Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers

Similar documents
A Novel Coaxial Borehole Heat Exchanger: Description and First Distributed Thermal Response Test Measurements

TEMPERATURE STRATIFICATION OF CIRCULAR BOREHOLE THERMAL ENERGY STORAGES

DISTRIBUTED TEMPERATURE MEASUREMENTS ON A MULTI-PIPE COAXIAL BOREHOLE HEAT EXCHANGER

This paper was presented at 12th REHVA World Congress (Clima 2016).

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Multi injection rate Thermal response test

Numerical and analytical analysis of groundwater influence on the pile ground heat exchanger with cast-in spiral coils

DISTRIBUTED TEMPERATURE MEASUREMENTS ON A U-PIPE THERMOSYPHON BOREHOLE HEAT EXCHANGER WITH CO 2

Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields

Comparison of Borehole Heat Exchangers (BHEs): State of the Art vs. Novel Design Approaches

APPLICATIONS OF A DYNAMIC THREE-DIMENSIONAL NUMERICAL MODEL FOR BOREHOLE HEAT EXCHANGERS. M. He, S.J. Rees, L. Shao

Improvement of a Two-Dimensional Borehole Heat Exchanger Model

Study on Heat Exchange Characteristics for PHC Energy Piles

Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump

Parametric Study for Evaluation of Design Parameters of Standing Column Well

INCORPORATION OF GROUNDWATER FLOW INTO NUMERICAL MODELS AND DESIGN MODELS

Enhancement of Heat Exchange Capacity of Ground Heat Exchangers by Injecting Water into Wells

Experimental Validation of a Numerical Model for the Thermal Response of a Borehole Field

First Thermal Response Test in Libya Abstract 1. Introduction 2. Background

Distributed Thermal Response Test on a Grouted U-pipe Borehole Heat Exchanger

A review on heat transfer enhancement of borehole heat exchanger

Magda Kaczmarczyk and Michał Kaczmarczyk

This is the published version of a paper presented at European Geothermal Congress 2016 Strasbourg, September 2016.

Available online at ScienceDirect. Energy Procedia 78 (2015 )

A SIMPLE MODEL TO ACCOUNT FOR THERMAL CAPACITY IN BOREHOLES

Citation for the original published paper (version of record):

Numerical Simulation of Critical Factors Controlling Heat Extraction from Geothermal Systems Using a Closed-Loop Heat Exchange Method

MODELLING OF A LARGE BOREHOLE HEAT EXCHANGERS INSTALLATION IN SWEDEN

REGRESSION ANALYSIS ON INFLUENCE OF VARIOUS FACTORS ON HEAT TRANSFER OF VERTICAL GROUND HEAT EXCHANGER

Simulations of a New Double U-tube Borehole Configuration with Solar Heat Injection and Ground Freezing

Hafiz M K U Haq 1, Birgitta J. Martinkauppi 1, and Erkki Hiltunen 1 1 Department of Energy Technology

Modeling of Usage of Air Injection Well in a Geothermal System

Modeling a Novel Shallow Ground Heat Exchanger

PREPROCESSOR FOR THE GENERATION OF G-FUNCTIONS USED IN THE SIMULATION OF GEOTHERMAL SYSTEMS

DESIGN AND OPTIMUM CONTROL OF A SWEDISH DUAL- SOURCE (AIR AND GROUND) HEAT PUMP SYSTEM

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE

Implementation of the Distributed Thermal Response Test at Characteristic Geological Regions throughout Croatia

A PILOT PROJECT OF THE CLOSED-LOOP GROUND SOURCE HEAT PUMP SYSTEM IN CHINA

GEOTHERMAL HEAT PUMPS CONFIGURATIONS/INSTALLATION

SUPERVISED ROCK-MASS STORAGE OF THERMAL ENERGY PRODUCED BY A SOLAR THERMAL PANEL

This is a repository copy of The Average Temperature of Energy Piles.

ENERGY SAVINGS, SIMULATIONS AND ECONOMIC ANALYSIS OF A GROUND SOURCE HEAT PUMP WITH VERTICAL BOREHOLE HEAT EXCHANGERS FOR A BELGIAN OFFICE BUILDING

PRELIMINARY INTERMODEL COMPARISON OF GROUND HEAT EXCHANGER SIMULATION MODELS

IMPROVED DESIGN METHODS FOR GROUND HEAT EXCHANGERS RACHEL MARIE GRUNDMANN. Bachelor of Science in Mechanical Engineering. Oklahoma State University

Pitfalls of Rules of Thumb in Geothermal Heat Pump Design

An Analysis on Cost Reduction Potential of Vertical Bore Ground Heat Exchangers Used for Ground Source Heat Pump Systems

Deep borehole heat exchangers

IMPROVEMENTS IN DESIGN PROCEDURES FOR GROUND SOURCE AND HYBRID GROUND SOURCE HEAT PUMP SYSTEMS JAMES R. CULLIN

Ground-source Heat Pumps State of the Art

Properties of different ethyl alcohol based secondary fluids used for GSHP in Europe and USA

Long-Term Heating Test Using the Semi-open Loop Ground Source Heat Pump System

Simulation of 2D Heat Transfer in a Horizontal Plane with Thermal Resistance-Capacitance Model

Finite Volume Based Computer Programs for Ground Source Heat Pump Systems

Analysis of building energy use and evaluation of long-term borehole storage temperature

LICENTIATE THESIS. Thermal Response Test - In Situ Measurements of Thermal Properties in Hard Rock. Signhild Gehlin.

February 20, 2014: The attached paper was presented at the 2014 ASHRAE Winter Meeting in New York City. It was published as a conference paper.

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS

An evaluation of ground thermal properties measure accuracy by thermal response test of horizontal ground heat exchangers

1 INTRODUCTION. Keywords: ground source heat pump; energy pile; geothermal; geophysics; ground temperature

Combination of solar collectors and ground-source heat pump for small buildings

Investigations on the mechanical behaviour of a Heat Exchanger Pile

Measurement of COPs for Ground Source Heat Pump (GSHP) System in Heating and Cooling Mode

Ground Source Heat Pumps: Testing three mediums surrounding the piping in geothermal field beds to evaluate performance

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

Prediction of the thermal performance of horizontal-coupled ground-source heat exchangers

Influencing Factors on Ground Heat Balance of GSHP System Xiaohong Zhang1, a *, Zehua Liu2,b, Chao Zhang3,c and Long Ma4,d

The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results

Thermal Performances Of Three Types Of Ground Heat Exchangers In Short-Time Period Of Operation

Research on Ground Source Heat Pump Design

HEAT TRANSFER ANALYSIS OF GEOTHERMAL HEAT EXCHANGERS IN GROUND-COUPLED HEAT PUMP SYSTEMS. Abstract. 1. Introduction

BENJAMIN BELLO CHARLINE LEGER

SIMULATION OF A DOMESTIC GROUND SOURCE HEAT PUMP SYSTEM USING A TRANSIENT NUMERICAL BOREHOLE HEAT EXCHANGER MODEL

Optimal Design for a Hybrid Ground-Source Heat Pump

Numerical Modelling of Geothermal Borehole Heat Exchanger Systems Miaomiao He

A quasi-two-dimensional standing column well model for ground source heat pump systems

The Superposition Borehole Model for TRNSYS (TRNSBM)

A SIMPLE TOOL FOR SIMULATION OF GROUND SOURCE HEAT PUMP SYSTEMS

A Comparative Study of Medium Deep Borehole Thermal Energy Storage Systems Using Numerical Modelling

Geothermal Heat Pump Systems Efficiency in Russia

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

Temperature Response functions (G-Functions) for Single Pile Heat Exchangers

Embedded Microfluidic/Thermoelectric Generation System for Self- Cooling of Electronic Devices

Task 45 Large Systems Seasonal Borehole Thermal Energy Storage Guidelines for design & construction IEA-SHC TECH SHEET 45.B.3.

Technical and Economical Evaluation of Medium Deep Borehole Thermal Energy Storages

Thermal Resistance of U-tube Borehole Heat Exchanger System: Numerical Study

SIMULATION AND OPTIMIZATION OF GROUND SOURCE HEAT PUMP SYSTEMS

Dynamic thermal simulation of horizontal ground heat exchangers for renewable heating and ventilation of buildings

DHI Sverige AB, Honnörsgatan 16, P.O. Box 3289, SE Växjö, Sweden, 3

A Simple Engineering Analysis Method to Evaluate the Geothermal Potential from a Hot Water Aquifer

EXPERIMENT AND NUMBERICAL ANALYSIS OF THE DISCONTINUOUS OPERATION FOR GROUND HEAT EXCHANGERS

An investigation of thermal energy storage for industrial heat waste recovery: Storing heat waste into a ground TES system for a ship s diesel engine

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

CFD Analysis of Earth-Air Heat Exchanger to Evaluate the Effect of Parameters on Its Performance

CFD Simulation Studies for Vertical Temperature Profile, Pitch Optimisation and Parametric Study of Borehole Heat Exchanger

Commercial Program Development for a Ground Loop Geothermal System: G-Functions, Commercial Codes and 3D Grid, Boundary and Property Extension

Abstract. Nomenclature. A Porosity function for momentum equations L Latent heat of melting (J/Kg) c Specific heat (J/kg-K) s Liquid fraction

Thermia Large capacity Heat pumps

Transcription:

Excerpt from the Proceedings of the COMSOL Conference 2009 Milan Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers J. Acuña, B. Palm The Royal Institute of Technology KTH Brinellvägen 68, 100 44 Stockholm Sweden, jose.acuna@energy.kth.se Abstract: The most common way to exchange heat with the bedrock in Ground Source Heat Pump (GSHP) applications is circulating a fluid through a U-formed closed loop in vertical boreholes drilled several tenths of meters into the ground. The quality of the heat exchange depends on the flow conditions along the channels, the pipe properties, and the relative position of the flow channels to each other and to the rock wall. One of the ways to measure the performance of such heat exchangers is determining and evaluating a thermal resistance that accounts for all these factors, the borehole thermal resistance. This study presents and compares the results of eight cross sectional U-pipe Borehole Heat Exchanger configurations, modeled with the software COMSOL Multi-physics. Values from recent experimental temperature measurements and calculated heat transfer coefficients are used as boundary conditions. The two dimensional problem is solved with steady state heat transfer equations, and the net heat exchanged with the ground is obtained. The borehole thermal resistance is subsequently calculated and a quantitative comparison among all cases is presented. Isothermal lines and heat flow directions illustrate the results, pointing out how opportune the use of certain U-pipe BHE configurations is. Keywords: Borehole heat exchanger, ground source heat pump, thermal shunt flow, borehole thermal resistance. 1. Introduction Thermal energy from the ground is being used to efficiently heat and cool buildings of different sizes in Europe and North-America, harnessed by means of Borehole Heat Exchangers (BHE) installed in vertical boreholes that are drilled several meters into the ground. Nowadays, almost all BHEs consist of a closed U-pipe, two single cylindrical pipes made of polyethylene through which a heat carrier fluid is circulated and thereby exchanging heat with the ground. These pipes are attached at the borehole bottom in U-form. Such a BHE has been successful in the market due to its easiness to install and its relative low cost. There are approximately 360 000 such systems installed in Sweden today, and a small improvement on their thermal performance could have a considerable influence on the Swedish energy system. A one degree Celsius change of the out coming fluid from a BHE could give a 2-3% increase to the heat pump system efficiency. It is therefore of interest to evaluate how U-pipe channels could perform in the most efficient way. Other BHE types of BHE are obviously also important, but they are not considered in this paper. One of the first studies in U-pipe BHE was carried out by Claesson et al [1], where the heat flows between the pipes and the outer rock were computed by an equation system based on a Fourier expansion around each pipe and the outer circle. The work by Hellström [3] presents a 3D temperature field around a U-pipe and very useful values of borehole thermal resistance for a single U-pipe as a function of borehole filling material for three different pipe positions in the borehole. Analytical solutions of the fluid temperature profiles and borehole thermal resistance for different BHE configurations were considered by Zeng et al[12]. A recent FEM analysis presented by Esen et al [4], shows the two-dimensional temperature distribution at three depths of U-pipe BHEs, indicating that thermal shunt flow takes place between channels and that it becomes larger with deeper boreholes. This study represents the first COMSOL Multi-physics results of a research project that aims at achieving more effective heat exchange with the ground. The study uses advanced temperature measurement equipment in order to depict the real temperature profiles along the borehole depths, and intends (among other goals) to validate models with the field measurements. Several BHEs are tested, including the common U-pipe, and the use of spacers, i.e. a

device used to ensure the separation of the channels along the depth and guarantee their proximity to the borehole wall. The tested spacer dimensions are 53 mm and 78 mm (center to center separation between pipes), installed in boreholes of 140 mm in diameters. The U-pipe tubes have an external diameter of 40 mm and a wall thickness of 2.4 mm. Figure 1 is a picture of the BHE equipped with the 38 mm spacers. It can be observed that the pipes are not in direct contact with the borehole perimeter, nor with each other. The first experimental works by Acuña et al [5] and Ten [6] illustrate that 13 mm spacers might not make a difference as compared to the common U-pipe. Figure 1. U-pipe BHE with 38 mm spacers 2. Methodology The present study intends to compare the above mentioned spacers by using the software COMSOL Multi-physics. The common U-pipe without spacers is also included, being the pipes located in four hypothetical positions that may occur when installing such systems. The pipe position variation along the depth has been experimentally identified by Acuña et al [7], showing the importance of the position for the performance of the BHE. As was previously mentioned, one of the indicators used to compare BHE thermal performance is the borehole thermal resistance, introduced by Hellström [2] and denominated as R b, being the result of dividing the temperature difference between the borehole wall and the average fluid temperature T f [K] by the total net heat flow [W/m] rejected or absorbed from or to the BHE channels, as expressed in equation 1. R b ΔT Tf T = = q' q' bhw eq. 1 Given the undisturbed ground temperature T rock, and a 140 mm borehole with two PE 40x2,4mm tubes having temperatures T 1 and T 2 (both higher than T rock ), there exist two independent temperature differences between the fluid and the undisturbed rock, and two independent heat flows. The total net heat flow q to the outer circle is the algebraic sum of the ones corresponding to each pipe. R b associates all the different parts that normally are involved in BHE heat transfer analysis, i.e. the arrangement of the BHE flow channels, the convective heat transfer in the ducts, and the thermal properties of the BHEs as well as the filling material (a typical borehole in Sweden is naturally filled with groundwater and this material is thus used as a sub-domain in this study). In groundwater filled boreholes, it is common to expect a certain degree of natural convection between the BHE pipes and the borehole wall, resulting in a lower R b values. This phenomenon has been neglected here and it is left as a next step. This has, however, partially been studied by Gustafsson [13] using a three dimensional CFD model where groundwater movement was induced. An equivalent radius model was also used and validated. COMSOL Multi-physics has been used in this paper in order to quantify the heat flow from the U-pipe channels to the rock at different pipe positions. These flows are then used to calculate the fluid to ground thermal resistance (total resistance from T f to T rock ), and subsequently subtracting the thermal resistance corresponding to the surrounding rock in order to obtain R b for each of the cases. This type of problem can be easily solved with an equations system. However, as demonstrated in [7], the channels position inside the borehole changes along the depth, giving importance to doing quantitative studies on the effect of these changes. Neither the borehole wall nor the rock temperatures in the vicinity of the borehole vary

in a symmetrical way. It is therefore of importance to use an outer ring located sufficiently far away from the borehole (1 meter in diameter was chosen in this case) as a boundary condition, instead of setting the borehole wall temperature to be constant. The thermal properties of the PEH pipes were taken from [9] and the ones corresponding to the rock (granite) are based on [10], except the thermal conductivity that was obtained from [7]. The COMSOL sub-domain characteristics and the boundary conditions are presented in Table 1 and Table 2, respectively. They are based on carefully performed thermal response test measurements. Average temperature values for both pipes are taken from 100 meters depth and set as boundary conditions for the models, among others. These measurements were taken with optical fiber cables installed in a real test installation. Table 1. Thermal properties of the sub-domains Rock Density [kg/m 3 ] 2700 Cp [J/kg K] 830 Thermal conductivity [W/m K] 3.1 Polyethylene pipes PEH Density [kg/m 3 ] 950 Cp [J/kg K] 2000 Thermal conductivity [W/m K] 0.4 Groundwater Density [kg/m 3 ] 1000 Cp [J/kg K] 4200 Thermal conductivity [W/m K] 0.56 The convective heat transfer in the ducts is modeled by introducing a previously calculated heat transfer coefficient as a boundary condition at the internal wall of the pipes. The volumetric flow rate is 0.5 liters per second, a typical rate in a Swedish application. The determination of these coefficients is based on thermal properties from [11] of an ethanol aqueous solution (16% in weight) at the measured temperatures. Table 2. Boundary conditions Heat transfer coefficient upwards 1162 [W/m 2 K] Heat transfer coefficient downwards 1242 [W/m 2 K] Temperature upwards [K] 287,05 Temperature downwards [K] 289,64 Undisturbed ground temperature [K] 281,74 3. Results and discussion Figures 2-9 illustrate the result of all eight cross section simulations (pipes apart; two possible arrangements of pipes together aside; pipes together centered in the borehole; and two for each of the spacer dimensions, centered and aside). Each figure shows the BHE channels placed at the different positions as well as isothermal lines and heat flow direction arrows. All figures use the same temperature scale. The heat flow arrows are only plotted in order to illustrate the direction of the heat flows. The arrow size should not be compared among figures. The exact values of the total net heat flow resulting from the COMSOL calculations are given in table 3 for each configuration. Table 3. Total heat flow for all models [W/m] Pipes apart 30,20 Pipes aside together 23,10 Pipes together - aside 2 25,23 Pipes together - centered 18,30 13 mm spacers - centered 19,81 13 mm spacers - aside 26,46 38 mm spacers - centered 24,14 38 mm spacers - aside 28,92

C Figure 2. Pipes apart Figure 3. Pipes aside together Figure 4. Pipes together aside - 2 Figure 5. Pipes together centered Figure 6. 13 mm spacers - centered Figure 7. 13 mm spacers - aside Figure 8. 38 mm spacers - centered Figure 9. 38 mm spacers - aside C

Figure 10. Comparison of R b for all the pipe positions Figure 2 represents the case where the pipes are almost in direct contact with the borehole wall. This is almost impossible to achieve in practice, unless a system is activated to separate the pipes once the BHE is into the borehole, a solution that has been tested in USA and presented in [8]. Figures 3 to 5 are probably the closest to a real installation, with the arrangement in figure 5 presumable the least probable. This is due to the fact that both BHE pipes are normally delivered together in a roll in such a way that they can be inserted into the borehole in parallel. It is clear from table 3 that these configurations do not offer the best heat transfer performance. On the other hand, it can be noticed that the highest heat flows take place for separated pipes (pipes apart) or for 38 mm spacers laying aside. These two solutions are probably intuitive, although their quantification makes them useful. Figures 6 and 7 illustrate the solution after modeling the 13 mm spacers in two different positions, centered and aside. It is possible to appreciate that, still with this distance, there is certain thermal influence between channels, visible at the warmer isothermal lines that go into the colder pipes, i.e. transferring heat to it. This phenomenon is even more obvious in the previous three figures (Fig 2-5). In contrast, Figure 2 demonstrates that total separation of the pipes partially eliminates their thermal contact. Figures 8 and 9 correspond to the solution of the 38 mm spacers in the centered and side position, respectively. The illustration is similar to the shorter version of spacers, but the shape of the isotherms in the surrounding of the pipes significantly change. The higher temperatures (14.5 to 16 K) are concentrated on the surroundings of the warmer pipe. It is relevant to put special interest on the borehole wall temperature for each model. The isothermal lines illustrate how the borehole wall temperature varies along the borehole perimeter, changing sometimes up to 4 degrees along the borehole periphery.

Finally, a useful illustration is presented in Figure 10, where the R b results are plotted for each of the pipe positions. The resistance values are within the range 0.118-0.260 K m/w. The lowest value corresponds to the configuration when the pipes are apart from each other, and the largest to when the pipes are together in the center. This figure demonstrates that the use of spacers does not necessarily mean an improvement of the heat transfer performance. 4. Conclusions Eight cross sectional U-pipe BHE configurations modeled and calculated with the software COMSOL Multi-physics were presented and compared. The boundary conditions were based on recent experimental temperature measurements and calculated heat transfer coefficients. The two-dimensional problem was solved with the steady state heat transfer equation. The borehole thermal resistance is calculated in order to quantitatively compare the thermal performance of all presented cases. Isothermal lines and heat flow directions illustrate how heat is transferred between the rock and the pipes as well as the thermal shunt flow occurring between channels. The best U-pipe BHE configuration corresponds to when the pipes are completely apart from each other, with a borehole thermal resistance of 0,118 Km/W. However, this pipe arrangement is hard to achieve. The 38 mm spacers may give a good thermal performance if located aside, i.e. next to the borehole wall. This arrangement is very likely to occur in real installations and has an R b value equal to 0.127 K m/w, about 10% lower than the separated pipes case. The same pipe location when using 13 mm spacers would as well be within the best three configurations, having an R b of 0.148 Km/W. Using 13mm and 38 mm spacers may not always be profitable. The spaced pipes may end up in certain positions that would decrease the thermal performance of the BHE, being even worse than certain non-spaced configurations. Therefore, the use of spacers does not necessarily mean an improvement of the heat transfer performance. 5. References 1. Claesson Johan, Bennet Johan, Multipole method to compute the conductive heat flows to and between pipes in a cylinder, Department of Building Technology and Mathematical Physics, (1987). 2. Hellström Göran, Ground Heat Storage Thermal Analyses of Duct Storage Systems, Doctoral Thesis, Lund (1991) 3. Hellström Göran, Thermal Performance of Borehole Heat Exchangers." The Second Stockton International Geothermal Conference. 1998. 4. Esen Hikmet, Inalli Mustafa, Esen Yuksel. Temperature distributions in boreholes of a vertical ground-coupled heat pump, Renewable Energy 2672-2679, (2009). 5. Acuña José, Palm Björn. Experimental comparison of four borehole heat exchangers, 8th IIR Gustav Lorentzen Conference. Copenhagen, (2008). 6. Ten Maria. Thermal Comparison of Two Borehole Heat Exchangers. MSc Thesis, The Royal Institute of Technology 008:458, Stockholm (2008). 7. Acuña José, Mogensen Palne, Palm Björn. Distributed thermal response test on a U-pipe borehole heat exchanger. EFFSTOCK Conference, Stockholm (2009). 8. Bose, J.E., M.D. Smith, J.D. Spitler. Advances in Ground Source Heat Pump Systems - An International Overview. 7th IEA Heat Pump Conference. 1:313-324. Beijing, (2002). 9. Basell, Technical Manual for Pipe Materials Polyethylene 10. Ericsson - Värmeutbyte mellan berggrund och borrhål vid bergvärmesystem, Chalmers University of Technology, Gothenburg (1985). 11. Melinder, Åke. Thermophysical Properties of Aqueous Solutions Used as Secondary Working Fluids, Doctoral Thesis,The Royal Institute of Technology, Sweden (2007). 12. Zeng H., Diao N., Fang Z. Heat transfer analysis of boreholes in vertical ground heat exchangers. Int. J. of Heat and Mass Transfer. Vol. 46, 4467-4481 (2003). 13. Gustafsson A-M, Thermal response test: numerical simulations and analyses. Licentiate Thesis 2006:14, Luleå University of Technology, Sweden, (2006).