LARGE WIND FARM AGGREGATION AND MODEL VALIDATION MULUMBA PROSPER PANUMPABI THESIS

Similar documents
Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012

Daniel Feltes Phone: Fax:

Comparative Analysis of Wind Energy Conversion System using DFIG and IG

SYNOPSIS OF THE THESIS. Enhanced Power Quality Management of Grid Connected Wind Farm

VOLTAGE STABILITY LIMITS FOR WEAK POWER SYSTEMS WITH HIGH WIND PENETRATION ALA TAMIMI AN ABSTRACT OF A DISSERTATION

Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System

Wind Farm Performance on the Grid: Perception and Reality

Dynamic Response of Large Wind Power Plant Affected by Diverse Conditions at Individual Turbines

AGGREGATED MODELLING ANALYSIS OF POWER FLOW FROM WIND POWER PLANT INTO GRID SYSTEM USING MATLAB/ SIMULINK SOFTWARE

What makes a Wind Plant Grid Friendly?

FINAL PROJECT REPORT WECC WIND GENERATOR DEVELOPMENT

California Independent System Operator Renewable Integration Study

Power Quality Improvement in Distribution System Using Distribution Static Compensator

ISSN Vol.07,Issue.16, November-2015, Pages:

Impact of Wind Integration on National Transmission Network

Principles of modeling large wind parks

Capacity and Location Effects of Wind Turbine Energy Systems on Power Systems Stability

Renewable Energy in Power Systems

WIND ENERGY GENERATION

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Electric Power Systems An Overview

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

BASIC CONCEPTS. Yahia Baghzouz Electrical & Computer Engineering Department

IMPACT OF THE WIND POWER PLANTS TO THE SETTING OF STEP 2 DISTANCE PROTECTION

ISSN Vol.09,Issue.04, March-2017, Pages:

Generation Application Part B: Technical Form

POWER QUALITY ASPECTS IN A WIND POWER PLANT IMAMHUSEN M PATIL. MASTER OF TECHNOLOGY IN ELECTRICAL ENGINEERING (Computer Controlled Industrial Power)

SESSION 3: Grid Integration Studies for Planning Secure and Reliable System Operations with Expected Shares of Variable Renewables

Voltage Stability Assessment of a Power System Incorporating Wind Turbine Using Power System Analysis Toolbox (Psat)

Investigation of Wind Farm Interaction with Ethiopian Electric Power Corporation s Grid

Impacts of the Decentralized Wind Energy Resources on the Grid

CENTRE FOR WIND ENERGY TECHNOLOGY CHENNAI INDIAN WIND GRID CODE

Critical Load Serving Capability by Microgrid using 100% Renewable Energy

Platte River Power Authority. Ten-Year Transmission Plan ( )

Power Quality and Voltage Stability of Power Systems with a large share of Distributed Energy Resources

GOLDEN VALLEY ELECTRIC ASSOCIATION

Steady-state and transient voltage stability analysis of a weak distribution system with a remote doubly fed induction generator-based wind farm

Information Document Protection System Information ID# R

ELG4126 Distributed Generation and Renewables

ECE 333 GREEN ELECTRIC ENERGY. 6. Limits on Conversion of Wind Into Electricity

A New Connection Concept to Connect an Offshore Wind Park to an Onshore Grid

Impact of Combined Wind Farm on Interconnected Distribution Systems

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Investigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection

Connection Study Requirements

Inverter-Based Resources During a Cascading Failure: Present State and Future State

Impact of Different Types of Wind Turbines Generators on Voltage Sag

Different Options for Multi-Rotor Wind Turbine Grid Connection

WIND TURBINE PLANT CAPABILITIES REPORT

Wind Generation Part I Planning, Design & Operations

Power-Flow Analysis of Large Wind Power Plant Collector Systems With Remote Voltage Control Capability

Comparing Single and Multiple Turbine Representations in a Wind Farm Simulation

Analysis of Calculation Methods to Evaluate Losses and Efficiency of Wind Generators

MEASUREMENTS AND SIMULATION FOR POWER QUALITY OF A WIND FARM

Facility Interconnection Requirements

JOURNAL OF APPLIED SCIENCES RESEARCH

Comparative Analysis between IG and DFIG for Wind Energy Conversion Systems using STATCOM

Control of a Microgrid in Islanded Mode

Optimization of Power Factor and Energy Management in Wind Energy Station

Analysis of Wind Power Integration for Power System Transient Stability

A. Behaviour of the Wind

Generator Interconnection Affected System Impact Study. Plains & Eastern Clean Line Final Report

ENABLING FREQUENCY AND VOLTAGE REGULATION IN MICROGRIDS USING WIND POWER PLANTS

Methodological Application to Integrate Renewable Energy Resource into Kuwait s Electrical Grid

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA

All Rights 1

ReliabilityFirst Regional Criteria 1. Verification and Data Reporting of Generator Gross and Net Reactive Power Capability

Wind Farms in Weak Grids Compensated with STATCOM

Steady State Power System Security Analysis with PowerWorld Simulator

GUYANA POWER AND LIGHT INC

J. Electrical Systems 10-2 (2014): Regular paper

International ejournals

Research Co-design Activity

Online Security Analysis of Power Grids with High Wind Penetration. By Ivan M. Dudurych, Alan Rogers, Robbie Aherne, Lei Wang, Fred Howell, and Xi Lin

Analysis of DG Influences on System Losses in Distribution Network

FACILITY CONNECTION REQUIREMENTS NERC TO-FAC 001-0

Dynamic Compensation of Reactive Power for Integration of Wind Power in a Weak Distribution Network

2009 AEE TECHWINDGRID 09, April, 2009 Madrid 1

Hanif Livani, PhD SEM 332, 1664 N. Virginia Street Reno, NV, Phone: (775)

Hydro-Quebec s experience with HYPERSIM Real-time Power System Simulator

Coordination of Multiple Voltage Controllers of Adjacent Wind Plants Connected to João Câmara II with Droop Function

Recent US Wind Interconnection Experience

Dynamic Behaviour of Large Scale Wind Farm

EFFECT OF WIND SPEED VARIATIONS ON WIND GENERATOR OUTPUT IN TROPICAL CLIMATE WEATHER CONDITION

SECURITY ASPECTS OF MULTI AREA ECONOMIC DISPATCH WITH RENEWABLE ENERGY AND HVDC TIE LINES.

Low SCR Wind Identification and Mitigation. Will Lovelace MIPSYCON 2015 November 11 th, 2015

Design and Modeling of Wind Energy Conversion System Based on PMSG Using MPPT Technique

DISTRIBUTED GENERATION AND POWER QUALITY

Standard MH-TPL Transmission System Planning Performance Requirements

Modelling of Generic Maximum Power Point Tracker for Wind Farms. Master s thesis in Electric Power Engineering. Joachim Andersson

R2 TESTING GUIDELINE. PREPARED BY: Network Models Systems Capability VERSION: Final RELEASE DATE: 28 June 2013

Centralized wind power plant voltage control with optimal power flow algorithm

COMBINING THE WIND POWER GENERATION SYSTEM WITH ENERGY STORAGE EQUIPMENTS MING-SHUN LU. Presented to the Faculty of the Graduate School of

Modeling, Design and Simulation of A Low Cost Supervisory Controller for Ramea Hybrid Power System

Influence of Renewable Integration on Frequency Dynamics

TABLE OF CONTENTS. UNCONTROLLED WHEN PRINTED 2 USA Operations

Laboratory experience in power engineering at the University of Queensland

WIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS. J O G Tande and K Uhlen. SINTEF Energy Research, Norway SUMMARY

POTOMAC ELECTRIC POWER COMPANY

Transcription:

LARGE WIND FARM AGGREGATION AND MODEL VALIDATION BY MULUMBA PROSPER PANUMPABI THESIS Submitted in partial fulfillment of the requirements for the degree of Master of Science in Electrical and Computer Engineering in the Graduate College of the University of Illinois at Urbana-Champaign, 2011 Urbana, Illinois Adviser: Professor Thomas J. Overbye

ABSTRACT In order to have a large production of electricity by wind, many wind turbines are installed on the same site, called a large wind farm. The connection of a large wind farm to the grid has raised new and challenging questions for the operation of the electrical grid. In this research we will be addressing these questions: 1. How can a large wind farm with multiple wind turbines be represented by just one equivalent single machine to study the load flow and stability? How well does the equivalent single machine capture the behavior of the large wind farm during a simulation study? 2. When a short circuit happens in a large wind farm, some wind turbines trip while others do not. What is the mechanism to understand and control the number of tripping wind turbines? 3. Is there any way to improve the low voltage ride-through of a large wind farm using intelligent devices to control the impact of a short circuit? The study is conducted using the General Electric GE doubly fed induction generator wind turbine modeled in the PowerWorld Simulator. ii

Through this research, we have shown that: A large wind farm using the GE DFIG wind turbines can be consistently aggregated to one equivalent machine for load flow and transient stability studies. The low voltage ride-through response can be improved by inserting a selfimpedance between the faulted feeder and the rest of the large wind farm during the fault. This impedance will reduce the number of wind turbines tripping during the fault, and increase the voltage stability of the wind farm. An intelligent device can be used within a large wind farm to locate a default feeder and automatically insert the self-impedance during the time of short-circuit. iii

ACKNOWLEDGMENTS I would like to express my gratitude to my adviser, Prof. Thomas J. Overbye, for giving me the opportunity to pursue graduate studies in the Power and Energy Systems Group at the University of Illinois at Urbana-Champaign. I am grateful for his guidance and support. I thank all the professors and students in the Power and Energy Group. I am grateful to Prof. José E. Schutt-Ainé of the Department of Electrical and Computer Engineering for his encouragement. I am indebted to Thomas Kay and Dr. David Schooley of the Commonwealth Edison (ComEd) Planning Department for initiating this research. I am grateful to the large wind farms operator in the US who agreed (very exceptionally and under a confidential agreement), to share all the data to simulate an existing large wind farm. Without such data, this study would not have been possible. This study would not be possible without the very recent development of Simulator 15 at the PowerWorld Corporation, which incorporates the load flow and transient stability analysis of wind turbines. I am grateful to Dr. Matt Davis of the PowerWorld Corporation for his advice during this work. I am grateful to Dr. Eduard Muljadi from the United States National Renewable Energy Laboratory (NREL) for his help. I owe a great debt of appreciation to my beloved wife Henriette Panumpabi for her love, support and prayers. I am grateful to my children Mireille Panumpabi, Christian iv

Panumpabi, Christelle Panumpabi, Olive Panumpabi, Sabine Panumpabi and Mardoché Panumpabi for their support and patience. I know that through our journey in America, you will be able to do more than I. Finally, I am grateful to my late father, François Mulumba Ntumba, for motivating me to become an electrical engineer. v

TABLE OF CONTENTS 1. INTRODUCTION... 1 2. GRID INTEGRATION OF WIND ENERGY... 5 2.1 Wind Turbine Types... 5 2.2 Electrical Grid Simulator... 7 2.3 Power Flows... 8 2.4 Short Circuits... 9 2.5 Transient Stability... 11 3. LARGE WIND POWER PLANT AGGREGATION... 15 3.1 Large Wind Farm Definition... 15 3.2 Equivalent Wind Turbine... 16 3.3 Equivalent Pad Mount Transformer... 17 3.4 Equivalent Collector System... 17 4. DOUBLY FED INDUCTION GENERATOR... 19 4.1 Active Power Control... 19 4.2 Reactive Power Control... 21 4.3 Voltage Control... 22 vi

5. CASE STUDIES... 25 5.1 Description... 25 5.2 Load Flow Analysis... 29 5.3 Transient Stability Plots... 30 6. LOW VOLTAGE RIDE-THROUGH... 33 6.1 LVRT with Fault outside the Collector System... 33 6.2 LVRT with Fault within the Collector System... 37 7. CONCLUSIONS AND FUTURE WORK... 44 APPENDIX: PRYSMIAN S GUIDE TO WIND FARM CABLES... 45 REFERENCES... 46 vii

1. INTRODUCTION The oil shock in the 1970 s and the subsequent soar in prices, the energy independence policies of governments, and the need to reduce the global emissions of greenhouse gases produced from electric power generation, have triggered the search for new, cleaner and domestic sources of electrical power. The power industry has focused on the development of new renewable sources such as wave, wind, solar, geothermal, biomass, and hydrogen to generate electricity. Electrical energy produced by wind turbines is called upon to make an important contribution alongside conventional sources of electricity. Government at many levels has implemented several policies to encourage investors in wind generation. These include incentives such as the Federal Production Tax Credit of 1999, the Renewable Energy Credit, the Property Tax Credit, State Green Power Purchasing, and the Renewable Energy Trust Fund. Better wind resources are available in remote locations or specific regions, so large quantities of electricity need to be moved from wind farm sites to load centers like large cities and industrial facilities. To maintain the reliability of the electrical grid, a perfect understanding of wind turbine modeling and simulation is needed with new investments in grid construction. In order to harvest more electrical energy from wind and maximize the benefit of this free and clean prime mover, wherever available in sufficient quantity, many wind turbines are installed on the same site through a local electrical network and connected 1

to the electrical grid. Such an installation is called a large wind farm. The total power of a large wind farm is expected to be the summation of power from individual wind turbines. In a large wind farm, while the turbines may be identical, the collector system is not identical for all wind turbines. The design of a collector system depends on land availability, wind distribution, power losses, and operating and troubleshooting conditions. The electrical generation technology used in wind turbines has progressed from a simple induction machine to a doubly fed induction generator (DFIG). The DFIG is the most used type of electrical machine for large-scale wind-electric energy production because it allows for better control of reactive power and improves the reliability of the electrical grid during a short circuit. It has an important electronic solid-state voltage converter incorporated in such a way as to change the behavior of the wind generator to meet the transmission system interconnection requirements. A large wind farm may have up to six hundred wind turbines. For a large wind farm, representing each individual wind turbine, each pad mount transformer, and each collector system branch during an electrical study will considerably increase the amount of computer resources needed, in addition to being time-consuming and inappropriate for some studies. To solve this problem, the large wind farm may be reduced (or aggregated) to a single wind turbine equivalent with an equivalent collector system. This leads to the question: What is the best equivalent representation of a large wind farm 2

for solving the power flow and studying both the transient stability and low voltage ridethrough? The answer to this question is linked primarily to the mathematical model used to represent the wind turbine. Wind turbine manufacturers in the market include General Electric (GE), Vestas, Gamesa, Siemens, Suzlon, Hyundai, etc. Information about their wind turbine modeling is mostly kept confidential because of the high competition in the market. In this work, we will be using the GE model especially for the wind turbine DFIG as it is published. In this research, we will start modeling, with the PowerWorld Simulator, an existing large wind farm of 120 turbines. In the second step, we will aggregate from 120 down to 8, and in the last step the 8 wind turbines equivalent will be reduced to a single equivalent wind turbine. As a way to study the impact of neglecting or including the medium voltage collector system, in the first scenario, we will use the National Renewable Energy Laboratory (NREL) algorithm for equivalencing the collector system reduction and another scenario ignoring the collector system. In the second scenario, we will assume that the impedance of feeders within the collector system is too low compared to the impedance of pad mount transformers, as they are connected in series, and we will ignore the collector system. 3

A power flow study will be conducted in the different cases to compare the flow of electricity on common devices. A transient stability study will be conducted with all cases to study the wind farm voltage response during a short circuit at the point of interconnection to the grid, and finally a low voltage ride-through will be studied by simulating faults within and outside of the medium voltage collector. For a fault within the collector system, the study will examine how to reduce the number of units tripping from the grid during the short circuit. In this thesis, we will not publish detailed data concerning the configuration of the wind farm, according to the terms of the confidential agreement. We will publish the one-line diagram and the global results of the simulations. 4

2.1 Wind Turbine Types 2. GRID INTEGRATION OF WIND ENERGY Wind turbines are classified into four major types [1] as illustrated in Figure 2.1: Type 1: Induction generators with fixed rotor resistance Type 2: Wound rotor induction generators with variable rotor resistance Type 3: Doubly fed induction generators (DFIGs) Type 4: Full converter generators Figure 2.1: Types of wind turbine generators Type 1 is a wind turbine which is directly connected to the grid. It has a gear box to maintain constant frequency to the grid as the wind speed changes. It consumes 5

reactive power from the grid. A bank of external capacitors is added to improve the power factor. Type 2 represents a wind turbine from an induction machine with a wound rotor. The rotor is connected to a resistor. During short circuit conditions, both type 1 and type 2 turbines must be disconnected immediately from the grid and cannot be used as a large source of electricity generation. During the short circuit, they take a significant amount of reactive power from the grid, increasing the voltage drop and negatively impacting the overall voltage stability of the grid. Type 3, the DFIG, is a wind turbine with a stator connected directly to the grid. The rotor is connected to the grid at a fixed frequency through a back-to-back electronic converter which converts from ac to dc and then back to ac. The type 3 wind turbine is capable of producing and consuming reactive power within given limits by changing the magnitude of rotor currents. The DFIG can stay connected to the grid during a fault because it can supply reactive power to sustain the voltage level. It is said that wind turbine type 3 can ride through the fault. 6

2.2 Electrical Grid Simulator Reproducing an electrical power system in a lab is too costly to be practical. Therefore modeling and simulation are done on a computer in order to understand the system behaviors. Planning engineers, operations engineers, and design engineers all use simulations to study electrical power systems. A visualization that can be made in a software package such as PowerWorld Simulator packs a large amount of information into a single computer-generated image, enabling viewers to interpret data more rapidly and more accurately than ever before [2]. PowerWorld is a tool to make more complex electrical computations and decisions easily understandable not only for engineers but also for decision makers such as executives, consumers, or voters. On a one-line diagram, the flows of electricity are represented in magnitude and direction by moving arrows. The proportions of current load to the maximum loadable capacity of transport equipment such as lines or transformers are represented by pie charts. If the power flow through the device gets higher than the maximum capacity or the voltage to the device is beyond the minimum and maximum acceptable voltage, the device will be automatically flagged. The PowerWorld Simulator allows increasing the situational awareness. 7

2.3 Power Flows The power flow, also called the load flow, is a program to compute the voltage magnitude and angle at each bus, real and reactive power circulating through all the transmission elements in an electric power system, and the power losses through the system under balanced three-phase steady-state conditions ([3], p. 280). The power flow solution in positive sequence is used to compute the initial conditions for transient stability. Within a large wind farm, several wind turbines are connected together by electrical underground wires called feeders. Their main characteristic is that they have a resistive component higher than the inductive component. The maximum allowable current flow in a feeder is determined by the nature of the cable, the nature of the soil, the depth of burial and whether or not the cable is crossing under a road. The actual flow in the feeder is checked against the maximum cable flow. Wind farms use special feeders to minimize the power losses and voltage drop. Within a single large wind farm, one uses different sections of cables (for examples, see the Appendix); the section of feeders within a wind farm is increased as the aggregation of currents from different wind turbines increases. A feeder may be composed of a three-phase cable or three single cables put together in way to produce a three-phase system. 8

During the power flow study, wind turbines are represented as fixed voltage sources, (PV) buses, delivering the maximum nominal active power and zero reactive power. A wind farm substation increases the medium voltage level to high voltage. An overhead power line connects the substation to the electrical grid. The pi equivalent will be used to represent both the substation and overhead power line in the simulation. Under abnormal conditions such as wind gusts, wind turbines can deliver more active power than normal. In such a condition, wind turbines will be shut down automatically. Pad mount transformers are transformers at the pedestal of the wind tower. They increase the voltage produced by the wind turbine to a medium voltage range to reduce power losses through the collector system. Since the impedance of the pad mount transformer is larger than the feeder cables, some studies neglect the feeder impedance. This thesis studies the validity of this approach. In this research, we have used data from a real wind farm to do different simulations. 2.4 Short Circuits A short circuit results whenever two different parts of a power system, with different voltage levels, come in direct contact. Short circuits are caused when equipment insulation fails. Insulation failures may be caused by lightning or switching surges, which cause an over-voltage condition that breaks down the insulation. Short circuits also may be caused by insulation contamination (salt spray or pollution), mechanical problems, 9

uncontrolled wildlife, vegetation growth, and unintended equipment procedure ([3], p. 355). Within a large wind farm, a short circuit can take place at different locations such as the terminals of the wind turbine, within a collector system, in the substation, or on the overhead power line. In each case, the short circuit current will be limited by the short circuit impedance between each wind turbine and the point of fault. The wind turbine has a very different behavior from a conventional generator during a short circuit. All the mechanical power captured in the wind is transformed into electrical power, and during a short circuit, a very small percentage of electrical power is needed to compensate for the losses through the fault. A control action should be taken to tilt the blades to reduce the amount of produced active power. The current during a short circuit is several orders of magnitude bigger than normal. The time after which short circuits are removed by the protection system is expressed in terms of cycles or seconds. Short circuits should be removed as quickly as the thermal capacity of the collector will allow. The wind farm protection system should be reliable, selective, speedy, simple and economical. The opening and reclosing of different breakers within a large wind farm change dynamically the configuration of the overall wind farm. 10

Short circuits are called symmetrical if they happen simultaneously and identically on the three phases. Any other type of short circuit is called an asymmetrical short circuit. 2.5 Transient Stability When a major disturbance as a short circuit appears to wind turbines, they react very differently from a synchronous machine. The synchronous machine will keep feeding the fault for as long as the protection devices do not disconnect the faulty section or the generator. The synchronous generator stays connected and It is said that it rides through the fault. During the fault, the synchronous machine is producing a very small amount of power to balance the losses of power through the collector system. The synchronous machine does not need to take reactive power from the grid and the voltage at the end of generator collapses almost to zero. During a major disturbance such as a short circuit, asynchronous wind turbine type 1 experiences an important voltage drop. The type 1 wind turbine needs reactive power to maintain the magnetizing field between the rotor and stator. As voltage drops, it needs more reactive power from the grid in order to stay connected. More flow of reactive power from the grid to the wind turbine increases the voltage drop and power losses through the grid. In such a condition, type 1 wind turbines should be disconnected immediately from the grid. They cannot be used for large-scale production of electricity. 11

The asynchronous machine, type 3 wind turbines exhibit a very interesting behavior during short circuits. Due to the back-to-back solid-state electronic converter, a type 3 wind turbine has the capability to feed back reactive power to the grid. This helps maintain higher voltage at the point of interconnection and contributes to the novoltage collapse. Z=R+jX U 1 P w + j Q w Large electrical Grid. U 2 Load P LD + j Q LD Figure 2.2: Grid connection of wind power Consider the electrical network in Figure 2.2. The voltage V 2 can be calculated as: U 2 = {- (2a 1 U 1 2 )/2 + [ (2a 1 - U 1 2 ) 2 /9 - (a 1 2 + a 2 2 )] 1/2 } 1/2 (2.1) where: a 1 = - R (P w P LD ) X (Q w Q LD ) (2.2) a 2 = - X (P w P LD ) + R (Q w Q LD ) (2.3) Equations (2.1), (2.2) and (2.3) show that the voltage V 2 depends effectively on the reactive power injected from the wind turbine to the grid ([4], pp. 31-32). An injection of 12

power from the wind turbine node helps increase the voltage V 2. It is then a good decision to keep the wind turbine connected to the grid during short circuits as a way to improve the voltage stability at the faulted node and its neighborhood. This is called low voltage ride-through (LVRT). Robust conditions require that the type 3 wind turbine stays connected to the grid even if its voltage drops to zero, which is called zero voltage ride-through (ZVRT). Keeping the wind turbine connected during a transient fault also helps maintain the integrity of the automatic control system through the entire grid. The control of the electrical grid uses devices such as energy management systems (EMS), supervisory control and data acquisition (SCADA) or PowerWorld Retriever. Inside those systems, each variable state is represented and its relation with other variables modeled. A sudden disappearance of state variable from the wind turbine may bring instability to the overall system. The generic graph for LVRT is in Figure 2.3. Voltage(p.u) 1.0 V 3 V 2 V 1 KEEP WIND TURBINE CONNECTED t 1 t 2 t 3 DISCONNECT WIND TURBINE Time (sec) Figure 2.3: Low voltage ride-through simulator 13

The General Electric ZVRT and LVRT curves are shown in Figures 2.4 and 2.5 [5]. Figure 2.4: GE 1.5 and 1.6 MW ZVRT Figure 2.5: GE 1.5 and 1.6 MW LVRT II 14

3. LARGE WIND POWER PLANT AGGREGATION 3.1 Large Wind Farm Definition A large wind farm, illustrated in Figure 3.1, is a set of several individual turbines connected together in a large area of land or water [1]. Having many turbines on a large site also helps smooth the irregularity of wind due to the wind diversity. Figure 3.1: Generic wind power plant topology A pad mount transformer is installed at the foot of each turbine. It increases the voltage level through an underground collector. The collector system is a set of feeders connecting all pad mount transformers both together and to the substation. The layout of a wind farm stays the same throughout its life unless an upgrade is considered. 15

A large wind farm is connected to a grid as shown in Figure 3.1. It is a good approach to reduce its size by equivalencing all the wind turbines to a single machine for load flow and stability study as shown in Figure 3.2. Planning and operations engineers use powerful computers to predetermine the behavior of the grid. Introducing many new buses will tend to slow the computation speed and will be inappropriate. Transmission line Collector equivalent Large Grid P.O.I. Substation Transformer Pad Mount Equivalent Wind Turbine equivalent Figure 3.2: Aggregation of a large wind farm to a single WTG 3.2 Equivalent Wind Turbine Reducing n wind turbines to a single wind turbine, the parameters for the equivalent machine are the active power in megawatts, the reactive power in megavolt amps reactive and the apparent power in megavolt amps. The parameters are given by: (3.1) (3.2) (3.3) 16

We will be using the GE wind turbines in this research. 3.3 Equivalent Pad Mount Transformer Reducing N pad mount transformers to a single transformer, the parameters for the equivalent pad mounted transformer are the apparent power in megavolts amps and the equivalent impedance. They are given by: (3.4) (3.5) 3.4 Equivalent Collector System The equivalent collector system should capture the behavior of the large wind farm in terms of power losses and voltage drop. An algorithm for equivalencing the collector system has been developed by the National Renewable Energy Laboratory (NREL) to compute the equivalent collector impedance and susceptance [1]. (3.6) (3.7) where: - is the impedance of a single line connecting the equivalent wind turbine to the substation. 17

- is the impedance of the branch. - is the total number of wind turbines connected to the bus i. - N is the total number of wind turbines to be aggregated. 18

4. DOUBLY FED INDUCTION GENERATOR 4.1 Active Power Control A wind turbine converts wind energy to electric power. The power P extracted from the wind is given by (4.1) where: - is the air density in kg /. - is the area intercepting the wind in. - is the wind speed in m/sec. - is the rotor efficiency. The coefficient is given by ( ) (1 - ) (4.2) where: is the ratio of downstream to upstream wind for a given position of blade pitch angle theta in degrees. The maximum power is delivered for = 1/3. The coefficient values of for GE wind turbines are given in Figure 4.1 [5]. 19

Figure 4.1: Rotor efficiency curves The control power objective of the wind turbine is to adjust the angle so that for the given wind speed and direction, the extracted power plus losses can match the demanded electric power. The active power control model for a GE turbine is given in Figure 4.2. Figure 4.2: Active power control emulator 20

4.2 Reactive Power Control The control of reactive power delivered by a DFIG wind turbine is done by the solidstate electric converter. The voltage at a given bus through the wind farm is monitored and compared to a reference value. The error is used by a PI controller along with the delivered active power at the time to determine the needed value of to bring voltage to nominal value. The GE reactive power control model for a GE turbine is given in Figure 4.3 [5]. Figure 4.3: Reactive power control model 21

4.3 Voltage Control During transient regime, the voltage at the wind turbine should not exceed a threshold value. A fast regulator and a phase-locked loop (PLL) are used to limit the injected reactive power injected to the wind turbine. The control function is summarized in Figure 4.4 [5]. Figure 4.4: DFIG generator / converter model 22

A complete model for a GE DFIG is provided in Figure 4.5 [5]. Different models of GE wind turbines have been developed in PowerWorld Simulator Beta 15. Figure 4.5: Wind turbine model block diagram 23

PowerWorld Simulator will be used for the simulations of our different case studies. The exciter, governor, and stabilizer parameter values for GE wind turbines are the default per unit values and are taken from Clark et al. [5]. 24

5. CASE STUDIES 5.1 Description For validating the equivalencing of a large wind farm, testing on a large wind farm has been carried out. Four cases are investigated. The large wind farm is composed of 120 GE DFIGs, each delivering 1.65 MW of active power. The wind turbine voltage is 600 V. One hundred twenty pad mount transformers increase the terminal wind generator voltage from 600 V to a medium level of 34.5 kv. The wind farm has 8 main 34.5 kv feeders. Feeders 9 to 14 make up the underground collector system. On each main feeder are connected 15 wind turbines. This case is identified as Case A diagrammed in Figure 5.1. The large wind farm 120 * 1.65 MW is aggregated to 8 GE DFIGs, each delivering 24.750 MW of active power. This case is identified as Case B in Figure 5.2. The 8 * 24.750 MW GE DFIG will be aggregated to one single wind turbine delivering 198.0 MW with an equivalent medium voltage collector system. This case is identified as Case C diagrammed in Figure 5.3. The 120 * 1.65 MW GE DFIG will be aggregated to one single wind turbine delivering 198.0 MW by simply ignoring the medium voltage collector system. This case is identified as Case D diagrammed in Figure 5.4. For all four cases, two simulations are carried out. 25

1. A power flow simulation is solved under normal conditions. The flows of power in terms of total active power and reactive power will be compared on common devices in the four cases. 2. A three-phase fault through an impedance of = 0 + j 0.08 p.u. on circuit 2 of the 345 kv line is simulated for transient stability study. 26

Figure 5.1: Case A: large wind farm with 120 turbines 27

Figure 5.2: Case B: aggregation 120 to 8 turbines Figure 5.3: Case C: aggregation to 1 turbine with medium equivalent collector system Figure 5.4: Case D: aggregation to 1 turbine without medium equivalent collector system 28

5.2 Load Flow Analysis A load flow study for Cases A, B, C and D has been summarized in Table 5.1. The flows of active and reactive power delivered by the wind farm are the same: 193.7 MW and 39.3 Mvar for Case A, 194.6 MW and 38.6 Mvar for Case B, 194.6.7 MW and 40.6 Mvar for Case C and 195.9 MW and 37.8 Mvar for Case D. Table 5.1: Power flow comparison for Cases A, B, C, and D Case A: Large wind farm with 120 turbines Total Current Flow Total active Power Total Reactive Power Feeder 9 409.2 Amps 24.4 MW 1.3 Mvar Feeder 10 406.1 Amps 24.3 MW 1.5 Mvar Feeder 11 407.1 Amps 24.3 MW 1.4 Mvar Feeder 12 408.6 Amps 24.3 MW 1.5 Mvar Feeder 13 408.7 Amps 24.3 MW 1.5 Mvar Feeder 14 408.7 Amps 24.3 MW 1.5 Mvar Feeder 15 406.9 Amps 24.2 MW 1.5 Mvar Feeder 16 409.9 Amps 24.4 MW 1.3 Mvar Substation 326.4 Amps 193.7 MW 39.3 Mvar Case B: Aggregation to 8 turbines Total Current Flow Total active Power Total Reactive Power Feeder 9 407.0 Amps 24.5 MW 1.2 Mvar Feeder 10 405.1 Amps 24.1 MW 1.5 Mvar Feeder 11 410.3 Amps 24.4 MW 1.2 Mvar Feeder 12 410.5 Amps 24.5 MW 1.2 Mvar Feeder 13 410.7 Amps 24.5 MW 1.2 Mvar Feeder 14 407.7 Amps 24.3 MW 1.5 Mvar Feeder 15 401.9 Amps 24.9 MW 1.8 Mvar Feeder 16 409.0 Amps 24.4 MW 1.4 Mvar Substation 326.8 Amps 194.6 MW 38.6 Mvar Case C: Aggregation to 1 turbine with medium equivalent collector system Total Current Flow Total active Power Total Reactive Power Substation 323.7 Amps 194.6 MW 40.6 Mvar Case D: Aggregation to 1 turbine without medium equivalent collector system Total Current Flow Total active Power Total Reactive Power Substation 329 amps 195.9 MW 37.8 Mvar 29

5.3 Transient Stability Plots A transient fault has been simulated on bus 2 and the voltage response at bus 3. The reactive and the active power delivered by the wind farm to the grid have been recorded in the four cases in Figures 5.5 to 5.8. Figure 5.5: Case A: wind farm 120*1.6 MW GE WTG Figure 5.6: Case B: aggregation to 8*24.7 MW GE WTG Figure 5.7: Case C: aggregation to 1*198 MW GE WTG with 34.5 kv collector system 30

Voltage p.u. bus 3 Figure 5.8: Case D: aggregation to 1*198 MW GE WTG without 34.5 kv collector system A cross-plot of transient voltages in Figure 5.9, for a transient fault at bus 2, the point between the wind farm substation and the overhead power line, shows that the voltages are the same in all cases. 1.3 1.2 1.1 1 turbine no 34.kv 1 turbine with 34.5 kv 8 turbines 120 turbines 1 0.9 0.8 0.7 0.6 0.5 0 0.5 1 1.5 2 2.5 3 3.5 4 Time (seconds) Figure 5.9: Cross-plot of voltages at bus 3 in Cases A, B, C and D The results of simulations, as summarized in Table 5.1, show that: 1. The flows of current, active power and reactive power are the same for Case A and Case B on feeders 9 to 16. 31

2. The flows of current, active power and reactive power are the same for Case A, Case B and Case C in the substation. The flows of power in the equivalent representation of the large wind farm, Case C and Case D, capture the behavior of the large wind farm. 3. The dynamic stability responses are identical for all cases. 32

6. LOW VOLTAGE RIDE-THROUGH 6.1 LVRT with Fault outside the Collector System A symmetrical three-phase solid fault, through an impedance = 0 + j 0 p.u., is simulated on bus 2 as shown in Figure 6.1 by the red arrow. The fault is located outside of the 34.5 kv wind farm collector system. Figure 6.1: Low voltage ride-through study with fault at bus 2 If the fault appears at 0.1 sec and is removed at 0.8 sec, the low voltage ride-through shows that the wind farm is able to recover all the total generation power as shown in the first plot of Figure 6.2. The time to clear the fault has been extended to reach the critical time, or stability limit of 0.833 sec. If the fault lasts for 0.733 sec or more, all 120 33

wind turbines will disconnect from the grid, and there is a total generation loss as shown in the second plot of Figure 6.2. The analysis of terminal voltages on all wind turbines during the fault shows voltages within the lowest value of 0.198 p.u. and the highest value of 0.221 p.u. as shown on the last plot of Figure 6.2. Figure 6.2: Simulation results for symmetrical three-phase solid fault at bus 2 For the same solid fault at bus 2, the low voltage ride-through has been simulated with the two aggregated models: one with the equivalent 34.5 kv equivalent collector system (Figure 6.3) and another without the equivalent 34.5 kv equivalent collector system (Figure 6.4). Figure 6.3: Low voltage ride-through with 34.5 kv equivalent collector 34

Figure 6.4: Low voltage ride-through without 34.5 kv equivalent collector The low voltage ride-through analysis shows that the two aggregated models are identical as shown in the two plots of Figure 6.5. The terminal voltage on bus 328 and the wind farm voltage at bus 3 have been represented. For the same fault conditions at bus 2, the three Cases A, C and D have the same stability limit time of 0.833 sec. Figure 6.5: Stability time limits for Cases C and D A symmetrical solid fault has been simulated outside of the collector system on bus 3, as diagrammed in Figure 6.6. The bus is located between the collector system and the 35

substation. For the fault at bus 3, the impedance of the substation does not contribute to the limitation of short circuit current from the large wind farm. Figure 6.6: Low voltage ride-through study with fault at bus 3 The fault appears at 0.1 sec. During the short circuit, the voltages on all wind turbines drop from 1 p.u. to the lower range between 0.004 and 0.04 p.u. All the wind turbines will disconnect from the grid at the same time of 0.33 sec as shown in Figure 6.7. The analysis of aggregated models of 120 wind turbines to a single wind turbine with and without the 34.5 kv equivalent collector system (Cases C and D) gives the same results, as shown respectively in the second and the last plots of Figure 6.7. Bus 3 represents the line of symmetry as the wind turbines see the fault. For faults located between bus 3 and the point of interconnection to the grid, all wind turbines 36

have the same behavior in terms of the time they will trip from the grid. They are likely to trip at the same time. Figure 6.7: Simulations results for a solid symmetrical fault at bus 3 6.2 LVRT with Fault within the Collector System A solid symmetrical fault, through an impedance = 0 + j 0 p.u., has been simulated within the collector system on the feeder 9 between the two daisy-chains of respectively eight wind turbines (238 to 244) and seven wind turbines (246 to 252), at bus 230 as shown by the red arrow in Figure 6.8. 37

Figure 6.8: Short circuit on the bus 230 within the collector system A monitoring of voltages on wind turbines has been performed on all wind turbines through the wind farm as shown in Figure 6.9. The plot of voltages shows that all wind turbines do not have the same terminal voltage during the short circuit. Wind turbines will trip at different times in accordance with the wind turbine LVRT curve. Figure 6.9: Low voltage ride-through study with fault at bus 2 38

The analysis of low voltage ride-through on each wind turbine on the faulted feeder shows that all the wind turbines from the last in the queue to the point of fault (wind turbines 238-245) have a lower voltage of 0.08 p.u. They will trip at time 0.317 sec. The feeder with very low impedance 0.002 + j0.00046 p.u. connects the bloc of 8 to the next bloc of seven wind turbines. The voltage on the wind turbines 246-252 is also 0.08 p.u. They will trip at the same time, 0.317 sec. The rest of the wind turbines will trip at time 1.333 sec marking a total wind farm disconnection from the grid. The fault on the last daisy-chain is likely propagating through the entire wind farm. In order to stop the propagation, a high impedance value is inserted by increasing 100 fold the impedance of the feeder between buses 223 and 230 during the short circuit. The plots of voltage during short circuit are given in Figure 6.10. Figure 6.10: LVRT with an increased feeder impedance during short-circuit 39

Voltages on the wind turbines 246-252 increase from 0.08 to 0.32 V. They will trip from the grid at 0.317 sec. We realize that in this case the wind farm is not going to trip as before at the time 1.333 sec. The fault will ride through for 0.484 sec more. The wind farm is going to disconnect totally from the grid at time 1.817 sec. A solid symmetrical fault has been simulated on bus 222 as diagrammed in Figure 6.11. The simulation shows the wind turbine 246 will have 0.078 p.u. volts during the fault and will trip at 0.317 sec as shown in Figure 6.12. The rest the turbines will be at the voltage level of 0.26 p.u and they will trip at same time 0.833 sec as shown in Figure 6.12. The fault is propagating through the entire wind farm. Figure 6.11: Short circuit on bus 222 within the collector system 40

Figure 6.12: Simulations results for a solid symmetrical fault at bus 222 During the fault, the impedance of feeder 15 will be increased 50 times to 0.0445+j0.6 p.u., and the fault clearing time increased to 3.99 sec. The low voltage ride-through analysis shows that the wind turbines 238-252 will trip and any other wind turbine will disconnect from the grid in spite the presence of the short circuit. The wind farm is able to deliver 155 MW to the grid during the short circuit as shown in Figure 6.13. Figure 6.13: LVRT with an increased feeder impedance during short-circuit at bus 222 41

During a short circuit within a large wind farm, the number of wind turbines tripping can be reduced by increasing the impedance of the feeder connecting the point of fault to the rest of the collector system. The insertion of impedance on the faulted feeder will also increase the stability limit time of the wind farm. An insertion of resistance will cause an increase of active power losses through the wind farm. An increase of 100 times has been done only on the reactive impedance component of feeder 15. The impedance of the feeder has been increased from 0.0089+ j0.006 p.u. to 0.0089+ j0.6 p.u. The low voltage ride-through simulation gives better results, as summarized in Figure 6.14. There is a net increase of wind farm voltage during the short-circuit. Figure 6.14: Improved LVRT using a self-impedance to increase the line impedance 42

An aggregated model cannot be used to determine why some wind turbines trip and others do not in a large wind farm, nor can it determine the sequence in which they will disconnect from the grid. Faults within a large wind farm are likely to appear anywhere within the wind farm; a number of points can be identified at the sectionalizing post to buffer the propagation of the fault. A proposal for the wind farm under study will be to insert self-impedance at the sectionalizing post, between bus 3 and the feeder. A smart system will locate the position of the short circuit, identify the faulted feeder (feeder 9 to 15) and insert a selfimpedance in series with the faulted feeder during the short circuit. 43

Through this research, it is shown that: 7. CONCLUSIONS AND FUTURE WORK A large wind farm using the GE DFIG wind turbines can be consistently aggregated to one equivalent machine for load flow and transient stability studies. The low voltage ride-through response can be improved by inserting a selfimpedance between the faulted feeder and the rest of the large wind farm during the fault. This impedance will reduce the number of wind turbines tripping during the fault, and increase the voltage stability of the wind farm. In our simulation, a large wind farm with 410 buses has been aggregated to an equivalent wind farm with 5 buses. This represents a reduction in size of the large wind farm by 99 % and is an important savings of resources and time. Future work will include the introduction of an automatic tool in the PowerWorld Simulator to do the equivalencing of a large wind farm to a single machine for any layout of the wind farm, and modeling for dynamic study of other wind farm turbines available on the market. 44

APPENDIX PRYSMIAN S GUIDE TO WIND FARM CABLES Indicative values of wind farm cables impedance are given in the Figure A.1. Figure A.1: Details from Prysmian s Guide to Wind Farm cables [6] 45

REFERENCES [1] A. Ellis and E. Muljadi, Wind Power Plant Representation in Large-Scale Power Flow Simulations in WECC, in 2008 IEEE Power and Energy Society General Meeting Conversion and delivery of Electrical Energy in the Century, 2008, pp. 1-6, pp. 1-6, 2008. [2] T. J. Overbye and J. D. Weber, "Visualizing the Electric Grid" in IEEE Spectrum, vol 38, pp. 52-58, February 2001. [3] J. Duncan Glover, M. S. Sarma, and T. J. Overbye, Power System Analysis and Design, 4 th ed. Toronto, Ontario: Thompson, 2008. [4] T. Ackermann, Wind Power in Power Systems. Chichester, UK: John Wiley and Sons, 2005, pp. 31-32. [5] K. Clark, N. W. Miller, and J. J. Sanchez-Gasca, Modeling of GE Wind Turbine Generators for Grid Studies, Version 4.4, September 2009, General Electric International Inc. [Online]. Available: http://www.gepower.com/prod_serv/products/utility_software/en/downloads/091 00_Modeling_of_GE_Wind_Turbine-Generators_for_Grid_Studies.pdf [6] PRYSMIAN S Guide to Wind Farm Cables, 2010 P.5. [Online]. Available: http://www.prysmianusa.com/export/sites/prysmianenna/attach/pdf/energy/brochures/2010_11_02_wind_farm_cable_guide.pdf 46