REPORT HOLDER: STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) 35 EAST WACKER DRIVE, SUITE 850 CHICAGO, ILLINOIS EVALUATION SUBJECT:

Similar documents
ICC-ES Evaluation Report. ESR-3064P Issued February 1, 2013 This report is subject to renewal February 1, 2014.

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT:

REPORT HOLDER: OLMAR SUPPLY INC RESEARCH DRIVE LIVERMORE, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: CALIFORNIA EXPANDED METAL PRODUCTS COMPANY (CEMCO) CROSSROADS PARKWAY NORTH, SUITE 325 CITY OF INDUSTRY, CALIFORNIA 91746

REPORT HOLDER: WARE INDUSTRIES, INC. (DBA Marino\WARE) 400 METUCHEN ROAD SOUTH PLAINFIELD, NEW JERSEY EVALUATION SUBJECT:

REPORT HOLDER: WARE INDUSTRIES, INC., d/b/a MARINO\WARE 400 METUCHEN ROAD SOUTH PLAINFIELD, NEW JERSEY EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS LLC

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A DIVISION OF MITEK

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A DIVISION OF MITEK

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: MITEK USA, INC.

DIVISION: METALS SECTION: COLD FORMED METAL FRAMING REPORT HOLDER: AEGIS METAL FRAMING, A MITEK COMPANY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC.

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: TENDON SYSTEMS, LLC

DIVISION: METALS SECTION: STEEL DECKING SECTION: STEEL FLOOR DECKING SECTION: STEEL ROOF DECKING REPORT HOLDER:

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: GRABBER NAILS FOR GYPSUM WALLBOARD INSTALLATION

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: BOSTITCH FASTENING SYSTEMS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: PLASTIC DECKING REPORT HOLDER: SILCA SYSTEM

REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC. EVALUATION SUBJECT: GRABBER FASTENERS FOR USG STRUCTURAL PANELS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: BORAL ROOFING LLC

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL FASTENINGS DIVISION: FINISHES SECTION: FASTENERS REPORT HOLDER: HILTI, INC.

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

DIVISION: OPENINGS SECTION: VENTS/FOUNDATION FLOOD VENTS REPORT HOLDER: SMARTVENT PRODUCTS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: CERTAINTEED CORPORATION

REPORT HOLDER: ispan SYSTEMS LP 70 BRENTWOOD DRIVE PRINCETON, ONTARIO N0J 1V0 CANADA EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: EXTERIOR INSULATION AND FINISH SYSTEMS REPORT HOLDER: DRYVIT SYSTEMS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: EXTERIOR INSULATION AND FINISH SYSTEMS REPORT HOLDER: PAREX USA, INC.

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO.

DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: ULTRALOX EVALUATION SUBJECT:

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-FABRICATED WOOD TRUSSES REPORT HOLDER: EAGLE METAL PRODUCTS

DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: CPG INTERNATIONAL LLC DBA THE AZEK COMPANY LLC EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: ULTRALOX 2955 LONE OAK DRIVE, SUITE 180 EAGAN, MINNESOTA 55121

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 100 PLANO, TEXAS 75024

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS REPORT HOLDER: WORTHINGTON ARMSTRONG VENTURE (WAVE)

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: HY-TEK FASTENERS INC. EVALUATION SUBJECT: HY-TEK NAILS

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CONCRETE ROOF TILES REPORT HOLDER: BARTILE ROOFS, INC. EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

REPORT HOLDER: GEORGIA PACIFIC GYPSUM LLC 2861 MILLER ROAD DECATUR, GEORGIA EVALUATION SUBJECT: DENSELEMENT BARRIER SYSTEM

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS SECTION: PLASTIC DECKING REPORT HOLDER:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: KAYCAN LTD.

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

DIVISION: MASONRY SECTION: MANUFACTURED BRICK MASONRY SECTION: MANUFACTURED STONE MASONRY REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: EQUITONE

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: PASLODE, AN ILLINOIS TOOL WORKS COMPANY

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: SIDING REPORT HOLDER: SHAKERTOWN 1992, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: TEJAS BORJA USA EVALUATION SUBJECT:

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: SUZHOU HONGLY HARDWARE CO., LTD.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW BUILDEX 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: SRL INDUSTRIES LTD.

REPORT HOLDER: SOPREMA, INC. 310 QUADRAL DRIVE WADSWORTH, OHIO EVALUATION SUBJECT:

REPORT HOLDER: HUBER ENGINEERED WOODS, LLC ONE RESOURCE SQUARE DAVID TAYLOR DRIVE, SUITE 300 CHARLOTTE, NORTH CAROLINA 28262

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS REPORT HOLDER: HB&G BUILDING PRODUCTS, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT:

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

REPORT HOLDER: BASF CORPORATION EVALUATION SUBJECT: MASTERSEAL AWB 660 I VAPOR RETARDER, AIR AND WATER-RESISTIVE BARRIER AND FLEXIBLE FLASHING

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: DEXTRA MANUFACTURING CO., LTD. EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-FABRICATED WOOD TRUSSES REPORT HOLDER: MITEK USA, INC.

DIVISION: OPENINGS SECTION: VENTS/FOUNDATION FLOOD VENTS REPORT HOLDER: FLOOD FLAPS, LLC EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: OPENINGS SECTION: VENTS/FOUNDATION FLOOD VENTS REPORT HOLDER: FLOOD FLAPS, LLC

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: BARRETTE STRUCTURAL DISTRIBUTION, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: KMEW CO., LTD. EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: FLAMEOFF COATINGS, INC. EVALUATION SUBJECT:

Trusted ICC ES HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: KP BUILDING PRODUCTS

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER:

DIVISION: CONCRETE SECTION: MAINTENANCE OF CONCRETE REPORT HOLDER: STRUCTURAL TECHNOLOGIES, LLC

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER:

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PEIKKO GROUP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CONCRETE ROOF TILES REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

Transcription:

0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-3064P Reissued 02/2015 This report is subject to renewal 02/2016. SECTION: 05 40 00 COLD-FORMED METAL FRAMING SECTION: 05 41 00 STRUCTURAL METAL STUD FRAMING SECTION: 05 42 00 COLD-FORMED METAL JOIST FRAMING SECTION: 09 22 16.13 NON-STRUCTURAL METAL STUD FRAMING STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) Look for the trusted marks of Conformity! 2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2015 ICC Evaluation Service, LLC. All rights reserved.

ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3064P* Reissued February 2015 This report is subject to renewal February 2016. A Subsidiary of the International Code Council Section: 05 40 00 Cold-Formed Metal Framing Section: 05 41 00 Structural Metal Stud Framing Section: 05 42 00 Cold-Formed Metal Joist Framing Section: 09 22 16.13 Non-Structural Metal Stud Framing STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) (312) 224-2570 www.ssma.com info@ssma.com ADDITIONAL LISTEES: ALLSTEEL & GYPSUM, INC. 1250 NW 23 RD AVENUE FORT LAUDERDALE, FLORIDA 33311 (954) 587-1900 www.allsteelproducts.com CONSOLIDATED FABRICATORS CORP. 8584 MULBERRY STREET FONTANA, CALIFORNIA 92335 (909) 770-8920 www.confabbpd.com CUSTOM STUD, INC. 8415 220 TH STREET WEST LAKEVILLE, MINNESOTA 55044 (952) 985-7000 www.customstud.com CRACO MANUFACTURING, INC. POST OFFICE BOX 1105 YORK, SOUTH CAROLINA 29745 (803) 684-5544 www.cracometals.com FRAMETEK STEEL PRODUCTS 1495 COLUMBIA AVENUE, BUILDING #4 RIVERSIDE, CALIFORNIA 92507 951-369-5204 www.frameteksteel.com OLMAR SUPPLY, INC. 2140 RESEARCH DRIVE LIVERMORE, CALIFORNIA 94551 (925) 447-3500 www.olmarsupply.com QUAIL RUN BUILDING MATERIALS, INC. 2102 WEST LONE CACTUS DRIVE PHOENIX, ARIZONA 85027 (602)269-2316 www.qrbm.com SCAFCO CORPORATION 2800 EAST MAIN AVENUE SPOKANE, WASHINGTON 99202 (509) 343-9000 www.scafco.com STEEL CONSTRUCTION SYSTEMS 11250 ASTRONAUT BOULEVARD ORLANDO, FLORIDA 32837 (407) 438-1664 www.steelconsystems.com UNITED METAL PRODUCTS, INC. 234 NORTH SHERMAN AVENUE CORONA, CALIFORNIA 92882 (951) 739-9535 www.unitedmetalproducts.info 1.0 EVALUATION SCOPE Compliance with the following codes: 2015, 2012 and 2009 International Building Code (IBC) 2015, 2012 and 2009 International Residential Code (IRC) 2013 Abu Dhabi International Building Code (ADIBC) The ADIBC is based on the 2009 IBC. 2009 IBC code sections referenced in this report are the same in the ADIBC. Property evaluated: Structural 2.0 USES The Steel Stud Manufacturers Association (SSMA) coldformed steel framing members are used for framing of nonload-bearing interior walls, curtain walls, and loadbearing walls, floors and roofs. 3.0 DESCRIPTION 3.1 General: The SSMA cold-formed steel framing members described in this report are factory-formed from coils of steel at *Revised September 2015 ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2015 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 4 1000

ESR-3064P Most Widely Accepted and Trusted Page 2 of 4 the facilities listed in Table 2. The cold-formed framing members include C-shapes (S-sections), tracks (T-sections), U-channels (U-sections) and hat furring channels (F-sections). The S-sections are manufactured with and without web punch-outs. All other framing members (T-sections, U-Sections, and F-sections) are manufactured without punch-outs. When provided, the punch-outs have a width of 1 1 / 2 inches (38 mm) and a length of 4 inches (102 mm) in S-sections with a depth of 3 1 / 2 inches (89 mm) or greater. In S-sections with a depth between 1 5 / 8 inches (41 mm) and 2 1 / 2 inches (64 mm), punch-outs have a width of 3 / 4 inch (19 mm) and a length of 4 inches (102 mm). The punch-outs are spaced a minimum of 24 inches (610 mm) on center and have a minimum distance between the end of the member and the near edge of the punch-out of 10 inches (254 mm). The SSMA S-sections, T-sections, U-sections, and F-sections are detailed in SSMA s catalogue titled Product Technical Guide, copyrighted 2015, effective August 14, 2015, which is distributed with this report. The following tables, figures, and pages from the catalogue are part of this report: Material Specification Page 4 General Product Information Page 5 Note: In Note #9, replace must be approved by a design professional with are outside the scope of this report. Definitions of Structural Property Symbols Page 6 Section Properties (S-Sections) Pages 7 14 Note: Holes in the web of members with a web heightto-thickness ratio in excess of 200 are outside the scope of this report. Members with a web height-to-thickness ratio in excess of 260 or a flange width-to-thickness ratio in excess of 60 are outside the scope of this report. Section Properties (T-Sections) Pages 15 18 Members with a web height-to-thickness ratio in excess of 260 or a flange width-to-thickness ratio in excess of 60 are outside the scope of this report. Interior Nonload-Bearing Wall Heights Composite Tables - Composite Pages 19-20 Additional notes applicable to pages 19 and 20: Gypsum wallboard must be a minimum of 5 / 8 inch (15.9 mm) thick and Type X, complying with ASTM C1396 and manufactured by American Gypsum, CertainTeed, Georgia Pacific, Lafarge, National Gypsum, Temple-Inland, or USG. Fasteners for attaching the gypsum wallboard to the studs and tracks must be No. 6, Type S, fine thread drywall bugle head screws conforming to ASTM C1002. Installation of the gypsum wallboard must be in accordance with GA-216 or ASTM C840. Each gypsum wallboard panel must be attached to the top and bottom track with a minimum of 3 fasteners spaced a maximum of 16 inches (406 mm) on center. Interior Wall Limiting Heights Non-Composite Fully Braced Span Tables Pages 21-22 Interior Wall Limiting Heights Braced at 48" o.c. Span Tables Pages 23-24 Curtain Wall Limiting Heights Single Span Pages 25-27 Curtain Wall Limiting Heights-Double Span Pages 28-30 Note: Exterior curtain walls must be designed for a transverse load of no less than 10 psf (478 Pa). Combined Axial and Lateral Loads Pages 31-41 Floor Joist Spans Pages 42-55 Header Loads Pages 56-57 Web Crippling Load Tables Pages 58 60 Note: Values for which the bearing length to web height ratio (N/h) exceeds 1 or bearing length to thickness ratio (N/t) exceeds 210 are outside the scope of this report. Ceiling/Soffit Spans (S-Sections) Pages 61-67 Section Properties & Ceiling Spans (F-Sections) Page 68 Section Properties & Ceiling Spans (U-Sections) Page 69 All other items and pages in the Product Technical Guide are outside the scope of this report. 3.2 Material: The SSMA metal framing members are cold-formed from steel coils conforming to ASTM A1003 Structural Grade 50 Type H (ST50H); ASTM A1003 Structural Grade 33 Type H (ST33H); ASTM A653 SS Grade 33; ASTM A653 SS Grade 50 Class 1; or ASTM A1003 Nonstructural Grade 33 (NS33). The steel conforming to ASTM A653 must have a minimum metallic coating designation of G60 or A60 in accordance with ASTM A653 for applications other than interior nonload-bearing walls. The steel conforming to ASTM A653 may have a minimum metallic coating designation of G40 or A40 in accordance with ASTM A653 for interior nonload-bearing wall applications. The steel conforming to ASTM A1003 ST50H or ST33H must have a minimum metallic coating designation of G60, A60, AZ50, GF30, T1-25, or T2-100 in accordance with ASTM A1003. The steel conforming to ASTM A1003 NS33 must have a minimum metallic coating designation of G40, A40, AZ50, GF30, T1-25, or T2-100 in accordance with ASTM A1003. 4.0 DESIGN AND INSTALLATION 4.1 Design: 4.1.1 IBC Method: The section properties for the coldformed steel framing members recognized in this report have been determined in accordance with the applicable edition of the North American Specification for Design of Cold-Formed Steel Structural Members (AISI S100). The moments listed in this report are allowable moments and are used with Allowable Strength Design (ASD) for flexural members with the compression flange fully braced. For other conditions of compression flange bracing, the allowable moment must be determined in accordance with the applicable edition of AISI S100. The design of flexural members must address combined bending and web crippling, and combined bending and shear, as applicable in accordance with the applicable edition of AISI S100. 4.1.2 IRC Method: The S-sections listed in Table 1 of this report qualify for use with prescriptive requirements of the IRC. T-sections with flange width of 1.250 inches (31.75 mm) or greater qualify for use with the prescriptive requirements of the IRC. For use of all other sections under the IRC, the cold-formed steel framing members must be limited to engineered structures, in accordance with IRC Section R301.1.3.

ESR-3064P Most Widely Accepted and Trusted Page 3 of 4 When the framing members are used to construct buildings that do not conform to the applicable requirements of IRC Sections R505.1, R603.1 or R804.1.1, and for framing members not identified in Table 1 of this report, the structural analysis and design must be in accordance with the IBC, as described in Section 4.1.1 of this report. 4.2 Installation: The framing members must be installed in accordance with the applicable code, the approved plans and this report. If there is a conflict between the plans submitted for approval and this report, this report governs. The approved plans must be available at the jobsite at all times during installation. 5.0 CONDITIONS OF USE The SSMA metal framing members described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The cold-formed steel members must be installed in accordance with the applicable code, the approved plans and this report. 5.2 Minimum uncoated base-metal thickness of the coldformed steel members as delivered to the jobsite must be at least 95 percent of the design base-metal thickness. 5.3 Complete plans and calculations verifying compliance with this report must be submitted to the code official for each project at the time of permit application. The calculations and drawings must be prepared and sealed by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 5.4 Framing members cold-formed from NS33 steel are limited to use in interior nonload-bearing walls subject to a maximum 10 psf (478 Pa) transverse load. Framing members without the steel classification designated must be considered NS33 steel (see Section 7.0). 5.5 Framing members with a height-to-thickness (h/t) ratio of more than 200 must be provided with web stiffeners in accordance with Sections B1.2 and C3.2.2 of AISI S100 and holes or punch-outs in the web are outside the scope of this report. 5.6 The interior nonload-bearing wall assemblies are limited to interior installation where the superimposed axial load is zero pounds. 5.7 Design of the attachment of the interior nonloadbearing wall assemblies to the surrounding structure is outside the scope of this report. 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with the ICC-ES Acceptance Criteria for Cold-formed Steel Framing Members (AC46), dated June 2012 (editorially revised April 2015). 6.2 Data in accordance with the ICC-ES Acceptance Criteria for Cold-formed Steel Framing Members Interior Nonload-bearing Wall Assemblies (AC86), dated May 2012 (editorially revised August 2015). 7.0 IDENTIFICATION At a spacing not exceeding 96 inches (2440 mm) on center, each cold-formed steel member is stamped, stenciled or embossed with the company name or initials (see the listees at the beginning of this report); the acronym ICC-ES ; the evaluation report number (ESR-3064P); and the minimum uncoated base-metal thickness in mils or decimal inches. For structural applications, the minimum yield strength and the protective coating designation (CP 60 or CP 90 as defined by AISI S200-12 or ASTM C955) are included. For nontstructural applications, the minimum specified yield strength if over 33 ksi (230 MPa); the metallic coating type and weight if other than ASTM A653 G40; and the designation NS are included.

ESR-3064P Most Widely Accepted and Trusted Page 4 of 4 TABLE 1 C-SHAPES (S-SECTIONS) FOR USE WITH THE IRC IRC MEMBER DESIGNATION 350S162-t 550S162-t 800S162-t 1000S162-t 1200S162-t EQUIVALENT SSMA MEMBER DESIGNATION t = 33 t = 43 t = 54 t = 68 t = 97 350S162-33 350S162-43 350S162-54 350S162-68 --- 350S200-33 350S200-43 350S200-54 350S200-68 --- 550S162-33 550S162-43 550S162-54 550S162-68 550S162-97 550S200-33 550S200-43 550S200-54 550S200-68 550S200-97 800S162-33 800S162-43 800S162-54 800S162-68 800S162-97 800S200-33 800S200-43 800S200-54 800S200-68 800S200-97 --- 1000S162-43 1000S162-54 1000S162-68 1000S162-97 --- 1000S200-43 1000S200-54 1000S200-68 1000S200-97 --- --- 1200S162-54 1200S162-68 1200S162-97 --- --- 1200S200-54 1200S200-68 1200S200-97 Allsteel & Gypsum, Inc. Fort Lauderdale, FL 33311 Consolidated Fabricators, Corp. Fontana Fontana, CA 92335 Consolidated Fabricators, Corp. Galt Galt, CA 95632 Craco Manufacturing, Inc. York, SC 29745 Custom Stud, Inc. Lakeville, MN 55044 TABLE 2 MANUFACTURING LOCATIONS Frametek Steel Products Riverside, CA 92507 Olmar Supply Inc. Livermore, CA 94551 Quail Run Building Materials, Inc. Phoenix, AZ 85027 SCAFCO Corporation Spokane Spokane, WA 99202 SCAFCO Corporation Stockton Stockton, CA 95206 Steel Construction Systems Orlando Orlando, FL 32837 United Metal Products, Inc. Corona Corona, CA 92882 United Metal Products, Inc. Phoenix Phoenix, AZ 85043

ICC-ES Evaluation Report ESR-3064P CBC and CRC Supplement Reissued February 2015 This report is subject to renewal February 2016. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council Section: 05 40 00 Cold-Formed Metal Framing Section: 05 41 00 Structural Metal Stud Framing Section: 05 42 00 Cold-Formed Metal Joist Framing Section: 09 22 16.13 Non-Structural Metal Stud Framing STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) (312) 224-2570 www.ssma.com info@ssma.com 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that SSMA Cold-Formed Steel Framing, recognized in ICC-ES master report ESR-3064P, has also been evaluated for compliance with Chapters 16, 16A, 17, 17A, 22, and 22A of the codes noted below. Applicable code editions: 2010 California Building Code (CBC) 2010 California Residential Code (CRC) 2.0 CONCLUSIONS 2.1 CBC: The SSMA Cold-Formed Steel Framing, described in Sections 2.0 through 7.0 of the master evaluation report ESR-3064P, complies with CBC Chapters 16, 16A, 17, 17A, 22, and 22A, provided the design and installation are in accordance with the International Building Code (IBC) provisions noted in the master report and the additional requirements of CBC Chapters 16, 16A, 17, 17A, 22, and 22A, as applicable. 2.2 CRC: The SSMA Cold-Formed Steel Framing, described in Sections 2.0 through 7.0 of the master evaluation report ESR-3064P, complies with CRC Chapters 5, 6 and 8, provided the design and installation are in accordance with the International Residential Code (IRC) provisions noted in the master report. This supplement expires concurrently with the master report, reissued February 2015 and revised September 2015. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2015 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 1 1000

ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3064P FBC Supplement Reissued February 2015 This report is subject to renewal February 2016. A Subsidiary of the International Code Council Section: 05 40 00 Cold-Formed Metal Framing Section: 05 41 00 Structural Metal Stud Framing Section: 05 42 00 Cold-Formed Metal Joist Framing Section: 09 22 16.13 Non-Structural Metal Stud Framing STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) (312) 224-2570 www.ssma.com info@ssma.com 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that SSMA Cold-Formed Steel Framing, recognized in ICC-ES master report ESR-3064P, has also been evaluated for compliance with the codes noted below. Applicable code editions: 2010 Florida Building Code Building 2010 Florida Building Code Residential 2.0 CONCLUSIONS The SSMA Cold-Formed Steel Framing, described in Sections 2.0 through 7.0 of the master evaluation report ESR-3064P, complies with the 2010 Florida Building Code Building and the 2010 Florida Building Code Residential, provided the design and installation are in accordance with the International Building Code (IBC) provisions noted in the master report. Use of the SSMA Cold-formed Steel Framing has also been found to be in compliance with the High-Velocity Hurricane Zone provisions of the 2010 Florida Building Code Building and the 2010 Florida Building Code Residential. For products falling under Florida Rule 9N-3, verification that the report holder s quality-assurance program is audited by a quality-assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued February 2015 and revised September 2015. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2015 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 1 1000

CC-ES Evaluation Report www.icc-es. org (800) 423-6587 ESR-3064P CC CC Supplement Issued September 2015 This report is subject to renewal February 2016. (562) 699-0543 A Subsidiary of the International Code Council Section: 05 40 00 Cold-Formed Metal Framing Section: 05 41 00 Structural Metal Stud Framing Section: 05 42 00 Cold-Formed Metal Joist Framing Section: 09 22 16.13 Non-Structural Metal Stud Framing STEEL STUD MANUFACTUR RERS ASSOCIATION (SSMA) 312) 224-2570 www.ssma.comm nfo@ssma.com 1.0 REPORT PURPOSE AND SCOPE The purpose of this evaluation report supplement is to indicate that SSMA cold-formed steel C-shapes (studs) and tracks members, recognized in ICC-ES master report ESR-3064P and Section 3.0 of this supplement, are certified to be in compliance with the ICC-ES Code Compliance Certification Program. Studs and tracks are periodically checked for mechanical properties, coatings, dimensions and labeling. 2.0 LABELING Certified products bear the following label: CC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty byy ICC Evaluation Service, LLC, express or implied, as o any finding or other matter in this report, or as to any product covered by the report. Copyright 2015 ICC Evaluation Service, LLC. All rights reserved. 1000 Page 1 of 2

ESR-3064P CCC Supplement Most Widely Accepted and Trusted Page 2 of 2 3.0 CERTIFIED MANUFACTURING FACILITIES Allsteel & Gypsum, Inc. Fort Lauderdale, FL 33311 Consolidated Fabricators, Corp. Fontana Fontana, CA 92335 Consolidated Fabricators, Corp. Galt Galt, CA 95632 Craco Manufacturing, Inc. York, SC 29745 Custom Stud, Inc. Lakeville, MN 55044 Frametek Steel Products Riverside, CA 92507 Olmar Supply Inc. Livermore, CA 94551 Quail Run Building Materials, Inc. Phoenix, AZ 85027 SCAFCO Corporation Spokane Spokane, WA 99211 SCAFCO Corporation Stockton Stockton, CA 95206 Steel Construction Systems Orlando Orlando, FL 32837 United Metal Products, Inc. Corona Corona, CA 92882 United Metal Products, Inc. Phoenix Phoenix, AZ 85043 This supplement expires concurrently with the master report, reissued February 2015 and revised September 2015.