A Detail Review Comparison of Refrigeration System with and without Ejector Aakash J. Bhatt 1 Fenil S. Jariwala 2

Similar documents
Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector


NUMERICAL INVESTIGATION OF AN R744 LIQUID EJECTOR FOR SUPERMARKET REFRIGERATION SYSTEMS

Compound ejectors with improved off-design performance

Energy and Buildings

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY

Parametric Study of a Double Effect Absorption Refrigeration System

Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system

A Review on Performance of Air Conditioning System using Two Phase Ejector

Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion Transcritical CO 2 Refrigeration Cycle

Computational Analysis Of Ejector With Oscillating Nozzle

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

High-Efficiency Joule-Thomson Cryocoolers Incorporating an Ejector

COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22

EFFECT OF THE NOZZLE EXIT POSITION ON THE EFFICIENCY OF EJECTOR COOLING SYSTEM USING R134A

Effect of Generator, Condenser and Evaporator Temperature on the Performance of Ejector Refrigeration System (ERS)

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

Carbon Dioxide as an Eco-Friendly Refrigerant for Electric Vehicles

Stefan Elbel Pega Hrnjak University of Illinois at Urbana-Champaign

Ejector Expansion Refrigeration Systems

A review on Present development in refrigeration jet ejector system

CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER

France Marie M. Orden and Menandro S. Berana. Proceedings of the World Congress on Engineering 2017 Vol II WCE 2017, July 5-7, 2017, London, U.K.

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

DEVELOPMENT OF A HYBRID AIR-CONDITIONING SYSTEM DRIVEN BY LOW TEMPERATURE WASTE HEAT

Experimental investigation of solar-driven double ejector refrigeration system

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING

Energy efficient Supermarket Refrigeration with Ejectors

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy


ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE

Copyright 2012 Neal D. Lawrence

BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS

ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR

Design of a Solar-Driven Ejector Cooling System

PERFORMANCE EVALUATION OF HEAT PUMP SYSTEM USING R744/R161 MIXTURE REFRIGERANT

Three-dimensional Numerical Investigations on Ejector of Vapour Jet Refrigeration System

Thermodynamic Analysis of Gas Turbine Trigeneration System

SIMULATION AND EXPERIMENT RESEARCH ABOUT TWO-PHASE R744 EJECTOR SYSTEM

Chapter 8. Vapor Power Systems

High efficient heat reclaim with CO2

OPTIMIZING THE GENERATOR AND ABSORBER THERMAL LOAD OF COMBINED ABSORPTION-EJECTOR REFRIGERATION SYSTEM

Energy and Exergy Analysis of Combined Ejector-Absorption Refrigeration System

Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery

Problems in chapter 9 CB Thermodynamics

Theoretical analysis of an integrated thermoelectric-absorption cooling system

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.

Department of Mechanical and Materials Engineering. Solar Energy Research Institute Faculty of Engineering and Built environment.

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008

Parallel Work of CO 2. Ejectors Installed in a Multi- Ejector Module of Refrigeration System. Journal of Physics: Conference Series.

EXPERIMENTAL STUDY OF ALTERNATIVE REFRIGERANTS TO REPLACE R134a IN A DOMESTIC REFRIGERATOR

Readdressing working fluid selection with a view to designing a variable geometry ejector

DEVELOPMENT OF SOLAR THERMAL HEATING AND COOLING SYSTEMS USING THE JET PUMP CYCLE

Solar Powered Vapour Absorption Refrigeration (SPVAR) System as a rural microenterprise

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Performance Analysis of a Solar Powered Adsorption Cooling System

Energy Optimization of an Installation of Reversible Geothermal Heat Pump

Ejectors in a Compressible Network for Gas Turbine Extended Operability

Enhancement of LNG Propane Cycle through Waste Heat Powered Absorption Cooling

Solar Cooling Using Variable Geometry Ejectors

CO2 solutions February 2018

Radial Turbine Preliminary Design and Modelling

NUMERICAL APPROACH TO A LOW PRESSURE GAS-INJECTION SCROLL COMPRESSOR

Superior Efficiency Reduced Costs Viable Alternative Energy Kalex Kalina Cycle Power Systems For Cement Kiln Waste Heat Applications

THERMAL ENERGY ANALYSIS OF SOLAR POWERED VAPOUR ABSORPTION COOLING SYSTEM

Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle

Chapter 10 VAPOR AND COMBINED POWER CYCLES

Faculty of Engineering 2 nd year 2016 Mechanical Engineering Dep. Final-exam (code: M 1222)

Modelling and Simulation of Solar-Biomass Hybrid Trigeneration using ORC-VCC

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia

Eng Thermodynamics I: Sample Final Exam Questions 1

THEORETICAL STUDY OF HEAT PUMP SYSTEM USING CO 2 /DIMETHYLETHER AS REFRIGERANT

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS

Thermodynamic Analysis of Organic Rankine Cycle using Different Working Fluids

PERFORMANCE ANALYSIS OF ORGANIC RANKINE CYCLES USING DIFFERENT WORKING FLUIDS

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant

CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER

Investigation of Separator Parameters in Kalina Cycle Systems

CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER

Energy analysis and performance evaluation of a novel multi-evaporator ejector refrigeration cycle (ERC)

Permanent City Research Online URL:

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

Alpha College of Engineering

Advanced heat driven cooling cycles for low-temperature waste heat recovery

Refrigeration Cycle With Two-Phase Condensing Ejector


A Validated Numerical Experimental Design Methodology for a Movable Supersonic Ejector Compressor for Waste Heat Recovery

CFD study of variable geometry ejector using R600a to detect optimal geometry for ejector refrigeration system

A SHOT IN THE COLD: A NEW OPEN REGENERATIVE CYCLE FOR HEAT-PUMPS AND REFRIGERATORS

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

Study on Performance Enhancement of Solar Ejector Cooling System

Thermodynamic analysis on post combustion CO 2 capture of natural gas fired power plant

Development of Terry Turbine Analytical Models for RCIC Off-Design Operation Conditions

Transcription:

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 11, 2015 ISSN (online): 2321-0613 A Detail Review Comparison of Refrigeration System with and without Ejector Aakash J. Bhatt 1 Fenil S. Jariwala 2 1 P.G. Student 2 Assistant Professor 1,2 Department of Mechanical Engineering 1,2 Shri S advidyamandal Institute of Technology, Bharuch-392001, Gujarat, India Abstract Recently, in refrigeration industry the use of efficient ejector refrigeration systems has been paid a lot of attention. These systems sound even more interesting when they are a combination of different kinds of conventional refrigeration systems. In this report thermally consisting of different types of refrigeration systems with and without ejector are proposed and investigated thermodynamically. In this report after the detailed study of the refrigeration system, the detailed study and analysis of the refrigeration system with ejector would be done and deviation in the performance of the system with ejector and without ejector will be studied. The performances of hybrid ejector systems are analyzed and optimized, using the Engineering Equation Solver. And also analysis of parameters like mass flow rate of working fluid, network, thermal efficiency of the cycle varies with the variation in inlet temperature of evaporator, condensation temperature, compressor pressure and different working parameters of the refrigeration systems. Keywords: Ejector refrigeration system, hybrid system, coefficient of performance the generator and the other flows through the expansion device and enters the evaporator, where it is evaporated to vapor. The vapor is finally entrained into the ejector again, thus finishing the ejector refrigeration cycle. II. DESCRIPTION OF DIFFERENT REFRIGERATION SYSTEM A. Vapour Compression Refrigeration System with Ejector: I. INTRODUCTION The ejector is a component that expands a high-pressure primary substance to absorb a secondary substance at a pressure slightly above the low pressure reached by the primary substance. In refrigeration cycles, the two substances are identical, so both flows mix together leading to mixture pressure increase due to the change of the flows momentum. An ejector is composed of a nozzle and a body. The nozzle is convergent divergent with a throat that defines the primary mass flow rate. The role of the nozzle is to create a low-pressure flow with high momentum, so it transforms the pressure potential energy into kinetic energy. Fig. 2: Schematic diagram of combined ejector vapour compression refrigeration system Fig. 1: A conventional ejector refrigeration system Fig. 1 shows a basic CERS. It mainly consists of a generator, an evaporator, a condenser, expansion device, ejector and circulating pump. In this system, the vapor (primary fluid) from the generator at high pres-sure flows through the nozzle of the ejector and entrains the vapor (secondary fluid) from evaporator at low pressure. The primary fluid and secondary fluid then mix in the mixing section and recover a pressure in the diffuser. The combined fluid flows to condenser where it condenses. And then the condensate is divided into two parts: one is pumped back to Fig. 3: p-h diagram 1) Thermodynamic Analysis: Compressor work: h 5 -h 4 Refrigerating effect: h 2 -h 7 COP: h 2 -h 7 /h 5 -h 4 Entrainment ratio: m s /m p B. Vapour compression refrigeration system without ejector: All rights reserved by www.ijsrd.com 446

Fig. 4: Schematic diagram of vapour compression refrigeration system Fig. 5: p-h diagram 1) Thermodynamic analysis: Compressor work: h 2 -h 1 Refrigerating effect: h 1 -h 4 COP: [ h 1 -h 4 ] /[ h 2 -h 1 ] The layout of the ejector expansion vapour compression refrigeration cycle in figure and the corresponding Pressure Enthalpy diagram is shown in figure. The primary flow from the condenser (state 1) and the secondary flow from the evaporator (state 2) are expanding through primary and secondary nozzles, respectively (1 1b and 2 2b) to mixing chamber pressure, mixing at constant pressure (1b, 2b 3m). The mixed flow is discharged through the diffuser (3m 3) of the ejector and then separated in forms of vapour (state 4) and liquid (state 6) so that this ratio matched with the inlet ratio of primary and secondary flows. Then the liquid circulates through the expansion valve (6 7) and evaporator (7 2), whereas the vapour flows into the compressor (4-5) and the condenser (5-1). There are three ejector parameters, entrainment ratio (secondary mass flow to primary mass flow), PLR (diffuser exit pressure to secondary nozzle inlet pressure), and geometric area ratio (total nozzle exit area to primary nozzle exit area), which greatly affect the system performance. III. LITERATURE REVIEW Jianlin Yu, et al. [1] A new ejector refrigeration system (NERS) with an additional liquid vapor jet pump was proposed. The jet pump was used to decrease the backpressure of the ejector, and then the entrainment ratio and the coefficient of performance (COP) of the new system could be increased. The theoretical analysis and simulation calculation was carried out for the new system. The comparison between NERS and conventional ejector refrigeration system (ERS) was made under the same operating condition. The variety of the new systems COP with generator temperature and backpressure was talked about for two refrigerants: R134a and R152a. The figuring results demonstrate the COP of NERS might be enhanced all the more adequately and that happens at the expense of more pump work. From the point of perspective of exergy, the new framework is of higher exergetic effectiveness and feasible. Daqing Li, et al. [2] An ejector development transcritical Co2refrigeration cycle is proposed to enhance the COP of the fundamental transcritical Co2cycle by lessening the development process misfortunes. A steady weight blending model for the ejector was created to perform the thermodynamic investigation of the ejector development transcritical Co2cycle. The impact of the entrainment degree and the weight drop in the getting area of the ejector on the relative execution of the ejector development transcritical Co2cycle was researched for regular cooling operation conditions. The impact of diverse working conditions on the relative execution of the ejector extension transcritical Co2 cycle was additionally explored utilizing expected qualities for the entrainment proportion and weight drop in the getting area of the ejector. It was observed that the COP of the ejector development transcritical Co2cycle might be enhanced by more than 16% over the fundamental transcritical Co2cycle for regular ventilating operation conditions. Hua Zhao, et al. [3] This paper displayed a novel autocascade refrigeration cycle (NARC) with an ejector. In the NARC, the ejector is utilized to recoup some accessible work to build the compressor suction weight. The NARC empowers the compressor to work at lower weight degree, which thusly enhances the cycle execution. Hypothetical reckoning model focused around the constant weight blending model for the ejector is utilized to perform a thermodynamic cycle examination for the NARC with the refrigerant mixture of R23/R134a. The impacts of some principle parameters on cycle execution were examined. The results demonstrate the NARC has an extraordinary legitimacy in diminishing the weight proportion of compressor and in addition increasing the COP. For NARC worked at the condenser outlet temperature of 40 C, the evaporator channel temperature of 40.3 C, and the mass part of R23 is 0.15, the weight proportion of the ejector compasses to 1.35, the weight proportion of compressor is diminished by 25.8% and the COP is enhanced by 19.1% over the routine autocascade refrigeration cycle. Stefan Elbel, et al. [4] This study presents test results got from a transcritical R744 framework utilizing a refrigerant ejector. The results were contrasted with that of an ordinary framework with a development valve. For the test conditions considered, the cooling limit and COP simultaneously enhanced by up to 8% and 7%, individually. Trials were broke down to quantitatively evaluate the consequences for framework execution as an aftereffect of progressions in essential ejector measurements, for example, thought process spout and diffuser estimating. Little plot of 5 c yielded best comes about for the static weight recuperation of the rapid two-stage stream entering the diffuser. Tests affirmed that like in an ordinary transcritical R744 framework with extension valve, the high-side weight control coordinated into the ejector could be used to expand the framework execution. Numerical reproduction results helped recognizing this essential pattern. Because of troubles in the ejector throat weight estimations, a more useful execution metric was acquainted in place with evaluate general ejector efficiencies. As indicated by this definition, the model ejector had the capacity recoup up to 14.5% of the throttling misfortunes. Matthew Birnie, et al. [5] An ejector refrigeration framework using water as a refrigerant is displayed in this report. Waste hotness from the fumes of a 11hp air cooled inside burning motor is supplied to a heater to bubble fluid water to a soaked vapor. This motor is joined with a All rights reserved by www.ijsrd.com 447

generator for which a custom burden bank has been made to give a variable load on the motor. The vapor then enters a meeting wandering spout called an ejector, quickening the vapor to supersonic paces. The mix of the kettle ejector stage utilizes this motor vitality to supply the important packing that the compressor in a run of the mill vapor layering cycle gives. Utilizing this strategy a volume will be cooled to 13 c in an encompassing temperature of 39 c without extra vitality necessities, as the hotness from the fumes is ordinarily disposed of to the air. A Mat lab reproduction was composed to focus the state in the ejector and each one hotness exchanger. Utilizing this recreation the important measurements of each one hotness exchanger were resolve. L. Kairouani, et al. [6] In this study, an enhanced cooling cycle for a routine multi-evaporators basic squeezing framework using ejector for vapor pre-compression is examined. The ejector-improved refrigeration cycle comprises of multi-evaporators that work at diverse presbeyond any doubt and temperature levels. An onedimensional scientific model of the ejector was created utilizing the mathematical statements legislating the stream and thermodynamics focused around the steady territory ejector stream model. The model incorporates impacts of rubbing at the steady territory blending chamber. The vitality productivity and the execution qualities of the novel cycle are hypothetically explored. The correlation between the novel and routine framework was made under the same working conditions. Additionally, an examination of the framework exhibitions with environment inviting refrigerants (R290, R600a, R717, R134a, R152a, and R141b) is made. The hypothetical results demonstrate that the COP of the novel cycle is superior to the customary system. V.O. Petrenko, et al. [7] In this paper an imaginative micro-trigeneration framework made out of a cogeneration framework furthermore a course refrigeration cycle is proposed. The cogeneration framework is a joined together hotness furthermore control framework for power era and hotness creation. The course refrigeration cycle is the mixture of a Co2mechanical clamping refrigerating machine (MCRM), fueled by created power, and an ejector cooling machine (ECM), determined by waste high temperature and utilizing refrigerant R600. Impact of the cycle working conditions on ejector and ejector cycle exhibitions is concentrated on. Ideal geometry of the ejector and execution attributes of ECM are dead set at extensive variety of the working conditions. The paper additionally depicts a hypothetical dissection of the Co2sub-basic cycle and demonstrates the impact of the MCRM dissipating temperature on the course framework execution. The acquired information give fundamental data to outline a little scale course framework with cooling limit of 10 kw for application in micro-trigeneration frameworks. Zine Aidoun, et al. [8] An outline system for basic ejector refrigeration frameworks of fixed cooling limit working with settled temperatures of the external fluids entering the generator, the condenser and the evaporator is displayed and requested a specific synthesis of these four parameters. The results make the presence of ideal qualities for the refrigerant weight in the generator (PG) and the temperature contrast in the hotness exchangers (DT) which minimize the aggregate warm conductance of the framework. These ideal qualities of pg and especially intriguing since they yield high values for the coefficient of execution and the exergetic effectiveness of the framework. They have been dead set for four refrigerants (R134a, R152a, R290, and R600a). A goal capacity, which to a first close estimation is corresponding to the result of the capital and operational expenses, is characterized and used to think about the execution of the system with these refrigerants. Fang Liu, et al. [9] This paper exhibits a technique for deciding inside ejector segment efficiencies utilizing a twostage stream ejector model. The measured execution information outside to the ejector in conjunction with the ejector model were utilized to focus the isentropic efficiencies of the intention and suction spouts, and the effectiveness of blending area. It was discovered that ejector segment efficiencies fluctuate with ejector geometries and working conditions, which are not the same as the steady efficiencies expected by past scientists. The efficiencies of the controllable ejector thought process spout, suction spout and blending segment range from 0.50 to 0.93, from 0.37 to 0.90, and 0.50 to 1.00, separately, in Co2refrig-eration cycles under diverse working conditions. Observational connections were made and joined into a Co2air molding framework model to gauge ejector part efficiencies at distinctive ejector geometries and working conditions. Ming Ma, et al. [10] This paper exhibits another ejector improved vapor layering refrigeration cycle operating with the refrigerant R32. In this cycle, an ejector with two suction bays is utilized to recuperate the extension process misfortunes of the cycle. The hypothetical model for the developed cycle is built and the execution of this cycle utilizing refrigerant R32 is examined. Moreover, the execution correlations of the created cycle, essential vapor clamping refrigeration cycle and traditional ejector extension refrigeration cycle have additionally been completed. The hypothetical study demonstrates that the created cycle gives a higher cooling (warming) limit and a higher coefficient of execution. The recently created cycle could make a commitment for the application of refrigerant R32 in refrigeration system. M. Yari, et al. [11] As of late, in refrigeration industry the utilization of productive double evaporator refrigeration frameworks has been gave careful consideration. These frameworks sound much all the more intriguing when they are a mixture of various types of ordinary refrigeration frameworks. In this paper three thermally determined chillers consisting of ingestion refrigeration and ejectorextension transcritical course Co2 cycles are proposed what's more researched thermodynamically. The frameworks are called "hybrid double evaporator" cycles. The stomach muscle sorption cycle in the frameworks is either the single-impact or twofold impact arrangement stream or twofold impact parallel-stream cycle for each of which a sunlight based authority is considered to supply the obliged high temperature in their generator. The exhibitions of cross breed double evaporator frameworks are examined and advanced, utilizing the Engineering Equation Solver and applying the standards of protection of mass and vitality too as the exergy equalization to every segment of every framework. Results demonstrate that brushing the twofold impact parallel ingestion refrigeration framework with All rights reserved by www.ijsrd.com 448

ejector-extension framework gives the most astounding coefficient of execution among alternate arrangements. In any case, a blend of single-impact retention refrigeration framework with ejector-extension cycle may be favored because of its less multifaceted nature and sensible exergy effectiveness. Comes about additionally uncover that at ideal generator temperature of 72.92 C. the coefficient of execution and exergy effectiveness of half and half double evaporator with single-impact assimilation are 1.182 and 0.2564, individually. What's more, it is watched that expanding the cooling limit proportion from 1 to 6 results in expansions of the coefficient of execution and exergy effectiveness of designs by up to 36.32% and 11.5% individually. A. B. KASAEIAN, et al. [12] In this study, another model of a sunlight based joined ejector-vapor layering refrigeration framework has been considered. The framework is outfitted with an inside hotness exchanger to upgrade the execution of the cycle. The impacts of working liquid and working conditions on the framework execution including COP, entrainment degree (ω), packing degree (rp) and exergy proficiency were examined. Some meeting expectations liquids proposed are: R114, R141b, R123, R245fa, R600a, R365mfc, R1234ze and R1234ze. The results demonstrate that R114 and R1234ze yield the most astounding COP and exergy productivity emulated by R123, R245fa, R365mfc, R141b, R152a and R600a. It is recognized that the COP estimation of the new sunlight based ejector-vapor squeezing refrigeration cycle is higher than that of the routine ejector cycle with R1234ze for all working conditions. This paper likewise exhibits that R1234ze will be a suitable refrigerant in the sunlight based joined together ejector-vapor squeezing refrigeration framework, because of its ecological amicable properties and better execution. Adriano Milazzo, et al. [13] Ejector refrigeration has been learned at DIEF (Dipartimento di Ingegneria Industriale Firenze) since the '90s. Utilization of ecologically sheltered liquids (steam) was tended to. A two-stage model with cooling limit 5 kw was upgraded and constructed. Later, the CRMC solution for the outline of the supersonic diffuser was centered. By a slow decrease of the liquid speed Further more a constant profile, the CRMC outline guarantees a diminishment of the typical stun that generally creates in the blending chamber. A second 40 kwf model was composed in 2010 for a mechanical accomplice (Frigel Firenze s.p.a.). The outline strategy utilized a thermodynamic code representing genuine gas conduct. This code gives a first outline of the blending chamber and diffuser as per the CRMC measure. It likewise gives an estimation of the grating misfortune along the diffuser. A correlation between distinctive working liquids was performed and brought about the determination of R245fa. A first outline of the ejector was fabricated in carbon fiber. The essential spout is mounted on a portable backing, so as to transform its pivotal position as for the blending chamber. As far as COP, first comes about were underneath the qualities anticipated by the reenactment code. In the interim a numerical reproduction was in advancement with FLUENT. From the first CFD results it was chosen that the diffuser throat must be moved forward from the essential spout retreat, keeping in mind the end goal to permit a complete blending between the essential and optional streams, and developed, the misfortunes experienced in the blending methodology being higher than anticipated and consequently the liquid thickness lower. This created a second ejector plan, which was fabricated and tried in 2012, demonstrating enhanced execution. These results recommended a third plan, with a further stretched diffuser, which has experienced a complete testing fight, permitting acceptance of the CFD results. The action performed till now proposes that ejector refrigeration plants have a powerful operation also might be effectively fabricated at generally minimal effort with off-the-rack parts, a part from the ejector itself, which however represent as little portion of the framework cost. Nonetheless, the COP is lower concerning retention refrigeration and henceforth needs significant change through definite thermodynamic and CFD plan enhancement. Suhas D Kshirsagar, et al. [14] The most recent advancements of the ejector refrigeration and joined together vapor packing ejector refrigeration frameworks are exhibited. Additionally their working conditions and the coefficients of execution, got by different researchers hypothetical and trial studies, are given. The criticalness of the working liquid in the execution of the framework is underlined in conjunction with the intercooler, which permits the utilization of two separate refrigerants at once in the plane and compressor subsystems. Looking proper refrigerants, some hypothetical and trial studies demonstrate the points of interest of utilizing R134a within these frameworks. Nonetheless, the utilization of hydrocarbon refrigerants like isobutene (R600a) is proposed as a decent choice, in spite of the fact that examination and some wellbeing systems need to be produced before applying these "nature friendly" refrigerant. Milan N. Sarevski, et al. [15] The paper describes the investigations of a novel R718 refrigeration cycle with single stage centrifugal compressor and two-phase ejector as a second stage compression device. The limitations of the R718 centrifugal stage pressure ratio, connected with small molecular mass of the water and high isentropic exponent, result on high impeller peripheral speed, high Mach number and high discharge temperature. Reynolds number is low and dimensions of the compressor stage are large. The complex thermal and flow phenomena inside two-phase ejector flow field are investigated and performance characteristics are estimated. Although efficiency of the concept of compression with hydraulic pump and two-phase ejectors is lower, the integration of two-phase ejectors in the R718 centrifugal unit results in low cost high capacity refrigeration system with high energy efficiency, competitive with traditional refrigeration systems by environmental, technical and economical reasons. Gourav Patel, et al. [16] Since long time, it has been perceived that coolers are the gadgets which work very nearly 365 days round the clock; consequently goal of vitality effectiveness change pulls in much. There are a few methods for enhancing the execution of a vapor clamping refrigeration cycle. Utilization of an ejector as extension gadget is one of the option way. The coming of new segment "Ejector" into refrigeration framework opened the new period of examination. The crucial segment, which chooses the compelling operation of the ejector extension refrigeration framework, is the ejector. Consequently, plan All rights reserved by www.ijsrd.com 449

of an ejector and investigates of its physical furthermore operational parameters have drawn uncommon consideration. The thermodynamic investigation of regular refrigerant (R 170) based vapor pressure refrigeration cycles is displayed in this article utilizing a steady weight blending ejector as a development gadget. Utilizing ejector as a development gadget, R 170 yields a greatest COP change of 24.12 percent. L. Garousi Farshi, et al. [17] Options to smelling ammonia/water absorption refrigeration cycles that have no requirement for cleansing incorporate smelling salts/lino3and alkali/nascn cycles. Like the other ingestion refrigeration cycles they have low coefficients of execution and exergy efficiencies at low generator temperatures. Joined together single impact cycles can diminish this issue. In these cycles the result development valve is supplanted with an ejector to take into consideration weight recuperation from the absorber and to upgrade blending of the frail result what's more refrigerant vapor from the evaporator. Reenactments are utilized to inspect the impact of different operating parameters on execution and the likelihood of crystallization in these cycles, and to analyze their exhibitions with single impact cycles. It is demonstrated that the joined together cycles have better performance than single impact ones at low generator temperatures. Cui Li, et al. [18] This paper displays a study on test and examination of variable region proportion ejector utilized within a multi-evaporator refrigeration framework (MERS). The trial apparatus and system are portrayed, and the entrainment and weight recuperation exhibitions of the variable ejector are measured at different operating and geometric conditions. The discriminating territory proportion is proposed as a marker of weight recuperation status; zone degrees more diminutive than the discriminating ones are obliged to verify that the framework works at vitality sparing mode. The examination results demonstrate that the entrainment degree, weight recuperation proportion what's more basic region proportion are firmly influenced by the essential weight and optional weight. More prominent entrainment degree might be gotten by expanding the auxiliary weight or diminishing essential weight. The inverse patterns are found for weight recuperation degree. In addition, the discriminating territory proportion differs incredibly with the operation condition, and could be anticipated by a linear fitting capacity of essential weight or a force work as far as optional weight. Armin Hafner, et al. [19] Supermarkets are commercial buildings with major energy consumption and relatively large contribution to direct emissions of greenhouse gases through refrigerant emissions of the refrigeration and air condition system. The majority of the European systems are applying HFC-404A as working fluid. Average annual leakage rates in Europe are in the range of 15-20% of the total charge. Worldwide the figure is about 30% and HCFC- 22 being the main refrigerant in use. Systems applying R- 744 as the only refrigerant have been developed and more than 2000 supermarkets exists in Europe, mainly in northern and mid-european countries. However, the systems still have large potential in development with respect to energy efficiency, heat recovery and cost efficiency. In this paper efficiencies and capacities for an R-744 supermarket system layout with ejectors and heat recovery have been compared for different climate conditions. First results show relevant improvements in system efficiency of up to 30%. M. Ramgopal, et al. [20] A two stage ejector suitable as an extension device in a Co2 based transcritical vapor clamping refrigeration framework is planned by developing the thermodynamic investigation and by interfacing with the framework recreation model. A uniting wandering spout is considered as essential spout of the ejector. For both configuration and parametric dissects, the efficiencies of spouts and diffuser have been thought to be 85% each. Further, gagged condition in the essential C-D spout and steady weight blending are expected. Parameters for example, COP, entrainment degree, weight lift and cooling limit were gotten for differing rationale bay and evaporator conditions. Intention delta is discovered to be vital for both execution and scope of attainable application. Results demonstrate a COP change of 21% contrasted with a proportionate ordinary CO 2 framework. A far reaching exergy investigation of the framework secures the defense of replacement of throttle valve by ejector in such system. IV. CONCLUSION On the basis of literature survey it has been found that an ejector refrigeration system is suitable for experimental studies, since it require ejector a simple component that significantly improves system performance. An ejector expansion cycle enhances the performance of a conventional CO2 cycle in a transcritical process for a gas cooler temperature above ambient temperature. A constant pressure-mixing-zone model for the ejector has been used to analyze the ejector thermodynamic cycle analysis. The influence of pressure drop at the ejector nozzle and gas cooler pressure on the performances of the ejector cycle is discussed using the model. From the theoretical results, it can be concluded that the NERC can improve the cycle COP and volumetric cooling capacity or heating capacity by using a two-stage suction ejector. REFERENCES [1] Jianlin Yu, et al. A new ejector refrigeration system with an additional jet pump, Institute of Refrigeration and Cryogenics Engineering, Applied Thermal Engineering 26 (2006) 312 319. [2] Daqing Li, et al. Transcritical CO2 refrigeration cycle with ejector-expansion device, School of Mechanical Engineering, Purdue University, International Journal of Refrigeration 28 (2005) 766 773. [3] Hua Zhao, et al. Application of an ejector in autocascade refrigeration cycle for the performance improvement, School of Energy and Power Engineering, international journal of refrigeration 31 (2008) 279 286. [4] Stefan Elbel, et al. Experimental validation of a prototype ejector designed to reduce throttling losses encountered in transcritical R744 system operation, Department of Mechanical Science and Engineering, international journal of refrigeration 31(2008)411 422 All rights reserved by www.ijsrd.com 450

[5] Matthew Birnie, et al. Ejector Refrigeration System, Design Advisor Prof. Gregory Kowalski. [6] L. Kairouani, et al. Use of ejectors in a multievaporator refrigeration system for performance enhancement, Unite de Recherche Energe tique et Environnement, international journal of refrigeration 32(2009)1173 1185. [7] V.O. Petrenko, et al. Design-theoretical study of cascade CO2 sub-critical mechanical compression/butane ejector cooling cycle, anew Energy Center, Department of Mechanical Engineering, international journal of refrigeration 34 (2011)1649-1656 [8] Abdelouahid Dahmani, et al. Optimum design of ejector refrigeration systems with environmentally benign fluids, Génie Mécanique, Université de Sherbrooke, Sherbrooke, QC J1K2R1, International Journal of Thermal Sciences 50 (2011) 1562-1572 [9] Fang Liu, et al. Study of ejector efficiencies in refrigeration cycles, School of Mechanical Engineering, Applied Thermal Engineering 52 (2013) 360-370. [10] Ming Ma, et al. Theoretical study on a novel R32 refrigeration cycle with a two-stage suction ejector, Xi an Jiaotong University, international journal of refrigeration 36 ( 2013) 166-172. [11] M. Yari, et al. Simulation study of the combination of absorption refrigeration and ejector-expansion systems, Faculty of Engineering, University of Mohaghegh, Renewable Energy 60 (2013) 370-381. [12] A. B. KASAEIAN, et al. performance analysis of solar combined ejector-vapor compression cycle using environmental friendly refrigerants, Faculty of New Science and Technologies, University of Tehran, Iran, IIUM Engineering Journal, Vol. 14, No. 1, 2013. [13] Adriano Milazzo, et al. Theoretical and experimental activity on Ejector Refrigeration, Dipartimento di Ingegneria Industriale, Energy Procedia 45 ( 2014 ) 1245 1254. [14] Suhas D Kshirsagar,et al. Combined Vapour Compression-Ejector Refrigeration System: A Review, M.tech student, Department of Mechanical engineering, Govt college of engineering, Amravati, Volume 6, Issue 1 (February 2013), PP. 41-52. [15] Milan N.Sarevski, et al. Preliminary study of a novel R718 refrigeration cycle with single stage centrifugal compressor and two-phase ejector, Faculty of Mechanical Engineering, University, international journal of refrigeration 40 (2014) 435-449 [16] Gourav Patel, et al. Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant, Mechanical Engineering Department, IET DAVV Indore, India, International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014. [17] L. Garousi Farshi, et al. Thermodynamic analysis and comparison of combined ejector absorption and single effect absorption refrigeration systems, Faculty of Mechanical Engineering, University of Tabriz, Tabriz, Iran, Applied Energy 133 (2014) 335 346. [18] Cui Li, et al. Analysis on performance characteristics of ejector with variable area-ratio for multi-evaporator refrigeration system based on experimental data, School of Energy and Power Engineering, Applied Thermal Engineering 68 (2014) 125-132. [19] Armin Hafner, et al. Multi-ejector concept for R- 744 supermarket Refrigeration, SINTEF Energy Research, 7465 Trondheim, Norway, interna tional j ourna l of refrigeration 43 ( 2014) 1-13. [20] M. Ramgopal, et al. Thermodynamic design and simulation of a CO2 based transcritical vapour compression refrigeration system with an ejector, Department of Mechanical Engineering, Indian Institute of Technology Kharagpur, International Journal of Refrigeration. All rights reserved by www.ijsrd.com 451