CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

Similar documents
MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3

MHWW-18-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 18,000 BTUH. Rev. 1.3

MHWW-12-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 12,000 BTUH. Rev. 1.3

MF Product Specifications

MV Product Specifications

Product Specifications

YORK PASSIVE CHILLED BEAMS ENGINEERING GUIDE

Air Conditioners 4AC13

EFFICIENT 13 SEER 3 PHASE AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Nominal Btu/hr. Min. Circuit Ampacity 18.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Air Conditioners 4AC14L

BLOWER COILS. 2 THRU 5 TONS SPLIT SYSTEM EBP Export Series FEATURES

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition

BLOWER COILS. 1½ THRU 5 TONS SPLIT SYSTEM EBP / EBX / EBXX Series FEATURES EBP MODEL FEATURES EBX/EBXXMODELFEATURES

CFFWA-XX-1-U. Rev. 1.2

Performance Rated for Water Loop Applications Cooling capacities : entering air conditions of 80.6ºF db / 66.2º F wb, 86ºF entering water temperature

Multi-Room Ductless heat-pump systems Submittal Data: MULTI18HP230V1CO 18,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date

Price High Performance Horizontal Fan Coil Units

K. All mechanical rooms shall be designed with a minimum 3-1/2 dropped floor.

Multi-Room Ductless heat-pump systems Submittal Data: MULTI24HP230V1CO 24,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date

ASPT Series. Multi-Position, Multi-Speed, ECM-Based Air Handler with Internal TXV 1½ to 5 Tons. Contents. Product Features

DAT Commercial ELECTRIC AIR HANDLERS FOR 7½ & 10-TON SPLIT SYSTEMS

YORK BULKHEAD MOUNTED CHILLED BEAMS ENGINEERING GUIDE

Non-Ducted Indoor Compressor Type DC Inverter Driven Rotary Rated Cooling Capacity BTUH RLA 10.8

Product Catalog. Odyssey Split System Heat Pumps R-22 Dry Charge 7½ - 20 Ton, 60 Hz SSP-PRC027-EN. June 2012

ELFOSpace WALL3. Technical Bulletin. Water terminal unit for indoor installation, wall-mounted CFW RANGE. DC Brushless Motor

CPRT SERIES 13 SEER PRODUCT SPECIFICATIONS. Split System Heat Pump. 2 to 5 Ton

BLOWER COILS COMMERCIAL

ASPT Series. Multi-Position, Multi-Speed, ECM-Based Air Handler with Internal TXV 1½ to 5 Tons. Contents. Product Features

Air Cooled Condensing Units - Technical Catalog. Featuring Copeland TM Compressors 404A and 507 Refrigerants

Product Data. 38AUZ Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6to12.5NominalTons FEATURES/BENEFITS. Factory-installed options (FIOPs)

Air Cooled Condensing Units - Technical Catalog. Featuring Bitzer TM Compressors 404A and 507 Refrigerants

1. ARI 410 Standard for chilled water, hot water and steam coils. 2. ARI 430 Central Station Air Handling Units

Fiberglass Cooling Towers

EBP. Product Specifications. EBP Fan Coils 2 THRU 5 TONS SPLIT SYSTEM FEATURES

DVPEC. Multi-Position, Variable-Speed air handler. Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons

Product Data. 38AUZ / 38AUD 60 Hz Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6to20NominalTons FEATURES / BENEFITS

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

Air Conditioners. Technical Data. Pair application EEDEN RXS-J

SECTION FUEL-FIRED UNIT HEATERS

Cabinet air leakage less than 2.0% at 1.0 inch H₂O when cooling and heat pump applications.

FXV. Closed Circuit Cooling Towers. Closed Circuit Cooling Towers. Product Detail FXV - C 1. Engineering Data FXV Models... C2

B. System Design and Performance Requirements

XC15. DAVE LENNOX SIGNATURE COLLECTION R-410A - SilentComfort Technology. SEER up to to 5 Tons Cooling Capacity - 22,000 to 56,000 Btuh

Pioneer Forced Draft Cooling Tower Specifications

ARUF Series. Multi-Position, Multi-speed Air Handler with PSC Motor 1½ to 5 Tons. Contents. Product Features

ENGINEERING DATA HOT WATER CAPACITIES, CALCULATIONS AND CORRECTION FACTORS

Product Catalog Split System Air Conditioners Odyssey

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

Lenntech. Tel Fax / Marley MS Cooling Tower /

DCG Commercial. 7½ - 12½ Ton Packaged Gas/ Electric Up to 11.3 EER / 80% AFUE

Page of ENGINEERING DATA - HOT WATER CAPACITIES, CALCULATIONS AND CORRECTION FACTORS Use the following two tables to determine

Air Conditioning. Technical Data EEDEN RXS-L

Central Station Air Handler Specification

TECHNICAL SUPPORT MANUAL Fan Coils FSM2X, FSM4X

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT

Pioneer Forced Draft Cooling Tower Specifications

Pump Specifications 450 Series 1/2 hp Submersible Sump Pump

ARUF Series. Multi-Position, Multi-speed Air Handler with PSC Motor 1½ to 5 Tons. Contents. Product Features

Design & Construction Standards, Revised January

The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1.

BLOWER COILS. 2 THRU 5 TONS SPLIT SYSTEM EBW 50 Hz Series FEATURES Sept. 2502

SECTION AIR COILS

Air Conditioners Technical Data

Price Fan Powered Terminal Units

T-Series SPLIT SYSTEM UNITS TSA R-410A - 60 HZ

Student Services & Classroom Addition

Split System Air Conditioner GSC13: 3-5 Tons GSC10: 7½ & 10 Tons

Split System. GSC13: 3-5 Tons GSC10: 7½ & 10 Tons. Air Conditioner

KCL-Line Air Cooled Condensers

WT Model Water-to-Water Heat Pump

AIR CONDTIONERS XC16. ELITE Series R-410A - Two-Stage Compressor - SilentComfort Technology

Large University Central Chiller Plant Design Considerations

SECTION SECONDARY UNIT SUBSTATIONS

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

PRICE AW-D PACKAGED OUTDOOR HEATING AND COOLING MAKE-UP AIR UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

SECTION AIR TERMINAL UNITS

SECTION HEAT TRACING FOR PLUMBING PIPING

C o u n t y o f F a i r f a x, V i r g i n i a

DIVISION 33 UTILITIES SECTION PACKAGED SEWAGE GRINDER PUMPING UNITS

FXT Open Cooling Towers... B46. Benefits... B48. Construction Details... B49. Custom Features and Options... B50. Accessories...

Attachment 1: RAE Corporation Technical Specification

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

SECTION Inline ULTRASONIC FLOW METERS

UNDP / PAPP OFFICE BUILDING RAMALLAH HVAC WORKS

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC

Split. Air Conditioning Technical Data RXM-M9

MINNESOTA STATE SECTION ADVERTISEMENT FOR BIDS

Unit Coolers SKB. 4 kw 30,5 kw.

2015 International Mechanical Code Errata (Portions of text and tables not shown are unaffected by the errata)

Cabinet Features Heavy-gauge, galvanizedsteel. powder-paint finish Full perimeter rail Sloped drain pan Easy to service

Water Source Heat Pump Unit Product Line WSHP

Price Active & Passive Beams Division 23 Heating, Ventilating, and Air Conditioning Section Chilled Beams Section Induction Units

technical data air conditioning systems RKS-F2V1B Split Sky Air

AVPTC. Multi-Position, Variable-Speed, ECM-Based Air Handler with Internal TXV ComfortNet Compatible 1½ to 5 Tons. Contents.

The following document can be provided to an Engineer, Contractor, or Owner to allow them to

Transcription:

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH Rev. 1.3

HVAC Guide Specifications Chilled and Hot Water Universal Mount Fan Coil 2-Pipe Nominal Size: 60,000 BTUH Multiaqua Model Number: CFFWA-20-1-U Part 1-General 1.01 System Description Multiaqua Chilled Water Fan Coils are manufactured with galvanized steel and high impact molded polymers. 1.02 Quality Assurance A. Certified in accordance with U.L. Standard 95, latest version (U.S.A.) B. Manufactured in a facility registered to ISO 9002, Manufacturing Quality Standard. C. Fully load tested at the factory. D. Damage resistant packaging. 1.03 Delivery, Storage and Handling A. Packaged and readied for shipment from the factory. B. Controls shall be capable of withstanding 150 F storage temperatures in the control compartment. C. Stored and handled per manufacturer s recommendations. Part 2-Product 2.01 Equipment A. General: 1. Unit shall be a factory assembled and tested chilled and hot water fan coil. 2. Shall be assembled with high quality. 3. Contained with the unit shall be all factory wiring, piping, associated controls and special accessories required prior to start up. B. Unit Cabinet: 1. Composed of galvanized steel with baked polyester powder and high impact polymers. 2. Shall be internally insulated to ensure quiet operation. C. Fan Motors: 1. Shall be available in 208/230-1-50/60 VAC. 2. Fan motors shall be three speed, direct drive, and PSC type. 3. Totally enclosed. 4. Internal overload protected. 5. Unit shall contain a swing motor to modulate the discharge air. D. Blower Wheels: 1. Blower wheels are tangential and dynamically balanced. E. Water Coil: 1. Manufactured with water coils containing 3/8 copper tubing mechanically bonded to aluminum fins. 2. Coils shall be factory tested to 350 psig. 3. Maximum inlet water temperature 180 F F. Drain Pan: 1. All drain pans shall be coated on both the interior and exterior with baked polyester powder to resist corrosion. 2. The exterior of all drain pans shall be insulated with closed cell to prevent condensation. 3. Pans shall contain drain tubing that is accessible from the back, bottom and side of the unit. G. Filters: 1. Unit shall contain 65% washable filters. 2

Part 3-Controls and Safeties 3.01 Controls A. Fan coils shall be completely factory wired and tested. B. Unit shall include a terminal block that is capable of incorporating a 24 VAC thermostat. C. Controls shall be capable of incorporating an optional hard-wired thermostat. 3.02 Safeties: A. Fan coil shall contain a non reusable fuse on the secondary voltage side of the transformer. Part 4-Operating Characteristics: 4.01 Electrical Requirements A. Electrical shall include a terminal block. B. Electrical power supply shall be rated to withstand 120 F operating ambient temperatures. Part 5- Definitions: 5.01 Abbreviations A. CFM = Cubic Feet per Minute B. DB = Dry Bulb Temperature C. EWT = Entering Water Temperature D. GPM = US Gallons Per Minute E. MBH = BTU X 1000 F. SC = Sensible Cooling G. TC = Total Cooling = Sensible + Latent H. WB = Wet Bulb Temperature I. WPD = Water Pressure Drop in feet of head J. db = Decibel Level K. m = Meter L. In = Inches M. FPI = Fins per Inch N. OD = Outside Diameter O. ID = Inside Diameter P. MCA = Minimum Circuit Amps Q. MOP = Maximum Over current Protection R. LBS = Pounds U.S. 5.02 Measurements A. All measurements with regard to length, width, and height shall be in inches. 3

208/230-1-50/60 CFFWA-20-1-U Product Specifications Physical Data Model Number Height Length Depth Weight (lbs.) Cooling Rows FPI Water Inlet Water Outlet Drain CFFWA-20-1-U 25.27 75.78 9.01 163.14 4-14 1 1 1/2 Electrical Data Model Number High Speed CFM Volts/ Phase/ Hertz Fan Motor HP Fan Motor Full Load Ampacity Fuse or HACR Circuit Breaker Per Circuit MCA MOP CFFWA-20-1-U 1335 1/8 & 1/8 3.18 3.59 5 4

CFFWA-20-1-U Chilled Water Performance Data CFFWA-20-1-U COOLING CAPACITIES CFM EWT GPM ENTERING AIR TEMPERATURE (F) ( F) 80 D.B. / 67 W.B. TC 55402 13.0 SC 37921 WPD 12.6 TC 58147 15.0 SC 39083 1335 42 WPD 16.6 TC 60225 17.0 SC 39993 WPD 21.0 TC 61816 19.0 SC 40686 WPD 25.9 *High Speed CFFWA-20-1-U COOLING CAPACITIES CFM EWT GPM ENTERING AIR TEMPERATURE (F) ( F) 80 D.B. / 67 W.B. TC 49650 13.0 SC 35548 WPD 12.6 TC 52083 15.0 SC 36553 1335 45 WPD 16.5 TC 53723 17.0 SC 37266 WPD 20.9 TC 55122 19.0 SC 37835 WPD 25.8 *High Speed Recommended minimum flow rate for this unit at > 2 fps is 6.75 gpm Recommended maximum flow rate for this unit at < 6 fps is 19.75 gpm 5

CFFWA-20-1-U Hot Water Performance Data This heating performance data is at dry bulb temperature indicated / wet bulb temperature not considered CFFWA-20-01-U HOT WATER CAPACITIES ENTERING NOMINAL ENTERING WATER TEMPERATURE ( F) GPM WPD AIR ( F) CFM 90 100 110 120 130 140 150 160 170 180 50 1335 13.0 11.9 46710 58470 70267 82094 93945 105816 117700 129596 141499 153408 15.0 15.6 47467 59407 71382 83385 95409 107450 119505 131570 143641 155718 17.0 19.7 48053 60133 72244 84381 96538 108710 120895 133089 145289 157494 19.0 24.3 48520 60710 72930 85173 97434 109710 121997 134293 146595 158901 CFFWA-20-01-U HOT WATER CAPACITIES ENTERING NOMINAL ENTERING WATER TEMPERATURE ( F) GPM WPD AIR ( F) CFM 90 100 110 120 130 140 150 160 170 180 60 1335 13.0 11.9 35109 46841 58615 70421 82253 94107 105976 117859 129750 141649 15.0 15.5 35670 47585 59538 71521 83528 95554 107595 119647 131708 143776 17.0 19.7 36104 48161 60252 72370 84511 96669 108841 121024 133215 145411 19.0 24.3 36450 48619 60820 73046 85292 97555 109830 122115 134408 146706 CFFWA-20-01-U HOT WATER CAPACITIES ENTERING NOMINAL ENTERING WATER TEMPERATURE ( F) GPM WPD AIR ( F) CFM 90 100 110 120 130 140 150 160 170 180 70 1335 13.0 11.8 23498 35204 46954 58740 70554 82390 94246 106115 117995 129883 15.0 15.5 23864 35756 47687 59651 71640 83651 95679 107719 119769 131827 17.0 19.7 24149 36183 48254 60354 72479 84623 96783 108954 121135 133322 19.0 24.3 24375 36523 48704 60914 73145 85395 97658 109933 122217 134507 CFFWA-20-01-U HOT WATER CAPACITIES ENTERING NOMINAL ENTERING WATER TEMPERATURE ( F) GPM WPD AIR ( F) CFM 90 100 110 120 130 140 150 160 170 180 80 1335 13.0 11.8 11879 23561 35289 47055 58852 70674 82515 94372 106242 118121 15.0 15.5 12053 23922 35833 47778 59752 71749 83764 95793 107834 119884 17.0 19.6 12188 24201 36253 48337 60447 72578 84726 96888 109060 121240 19.0 24.2 12296 24424 36588 48782 60999 73237 85490 97755 110031 122314 Heating at ANSI/AHRI 440 with addendum 1, 6.3.2 Table 1 as follows: ENTERING AIR TEMPERATURE 70 F DB / 60 F WB GPM ENTERING WATER TEMPERATURE 140 F 13.0 83180 15.0 84475 17.0 85475 19.0 86269 6

CFFWA-20-1-U Sound Data MODEL # Fan Speed CFFWA-20-1-U db @ 1 m H 50 7

CFFWA-20-1-U Dimensional Drawing 8