwest façade. The case study building is a high rise (22 floors) office building in the centre of Bratislava, Slovakia (see figure 1). The main focus of an analysis is given on the southwest naturally cross ventilated double skin element façade (see figure 2 and figure 3). KEYWORDS Simulation application, double skin façade, natural ventilation, energy simulation, CFD simulation INTRODUCTION Despite of many known positive effects of double skin façade constructions on energy efficiency and thermal comfort (Oesterle et. al. 2001), the effect on the room natural ventilation is usually negative. The reason for this is that double skin façade construction represents increased air flow resistance, increased air temperature and more importantly in some cases an unwanted mixing of an ambient fresh air with used room air. Two distinct building simulation techniques are applied in this application study. Firstly, it is a Computational Fluid Dynamics (CFD) technique to assess wind effects on building façade as a main driving force to the natural ventilation and to carry out detailed simulation of natural ventilation of an office via double skin façade with main focus on predicting CO2 concentrations, mean age of air and an overall air exchange number. Figure 1 Building of Faculty of Civil Engineering STU Bratislava with new façade in construction progress (May 2010) Figure 2 New double skin façade interior view Building Performance Simulation in a Changing Environment - A. Mahdavi / B. Martens (eds.) - 262

Evaluated building Figure 3 Visualisation of the double skin façade ventilation pattern The aims that have been set out for the simulation were to predict the façade performance related to the expected heating demand reduction, reduction of the summer overheating potential and the effect on natural ventilation via new proposed double skin façade. WIND STUDY Wind pressure coefficients C p (-) are used to determine wind induced boundary condition on a building façade as a main driving force for a natural ventilation in a windy location as Bratislava, Slovakia. In this study a computational wind engineering method (Blocken et. al. 2009) was applied to determine a database of wind pressure coefficients for both northeast and southwest façades as a function of wind directions. CFD program Phoenics Flair 2009 (Phoenics 2009) has been used for this task. A digital 3D model of Bratislava city has been used to setup a computational domain for a wind study (see figure 4). Logarithmic wind profile with an effective terrain roughness z o = 1 m has been used together with a standard k ε turbulence model (Versteeg 1995). Resulting pressures at the building facades (see figure 5) have been processed in order to derive a set of C p coefficients. Evaluated building Figure 4 3D model for CFD wind study Figure 5 Predicted building façade pressure field Figure 6 shows an example of the predicted sets of C p coefficients. Cp (-) 2.5 2.0 1.5 1.0 0.5 0.0-0.5-1.0-1.5-2.0-2.5 0.0 22.5 Cp values for facades at 13.8 m above ground NE_facade SW_facade 45.0 67.5 90.0 112.5 135.0 157.5 180.0 202.5 225.0 Wind approache angle ( o ) Figure 6 Predicted wind pressure coefficients ENERGY SIMULATION The main aim of the study was to determine the proposed façade retrofit performance related to the reduction of heating demand, summer overheating and natural ventilation effectiveness. A method of building energy simulation coupled with a mass flow network (Clarke 2001, Hensen 2002) has been selected for an analysis because of its ability to simulate an annual dynamic performance of the analysed system of climate building/façade natural ventilation thermal comfort indoor air quality. Two building energy simulation models in program ESP-r (Clarke 2001) has been set up. A base case model that represents an existing poorly performing building façade (see figure 7) and a new case that represents proposed façade retrofit with the double skin façade at southwest façade and a typical façade design with internal shading on northeast façade (see figure 8) have been constructed. A new case has been modelled in two alternatives alternative 1 northeast façade with insulation triple glazing unit and 247.5 270.0 292.5 315.0 337.5 Building Performance Simulation in a Changing Environment - A. Mahdavi / B. Martens (eds.) - 263

alternative 2 northeast façade with insulation double glazing unit. Natural ventilation window opening based on CO 2 concentration over 1.5 g/kg The main simulation results from an annual runs are summarised on figure 9 to figure 11. Comparison of predicted heating demand (see figure 9) shows a significant theoretical heating energy saving potential of 70 % to 80 % that could be attributed mainly to the very poor insulation and air permeability performance of an existing old façade together with inadequate heating system zoning and control. Heat Demand 160.00 140.00 120.00 134.50 134.50 Previous State New State - alt.1 New State - alt.2 Demand (kwh/a.m 2 ) 100.00 80.00 60.00 40.00 30.86 30.86 41.15 46.31 20.00 Figure 7 Energy simulation model with mass flow network of the existing façade 0.00 Office_SW Office_NE Figure 9 Comparison of an annual heating demand Occurrence of operative temperature above 28 C per year Occurrence (h) 900 800 700 600 500 400 300 842 841 770 405 Previous State New State - alt.1 New State - alt.2 636 517 200 100 0 Office_SW Office_NE Figure 10 Comparison of an occurrence of operative temperature above 28 o C. Occurrence of CO2 concetration above 1.75 g/kg per year Figure 8 Energy simulation model with mass flow network of the new facade The main model operational and control parameters has been set as follows: Typical office schedule based on two person per office emission of heat and CO 2 Solar blind control based on incident solar irradiance on the façade plane over 100 W/m 2. Occurrence (h) 300 250 200 150 100 50 0 239 240 0 0 Office_SW 8 9 Office_NE Previous state New State - alt.1 New State - alt.2 Figure 11 Comparison of an occurrence of CO 2 concentration above 1.75 g/kg. Building Performance Simulation in a Changing Environment - A. Mahdavi / B. Martens (eds.) - 264

In order to realise this predicted theoretical heating energy saving potential the most important factor will be an ability of the existing heating system zoning and control to adjust to the new heating load requirements after façade retrofit. The failure to do so could result in building overheating even in winter and in reduction of heating energy saving potential. Figure 10 shows and annual statistics of an operative temperature over 28 o C occurrence that we used as an indication for the office overheating. Two trends are visible from the results. For the northeast office there is predicted a clear trend towards increased overheating by more than 200 hours with triple glazing unit and by over 100 hours with double glazing unit. This tendency is a result of a dramatic improvement in thermal insulation and air permeability performance of the new façade that helps to retain heat in the building. For the southwest office with the double skin facade there is predicted almost no change in overheating potential if triple glazing unit is used in the northeast office. However if double glazing unit is used in the northeast office there is predicted a slight decrease by 70 hours of an overheating potential. Figure 11 shows and annual statistics of an occurrence of CO 2 concentration over 1.75 g/kg that we have considered as border line between ideally and marginally ventilated room (see table 1). The effect of decreasing natural ventilation via double skin façade in the southwest office is clearly visible. On the other hand predicted around 240 hours with marginal natural ventilation represents about 10 % of a working hours and can be attributed to the situations with no or low wind velocities and small temperature differences between ambient and the office. Table 1 CO 2 concentration limits as indicator of room ventilation (Sand 2004) Ventilation Concentration CO 2 Concentarion CO 2 Air Rate (ppm) (g/kg) Exterior 400-600 0,6 0,9 - Overventilated 600 800 0,9 1,2 25-30 clm/p Ideal 800 1200 1,2 1,8 15-20 clm/p Marginal 1200-1400 1,8 2,1 10 clm/p Underventilated 1400 1800 2,1-2,7 Poor 1800-2000 2,7 3,0 8 clm/ p Very poor 2000 2200 3,0 3,3 6 clm/ p Unacceptable > 2200 > 3,3 5 clm/ p CFD METHOD In order to further investigate in more details a mechanism of a natural ventilation via the double skin façade a CFD simulation under adverse boundary conditions (no wind, small temperature difference) has been carried out with aim to optimise natural ventilation. Stable state CFD simulation have been carried out on the model of the southwest office with corresponding double skin façade modules to preserve principal flow patterns in the façade (see figure 12 and figure 13) Figure 12 Visualisation of natural ventilation flow pattern with only low windows opened Figure 13 Visualisation of natural ventilation flow pattern with low and upper windows opened The number of alternatives of lower and upper ventilation window opening have been simulated: Alternative 1: only lower windows (figure 14) - with solar irradiance Alternative 2: only lower windows (figure 14) - without solar irradiance Alternative 3: lower and upper windows (figure 15) - without solar irradiance Alternative 4: lower and upper windows (figure 15) - with solar irradiance Alternative 5: lower and one upper windows (figure 16) - without solar irradiance Alternative 6: lower and one upper windows (figure 16) - with solar irradiance Building Performance Simulation in a Changing Environment - A. Mahdavi / B. Martens (eds.) - 265

office temperature) and boundary condition with solar irradiance (façade gap air temperature above office temperature). Otherwise all boundary conditions were set to 20 o C and only a heat source from two occupants was considered. These boundary conditions have resulted in a small temperature difference up to 2 K between ambient and office that represents very small driving forces for the natural ventilation. The results from CFD analysis of the natural ventilation of the office via the double skin facade are summarised in table 2. Table 2 shows predicted air flow rates, air exchange number and CO 2 concentration at the level of occupant head. Figure 14 CFD model with lower window opening Alternativ e Table 2 CFD summary results for office ventilation Air flow rate Air flow rate (m 3 /h) (m 3 /h.person ) Air exchange number (1/h) CO 2 Concentratio n (ppm) 1 33,74 16,87 0,78 1650 2 57,26 28,63 1,325 2900 3 102,0 51,0 2,36 1350 4 158,55 79,275 3,67 1400 5 66,98 33,49 1,55 1750 6 120,1 60,05 2,78 1920 Figure 15 CFD model with lower and upper window opening Figure 16 CFD model with lower and only one upper window opening In order to simulate two distinct ventilation patters we have used the boundary conditions with no solar irradiance (façade gap air temperature lower than Based on the results from table 2 an important design conclusion related to the ventilation window opening has been made. It was demonstrated that to achieve at least marginal ventilation under adverse boundary conditions it is necessary to open both windows lower and upper ones at the given opening angle. CONCLUSION Results of this application simulation study clearly show that a particular design of a double skin façade has a significant negative effect on natural ventilation when compared to the typical operable window ventilation. On the other hand simulation results also show that this negative effect is limited only to the relatively small number of working hours mainly connected with no or low wind velocity and small temperature differences between ambient and the office. An application of simulation techniques also helped to optimise double skin façade ventilation openings sizing and positioning and to find an optimal office window opening strategy to achieve at least marginal natural ventilation effectiveness even under boundary conditions with very small driving force. The most interesting research observation from this application study is the fact that natural ventilation assessment based on typical parameter of an office air exchange number could lead to the erroneous conclusions. The main reason for this is a presence of very strong mixing effect of an ambient fresh air and Building Performance Simulation in a Changing Environment - A. Mahdavi / B. Martens (eds.) - 266

polluted room air in the double skin façade that is being re-circulated to the ventilated room. The facade retrofit is currently (May 2010) under a construction and therefore no site experimental measurements could be presented in this paper. However authors are already planning ahead the experimental measurements of the double skin facade thermal and ventilation performance that will be confronted with the theoretical results from building simulations. ACKNOWLEDGEMENT Work on this paper has been supported by APVV- 0204-07 and VEGA No. 1/9647/09. REFERENCES Clarke J. A. Energy Simulation in Building Design 2nd ed. Oxford (UK): Butterworth-Heinemann, 2001. Versteeg H. K., Malalasekera W.: An introduction Instruction to computational fluid dynamics.the finite volume method. Longman Group Ltd 1995 Sand James R., Demand Controlled Ventilation Using CO 2 Sensors. U.S. Department of Energy Efficiency and Renewable Energy, by Oak Ridge National Laboratory. Washington D.C. 2004. Oesterle E., Lieb R-D., Lutz M., Heusler W. 2001. Double Skin Facades Integrated Planning. Prestel Verlag: Munich, Germany 2001 Hensen, J.L.M., Bartak, M., & Drkal, F. 2002. Modeling and simulation of double-skin facade systems. ASHRAE Transactions, vol. 108:2, American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Atlanta 2002, GA. Blocken B., Stathopoulos T., Carmeliet J., Hensen J., 2009. Application of CFD in building performance simulations for outdoor environment. Eleventh International IBPSA conference 2009, Glasgow, Scotland. Phoenix: http://www.phoenix.co.uk/ ESP-r 11.4: http://esru.strath.ac.uk/ Building Performance Simulation in a Changing Environment - A. Mahdavi / B. Martens (eds.) - 267