Heat transfer analysis of hybrid stainless-carbon steel beam-column joints

Similar documents
Behavior of Concrete Filled Steel Tubular (CFST) triple-limb laced columns subjected to ISO 834 Standard Fire

FE MODELLING OF SLENDER CONCRETE-FILLED STAINLESS STEEL TUBULAR COLUMNS UNDER AXIAL COMPRESSION

Available online at ScienceDirect

Temperature Field Calculation and Analysis within Steel Tube Reinforced Columns

Numerical and Experimental Behaviour of Moment Resisting Connections using Blind Bolts within CFSHS columns

Fire Resistance of Concrete-filled High Strength Steel Tubular Columns. Citation Thin-walled Structures, 2013, v. 71, p

Behavior of Steel Beam to Concrete Filled Tubular Steel Joints after Exposure to Fire

Experimental research on reduced beam section to concrete-filled steel tubular column joints with RC slab

FINITE ELEMENT ANALYSIS OF STEEL BEAM-CFST COLUMN JOINTS WITH BLIND BOLTS

AXIAL BEHAVIOR OF STAINLESS STEEL SQUARE THIN-WALLED TUBES STIFFENED INTERNALLY

FIRE DESIGN METHOD FOR COLD-FORMED STEEL SHEETING SYSTEM

TABLE OF CONTENTS FINITE ELEMENT MODELING OF CONCRETE FILLED DOUBLE SKIN

THE STRUCTURAL BEHAVIOUR OF COMPOSITE CONNECTIONS WITH STEEL BEAMS AND PRECAST HOLLOW CORE SLABS

School of Civil Engineering, Shenyang Jianzhu University, Shenyang , China.

BEHAVIOUR OF PRE-FIRE AND POST-FIRE PERFORMANCE OF ECCENTRICALLY LOADED SRC COLUMNS AND JOINT

composite elements, lateral loads, strain analysis, behavior Composite steel concrete elements made by steel and concrete are used in world wide almos

Analysis of Concrete Filled Steel Tubes using Ansys

Stress-strain curves of prestressing steel after exposure to elevated temperatures

ISSN: ISO 9001:2008 Certified International Journal of Engineering and Innovative Technology (IJEIT) Volume 4, Issue 6, December 2014

A COMPOSITE FLOOR TRUSS TOP CHORD USING CONCRETE-FILLED STEEL TUBE (CFST)

Journal of Asian Scientific Research EVALUATION OF RECTANGULAR CONCRETE-FILLED STEEL-HOLLOW SECTION BEAM-COLUMNS

The Chinese Performance-based Code for Fire-resistance of Steel Structures

Ultimate Capacity Estimate of Self-Compacting Concrete-Filled Small Diameter Steel Tubes under Axial Load

BEHAVIOUR OF COLD-FORMED Z-SHAPED STEEL PURLIN IN FIRE

BEHAVIOUR OF REINFORCED CONCRETE STRUCTURES IN FIRE

Parametric Study of Concrete Filled Steel Tube Column

Temperature distribution of intumescent coated steel framed connection at elevated temperature.

Investigation on Mechanical Behavior of I-Section Steel Columns After Elevated Temperature

ULTIMATE STRENGTH AND DUCTILITY OF PARTIALLY CONCRETE-FILLED STEEL RIGID-FRAME BRIDGE PIERS

Analysis of Bolted Beam-Column Connections with Multiple Bolts per Row and Column Web Stiffeners

Structural Performance of Long-Span Composite Truss and Beam Systems in Fire

THE ROLE OF COMPOSITE JOINTS ON THE PERFORMANCE OF STEEL-FRAMED BUILDINGS IN FIRE. Prof. Khalifa S. Al-Jabri

Load Transferring Mechanism and Design Method of Effective Detailings for Steel Tube-Core Concrete Interaction in CFT Columns with Large-Section

SHEAR PANEL COMPONENT IN THE VICINITY OF BEAM-COLUMN CONNECTIONS IN FIRE

Non Linear Analysis of Composite Beam Slab Junction with Shear Connectors using Ansys.16

Demountable Shear Connectors for Sustainable Composite Construction

EXPERIMENTAL STUDY ON FLEXIBLE END PLATE CONNECTIONS IN FIRE

AN EQUIVALENT STRESS METHOD FOR CONSIDERING LOCAL BUCKLING IN BEAM FINITE ELEMENTS IN THE FIRE SITUATION

REPORT No MRF /B

Analysis of Concrete Filled Double Skin Steel Tube (CFDST) column with CFRP wrapping

Analytical Investigation of Steel Column Fire Tests

FRP-confined concrete-encased cross-shaped steel columns: stub column tests

Effect of beam dimensions on structural performance of wide beam-column joints

BUCKLING OF STEEL AND COMPOSITE STEEL AND CONCRETE COLUMNS IN CASE OF FIRE

EXPERIMENTAL STUDY ON FIRE RESISTANCE OF SQUARE HOLLOW SECTION (SHS) TUBULAR T-JOINT UNDER AXIAL COMPRESSION

COVER SHEET. Title: Component-Based Element of Beam Local Buckling Adjacent to Connections in Fire. Authors: Guan Quan Shan-Shan Huang Ian Burgess

Behaviour of Concrete Filled Rectangular Steel Tube Column

CIRCULAR TUBE COLUMNS IN HIGH STRENGTH STEEL Economical solutions for building frames

The Effects of Protected Beams and Their Connections on the Fire Resistance of Composite Buildings

RELIABILITY OF SEISMIC LINKS IN ECCENTRICALLY BRACED STEEL FRAMES

Fire Resistance of Composite Beams Composed of Rolled Steel Profile Concreted Between Flanges

UPGRADING OF AN EXISTING CONCRETE-STEEL BRIDGE USING FIBRE REINFORCED POLYMER DECK- A FEASIBILITY STUDY

A simple computational tool for the verification of concrete walls reinforced by embedded steel profiles.

Determination of the residual stress distribution of steel bridge components by modelling the welding process

Hybrid-steel concrete connections under reversed cyclic loadings

BUCKLING ANALYSIS OF PULTRUDED GFRP HOLLOW BOX BEAM

7. SPECIFIC RULES FOR STEEL CONCRETE COMPOSITE BUILDINGS

PLASTIC DESIGN OF STAINLESS STEEL STRUCTURES

ANALYTICAL AND EXPERIMENTAL STUDY ON COMPOSITE FRAMES

3D FINITE ELEMENT MODELS OF PLAIN AND BOND-BEAMED HOLLOW MASONRY WALLS SUBJECTED TO CONCENTRIC AND ECCENTRIC CONCENTRATED LOADS

A Numerical Investigation on the Structural Behavior of Deficient Steel Frames Strengthened using CFRP Composite

M. H. Lai a, J. C. M. Ho b,*

Modelling and parametric analysis of bolted connections on retrofitted transmission tower leg members

ANALYSIS OF INFLUENCING FACTORS ON COMPOSITE ACTION FOR REINFORCED GROUTED CONCRETE BLOCK WALL-BEAM

Compression Members. Columns I. Summary: Objectives: References: Contents:

Structural Members Behaviour

Time-dependent deflection of composite concrete slabs - a simplified design approach

Analysis and Design of Steel

Structural behaviour of recycled concrete filled steel tube columns strengthened with CFRP sheets under axial loading

This is a repository copy of Recent research and development in semi-rigid composite joints with precast hollowcore slabs.

FE MODELING OF CFRP STRENGTHENED CONCRETE BEAM EXPOSED TO CYCLIC TEMPERATURE, HUMIDITY AND SUSTAINED LOADING

Effect of upgrading concrete strength class on fire performance of reinforced concrete columns

Numerical Analysis and Experimental Studies on Welded Joint for Buildings

Seismic Behaviour of RC Shear Walls

Theory Composite Beam Design

Nonlinear Analysis of Smart Concrete Beams with Piezoelectric Actuators

NEW COMPOSITE CONSTRUCTION OF HYBRID BEAMS COMBINING STEEL INVERTED T-SECTION AND RC FLANGE

New approach to improving distortional strength of intermediate length thin-walled open section columns

The need to design for robustness in fire. Ian Burgess

The Effect of Axial Force on the Behavior of Flush End-Plate Moment Connections

Analysis of Non Composite and Composite Space Frame for Varying Support Condition

CHAPTER 7 ANALYTICAL PROGRAMME USING ABAQUS

BLIND-BOLTED MOMENT RESISTING CONNECTIONS TO CONCRETE-FILLED STEEL TUBULAR COLUMNS

Experimental and numerical validation of the technical solution of a brace with pinned connections for seismic-resistant multi-story structures

OVERVIEW OF EMPIRICAL EQUATION PREDICTION FOR ULTIMATE AXIAL LOAD OF PRECAST LIGHTWEIGHT FOAMED CONCRETE SANDWICH PANEL (PLFP)

Influence of welding sequence on residual stress and deformation of deck-rib welding details

THE EXTENDED N2 METHOD IN SEISMIC DESIGN OF STEEL FRAMES CONSIDERING SEMI-RIGID JOINTS

DISTORTIONAL BUCKLING BEHAVIOUR OF FIRE EXPOSED COLD-FORMED STEEL COLUMNS

Thermal Stress Analysis of Beam Subjected To Fire

SIMPLE INVESTIGATIONS OF TENSILE MEMBRANE ACTION IN COMPOSITE SLABS IN FIRE

Encased Beam with Variable Upper Steel Flange Position

THE APPLICATION OF ADVANCED FINITE ELEMENT ANALYSIS FOR STRUCTURAL FIRE DESIGN

Finite Element Analysis of Slender Composite Column Subjected to Eccentric Loading

Experimental Tests and Numerical Modelling on Slender Steel Columns at High Temperatures

EXPERIMENTAL STUDY ON FLEXURAL BEHAVIOR OF RC BEAMS STRENGTHENED WITH SMPM

FIRE RESISTANCE OF CONCRETE SLABS ACTING IN COMPRESSIVE MEMBRANE ACTION

Experimental Study on Concrete in-filled Light Gauge Steel Hollow Sections

Hybrid FRP-concrete-steel double-skin tubular columns: Cyclic axial compression tests

NLFEA Fire Resistance of 3D System Ceiling Panel

Finite Element Analysis of Concrete Filled Steel Tube Flexural Model

Transcription:

Heat transfer analysis of hybrid stainless-carbon steel beam-column joints Ali Razzazzadeh 1), *Zhong Tao 2) and Tian-Yi Song 3) 1), 2), 3) Institute for Infrastructure Engineering, University of Western Sydney, Penrith, NSW 2751, Australia 2) z.tao@uws.edu.au ABSTRACT A finite element () model is established to investigate the temperature field of hybrid stainless-carbon steel beam-column composite joints under the ISO 834 fire including a cooling phase. Two types of joints, including concrete filled carbon steel tubular column to steel beam joints and concrete filled stainless steel tubular column to steel beam joints are simulated. Based on the modelling, the temperature development of the composite joints in the heating and cooling fire stages is analysed and discussed. Keywords: concrete filled steel tube (CFST); stainless steel; hybrid structure; joint; temperature field; fire 1. INTRODUCTION Concrete filled steel tubular (CFST) columns have been widely used in many countries' construction industry due to their excellent structural performance. Traditionally, carbon steel tube is usually adopted in CFST columns. However, with the rising demand on the durability of structures, employing the stainless steel materials in the CFST structures as an alternative replacement for carbon steel is regarded as an effective method due to the fact that stainless steel is more durable and has great corrosion resistance (Tao et al. 211). To use concrete filled stainless steel tubular (CFSST) columns in a structure, there is a strong need to develop economical and reliable connections between CFSST columns and other connected components. Connections play the most important role in transferring applied structural loads and providing stability to the entire structure by linking principal structural elements. Recently, some studies have been carried out to investigate the realistic behaviour of composite joints with CFST columns under fire condition. Wang and Davies (23) carried out experimental study on fire behaviour of CFST column assemblies with 1) PhD Candidate 2) Associate Professor 3) Doctor 1339

extended end plates. Ding and Wang (29) tested 1 CFST columns connected to steel beams under the ISO 834 fire exposure condition, and the joint component temperatures were measured. Han et al. (28) carried out 6 fire tests on reinforced concrete (RC) beam to CFST column joints under ISO 834 standard fire. Song et al. (21) reported 3 tests on CFST column to steel beam joints in heating and cooling fire, and a finite element model was proposed to simulate the test results. A literature review indicates that no research has been conducted on the fire performance of the hybrid stainless-carbon steel composite beam-column joints consisting of the carbon steel beam and stainless steel composite column. To fill this research gap, this paper will focus on investigating the temperature distribution of the hybrid joints in heating and cooling fire theoretically. Based on the research in this paper, mechanical analysis of this type of composite joints can be done in the future to consider both the heating and cooling stages of a fire. 2. FINITE ELEMENT ANALYSIS MODELLING To analyse the mechanical performance of CFSST column to steel beam joints with bolted connections in heating and cooling fire, generally, heat transfer analysis has to be carried out before the mechanical analysis to provide the temperature distributions according to the fire conditions. Therefore, in this paper, a finite element () model is developed by using ABAQUS software to simulate the temperature field of CFSST column to carbon steel beam joints. The joint is composed of one square CFSST column, two H-shaped carbon steel beams and one composite slab. Steel end plates are welded to the ends of the beams, and blind bolts are used to connect the beams to the steel tube. One row of shear connectors with uniform spacing of 2 mm are used to connect the composite slab to the steel top flanges. 2.1 Fire curve Temperature distribution in the joint is directly influenced by the applied fire amplitude. A real fire event is characterised by three phases including growing phase, full-developed phase and decay phase. Due to changes in the amount of oxygen combustible material, prediction of growing fire is a difficult task, which is not an aspect covered in this paper. To evaluate structural behaviour under fire conditions, commonly the standard fire curve proposed by ISO 834 (198) is adopted by many researchers. In this research, the same fire curve in ISO 834 (198) including heating and cooling phases, as shown in Fig. 1, is adopted. In this figure, T is the fire temperature in C; t is the fire exposure time in minute; t h is the heating time in minute; T h is the fire temperature corresponding to t h ; t p is the total fire exposure time in minute and T o is the ambient temperature in C, which is considered to be T o = 2 C. 2.2 Material properties Material thermal properties required in identifying development of temperatures in 134

structural members include thermal conductivity, specific heat and density. For concrete, the thermal properties proposed in Eurocode 2 (25) part 1-2 are adopted in this paper, in which the thermal conductivity and specific heat capacity are temperature dependent. The concrete density is taken to be varied with temperature in accordance with Eurocode 2 (25) part 1-2, and the concrete moisture content is taken as 5%. The thermal conductivity and specific heat of carbon steel are taken from Eurocode 3 (25) part 1-2, and the steel density is considered to be independent of the temperature and equals to 785 kg/m 3. For the stainless steel, thermal conductivity and specific heat models given in Eurocode 3 (26) part 1-4 are used in the current analysis, and the stainless steel density is 785 kg/m 3. Fig. 1 Heating and cooling fire curve in ISO 834 (198) 2.3 Boundary conditions In the model, fire load is applied to the bottom parts of the joint below the composite slab, and the joint above the composite slab is exposed to the ambient temperature. The effects of heat convection and radiation are set as boundary conditions in the temperature field analysis. During the heating phase of the fire, the heat flux transfers from fire environment to the composite joint, whereas in the cooling phase of the fire, the heat flux transfers from the composite joint to the environment. The initial ambient temperature before the application of the fire load is considered to be 2 C and is assigned as a predefined condition to the model. According to ECCS (1988), the boundary conditions can be set from Eq. (1). (1) in which, λ is the material thermal conductivity in W/(m K); T is the temperature at the point (x, y, z); α is the coefficient of convective heat transfer; T f is the fire temperature which is time dependent as per ISO 834 (198) standard fire curve; ε is the emissivity of surface; σ is the Stefan-Boltzmann constant with the value of 5.67 1-8 W/(m 2 K 4 ); and T z is the absolute zero temperature equal to -273 C. 1341

The value of coefficient of convective heat transfer for carbon steel is considered to be 25 W/m 2 K as recommended in Eurocode 1 (22) part 1-2. However, the value of emissivity used in steel temperature calculation called relative emissivity in the current version of Eurocode 3 part 1-2 (25) has been changed from.5 to.7. An examination of the background documents shows that introducing the shadow factor and box value in the current version of Eurocode 3 is due to the different values of resultant emissivity recommended by the two versions of Eurocode 3 (Ding and Wang 29). A study by Franssen (26) reveals that using the formula recommended by the current version of Eurocode 3 (25) part 1-2 for I-sections leads to a smaller section size, whereas the temperature at required fire resistance time remains the same. This results in unsatisfactory load-bearing capacity of the section. While shadow effect for square and circular hollow tubes is not considerable, adopting a resultant emissivity of.7 is accurately acceptable for CFST columns. In this paper, a resultant emissivity of.5 is considered for all fire exposed surfaces except the surface of the CFST column. In Eurocode 3 (25), a convective heat transfer coefficient ( ) of 25 W/m 2 K and an emissivity coefficient ( ) of.4 are recommended for stainless steel. However, based on test data carried out on temperature development in structural stainless steel sections, modified values of 35 W/m 2 K and.2 for convective heat transfer coefficient ( ) and emissivity ( ) respectively, were proposed by Gardner et al. (21) for stainless steel materials. Due to either initial gap between the steel tube and concrete or difference between the concrete and steel thermal expansions, an air gap may be developed at the interface between the steel and concrete core in the fire condition. The air gap causes a delay in concrete temperature rise. To reflect the heat resistance in the interface between the concrete and steel due to the developed air gap, a simplified model proposed by Tao and Gannam (212) as shown in Eq. (2) is adopted. h j = a (l c /1) b (2) in which h j is the thermal contact conductance in W/m 2 K; l c is the diameter of a circular tube or the side length of a square or rectangular tube in mm; a and b are constants of 516 and 2.373 for circular columns, and 115 and.85 for rectangular columns, respectively. If the cross-sectional size is over 3 mm, h j is simply taken as 38.1 and 45.2 W/m 2 K for circular and rectangular columns, respectively (Tao and Ghannam 212). 2.4 Element divisions In the model, the concrete in the column, steel tube, concrete slab, end plates, blind bolts and shear connectors are modelled using 8-node brick elements (DC3D8). The profile steel sheet is modelled using 4-node shell elements (DS4), and the steel bars in the slab are modelled by 2-node truss elements (DC1D2). The maximum element dimension is considered to be less than 12 mm. The actual blind bolts are not modelled exactly but replaced by cone-shaped blocks that are tied to the surface of connected members. Welds between the steel beam and end plate are not modelled. Instead, welded components are tied together to allow temperature transfer between 1342

the connected components. All of the parts inside the concrete, including blind-bolts and slab reinforcement, are embedded in the concrete by using embedded constraint. Typical element meshes and parts configurations for the CFSST column to steel beam joint are presented in Fig. 2. Composite slab Distribution bars Longitudinal bars Shear connectors Blind bolts CFSST column H-shaped steel beam Profile steel sheet End plate Fig. 2 Element meshing of the CFSST column to steel beam joint 3. Verification of the model Due to the lack of test data of hybrid stainless-carbon steel beam-column joints subjected to heating and cooling fire, three types of temperature test data, including CFST column to steel beam joints in heating fire (Ding and Wang 29), steel column to steel beam joints in heating fire (Dai et al. 27) and CFST column to steel beam joints under heating and cooling fire (Song et al. 21), are used to verify the established model. 3.1 CFST column to steel beam joints in heating fire Experimental analysis of temperatures in different unprotected CFST column to steel beam joints was performed by Ding and Wang (29). Five types of connections, including fin plate, web cleat, flush endplate, flexible endplate and extended endplate connections, were adopted in the joint specimens. Reinforced concrete slabs were not provided. But their effect on the temperature development was considered by using fire protection material (ceramic fibre blanket) to wrap the beam top flanges. The ISO 834 (198) heating fire curve was adopted in the tests. Among different joints investigated, extended endplate joints are considered in the verification study in this paper. Fig. 3 shows the comparisons between the tested and predicted temperature (T) versus time (t) curves corresponding to difference temperature measuring points, including points located at the top flange and web of the steel beam mid-section, end plate and bolt. The measuring points are marked on the sections by circles and crosses shown in Fig. 3. It can be seen that the model can predict the test results very well. 1343

8 6 8 6 P- 4 T( C) 4 2 2 5 1 15 2 25 3 (a) Top flange of the steel beam 5 1 15 2 25 3 (b) Web of the steel beam 8 8 6 6 4 T( C) 4 2 2 5 1 15 2 25 3 5 1 15 2 25 3 (c) End plate (d) Bolt Fig. 3 ed and predicted temperature (T) versus time (t) curves of a CFST column to steel beam joint (tests 6 and 7 with extended end plates) in heating fire 3.2 Steel column to steel beam joints in heating fire Dai et al. (27) reported temperature test results of steel column to steel beam joints with composite slabs subjected to ISO 834 (198) heating fire. Each joint specimen consisted of two beams connected to the steel column via fin plate connection. Fig. 4 shows some of the comparisons between the tested and predicted temperature (T) versus time (t) curves for a steel column to steel beam joint, and the predicted results agree well with the test results. T( C) 1 8 6 4 2 1 2 3 4 5 6 1 2 3 4 5 6 (a) Bottom flange of the steel beam (b) End plate Fig. 4 ed and predicted temperature (T) versus time (t) curves of a steel column to steel beam joint with flush end plates in heating fire 1 8 6 4 2 1344

3.3 CFST column to steel beam joints in heating and cooling fire Song et al. (21) carried out experimental and theoretical research on three CFST column to steel beam joints with RC slabs subjected to the heating and cooling fire. The temperature distributions of the composite joints were measured during the tests, and a model was built to simulate the temperature development. Based on the proposed model in this paper, the temperature (T) versus time (t) curves of CFST column to steel beam joints in heating and cooling fire were predicted as shown in Fig. 5. Compared with the analysis in the original study, the following modifications are considered in the current model: (1) Resultant emissivity of.5 for the beams, end plates and bolts and.7 for the column are adopted in the current model. A value of.5 was used for all components in the model proposed by Song et al. (21). (2) To reflect the heat resistance in the interface between the steel tube and concrete core, a simplified model proposed by Tao and Gannam (212) is adopted in the current model, as described before. Instead, Song et al. (21) ignored the heat resistance between the steel tube and concrete core. 4 3 2 by Song et al. (21) 4 3 2 by Song et al. (21) 1 1 2 4 6 8 1 12 2 4 6 8 1 12 (a) Bottom flange of the steel beam (b) Concrete core of the CFST column Fig. 5 ed and predicted temperature (T) versus time (t) curves of a CFST column to steel beam joint (specimen JCFST2) in heating and cooling fire Fig. 5 shows the comparison between the measured T-t curves, predicted curves by Song et al. (21) and current predicted results corresponding to points at the bottom flange of the steel beam and in the concrete core of the CFST column in the panel zone. The preceding modifications considerably improve the predictions in the heating phase. The current predicted curves in the cooling phase are less accurate. Further research is required to investigate the thermal properties of materials in the cooling phase. 4. Temperature development analysis Based on the verified model, the temperature distribution of a CFSST column to steel beam joint with a composite slab in heating and cooling fire is calculated and analysed. The results are compared with those of the joint with a carbon steel 1345

composite column. For simplicity, joints with CFSST and CFST columns are referred to as CFSST and CFST joints in the following, respectively. 4.1 Calculation conditions A cruciform beam-column joint isolated from a planar frame is chosen for the temperature development analysis, as shown in Fig. 6. The height of the CFSST column is 38 mm. The width and thickness of the square stainless steel tube are 3 and 5 mm, respectively. The length of the H-shaped steel beam is 39 mm. The height and width of the cross section of the steel beam are 252 mm and 146 mm, respectively. The thickness of the web and flanges of the steel beam are 6.1 mm and 8.6 mm, respectively. The thickness of the composite slab is 12 mm, and the width and length are 12 mm and 2 mm, respectively. Other details of the CFSST joint are shown in Fig. 6, where BN and CN represent the beam and column sections at a distance 5 mm away from the column face or the bottom flange of the beam, respectively; and BJ and CJ represent the beam and column sections near the column face or in the panel zone, respectively. The ISO 834 (198) heating and cooling fire, as shown in Fig. 1, is applied on the parts of the composite joint below the composite slab. The heating time (t h ) is taken as 3 min. For the CFST joint, the same dimensions as these of the CFSST joint are adopted except that the stainless steel tube is replaced by a carbon steel tube. Blind bolt 5 7 B 2 Endplate C 5 21 5 B C 3 Column center line Beam end plate A-A 2 Longitudinal bar 6φ12@2 A 372 252 12 12 Distribution bar 2φ8@2 BN BN BJ 5 CJ BJ 1 CN CJ CN 5 1 Beam and slab center line A 38 1 19 Profile steel sheet 6 6 132 1 B-B Endplate 39 Fig. 6 Dimensions of the CFST column to steel beam joint (Unit: mm) C-C 1346

4.2 Temperature distributions in the beam and slab Due to the short heating time of 3 min, the temperature distribution of the beam and slab away from the panel zone is quite close to that of the section close to the panel zone. If stainless steel is used, the beam temperature of section BJ may be slightly lower. However, due to good thermal conductivity of the steel the steel type of the column has inconsiderable influence on the temperature distribution of the beam and slab. This influence is more obvious for the points inside the concrete slab. Fig. 7 shows the temperature (T) versus time (t) curves corresponding to different points in section BJ (see Fig. 6) during the heating and cooling fire. The following observations can be made: (1) A highest temperature of about 81 C can be observed in the bottom flange of the beam. Due to the excellent thermal conductivity of steel, there is not considerable temperature difference between the point on the bottom flange and the point on the web of the beam. (2) The maximum temperatures of 66 C, 57 C and 3 C are obtained for the points on the top flange of the beam, on the profile steel sheet and inside the concrete slab respectively. It can be observed from the results that due to the heat absorption (heat sink effect) by the slab, a significant temperature difference appears between the bottom flange of the beam and the concrete slab. The temperature difference between the top and bottom flanges of the beam is about 15 C, but that between Point 5 inside the slab and Point 1 on the bottom flange of the beam reaches 51 C. The temperature of the inside concrete keeps increasing in the beginning of the cooling phase. At a t of 1 min in the cooling stage, the temperatures inside the concrete slab are higher than those of the steel beam. At this moment, the maximum slab temperature is 17 C. 1 8 6 4 2 Heating time: 3 min Point 1 Point 2 Point 3 Point 4 Point 5 1 1 2 3 4 5 t (time) Fig. 7 Temperature (T) versus time (t) curves for different locations in the beam section BJ near the panel zone 5 4 3 2 4.3 Temperature distributions in the column Fig. 8 shows the maximum temperatures at different points in the column sections CJ and CN for both CFSST and CFST joints. The following observations can be made: 1347

(1) For the steel tube of Section CN, the maximum temperatures at Point 1 are 63 C and 71 C for stainless steel and carbon steel, respectively. The temperature difference indicates possible improved fire performance for the CFSST column in comparison to the CFST column. But for the steel tube in the panel zone, the temperature difference between the CFSST and CFST columns is minor, as shown in Fig. 8(a). (2) For the inner part of the concrete core, the temperature at a location keeps increasing for a considerably long time after the commencement of the cooling phase and reaches its maximum value at a later stage. For Section CN of the CFST column, the maximum temperature of 188 C is obtained at Point 5 after 2 min from the beginning of the cooling phase. Similarly, at the same location of CFSST column, the maximum temperature is 15 C, which occurs after 34 min from the beginning of the cooling phase. The concrete core heats up with a lower rate in the CFSST column. (3) For CFST columns, the temperature at Point 1 in the panel zone is lower than that at the same location (Point 6) away from the panel zone. This has been well-documented by many researchers due to the fact that the adjacent components in the panel joint absorb part of the heat that should be transferred to Point 1. But for CFSST columns, the trend is on the opposite. This may be attributable to the fact that additional heat is transferred from the carbon steel beam to the stainless steel column. 8 6 CFSST CFST 8 6 CFSST CFST 4 5 4 3 2 1 4 1 9 8 7 6 2 2 Point 1 Point 2 Point 3 Point 4 Point 5 Point 6 Point-7 Point 8 Point 9 Point 1 (a) Column section CJ in the panel zone (b) Column section CN Fig. 8 Maximum temperatures of different points in CFSST and CFST columns 75 6 45 3 15 75 Bolts on bottom row (Point 1) End PL-Top (Point 3) Bolts on top row (Point 2) 6 End PL-Mid (Point 4) End PL-Bott (Point 5) 1 45 3 2 3 15 5 4 t h 1 2 3 4 5 t 1 2 3 4 5 h (a) Blind bolt (b) End plate Fig. 9 Temperature (T) versus time (t) curves for the end plate and blind bolts in the CFSST joint 1348

4.4 Temperature distributions in the bolts and end plates The temperature distributions for the end plates and bolts in CFSST and CFST joints are observed to be similar. Thus only the results of the CFSST joint will be presented in this section. Fig. 9 shows the temperature (T) versus time (t) curves in the bolts on the top and bottom rows and those at different positions of the end plate. Fig. 9(a) indicates that the T-t curves of the bottom and top bolts are nearly the same. The blind bolts are embedded in the concrete, and their temperatures are affected more by the concrete core compared a normal bolt. The temperature of the embedded part of a blind bolt is lower. Future research is required to check the potential beneficial influence. Fig. 9(b) shows that the temperature at Point 3 on the top of the end plate, which is near the concrete slab, is slightly lower than that at other locations of the end plate. The maximum temperatures of 63 C and 68 C are obtained for Point 3 and Point 5, respectively. This is attributable to the heat sink effect of the slab. 5. Conclusions The following conclusions can be drawn based on the current study: (1) A model is established to simulate the temperature field of the CFSST column to carbon steel beam joint in heating and cooling fire. The influence of different resultant emissivity for different components and the heat resistance between the steel tube and concrete core are considered in the model. (2) Beam and slab temperature distributions are not obviously affected by the steel material used in the column. For sections with different distances from the panel zone, the temperature distributions are almost similar. The influence of the steel type of the column is minor for the temperature distribution of the beam and slab. (3) In terms of the temperature distribution in the column, some differences between the CFSST and CFST columns are observed. For the CFSST column, the temperature in the panel zone is higher than that at the same location away from the panel zone. Acknowledgements The research reported in the paper is part of the Discovery Project scheme (DP121971) supported by the Australian Research Council (ARC). The financial support is gratefully acknowledged. References Dai, X., Wang, Y.C. and Bailey, C., (27), Temperature distribution in unprotected steel connections in fire, Proceedings of 3 International Conference on Steel and Composite Structures, Manchester, UK, 535-54. 1349

Ding, J. and Wang, Y.C. (29), Temperatures in unprotected joints between steel beams and concrete-filled tubular columns in fire, Fire Safety J., 44(1), 16-32. ECCS-Technical Committee 3 (1988), Fire safety of steel structures, technical note: Calculation of the fire resistance of centrally loaded composite steel-concrete columns exposed to the standard fire. Eurocode 1. BS EN 1991-1-2: 22 (22), Actions on structures, Part 1-2, General actions actions on structures exposed to fire. British Standards Institution, London. Eurocode 2. BS EN 1992-1-2:24 (25), Design of concrete structures, Part 1-2, General rules structural fire design. British Standards Institution, London. Eurocode 3. BS EN 1993-1-2:21 (25), Design of steel structures, Part 1-2, General rules structural fire design. British Standards Institution, London. Eurocode 3. BS EN 1993-1-4:26 (26), Design of steel structures, part 1 4: General rules supplementary rules for stainless steel, British Standards Institution, London. Franssen, J.M. (26), Calculation of temperature in fire-exposed bare steel structures: Comparison between ENV 1993-1-2 and EN 1993-1-2, Fire Safety J., 41(2), 139-143. Gardner, L., Insausti, A., Ng, K. and Ashraf, M. (21), Elevated temperature material properties of stainless steel alloys, J. Constr. Steel. Res., 66(5), 634-647. Han, L.H., Zheng Y.Q., Tao, Z. and Wang, W.H., (28) Experimental behaviour of reinforced concrete beam to concrete filled steel tubular column joints under fire. Proceedings of 1 International Symposium on Structural Engineering for Young Experts, Changsha, China, 47-52. ISO 834 (198), Fire-resistance tests-elements of building construction, International Standard ISO 834: Amendment 1, Amendment 2. Song, T.Y., Han, L.H. and Uy, B. (21), Performance of CFST column to steel beam joints subjected to simulated fire including the cooling phase, J. Constr. Steel. Res., 66(4), 591-64. Tao, Z. and Ghannam, M. (212), Refined model to predict the temperature field within concrete-filled steel tubes, Proceedings of Seventh International Conference on Advances in Steel Structures, Nanjing, China, 781-789. Tao, Z., Uy, B., Liao, F.Y. and Han, L.H. (211), Nonlinear analysis of concrete-filled square stainless steel stub columns under axial compression, J. Constr. Steel. Res., 67(11), 1719-1732. Wang, Y.C. and Davies, J.M. (23), An experimental study of the fire performance of non-sway loaded concrete-filled steel tubular column assemblies with extended end plate connections, J. Constr. Steel. Res., 59(7), 819-838. 135