DESIGN AND CONSTRUCTION STANDARDS. Section 2: Standards for Specific Categories of Work. Laboratory Standards

Similar documents
.2 These guidelines should be read with the specific technical sections of McGill s Building Design and Technical Standards.

1 data PIC location (with 2 ports) typically asf for multiple staff members

Communications Page 1 of 9

Whitley Shower Locker Toilet Facilities

NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

1. Adequate framing details, sizing, spacing and technical information shall be indicated on the documents.

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)

Telecommunication Spaces

Division 09 FINISHES TABLE OF CONTENTS

AUTOMOTIVE SERVICE TECHNOLOGY September 30, 2010

This section applies to service areas and loading docks for new construction and major renovations.

Gerald Desmond Bridge Replacement

Deficiency ID Qty UoM Priority. Concrete Walks Are Damaged And Require Replacement ,000 SF 3

NC State University Design and Construction Guidelines Division 00 Planning & Design Space Planning

Include a paint or finish schedule on the drawings, listing colors, locations and types of materials.

F.C.L. INTERIOR FINISHES CHECK LIST 2010 PRODUCT SELECTION - FLOORING GENERAL ITEMS PRODUCT SELECTION GENERAL ITEMS

260,000 SF Building Profile

SECTION OUTLET, PULL, AND JUNCTION BOXES

Facilities Management Service and Support Function Needs

ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED.

Expanding Your Development & Investment Perspectives 159,000 SF Building Profile

SECTION The specification section is organized by placing information in three standard parts:

INVENTORY FORMS FOR NONSTRUCTURAL ELEMENTS

2. In moist areas, portland cement plaster should be used if a more permanent material is not within budget limits.

Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington

APPLICATION FOR FINISHED BASEMENT PERMIT

University of North Carolina at Charlotte Design and Construction Manual Section 2, Division 11 Equipment SECTION 2 DIVISION 11 EQUIPMENT

Deficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2

Lab Sketchbook 2nd Floor Biology Science Building Saddleback College 2011 December 08

SECTION 2 DIVISION 11 EQUIPMENT

CONTENTS. B. System Design and Performance Requirements

workstationindustries.com Made in the USA

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1

Introduction. Disclaimer. Table of contents

PHONE FAX WEB Mitchell Road Newbury Park, CA 91320

Facilities Management Services & Funding Guide Centrally Funded and Recharge Services

SECTION NON-STRUCTURAL METAL FRAMING

186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS ADDENDUM #1 PERFORMANCE WORK STATEMENT

MECHANICAL M-1 LEGEND AND DETAILS M-2 FLOOR PLAN - DUCTWORK M-3 FLOOR PLAN - PIPING

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations

Science Education Facilities

The University of Texas at Austin September 30, 2011

Bureau of Indian Affairs

Timberglen Recreation Center Summary

SPACE TYPE: ENHANCED OFFICE

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

A. All tackboards shall be mechanically fastened to walls; gluing shall not be allowed.

SCI-FAB Product Specifications. Casework Section 1. Part 1 General

DIVISION 9 FINISHES. This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards

UBC Technical Guidelines Division Edition Furnishings Page 1 of 1 INDEX

2 Main Building BLDG-959A Building Purpose Building Area Bus Terminal 14,890 SF Inspection Date August 18, 2016 Inspection Conditions Facility Conditi

SECTION 11 Architectural and Nonstructural Elements Field Investigation

Introduction. Disclaimer. Table of contents

UBC Technical Guidelines Division Edition Furnishings Page 1 of 1 INDEX

ADDENDUM 2 - JULY 14, 2015

CITY OF FORT COLLINS BUILDING STANDARDS SPECIFICATIONS/DIV 8

10155 Toilet Compartments

C. Wallboard shall not be glued directly to masonry or concrete walls below grade: provide furring.

Residential Outline Specifications

PHASE I ACADEMIC BUILDING CORE RENOVATIONS RCNJ Project No C

CLINICS. LABS. PHARMACIES. PREP AND PACK.

Casework Midmark Animal Health Products

SECTION SECTIONAL OVERHEAD DOORS 511 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

CONSTRUCTION TRADES LABORATORY September 30, 2010

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS

TENANT CRITERIA MANUAL INSERT PHOTO HERE

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION SECTIONAL OVERHEAD DOORS 416 SERIES SECTIONAL STEEL DOORS

G703 Continuation Sheet Minimum Schedule of Values Please use the breakdown listed below when submitting your billing for the project

A. Submit the following in addition to the standard requirements.

SECTION SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS

TABLE OF CONTENTS Public Safety Building

2) These Standards are available on the University s website at:

Mills Elementary School Site Summary

SECTION ACCORDION FOLDING PARTITIONS

Interior finishes include wall finishes, floor finishes, wall base finishes, and ceiling finishes.

ALARIS CONSOLE ABOUT ALARIS CONSOLE ALARIS CONSOLE FEATURES. Product Specification Document Date Published: September 17, 2004

ADDENDUM A CONSTRUCTION SPECIFICATIONS

NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

E. Fume hood to have set baffling system. No adjustable baffles allowed.

COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION

SECTION Manufactured Metal Casework FLEXIBLE LABORATORY FURNITURE SYSTEM (OPTIMA) USA VERSION

SUBMISSION GUIDE FOR ARCHITECTS

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School

APPENDIX A CHECK-LIST FOR SCIENCE SAFETY REQUIREMENTS. (Required Minimums for Approval by the N.C. Board of Education)

Building Systems and Design Elements included in SliDeRulE

Wellington Manor Series

SECTION SECTIONAL OVERHEAD DOORS 418 SERIES INSULATED STEEL DOORS

OVERHEAD SERVICE DISTRIBUTION

SECTION SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS

TABLE OF CONTENTS. (Δ = Rev 06/08)

Budget Estimate Basic Tenant Improvement

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free

Manufacturing Facilities Proposal

Wall Plan (01011 Design Requirements, Section ) First Floor, Building 5111

2013 California Building Code Advisory

C. Preparation and submission of complete engineered shop drawings for approval. E. Coordination with other affected work, trades and inspections.

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

Transcription:

Laboratory Standards These criteria include general planning guidelines. They are intended for use of Designers during the design phases of the project. Planning Assumptions Overview In order to maximize the adaptability of the laboratory spaces, modular design will be utilized in the planning of all building systems including architectural, mechanical, plumbing, electrical, and furnishings. Adaptability Adaptability is the reserve capacity that is required to be designed into the structural, mechanical, and other building components to accommodate future growth and change. Dedicated zones for mechanical, plumbing, electrical, communication systems, etc. are another form of reserve capacity. The ability to respond to future changes depends on easy access to the building s utility systems and the adequate design of those systems. Ease of maintenance, repair, and change legislate the need for access to systems to minimize costly and time-consuming disruptions to ongoing laboratory activities. A design that effectively integrates accessibility for the ease of change can also simplify, and perhaps expedite, the construction process. Accessibility Providing accessibility for persons with disabilities should conform to applicable local, state, and federal regulations. Considerations should be given to the following accessibility aspects: All parts of the building should be accessible by persons with disabilities. Accessible workstations and fume hoods should be provided in the laboratories based on code requirements and campus practices. Accessible workstations should be located close to eyewash and safety showers. Allow 18 clearance on the pull side and 12 clearance on the push side of doors. Some general criteria and guidelines for accessible workstations in laboratories are as follows: Work surfaces 30 to 34 above floor with wheelchair clearance below. Adjustable work surfaces can provide a range of possible height adjustments. Page 1 of 5 Laboratory Standards Original 5/3/2007

Laboratory service controls, equipment, and equipment controls within easy reach for persons with limited mobility. Controls should have single-action levers or blade handles for easy operation. Aisle widths and clearances adequate for maneuvers of wheelchair bound individuals. Aisles 5-0 wide are recommended with turnaround areas. Modular Planning The laboratories shall be developed from multiples of, or fractions of, a standard module of 11-0 wide and 30-0 deep. The module may be sub-divided to create smaller spaces as needed. The 11-0 width was justified by a study of those elements that would go into a single module width, face to face, across a user s aisle, such as the laboratory casework (based on a 2-9 wide single or 5-6 double bench width) and equipment, with an access aisle sufficiently wide to promote safety and convenience of movement without being wasteful. Laboratory Furnishings Laboratory Casework Material: Wood, plastic laminate or metal to be determined during the Design Development phase. System: Floor mounted or C-Frame to be determined during the Design Development phase. Architectural Systems Interior Partitions Offices and Laboratories Metal studs and gypsum wallboard, reinforced on the laboratory side to support wall hung devices. Fire ratings are to be determined during code review. Painted unit masonry may be used for corridor and storage areas requiring durable surfaces and/or structural integrity, such as cylinder storage areas and high security areas. Laboratory Doors Swing: In direction of egress Minimum Width: 3 6. For Special Equipment Rooms, provide (2) 3-0 doors for a 6-0 opening. Minimum Height: 7-0 Rolling overhead doors to exterior for selected spaces Security: To be determined during later phases. Consideration should be giving to installing selected doors with frames, conduit, and power to accept card readers at a future date. Page 2 of 5 Laboratory Standards Original 5/3/2007

Ceilings Minimum Ceiling Height: 9-6 Laboratories, 8-0 Offices Ceiling Type: Provide acoustic treatment as part of ceiling or underside of floor above if no ceiling is provided. Provide hard ceilings in areas of high cleanliness and BSL-3 suites. Flooring Sheet vinyl seamless flooring for the Laboratories and BSL-3 spaces. Carpeting in Faculty Offices, Administrative suites, and Conference/Meeting Rooms. Epoxy flooring is desirable in animal holding rooms and wet areas. Sealed concrete for the selected Support Spaces. In general, semi gloss enamel interior paint is a satisfactory material for the majority of spaces. Special finishes are to be used for architectural design considerations or to satisfy local needs. Epoxy paint is to be used on selected surfaces. Laboratory Corridors Minimum width 7-0 Minimum ceiling height: 8-0 Provide bulletin boards/display cases in Laboratory Corridors Provide space for spill kits, air packs, fire blankets, etc. Space Descriptions Office/Conference Room Suspended acoustical ceiling with integral light fixtures. Carpeted floors - Faculty Offices, Administrative Suites, and Conference. Sheet vinyl floors Technician Office and Storage Rooms. Enamel painted gypsum board walls Environment Year round air conditioning Windows at the exterior offices Page 3 of 5 Laboratory Standards Original 5/3/2007

Recycled ventilation is acceptable One HVAC zone per office with low velocity diffusers Services 120V receptacles, a maximum of 6 on center, 40 amps per office minimum Phone/Data connectors Fixed equipment Whiteboards in offices and Conference Rooms Laboratories Suspended, non-flaking faced acoustical ceiling with pendant light fixtures Sheet vinyl floors Enamel painted walls Environment Year round air conditioning Windows at the exterior 24-hour 100% once-through ventilation with temperature control Services Electrical 120V/280V, 3 phase, 5 wire system with receptacles 36 on center in modular plug-in strip on walls and overhead service carrier Dedicated 42 circuit 120V/208V, 3 phase panel per 640 net square feet Dual switched lighting providing 80 to 100 foot-candles at 36 above the finished floor Fixed Equipment 36 high fixed wall bench with large sinks, cupboard and drawers below and with wall cabinets and drying racks above sinks. As an option to fixed bench work, overhead service carrier in middle of lab, at 7-0 above finished floor for 120V/208V plug strip with receptacles 36 on center 4-0 wide tall storage cabinet with locked doors. Page 4 of 5 Laboratory Standards Original 5/3/2007

Building Support Areas See custodial standards See instructions to Designers Freight Elevator Minimum size: 8-0 x 10-0 Minimum load capacity: 5000 pounds Page 5 of 5 Laboratory Standards Original 5/3/2007