Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

Similar documents
Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Overview Revised 11/17/2016

Stone and Masonry Veneer

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses. DD No

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Design Guide Revised 11/17/2016

Masonry Veneer - Chapter 6. Masonry Veneer Anchored Veneer

CONCRETE MASONRY VENEERS TEK 3-6C

Changes in the 2007 Supplement to the 2006 International Building Code That Affect Component Manufacturers

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

Individual Truss Marking Is it a Building Code Requirement?

CONNECTOR S T U D S H E A R. Design for Composite Structural Action STUD SHEAR CONNECTOR APPLICATION

Brick Masonry. Best Practices Guide

Earthquake Resistant Residential Design and Construction, Part 2

Wall bracing panel requirements

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

CONNECTOR B L O C K S H E A R. Design for Composite Structural Action BLOCK SHEAR CONNECTOR APPLICATION. Airspace

Building Division Informational Handout

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC)

2003 International Residential Building Code

Administrative Changes

Brick Veneer / Wood Stud Walls

ANALYTICAL MODELING OF IN PLANE SHEAR OF BRICK VENEER AND WOOD STUD WALLS

ALTERNATE DESIGN METHODOLOGY FOR UNREINFORCED MASONRY BUILDINGS

Contents. 1.1 Introduction 1

NCMA TEK RESIDENTIAL DETAILS FOR HIGH WIND AREAS. TEK 5-11 Details (2003)

Advanced Wind Mitigation Methodologies, Pt. 1- Internet Course (5th Edition)

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018

Version 2.1 IBS 2010 Special Resource Edition

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC)

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

WTCA 6300 Enterprise Lane Madison, WI / / (fax)

Long Span Truss Installation

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures

WALL SYSTEMS ( Ref: The Building Illustrated, Ching, Francis DK )

MASONRY ANCHORS AND CONNECTORS May 6, 2014

TER No Cultured Stone & ProStone Applications Over Continuous Insulation

R Code and Commentary for 2012 NC Residential Code final 03/06/13

APPENDIX A1 WIND AND SEISMIC BRACING GUIDELINE FOR ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT

POST FRAME BUILDING STANDARDS

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood, Plastics, and Composites (06) SECTION: Structural Panels ( )

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

PHOTO 1: View from Inside the Structure. Note the Rotation of the WSP, Failure at the Lower Leading Edge and Deformation of the Top Plate

Heel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017

Building Guide. Colorado Chapter of the International Conference of Building Officials. Building Guide

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

Residential Deck Safety, Construction and Repair. Juneau Permit Center, 4 th Floor Marine View Center,(907) February 2016

Pulaski County, Virginia Practical Wall Bracing

BUILDING CODE REQUIREMENTS FOR BRICK VENEER IN SEISMIC AREAS

PS 3000 Installation Manual Step-By-Step Procedures C.9. DOOR AND WINDOW OPENINGS C.9.1 PREPARE IN ADVANCE. C.9.2 VBUCK CONSTRUCTION.

Proposed Modification to the Florida Building Code

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Technical Notes 28 - Anchored Brick Veneer, Wood Frame Construction Rev August 2002

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing

Framing Methods Structural Components

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading

Accommodating Expansion of Brickwork

DIVISION 04 MASONRY. Section Title Number MASONRY Maintenance of Masonry Masonry Mortaring Masonry Accessories

ICC-ES Evaluation Report Reissued November 2014 This report is subject to renewal November 2016

TECHNICAL EVALUATION REPORT No. 27/2008/2060

Signage Code. H101.2 Signs exempt from permits. The following signs are exempt from the requirements to obtain a permit before erection:

Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems

Union County Vocational - Technical Schools Scotch Plains, New Jersey

PRODUCT: Structural Insulated Panels (SIP) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( )

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( )

Live Load Considerations for Truss Bottom Chords

Originally Issued: 01/01/2014 Revised: 03/15/2018 Valid Through: 01/31/2019

WALL CONSTRUCTION CHAPTER 6

assembly an open space between the roof and ceiling of a building attic balloon frame a joist constructed of steel with bars in the verticle web space

Lonsdale Building Inspections Department 415 Central Street W. PO Box 357 Lonsdale, MN (507) fax (507)

research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-2

NCMA TEK TEK 19-5A FLASHING DETAILS FOR CONCRETE MASONRY WALLS

Typical Deck Details. Shenandoah County, Virginia. Based on the 2012 International Residential Code

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS

A Simple Solution for Meeting

FACT SHEET #2 DECK INFORMATION

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: DIVERSIFOAM PRODUCTS EVALUATION SUBJECT:

CHIMNEYS AND FIREPLACES

August 31, Myrna Webber Managing Broker 201 West Springfield Ave., 11 th Floor P.O. Box 140 Champaign, IL

Typical Deck Details Based on the 2009 International Residential Code (Designed and Printed August 2010)

Post-Frame Construction and the International Building Code By Amanda Stauffer

ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section )

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: TRESPA NORTH AMERICA, LTD.

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Residential Wood Deck Design

WFCM 90 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

Building for Energy Efficiency Part 2 Advanced Framing Workshop. Objectives for this presentation...

WFCM 120 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

Technical Notes 43G - Brick Passive Solar Heating Systems - Part 7 - Details and Construction [Mar./Apr. 1981] (Reissued Sept.

Residential Patio Cover Specifications

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

Transcription:

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Released May 20, 2009 Updated March 9, 2011 Introduction: Wood frame structures with attached brick masonry veneer cladding are a common form of residential construction throughout the United States. In particular, this type of construction is used in Central and Southeastern regions with moderate seismic and/or high wind activity. Brick veneer cladding is appreciated for its pleasant appearance, excellent thermal performance, and ability to act as an approved weather covering. Typical residential brick veneer wall systems consist of an exterior brick masonry veneer wall and an interior wood frame wall (backup framing), separated by an air cavity and metal ties connecting the brick veneer cladding to the backup framing. The cavity between the brick veneer and backup wood frame provides drainage and acts as a thermal barrier. The brick veneer provides weather resistance. Together, this is known as a simple rain screen wall construction. No significant structural problems have been reported: (1) where brick veneer cladding was capable of supporting its own weight all the way down to the foundation, or (2) where it was supported by properly sized steel lintel angles and/or wood structural components at commonly sized window and door openings. However, supporting brick veneer cladding above larger openings, such as a two-car garage door, a large bay window and/or patio doors, represents more challenging conditions. In a typical brick veneer wall system, the wood framing is designed to carry all lateral and gravity loads, except for the self weight of the brick masonry. However, in reality, brick veneer cladding does carry a portion of lateral load due to its higher stiffness compared to the wood backup structure. These lateral loads from exterior masonry walls are transferred through the tie connections. Therefore, the properties of these connections play a key role in the overall behavior and performance of residential brick veneer wall construction. Issue: The use of brick veneer supported by metal plate connected wood trusses is not covered by the prescriptive methods of either the International Residential Code (IRC) or the design methods of the International Building Code (IBC). However, the code-compliant use of metal plate connected wood trusses to support brick veneer can be accomplished by both individual design and by adhering to the recommendations that follow. This Tech Note focuses on a common use of brick veneer with metal plate connected wood trusses. This involves a gable end at the transition from a wider section of a building to a narrower section. In this case, the truss typically bears on an exterior wall for part of the span and then clear spans the remaining distance. The brick veneer is supported by the exterior bearing for part of the span, but it requires some other support where the brick veneer extends past this bearing. Using the truss to provide this support may be necessary (see Figure 1). The concepts provided surrounding these brick veneer application issues can be applied to many different situations utilizing metal plate connected wood trusses. SBCA 6300 Enterprise Lane Madison, WI 53719 608/274-4849 608/274-3329 (fax) www.sbcindustry.com

Brick veneer supported by Structural Gable End Frame Structural Gable End Frame vertical web a) Brick veneer supported by foundation Brick veneer supported by Structural Gable End Frame Continuous truss support above the wall b) Brick veneer supported by foundation Illustration of brick veneer supported with metal plate connected wood trusses FIGURE 1 Historically, considerable damage has been reported to residential brick veneer exterior cladding, including cracking, relative displacement and collapse of veneer brick masonry under out-of-plane loading. This often results from strong wind and/or moderate earthquakes. Most of the reported failures were caused by out-of-plane lateral loads. However, several failures, including cracking and/or wall arching, were reported to be caused by inadequate anchorage of the steel lintels supporting the brick masonry, excessive deflections due to inadequate design of the steel lintel, poor mortar quality, tie corrosion and poor installation of the veneer tie. Key issues include: Out-of-plane wall damage occurs as brick veneer moves away from gable end frames and the wall below due to wind suction and/or seismic loading. This loading places a high demand on the attachment capacity of the ties. Errors during installation can affect long-term performance. This includes tie fastener pullout, failure of workers to embed ties into the mortar, poor bonding between ties and mortar, poor quality of mortar, and tie corrosion. Ties are installed improperly. This can include placement above or below the mortar joints due to the ties being installed before the brick laying process begins. o When misaligned, the ties have to be bent up or down in order to be embedded into the mortar joints. o Misalignment not only reduces embedment depth, but also reduces the effectiveness of the ties. This reduction is due to the wind suction force not acting parallel with the ties. Roof gable end trusses and wall attachment/connection details are inadequate for the steel shelf angle. SBCA Tech Notes Page 2

Recommendations: Metal plate connected wood trusses can effectively support brick masonry veneer walls as long as brick veneer is supported by a steel lintel angle that is properly designed, detailed and attached to the truss members. The steel lintel must be bolted to the structural gable truss vertical members as recommended in Figures 2 and 3. This detail may be used by the building designer as a template to achieve a codeconforming steel lintel connection. In addition, the lateral support of brick veneer should be provided by the ties and wood backing system, including proper restraint of the metal plate connected wood truss, to resist the lateral loads imposed on them (see Figures 2, 3 and 4). Illustration of brick veneer supported with metal plate connected wood trusses FIGURE 2 SBCA Tech Notes Page 3

Illustration of brick veneer supported with metal plate connected wood trusses utilizing a steel angle lintel: steel shelf angle connection detail FIGURE 3 SBCA Tech Notes Page 4

Steel shelf angle with vertical stops welded in the crook of the shelf angle for roof slopes exceeding 7/12 FIGURE 4 The ties must be capable of resisting tension and compression resulting from forces acting perpendicular to the truss plane (see Figure 5). Structural Gable End Frame vertical web Wood Structural Panel Sheathing Brick veneer anchors as specified by the Building Designer 90 1 Min. 1½ Min. 5/8 Min. 1 Air Space 8d common ring-shank nails min. (0.131 dia. x 2.5 length) Recommended detail for masonry brick veneer corrugated steel tie embedment FIGURE 5 SBCA Tech Notes Page 5

Brick veneer masonry should be designed and installed with vertical expansion joints spaced at a maximum of 24 feet on-center. The actual location of the vertical expansion joints in a structure depends on structural configuration, as well as the expected amount of horizontal movement. The expansion joint in residential construction is typically sized to be of a similar width as a mortar joint, usually between 3 / 8 inch (10 mm) and ½ inch (13 mm). In addition, vertical expansion joints should be considered at corners, offsets, openings, wall intersections and changes in wall height (see Figure 6). Recommended expansion joint location for brick veneer cladding supported with metal plate connected wood trusses through a steel lintel FIGURE 6 The truss manufacturer shall obtain the truss design criteria, connection details and related requirements (including information about brick veneer masonry) from the construction documents. All information shall be communicated to the truss designer. Since the design of metal plate connected wood trusses accounts only for gravity and environmental loads in the plane of the truss, lateral loads (i.e., wind and seismic) acting perpendicular to the face of a truss must be addressed by the building designer or Registered Design Professional. The building designer or Registered Design Professional, who understands the intended flow of loads for the entire building system, is responsible for accounting for those loads, designing the building stability bracing (including the entire truss roof system lateral restraint and diagonal bracing), and safely transferring those loads through the building and into the ground. SBCA Tech Notes Page 6

Appendix Background & Analysis Prescriptive installation requirements for supporting brick veneer with wood frame structures are specified in the 2006 IRC with limitations. Supporting brick veneer can include steel angles bolted to wall framing or steel angles supported by beefed up rafters. A movement joint is required to be installed between veneers supported by foundation and veneers supported by wood or steel. Additional prescriptive installation requirements are specified in the 2005 Masonry Standards Joint Committee Code (MSJC) and the 2005 Brick Industry Association (BIA) Technical Notes 28, 31B, 18A, and 44B. According to 2006 IRC, brick veneer masonry can be supported by wood framing when observing these stated limitations: R703.7.2 Exterior veneer support. Except in Seismic Design Categories D0, D1 and D2, exterior masonry veneers having an installed weight of 40 pounds per square foot (195 kg/m2) or less shall be permitted to be supported on wood or cold-formed steel construction. When masonry veneer supported by wood or coldformed steel construction adjoins masonry veneer supported by the foundation, there shall be a movement joint between the veneer supported by the wood or cold-formed steel construction and the veneer supported by the foundation. The wood or cold-formed steel construction supporting the masonry veneer shall be designed to limit the deflection to 1/600 of the span for the supporting members. The design of the wood or cold-formed steel construction shall consider the weight of the veneer and any other loads. R703.7.2.1 Support by steel angle. A minimum 6 inches by 4 inches by 5/16 inch (152 mm by 102 mm by 8 mm) steel angle, with the long leg placed vertically, shall be anchored to double 2 inches by 4 inches (51 mm by 102 mm) wood studs at a maximum on-center spacing of 16 inches (406 mm). Anchorage of the steel angle at every double stud spacing shall be a minimum of two 7/16 inch (11 mm) diameter by 4 inch (102 mm) lag screws. The steel angle shall have a minimum clearance to underlying construction of 1/16 inch (2 mm). A minimum of two-thirds the width of the masonry veneer thickness shall bear on the steel angle. Flashing and weep holes shall be located in the masonry veneer wythe in accordance with Figure R703.7.2.1. The maximum height of masonry veneer above the steel angle support shall be 12 feet, 8 inches (3861 mm). The air space separating the masonry veneer from the wood backing shall be in accordance with Sections R703.7.4 and R703.7.4.2. The method of support for the masonry veneer on wood construction shall be constructed in accordance with Figure R703.7.2.1. The maximum slope of the roof construction without stops shall be 7:12. Roof construction with slopes greater than 7:12 but not more than 12:12 shall have stops of a minimum 3 inch x 3 inch x 1/4 inch (76 mm x 76 mm x 6 mm) steel plate welded to the angle at 24 inches (610 mm) on center along the angle or as approved by the building official. R703.7.2.2 Support by roof construction. A steel angle shall be placed directly on top of the roof construction. The roof supporting construction for the steel angle shall consist of a minimum of three 2-inch by 6-inch (51mm by 152 mm) wood members. The wood member abutting the vertical wall stud construction shall be anchored with a minimum of three 5/8-inch (16 mm) diameter by 5-inch (127 mm) lag screws to every wood stud spacing. Each additional roof member shall be anchored by the use of two 10d nails at every wood stud spacing. A minimum of two-thirds the width of the masonry veneer thickness shall bear on the steel angle. Flashing and weep holes shall be located in the masonry veneer wythe in accordance with Figure R703.7.2.2. The maximum height of the masonry veneer above the steel angle support shall be 12 feet, 8 inches (3861 mm). The air space separating the masonry veneer from the wood backing shall be in accordance with Sections R703.7.4 and R703.7.4.2. The support for the masonry veneer on wood construction shall be constructed in accordance with Figure R703.7.2.2. The maximum slope of the roof construction without stops shall be 7:12. Roof construction with slopes greater than 7:12 but not more than 12:12 shall have stops of a minimum 3 inch x 3 inch x 1/4 inch (76 mm SBCA Tech Notes Page 7

x 76 mm x 6 mm) steel plate welded to the angle at 24 inches (610 mm) on center along the angle or as approved by the building official. However, the 2006 IRC includes no prescriptive provisions to specifically address an exterior brick veneer wall supported by metal plate connected wood trusses. IRC Requirements and Limitations Regarding Metal Plate Connected Wood Trusses: The IRC provides two details for attaching a steel angle to wood framing (Figures R703.7.2.1 and R703.7.2.2). In both details, there is an adjacent wood framed backup wall. The IRC does not address metal plate connected wood trusses supporting brick veneer masonry at all. For buildings with conventional construction that contain structural elements exceeding the limits in Section R301, or otherwise not conforming to this code, the IRC has provisions regarding designing these elements in accordance with accepted engineering practice. R301.1.3. Engineered design. When a building of otherwise conventional construction contains structural elements exceeding the limits of Section R301 or otherwise not conforming to this code, these elements shall be designed in accordance with accepted engineering practice. The extent of such design need only to demonstrate compliance of non-conventional elements with other applicable provisions and shall be compatible with the performance of the conventional framed systems. Engineered design in accordance with the International Building Code is permitted for all buildings and structures, and pars thereof, included in the scope of this code. Furthermore, a similar conceptual provision for structural components and/or assembly exceeding the limitation of conventional construction is addressed in Section 2308.1.1 of the 2006 IBC. 2308.1.1 Portions exceeding limitations of conventional construction. When portions of a building or otherwise conventional construction exceed the limits of Section 2308.2, these portions and the supporting load path shall be designed in accordance with accepted engineering practice and the provisions of this code. For the purpose of this section, the term portions shall mean parts of building containing volume and area such as room or a series of rooms. References: 1 American Forest & Paper Association (AF&PA). 2005 National Design Specification (NDS) for Wood Construction. AF&PA, 1111 19 th Street, NW, Suite 800, Washington, DC 20036 2 Masonry Standard Joint Committee (MSJC), Building Code requirements for Masonry Structures (ACI 530-05/ASCE 5-05/TMS 402-05) and Specifications for Masonry Structures (ACI 530.1-05/ASCE 6-05/TMS 602-05) 3 IRC. International Residential Code (2000/2003/2006 editions). International Code Council, Inc., Washington, DC 4 IBC. International Building Code (2000/2003/2006 editions). International Code Council, Inc., Washington, DC 5 ASCE, 2005. Minimum Design Loads for Buildings and Other Structures (ASCE 7-05), American Society of Civil Engineers, Reston, VA 6 Masonry Advisory council. Supporting Exterior brick veneer on Wood Construction 7 The Brick Industry Association. Technical Notes on Brick Construction 18A, 28 and 28A View all SBCA Tech Notes at www.sbcindustry.com/technotes.php SBCA Tech Notes Page 8