Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Similar documents
Energy Analysis of Using Thermal Mass in a Hot Humid climate

Analysis of different shading strategies on energy demand and operating cost of office building

ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Advanced Ventilation Technologies

Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings

Aalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings General rights Take down policy

Slab cooling system design using computer simulation

A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

Paul Tuohy*, Sue Roaf, Fergus Nicol, Mike Humphreys and Atze Boerstra

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling

CAE 331/513 Building Science Fall 2017

IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS

Advanced Ventilation Technologies

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study

In office buildings, often large windows have been. Total economy of windows and facades in low energy office buildings. Articles

Analysis of Night Ventilation Potential for Residential Buildings in Hot-Humid Climate of Malaysia

Lecture 3: Utilization of Passive Solar Technology

EXPERIENCES WITH LOWEX PCM CHILLED CEILINGS IN DEMONSTRATION BUILDINGS

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

Energy consumption and thermal comfort in a passive house built in Romania

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Responsive Building Elements Actual Development and Trends Within IEA

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Project Description. Projected build start date 01 Mar 2010 Projected date of occupation 01 Aug Energy target.

Modeling the Brillhart House

COMFORT DRIVEN ADAPTIVE WINDOW OPENING BEHAVIOR AND THE INFLUENCE OF BUILDING DESIGN

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Assessment of rammed earth as external cladding for thermal comfort and energy consumption of a low cost house in Bangladesh

Demonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy

Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles

Adaption of the passive house concept in northern Sweden - a case study of performance

Phase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing

FORMULATING A BUILDING CLIMATE CLASSIFICATION METHOD

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building

Building Performance Evaluation

BEEP Guidelines for Energy Efficient Design of Multi-Storey Residential Buildings

Results from the Application of the Maltese Energy Performance Rating of Dwellings in Malta EPRDM Software to a New Block of Apartments

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

THE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA

Cost-Benefit Analysis of Dwelling Retrofit Options

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad

Introduction to basics of energy efficient building design

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

Bruck an der Mur. Project summary. Energy concept: Background for the renovation reasons

INTEGRAL BUILDING AND ENERGY DESIGN OF AN OFFICE BUILDING COMPARISON OF INITIAL DESIGN IDEAS WITH MONITORED RESULTS

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

Demonstration of Load Shifting and Peak Load Reduction with Control of Building Thermal Mass

PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Sapporo Net-Zero Energy Home Hokkaido, Japan. Description. Setting. Super E Canadian Member. Super E Japanese Member. Super E Case Study

PCM s in application for acclimatization of buildings. Nick Barnard, Faber Maunsell VSK2008, Workshop on heat storage

PERFORMANCE EVALUATION OF PV VENTILATED GLAZING

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

Built for sustainability Built for the environment Built for fuel efficiency Built for life

Passive and low energy cooling techniques for the Czech Republic

ENERGY-EFFICIENCY IN EDUCATIONAL BUILDINGS IN IRAN: ANALYSIS AND MEASURES. Faculty of Engineering, Ilam University, Ilam, Iran

A Case Study of Energy Demand in Housing Units

Retrofit of an historical building toward NZEB

Advanced Design and Building Information Modeling February. Would you like to develop a BIM model of this project? no

Building performance analysis for double skin residential buildings ABSTRACT BACKGROUND. Porooshat Akhgari

ABSTRACT INTRODUCTION

Modeling Energy Consumption Effects of Glazing

AM-55, AM-56) B U I L D I N G P A R T N E R S H I P S F O R E N E R G Y S E C U R I T Y

Be Aggressive About the Passive Solutions

THE USE OF SOLAR DESIGN DAYS IN A PASSIVE SOLAR HOUSE CONCEPTUAL DESIGN TOOL

RECENT CZECH BUILDING ENERGY SIMULATION CASE STUDIES

Building Technology Research in Architectural Practice: Lessons Learned from Implementations of Energy-Efficient Advanced Building Technologies

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

Infiltration simulation in a detached house empirical model validation

ECO-RETROFITTING VERY OLD DWELLINGS: CURRENT AND FUTURE ENERGY AND CARBON PERFORMANCE FOR TWO UK CITIES

THE IMPACT OF BUILDING ORIENTATION ON ENERGY USE: A CASE STUDY IN BUNG HATTA UNIVERSITY, INDONESIA

The optimization of the mechanical night cooling system in the office building

THE IMPORTANCE OF THERMAL MASS IN PREDICTIVE CONTROL CASE STUDY: A ZONE WITH FLOOR HEATING AND A CHILLED BEAM

Deep thermomodernization of three residential buildings in Kryvyi Rih, Ukraine

ARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi

Passive Houses in South West Europe

Advanced Ventilation Technologies

Thermal comfort analysis in a passive house using dynamic simulations*

Near zero energy building with steel solutions case study. Jyrki Kesti, Technology Director, Ruukki Construction

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

Effects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance of Open-Plan Office Buildings

Passive house optimization for Southern Italy based on the New Passivhaus Standard

The Importance of Slab Edge & Balcony Thermal Bridges

SURNA Grow Facility: Systems Comparison - IEA

COMPUTATIONAL ASSESSMENT OF COOLING WITH LOW-TEMPERATURE HEATING SYSTEMS

GREEN BUILDING CONGRESS 2011 NEW DELHI

A SIMPLE USER INTERFACE FOR ENERGY RATING OF BUILDINGS

Chapter 6. Space heating load

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

F. Flourentzou Lefkosia new townhall passive bioclimatic Minergie design. Flourentzos Flourentzou: Innovation park EPFL Lausanne, Switzerland

Optimising Ventilative Cooling and Airtightness for [Nearly] Zero-Energy Buildings, IAQ and Comfort

Assessment of Building Energy Performance for EEMs A Case Study in Mumbai

Assessing the energy performance of modern glass facade systems

Transcription:

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Andrzej Baranowski 1,2 and Joanna Ferdyn-Grygierek 1,2 1 Silesian University of Technology, Gliwice, Poland 2 Upper Silesia Industrial Park, Katowice, Poland Corresponding email: Andrzej.Baranowski@polsl.pl SUMMARY Ensuring of a proper indoor environment in office buildings requires, among others, the achievement and maintenance of comfort for those abiding in the existing temperature of the air. The paper presents the results of an analysis of the influence of internal heat gains on the consumption of energy in an office building designed in compliance with passive technology. The main energy consuming process in such type of buildings is air-conditioning and cooling. The building was designed as a low-energy one, cooled by means of cooling ceilings. The architect s and designer s assumptions were checked by the numerical simulation made by means of the ESP-r software. Basing on the simulation results, the annual energy consumption was analyzed for the different internal heat gains in the office rooms. INTRODUCTION The indoor environment quality was not always the main priority when the office buildings were designed. In the end of the last century the higher standard of the indoor environment was forced by users but the proper thermal comfort, indoor air quality as well as the office lighting was reached by the large energy consumption, very often more than 5 kwh/(m 2 a). In public buildings the problem is not the heating, but rather cooling of the rooms. The reason for that is the specific usage of the office space, where, in a relatively small cubature considerable internal heat gains do occur, resulting both from the presence of people and appliances. Research programs and practical implementation of low energy public buildings were undertaken already in the 198s. The effect of such actions were numerous studies and analyses concerning monitoring of the operation of such buildings [1] and preparation of the energy-efficient systems and methods of heating and cooling for such facilities [2]. Despite the above experiences, the subject of energy-efficient, passive or zero-energy buildings is still topical [3]. From the technical point of view, the existing air conditioning systems can ensure the required microclimate in the offices, the problem, however, concerns the energy effectiveness of the applied solutions and the investment and operating costs. The performed research works point out the main factors determining the energy consumption in the public buildings [4]: external wall insulation

internal heat gains strategies of heating and cooling. These factors influence the energy consumption due to differences of the climatic conditions, the building and standards regulations, and buildings operation in particular countries. METHODS The investigation concerned the newly designed, nine-storey office building with heavy reinforced concrete structure (external walls 25 cm, ceilings 3 cm). The external walls and the roof of the building are well insulated (U =.13 ). The building is heated by means of fan-coils. The way of cooling is based on the application of thermo-active cooling ceiling with a cooling agent with a temperature of 1 o C. The total office space amounts to over 2, m 2 is subdivided on the single, small office rooms and the larger open space offices. The numerical model for simulation was created for the single small office with the dimensions 2. x 8.1 x 2.8 m and with a single window equipped with external shutter. 258mm Figure 1. Floor plan of the office room under consideration. 8mm Table 1. Construction data and main values of the heat transfer coefficients External walls: reinforced concrete 25 cm, glass wool 3 cm Ceilings: concrete slab 25 cm Roof: reinforced concrete, mineral fibre 4 cm Windows: Aluminium/PVC, triple glazed pane U=.13 U=1.3 U=.9 U=.8 Simulation calculations were carried out by the ESP-r program [5] concerning climatic data of one of the Polish towns. The aim of the numerical calculations of the building system HVAC system was to investigate the dynamics of the cooling and heating load as well as the actual and annual demand for cooling and heating. Besides the internal heat gains, also the gains due to solar radiation have been taken into account in the calculations. Simulations were carried out for the single office segment, basing on the following assumptions: - indoor air temperature: 24 o C for cooling, 2 o C for heating, - air supply with a temperature of 2 o C, - the internal heat gains in the office result from the presence of the occupants, the appliances and the lighting []. Several variants of the internal heat gains have been dealt with, varying both the number of persons working in the office and the power rating of the installed appliances (Table 2).

Table 2. Variants of the internal sensible heat gains v. 1 v. 2 v. 3 v. 4 Occupants 1 x 77 W 3 x 77 W 3 x 77 W 3 x 77 W Computers 1 x W 1 x W 3 x W 3 x 3 W Lighting 3 x 5 W 3 x 5 W 3 x 5 W 3 x 5 W Total 377 W 531 W 831 W 81 W Additionally, the simulation of the office without internal heat gains was performed, giving the data on the energy consumption when the office is closed (variant ). The building was assumed to be used from Monday to Friday from 7 a.m. to p.m. and on Saturday from 7 a.m. to 2 p.m. Additional simulation was performed for the "traditional" office building: external wall insulation was five times worse (U =.55 ), double glazed windows (U = 1. ) without external blinds, poor possibilities of heat/cold accumulation inside the building partitions as well. Such type of buildings still exist and often dominate in many countries. RESULTS The simulations give the self-evident results if the internal heat gains in the office rise, the cooling demand to maintain the proper indoor air temperature also increases. It also depends on the ambient temperature (Figure 2). cooling demand, W 2 18 1 14 1 8 4 2 11-8 -8 13-8 14-8 -8 1-8 17-8 v. v.1 v.2 date v.3 v.4 Te Figure 2. Variation of the actual cooling load in the selected period in summer. Table 3 gives results of the simulation for all variants including annual energy consumption as well as the actual maximum cooling demand. The results of the simulation proved that in all variants of the assumed internal gains the office does not need to be heated even at a low ambient temperature, but should be cooled. The only exception is variant 1 (one person in the office) where the heating is necessary for a few in January - it needs total of. kwh of 35 25 5-5 - -25-35 -45 ambient temp. o C

energy per year. Heating in winter is also necessary in the object where there are no internal heat gains (variant ). Table 3. Cooling demand for different internal heat gains Annual energy Maximum demand for cooling load, cooling, [kwh] [kw] Period of cooling during the year, [month] v. 148 32 2.5 v. 1 891 58 7. v. 2 13 71 8. v. 3 2323 97 1. v. 4 428 149 1.5 The last column of Table 3 shows how long - during the year the office should be cooled depending on the variants of the internal heat gains - it varies from seven up to eleven months in the year. When the unoccupied office is considered the cooling is needed during two and a half month, mainly from June to August. In this case also the heating is necessary during the winter. The heavy structure of the building is an advantage. As the result of the accumulation of the heat in the building partitions the peak of cooling demand is considerably lower than the internal heat gains penetrating into the room (Figure 3). 14 heat gains cooling demand Q, W 1 8 4 2 solar rad. lighting computers people Figure 3. Comparison of cooling demand and heat gains in the office (variant 3). The role of solar radiation for cooling demand was checked by comparing the results of simulation for different window location (south north): the average 24 hours cooling load was higher for south windows location from 1 % to 4 % depending on the weather conditions (Figure 4a). The influence of the external blinds on cooling demand is shown in Figure 4b. The energy consumption increases from 1 % up to 5 % when the windows are without blinds (an average about 2 %).

24h cooling load, kwh 9 3 north window south window 24h cooling load, kwh 9 3 with blinds without blinds 1 2 3 4 5 7 8 9 1 11 13 14 1 2 3 4 5 7 8 9 1 11 13 14 a) b) Figure 4. Comparison of 24 hours cooling demand for different windows location. a) north vs. south window exposition, b)south exposition, widows with and without blinds. Comparative calculations concerning the same segment of the office, but constructed with traditional partitions (lighter structure of the external walls, the heat transfer coefficient nearly three times higher) were performed. It can be noticed that when the ambient temperature is higher the cooling demand is smaller for heavy construction building. For relatively lower external temperature just opposite the heavy building requires more cooling than traditional one which results from its large heat capacity of the walls and ceilings and worse heat transmission outside of the building (Figure 5a). 24h cooling load, kwh 2 18 1 14 1 8 4 2 a) b) Figure 5. Comparison of 24 hours cooling demand for different building construction. a) windows with blinds, b) windows without blinds. When the windows of the traditional office building are equipped with the external blinds the energy demand for cooling is lower than for the building with heavy construction (about % on average - Figure 5b). DISCUSSION light heavy temp. 1 2 3 4 5 7 8 9 1 11 13 14 25 2 1 5 Ambient temp., o C The performed simulations indicate that practically for all variants of the assumed internal heat gains the office building with heavy concrete construction must be cooled through the longer time of the year. The heating is unnecessary at all or is a small part of the total energy consumption. 24h cooling load, kwh 2 18 1 14 1 8 4 2 light heavy temp. 1 2 3 4 5 7 8 9 1 11 13 14 25 2 1 5 Ambient temp., o C

When the building envelope is well insulated there is a problem with the transmission of the redundant heat to the environment. A traditional building with worse insulation is cooled down during the night better than the building with a greater possibility of the heat accumulation in the heavy partitions. Thus the question arises whether it is expedient to augment the insulation of the external walls in buildings where the offices are intensively utilized. It also means that in such office buildings the internal heat gains are a important component of the balance determining the cooling demand, and the insulation of the partitions is of a secondary importance. The calculation results pointed out also the importance of the solar heat gains on the energy demand for cooling. The external blinds can reduce these gains from 1 % up to even %. The benefits of using the heavy concrete construction of the partitions lays in the allowance to set down the peak demand for cooling. Thanks to the cumulative ability of the walls and ceilings the rooms can be cooled down also during the night. The potential benefits of using low-energy and passive technologies are great. Although there are no significant technical barriers, these technologies are not universally introduced for economic reasons. ACKNOWLEDGEMENT These investigations have been sponsored by the Upper Silesia Industrial Park Ltd. in Katowice within the Frame of the project "Development of the First Polish Cluster of Passive and Energy-Saving Building Engineering", realized in compliance with the Operative Programme "Innovative Economy", sphere of activity 5.1. REFERENCES 1. Pfafferott, J, Herkel, S, Wambsganss, M. 24. Design, monitoring and evaluation of a low energy office building with passive cooling by night ventilation. Energy and Buildings. Vol. 3, pp 455 45. 2. IEA ECBCS 23. Annex 37 Low Exergy Systems for Heating and Cooling of Buildings. Heating and Cooling with Focus on Increased Energy Efficiency and Improved Comfort. VTT, Finland. 3. Schnieders J, Hermelink A. 2. CEPHEUS results: measurements and occupants satisfaction provide evidence for passive houses being an option for sustainable building. Energy Policy. Vol. 34, pp 1-171. 4. Tuohy, P, McElroy, L, Johnstone, C. 25. Thermal mass, insulation and ventilation in sustainable housing an investigation across climate and occupancy. Proceedings of the 9th International IBPSA Conference on Building Simulation. Montreal, Canada. 5. Clarke, J A. 21. Energy Simulation in Building Design. Butterworth-Heinemann, London, UK.. ASHRAE Handbook-fundamentals, 25. American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc., Atlanta, USA.