Building code language is unclear regarding low-slope roof assembly ventilation. by Brian Erickson, P.E., and Liberty Lewis, P.E.

Similar documents
O HAGIN ATTIC VENTILATION PRODUCTS ARE IN COMPLIANCE WITH THE REQUIREMENTS OF THE MOST RECENT BUILDING CODES FOR ATTIC VENTILATION

26 May 2011

Sloped Roofs vs Walls. Problems. Review Roof Components. University of Waterloo and Balanced Solutions

BASIC VENTILATION REQUIREMENTS

Building Enclosure Detailing for Walls and Low-Sloped Roofs

A Closer Look Inspection Service 2015 IECC Residential DFW area handout

Welcome to this continuing education seminar. This is the first of three parts of the Building Enclosure Fundamentals series.

Eradicating ice dams begins below the roof deck. by Maciek Rupar

2009 IECC Chapter 1 Additions, alterations, renovations or repairs.

ENERGY SAVINGS FOR LIFE

2006 INTERNATIONAL ENERGY CONSERVATION CODE

2015 MICHIGAN UNIFORM ENERGY CODE Effective: February 8, 2016

1. PREINSPECTION RESIDENTIAL ENERGY EFFICIENCY 7

A.ENVELOPE AIR SEALING

Table Air Barrier and Insulation Inspection Component Criteria

Building with Ducts in Conditioned Spaces Conditioned Attics


Advanced technologies for enhancing the building envelope. 3M Building and Construction Market

Insulation Technologies and Installation Specifications for Better Energy Performance of Commercial Buildings

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont

Goals of Session. Building a Better Thermal Envelope. Thermal Envelope Priorities. Disclaimer. Insulation performance (Real World)

ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section )

ADDITION A NEW. This year s volume of The NRCA Roofing Manual completes the current four-volume set. by Maciek Rupar

Where to Draw the Line with Thermal Boundaries

Airspace R-Values. Educational Overview. Revised 12/6/2016

INSULATION BATT (1) (2) Code Reference: 2016 Title 24, Reference Appendices RA3.5. Pressure or Friction Fit

Air Sealing for 5 ACH 50

AIR BARRIER SYSTEMS VAPOR-PERMEABLE AND NON-PERMEABLE. Sealed, Smart, and Sustainable WATERPROOFING & BUILDING PRODUCTS COMMERCIAL PRODUCT

Boulder City NV Prepared by (Print Name) Signature Date

Index. STP779-EB/Jul. 1982

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC

New Construction Procurement Guidelines for the Pacific Northwest

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

EE13-3 Improving Building Enclosures Thermal Performance as a Goal of Energy Efficiency. Paul E. Totten, PE Marcin Pazera, Ph. D.

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance

Residential Plan Review for New One and Two Family Dwellings

Thermal Control in Buildings by John Straube (updated )

WeatherSmart Air Barrier Installation Guide

2018 IECC Residential Provisions with Corresponding IRC Sections

Residential Requirements of the Texas Energy Code 2009 IRC Chap 11

PREP + INSULATION. DISCLAIMER: These tools are for illustrative purposes only and

Thermal Bridging in Residential Construction

Moisture Considerations for Insulated Building Assemblies

BUILDING ENCLOSURE AIR TIGHTNESS TESTING Course Number: BCLUNA018-01P

Understanding Energy Codes

Advanced Ventilation for Residential applications FBC Res 2010.

Spray Polyurethane Foam. Insulation and Air Barrier Requirements of the 2012 I-Codes. Spray Foam Coalition

Insulating Basements: Part 1 Fundamentals

2006 Building Science Press All rights of reproduction in any form reserved.

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER

2015 IECC Air Sealing Multifamily For Code Compliance Funding for Energy Code Training

Feature Zone IECC 2009 IECC

Insight. Doubling Down: How Come Double Vapor Barriers Work? By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE

Residential Codes FAQs: 2015 International Energy Conservation Code (IECC) with MA Amendments & MA Stretch Energy Code

Air Barrier Requirements for Low-Slope Roof Assemblies Myths vs. Facts

Truss Heel Heights and Energy Code Requirements. Overview Revised 2/17/2017

Crawl Spaces and Basements: Defining the Building Envelope

City of High Point Airport Overlay District Noise Level Reduction Design Standards

NAHB s Recommendations on Critical 2015 ICC Code Change Proposals

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

Mark Lawton, P.Eng., FEC. Airtightness in Buildings A Canadian History June 2017

Radon Vent Pipe System. Labeling Performance Indicators

the re-cover option, there are several elements to keep in mind to achieve proper longevity of the new roof system. Replacement vs.

SECTION THERMAL INSULATION

Low-cost Construction for High-energy Savings. Brian J. Wimmer Construction Manager Rochester Area Habitat for Humanity

ROOFING APPLICATION STANDARD (RAS) No. 109

MOISTURE VAPOR MOVEMENT AND VAPOR PERMEANCE

How-to: Commissioning Design Reviews for the Building Envelope

INTERIOR ENVIRONMENT

IECC Residential Significant Changes Summary. Tier I

Town/City: State: Zip: Town/City: State: Zip: Phone: Cell: Phone: Cell:

Healthy, Durable, Low Energy Buildings: Thermal: High R. Thermal bridges. Fundamentals, techniques, and pitfalls

IECC. EnergyWise. re-energized

Metal to the metal. by W. Lee Shoemaker, Ph.D., P.E. and Vincent E. Sagan, P.E. and Dale Nelson

International Code Council

Charter Township of Washington

Welcome to this continuing education seminar. This is the first of two parts of the High- Performance Building series.

By James Tente, MCP, CBO,CFM

ICE DAMS PROTECTING YOUR HOME FROM

Overview of Presentation. Airflow Control: Why. Airflow Control: what kind?

Recommendations on Proposed International Code Changes

RECREATIONAL EAGLE CENTER METAL ROOF ASSESSMENT AND SOLUTION

RESIDENTIAL ENERGY CODE. The 2015 International Energy Conservation Code (IECC) as modified below.

FRAMING INSPECTION GENERAL

6. Moisture Design. Objectives: 3. Prevent vapor condensation (surface, concealed) 4. Prevent rain penetration

The Lower The HERS Score The Better. Tight Building Envelope. Renewable Energy Sources. Materials & Waste Management. Energy Efficient Lighting

Quality Insulation Installation (QII) Insulation Installation (Page 1 of 4)

IECC - RESIDENTIAL - ENERGY TAC

2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building

THE SITUATION WITH STEEL DECKS

Residential Energy Code Update

In addition to performing as an interior vapor retarder, MemBrain the Smart Vapor Retarder may be installed as a continuous, interior

2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building

Managing Condensation and Thermal Performance with Continuous Insulation

Building Enclosure Details and Assemblies for Wood-Frame Buildings

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

September 3, Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

PROJECT DIRECTIVE # FOR KALISPELL PUBLIC SCHOOLS

General Contractor: Company Name: Location of Proposed Structure: Tax Map #: Lot #:

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

Transcription:

Building code language is unclear regarding low-slope roof assembly ventilation by Brian Erickson, P.E., and Liberty Lewis, P.E. 32 November 2009 www.professionalroofing.net

Because of our current litigious environment, many roofing professionals are careful to follow building code requirements exactly lest they face legal challenges. However, there may be instances when strictly adhering to the prescriptive code without engineering analysis and evaluation does more harm than good. For example, the 2006 International Building Code s (IBC s) roof ventilation requirements do not distinguish between low- and steep-slope roof assemblies. In fact, the language suggests the ventilation requirements are for steep-slope assemblies only. However, some roof system designers and code officials have interpreted the code literally and designed or required roof ventilation systems for low-slope assemblies, which can be more deleterious than beneficial. 2006 prescriptive requirement Roofing professionals who look to IBC 2006 for ventilation requirements for lowslope roof assemblies will find Chapter 15, Roof Assemblies and Rooftop Structures, Section 1503 Weather Protection, 1503.5 Roof Ventilation, which reads: 1503.5 Roof ventilation. Intake and exhaust vents shall be provided in accordance with Section 1203.2 and the manufacturer s installation instructions. Note this does not distinguish between steep- and low-slope roof assemblies and does not clarify which manufacturers instructions dictate ventilation. Should one consult the roof covering manufacturer, vent manufacturer or insulation manufacturer? To add to the confusion, no lowslope roof system manufacturers strictly require ventilation, but many roofing material and system manufacturers discuss the need for a properly designed air barrier or vapor retarder in a roof assembly, indicating emphasis on eliminating interstitial condensation. Following the trail in the code, the user then will reference Section 1203.2 to determine the requirements for intake and exhaust vents in roof assemblies. There is a lot of information presented in Section 1203.2 regarding prescriptive requirements for roof ventilation, but this information does not necessarily apply to low-slope roof assemblies. Although alternative materials, design, construction methods and equipment are allowed under IBC Section 104.11, in our experience, designers, contractors and code officials can be reluctant to deviate from prescriptive code requirements either because they fear litigation or do not possess adequate knowledge of building enclosure systems and hygrothermal analysis. However, there are potential limitations and pitfalls if users strictly adhere to IBC 2006 requirements for lowslope roof assembly ventilation. Section 1203.2 The title of IBC 2006 s Section 1203.2 Attic spaces seems to automatically exclude lowslope roof assemblies from the ventilation requirement because attic spaces generally are present in steepslope residential roof systems. However, users and interpreters of IBC 2006 will defer to the first statement in Section 1203.2 to justify ventilating low-slope Photo 1: In this low-slope roof assembly, holes are provided in roof framing members in an attempt to provide cross-ventilation. assemblies, which reads: Enclosed attic spaces and enclosed rafter spaces formed where ceilings are applied directly to the underside of roof framing members shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain and snow. The section we bolded generally is referenced by designers or code officials who require ventilation for low-slope roof assemblies where drywall is applied to the bottom side of roof framing members. Photo 2: This is a close-up of condensation development on the bottom side of a roof deck in a vented low-slope roof assembly. Photos courtesy of Professional Investigative Engineers, Arvada, Colo. ProfessionalRoofing November 2009 33

Photo 3: Condensation developed on the underside of roof sheathing in this low-slope roof assembly in a heating climate. If the bolded section does not apply to a low-slope roof assembly (because of dropped ceiling tiles, exposed metal deck, pre-cast concrete, etc.), you may reasonably conclude the code does not have a prescriptive requirement for ventilating such low-slope roof assemblies. And it should not. Problems can arise when a roof and ceiling assembly has drywall attached to framing members and designers and code officials interpret the remaining Section 1203.2 ventilation requirements as applicable. The first practical obstruction in adhering to IBC 2006 requirements is in the first sentence, namely shall have cross ventilation for each separate space. In low-slope assemblies, each separate space can mean the cavity between roof framing members. Therefore, a vent opening would be required between each framing member. With open-web trusses and joists, it can easily be achieved, but if solid members are used, cross-ventilation is difficult at best. We have seen designers specify holes in framing members to connect the cavities and create a larger or uniform space (see Photo 1). Assuming the holes do not adversely affect the framing members structural capacity, any crossventilation or airflow achieved between cavities is suspect. For air movement to occur, two conditions must exist: a hole or opening for air to pass through and pressure differential across the opening. Obviously, the first requirement is met by specifying holes in the framing members, but how is a pressure differential created between roof framing members that allows air to flow through the openings? Air pressure differences can only be created by wind, buoyancy or mechanical means, such as fans. Buoyancy-induced pressures Buoyancy forces are caused by air temperature differences that affect air density, sometimes referred to as the stack effect or chimney effect. Because warm air is less dense than cold air, warmer air will rise in a column or space where there are temperature differentials. In a low-slope roof assembly with openings provided between framing members, temperature differentials are unlikely to occur because the holes are at the same elevation; therefore, lateral air movement is negligible. However, breather vents or parapet openings may cause airflow into and out of the roof and ceiling assembly from buoyancy forces, but this movement is not likely to occur between framing members. Therefore, wind-induced pressure differentials or mechanically induced pressure differentials are the only remaining mechanisms by which crossventilation can be achieved for each separate space. Wind-induced pressures Wind blowing across a low-slope roof system will create localized pressure differentials, generally negative pressures with the greatest negative pressure zones at the perimeter and corners. Where parapet walls are constructed, the pressure would be positive on the windward side of a parapet and negative on the leeward side. Negative pressures across a roof assembly will pull air out of ventilation openings. As this air is removed from a roof and ceiling assembly, it must be replaced with air from a different source, such as the interior environment, because other openings to the atmosphere also are likely under a negative pressure. The air within conditioned interior environments can contain a greater amount of water vapor when compared with exterior air in heating climates; the opposite is true in humid, cooling climates. In heating climates, the outdoor air during winter generally contains a low concentration of water vapor compared with the indoor air; therefore, replacing attic air with outdoor air would be beneficial from the standpoint of contaminant dilution. However, this strategy comes with a penalty of reduced thermal performance. Any thermal resistance gained from a roof deck and covering material, including a potential benefit of solar heat gains through a dark membrane, is lost as the temperature above the insulation is made equal to ambient air temperatures. Moreover, unless the cavity insulation is installed perfectly (tight and completely filling each cavity), convective loops are likely to occur, resulting in localized cold areas of the ceiling assembly. If these areas temperatures are below the interior air s dew-point temperature, condensation will develop. 34 November 2009 www.professionalroofing.net

Replacing the air within a roof and ceiling assembly with warm, humid interior air greatly increases the risk of condensation development within the assembly, especially as the roof surface temperature is below the dew-point temperature of the interior air (see Photos 2 and 3). Strictly speaking, ventilation s purpose is to remove contaminants from a space so they do not cause harmful effects. In humid climates, replacing attic air with conditioned interior air results in a complex hygrothermal interaction, and the resulting mixed air and surface temperatures are not necessarily beneficial from the standpoint of condensation avoidance. In addition, positive pressures (at parapets) could cause humid exterior air to enter a roof and ceiling assembly where ceiling temperatures likely are less than the dewpoint temperature. When parapet walls are present, there will be a combination of positive and negative pressures where strategically placed ventilation openings can take advantage of these pressure differentials to avoid pulling interior air into an assembly. For crossventilation to occur with parapet walls, a vent opening in the parapet may have to be provided in nearly every framing cavity with an unobstructed path across the entire roof. Additionally, the framing configuration must allow for airflow past any top plate or rim joist into the roof joist bay without compromising the bearing and lateral structural connections. You can imagine the number of parapet wall openings that would be necessary to cross-ventilate such a roof system. These vent openings must allow outdoor air to flow into them but not allow rain or snow to enter. Such vent products may only exist in theory or marketing literature. Indeed, by increasing the number of ventilation openings on a roof for crossventilation, the likelihood of rain and snow entering the roof and ceiling assembly increases significantly. Moreover, the same problem arises in humid climates where the introduction of outdoor air into a roof and ceiling assembly can increase the risk of condensation. Attempting to provide ventilation openings to take advantage of wind-induced pressures is difficult and may result in far greater water-related problems than if no vent openings were provided at all, not to mention the fact that wind does not always blow from the same direction at the same speed or at all. Common products used to ventilate lowslope roof assemblies (generally above decks but not always) are referred to as breather, or gravity, vents. These vents contain a Mylar or cellophane damper near the roof surface that only opens outward, or toward the sky, when wind-induced pressures or vapor pressure differentials are present. Breather vents also are called oneway vents air is allowed to leave the roof assembly through the vent but may not enter. Some breather vents are driven by solar heat gains and buoyancy forces. Breather vents are designed to not allow wind-driven rain or snow to enter the vent assembly, and the damper also assists in stopping wind from entering the vent and, ultimately, roof assembly. However, even if these vents were to perform as advertised, the air leaving the vents would have to be replaced by air from another location. Also, the presence of multiple vents on a roof will reduce an attic assembly s temperature because the Mylar or cellophane damper and aluminum frame do not act as insulators. Finally, the presence of multiple additional penetrations in a roof membrane increases the likelihood for flashing and Photo 4: This is an example of a mechanically vented cathedral ceiling (similar to low-slope construction in cross-section). Airflow measured at the two vents adjacent to the fan matched the fan draw velocity. No airflow was measured at the exterior bay, which was just 64 inches from the fan, despite 2-inch diameter holes cut through the joists in line with the fan. No airflow was measured at eave vents. leakage problems compared with conditions where no vents are installed. You should note that some breather vent roof systems are proprietary designs and have been shown to perform well in severe climates, such as along Florida s coast. These systems generally are installed in reroof or re-cover applications and not necessarily in new construction. Fan-induced pressures To avoid relying on wind-induced pressures, some designers will incorporate a system of fans in a roof and ceiling assembly to control air movement (see Photo 4). In theory, it is possible to design a combination of fans and openings in the framing members to achieve uniform cross-ventilation. The air exhausted from the framing members and roof assembly will be replaced by either interior or exterior air; both sources have potential limitations as replacement air. For a ventilation system to be effective, the incoming air must have lower contaminant concentrations than the air it is replacing; otherwise, problems are created rather than solved. One solution to these potential problems is that designers could specify fans ProfessionalRoofing November 2009 35

Photo 5: How much airflow will occur between framing members with 1-inch airspace in this assembly? controlled by humidity sensors in roof assemblies. The fans would operate and replace the roof assembly air only when the measured relative humidity reaches the sensor set point. Our experience with humidity-controlled fans is the fans tend to operate more often than intended because small variations in temperature and outdoor precipitation cause the relative humidity of the air around the sensor to temporarily rise, triggering the fans to operate even when this period of high relative humidity is not harmful to the roof assembly. There also are Photo 6: This is an example of prescriptively following IBC 2006 s ventilation ratios. The opposite parapet wall also has the same vent spacing. We calculated that even this quantity was not enough to meet the 1/300 ratio. conflicting opinions regarding the proper relative humidity threshold at which the fans should operate. Finally, multiple sensors may be necessary to verify the outdoor relative humidity and more important that the water vapor concentration is lower than the attic assembly before triggering the fans to operate. These solutions to potential problems with mechanical ventilation systems for low-slope roof assemblies involve complex electrical system design and controls, not to mention potential electrical and fire code issues that are not likely worth the added effort for minimal benefit. Even with mechanical ventilation, there must be enough space in a roof assembly to allow true airflow across the roof s length, which requires holes between the joist bays and significant draw from the fan. In our experience, mechanically vented systems do not perform as designed because of constricted air space limiting airflow. The previous discussion should indicate that strictly following IBC 2006 s prescriptive requirement is challenging and may result in moistureand energyrelated problems in a roof assembly. And that is only with the first requirement. Blocking and bridging The next prescriptive requirements read: Blocking and bridging shall be arranged so as not to interfere with the movement of air. A minimum of 1 inch of airspace shall be provided between the insulation and the roof sheathing. Assuming there is airflow in a low-slope roof assembly, one could argue any arrangement of blocking and bridging would affect air movement. This is because the no-slip boundary condition of elementary fluid mechanics (insulation is the boundary and airflow is zero at that level), turbulent flow, and differing surface temperatures of the blocking and bridging members (caused by thermal bridging) create small buoyancy forces that affect airflow. Basically, air movement is reduced at the insulation and around blocking members. In addition, the building code states a 1-inch air space between insulation (generally fiberglass batt) and roof sheathing is sufficient for airflow to occur. In practice, achieving a uniform 1-inch air space between fiberglass batt insulation and roof sheathing does not easily occur, especially without baffles (which also will affect airflow). Also, the surface roughness of the fiberglass insulation will increase the resistance to airflow to the point that a 1-inch space may not be sufficient (see Photo 5). Minimum ventilation ratios Our final discussion point regarding IBC 2006 s prescriptive requirements for lowslope roof assembly ventilation is the minimum ventilation ratio requirements of 1/150 and 1/300. IBC 2006 states: The net free ventilating area shall not be less than 1/150 of the area of the space ventilated. The minimum required net free ventilating area shall be 1/300 of the area of the space ventilated, provided a vapor retarder having a transmission rate not exceeding 1 perm in accordance with ASTM E96 is installed on the warm side of the attic insulation. 36 November 2009 www.professionalroofing.net

The scientific basis for these ratios is unknown to us and may not exist, but researchers and code officials will state that thousands of roof assemblies have been constructed with these ventilation ratios and are performing well. Although this may be true for steep-slope roof assemblies, the ratio of 1/150 or 1/300 may be excessive for low-slope roof assemblies because the surface area for low-slope roof systems generally far exceeds that of steep-slope roof systems. For example, a 10,000-square-foot lowslope roof system that contains a vapor retarder in a cold climate would require 33.3 square feet of net free ventilation area by ventilators. At first glance, this may not appear to be an unusually large number and could reasonably be achieved. However, a typical breather vent damper s diameter is between 3 and 4 inches, which calculates to an area between 2 and 4 inches. An incorrect assumption would be that this area is equal to the net free ventilation area, but for the sake of this example, we will make the assumption. (Generally, the net free ventilation area is about 50 percent of the vent s actual surface opening area.) If one breather vent is assumed to provide 4 inches of net free ventilation area, the number of vents required for a 10,000- square-foot low-slope roof assembly with a vapor retarder would be 1,199. A 5,000- square-foot roof would require 600 breather vents to meet the minimum IBC 2006 ventilation ratio requirements. The large number of vents necessary to meet these minimum requirements is similar when they are installed in a parapet wall (louvered grilles) as shown in Photos 6 and 7. Each of these vents needs to be flashed in a watertight manner or leakage will occur. They also must prevent rain and snow from entering but allow airflow. Proper flashing around penetrations does not always occur, especially at the parapet where penetrations can be added after roofing materials have been installed. The airflow within these parapet wall vents also may reduce the insulation effectiveness within the ceiling or wall assembly because of convective loops. Breather vent manufacturers and industry guidelines recommend breather vents be placed every 1,000 feet for roof surfaces with vapor retarders, which is less than building code ratios. Keep an open mind Photo 7: This is a close-up of a typical parapet vent. Will it allow wind to enter but not rain or snow? The marketing literature says yes. We hope you understand the potential consequences of strictly following IBC s prescriptive requirements for ventilation when designing and constructing low-slope roof assemblies. It may seem obvious that limitations exist, but this knowledge is not always easily relayed to designers or local code officials who fear litigation or other repercussions for not strictly following the building code. In our review of research and field experience, there is no compelling reason to ventilate a low-slope roof assembly in any environment. Insulation can always be provided on the topside of roof deck sheathing to eliminate thermal bridging and control the interior roof surface s dew-point temperature. A vapor retarder can be specified at the appropriate location to further reduce water vapor transmission into a roof assembly. An airflow retarder, or air barrier, always should be specified to prohibit the uncontrolled movement of air through a roof assembly, especially at the roof-to-wall interface. Uncontrolled air movement may result in interstitial condensation and increased thermal loads and may reduce a roof assembly s wind-uplift capacity. Interior water vapor sources always should be controlled by local exhaust ventilation or dehumidification. Of course, this is easier said than done, but by attempting to provide ventilation in a low-slope roof assembly, the potential consequences may outweigh the benefits. The IBC always is evolving and being updated based on research and field experience in an effort to establish the minimum requirements to safeguard the public health, safety and general welfare through structural strength, means of egress facilities, stability, sanitation, adequate light and ventilation, energy conservation. We hope designers, code officials, contractors and consultants increase their understanding of the IBC s intent and realize prescriptive requirements may not apply to all building types in all climates. Brian Erickson, P.E., is the Minnesota branch manager of Arvada, Colo.-based Professional Investigative Engineers, and Liberty Lewis, P.E., is the Construction Engineering Compliance Department manager with Professional Investigative Engineers. ProfessionalRoofing November 2009 37