Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Similar documents
NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual

Huntsville Utilities Underground Residential Service Requirements

Section 2: Underground

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

Please check with your local inspection authority for any additional requirements before installation.

(Condensed from National Electric Code)

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

Demarcation Points. Example 1

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

Residential Electric Policy

PRIMARY LINE EXTENSION

Duke Energy Carolinas Distribution Construction Standards Reference Guide

COMMERCIAL CONDUIT RULES AND REGULATIONS

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

Electric Engineering Division RESIDENTIAL CONDUIT RULES AND REGULATION. S:\COO_ACM_US_Electric_Telecommunications\COO_ET_Engineering\Conduit Policies

Section 7: Specifications

UNDERGROUND SERVICES SECONDARY

TABLE OF CONTENTS. PUD SERVICE TERRITORY & CONTACTS... Page 1. NEW SERVICE QUESTIONNAIRE... Page 2. TRENCHING SECONDARY (120/240 volts)...

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE

1. Contractor shall obtain a valid electrical permit from the Town of Perinton.

CONDUITS AND FITTINGS

SALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL

Standard of Practice - Campus Electrical Distribution System

Electric Service Standards

Section 4 Underground Service

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

Specifications for Residential Underground Electric Service Installation

400 watt, high pressure sodium. Type C watt, high pressure sodium Collector Street Light Units

CHAPTER 11 CONDUITS AND FITTINGS

Commercial Electric Policy

Welcome to Douglas County PUD

An altered service that is moved, upgraded (ex., 200 to 400 amp) or changed to meet today's standards for electric service.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

16300 HIGH VOLTAGE DISTRIBUTION

ANY SPECIFICATION DRAWINGS OR DATED PRIOR TO SEPTEMBER 2015 WILL NOT BE HONORED.

CONSTRUCTION HANDBOOK Guidelines and Information for Members, Builders & Developers

OVERHEAD SERVICES - SECONDARY

Electric Service Requirements & Guidelines

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

GV 001 Equipment Bases and Enclosures General Information

Specifications for Electrical Underground Residential Distribution Systems

Post Office Box 500 Carson, WA Phone (509) Fax (509) Toll Free (800)

Contact Clark Public Utilities Construction Services department at (360) to initiate a request for service.

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

SECTION MEDIUM VOLTAGE ELECTRICAL DISTRUBUTION (ABOVE 600 VOLTS)

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy.

Electric Service Handbook

TEMPORARY FACILITIES

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

OVERHEAD SERVICE. Table of Contents - Section 400

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

Basic Service. This Section provides information regarding a. Introduction

SECTION GROUNDING AND BONDING

WIRING METHODS CHAPTER 38

DETAILED SCOPE OF WORK IN-STREAM TIDAL GENERATING PLANT TISEC COLLECTOR CIRCUITS DEVELOPMENT

SECTION GROUNDING

Specifications for Electrical Underground Distribution Systems from Overhead Transformation, Apartments & Condominiums

RESIDENTIAL QUICK REFERENCE

Merrimac Municipal Light Department. Commercial Developments Policy

Electric Service Handbook

PART 7 COMMUNICATIONS, LIGHTING, TRAFFIC CONTROL, POWER

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

UNDERGROUND SERVICE INDEX JUN 18 SECTION 3

For more information contact: Engineering Department (800) Ext RURAL RESIDENTIAL SERVICE INSTALLATION GUIDE.

CONTENTS. B. System Design and Performance Requirements

SECTION ELECTRICAL UTILITY SERVICES

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

Underground Service Requirements and Instructions

City of Santa Monica Building and Safety Division

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

Welcome to Douglas County PUD

Gas meter clearances and service installation requirements

OPERATING PROCEDURE NO. 310

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT NON-NETWORK SYSTEMS SECTION

Design Standard Conduit for Electrical Systems

Specifications for Residential Overhead Electric Service Installation

Student Services & Classroom Addition

STANDARDS AND SPECIFICATIONS CITY OF HURRICANE DESIGN AND INSTALLATION OF UNDERGROUND POWER DISTRIBUTION SYSTEMS BOOK NO.

METERING INSTALLATION

ELECTRIC DEPARTMENT CONSTRUCTION STANDARDS

NEC 2014 Code Changes

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

Member Service Electric Wiring Guidelines

SECTION GROUNDING AND BONDING

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Transcription:

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available upon O/D request) Trench Primary riser (3 phase) Primary switch pad (3 phase) Transformer pad (3 phase) Transformer pad with retaining wall (3 phase) Primary riser (1 phase) Primary switch pad (1 phase) Transformer pad (1 phase) Transformer pad with retaining wall (1 phase) Secondary riser (3 phase) Secondary riser (1 phase) Secondary and Service pull box Typical service from transformer pad Secondary and service cable rating... 8 2

Underground Residential Distribution (URD) General Discussion 1. To offset the extra installation cost for underground electrical service over cost of overhead service, the owner or developer (O/D) will be required to furnish and / or install a portion of the required facilities where underground is requested. 2. Easements must be provided and clearly indicated on subdivision plats and other property plans. Except for individual services, these easements designate reserved areas for construction and maintenance activities as necessary, and must remain accessible to personnel and equipment of Pulaski Electric System (PES). Trees, large shrubs, structures, or objects that impede access or cause damage to electrical facilities will not be allowed within easements or in proximity to them. 3. Electrical facilities will not be totally below ground. Items such as transformers, switching enclosures, and service pedestals will be pad or surface mounted for durability, easy access, and serviceability. These will be low profile, natural green color, and easy to shield. 4. Generally, single-phase underground cables with loop feed will by used. Switching enclosures will be used for multi-cable taps and as required to limit pulling runs. 5. Units with alternate heating and/or otherwise low usage may require a cash contribution for underground service. 6. Should a special request or change result in extra cost of construction, O/D must bear these extra costs. 7. Multi-family units such as apartments or condominiums may require pedestals for cluster mounting of meters, and these will be furnished by O/D to meet PES specifications. 3

8. Special arrangements for temporary service per agreement of PES must be at O/D s expense. 9. Progression of installations by O/D must allow for timely inspections by PES before backfilling or pouring concrete. This applies especially to conduits, crossings, pads, sleeves, pull boxes, etc. 10. A pull rope of ¼ (or larger) must be left in all conduits. 11. All material furnished and installed by O/D in completion of the project become property and under control of PES. However, PES will not be responsible for negligent acts of employees or agents of O/D. 12. Descriptions and drawings provide guidelines for construction. O/D or Consumer indicates Owner or Developer. EU, Utility, or PES indicates Pulaski Electric System. 4

Underground residential distribution (URD) Easements A continuous strip fifteen feet in width at front edge of lots on both sides of street shall be designated as electric utility easement, plus other shared 15ft easements along common lot lines as may be needed should front-to-back runs be required. Trenching and Excavation O/D shall perform all trenching, excavation, backfill, and compaction (including street crossings) as required by PES. O/D must obtain any permits required for crossings or other work on public or private property or right-of-way, and install warning tape (provided by PES at time of inspection). O/D must lay #4 SDBCu ground wire in bottom of every trench except for services. Conduits and foundations O/D shall furnish and install, to PES s satisfaction, all conduit and fittings, including stub-ups at riser poles, foundation pads, or sleeves, and at secondary pedestals or pull boxes. PES shall furnish and O/D shall install to PES s satisfaction conduit vents, pedestals, and pull boxes. O/D shall furnish and install to PES s satisfaction all materials for any concrete pads or structures required by PES for construction of the underground facilities. Pole Risers O/D shall furnish and install first ten feet of galvanized conduit past conduit vent (of specified diameter) for pole riser. PES will provide conduit vent to be installed by O/D. Remaining riser material will be furnished and installed by PES. Location of riser on pole must be followed per drawing to prevent over lapping of phone. Electrical Cables PES shall furnish and install all primary, secondary, and service cables, terminations, and accessories at pole risers, transformers, pedestals, and source side of meter bases. Metering O/D shall furnish and install meter base, and all conduits and supports required in the metering installation. PVC Conduit and Trench Primary cable to be at 48 depth: 3 diameter for one primary cable 3-3 diameter conduit for 3-phase primary Secondary cable to be at 36 depth: 3 diameter for 1-4/0 UG trip or 1-350 UG trip 5

Concrete Enclosed Duct At small stream or deep ditch crossings, pole risers, and at all locations at less than normal conduit depths, to extend 3 (three) feet beyond such crossing, PVC conduit must be concrete encased with minimum of three inches concrete cover according to construction drawings. Road crossings for primary cable must be concrete enclosed duct also, or galvanized metal conduit. Primary Cable 1/0 Aluminum 7 strand XLP, full cu. Conc. neut., overall PVC jacket, type URD, tree resistant, 15KV, 220 mil insulation. 750 Aluminum 60 strand, full cu. Conc. neut., overall PVC jacket, type URD, tree resistant, 15KV, 220 mil insulation. Primary cable to be furnished and installed by PES. Secondary and Service Cable 4/0 Aluminum 19 strand XLP with 2/0 aluminum 19 strand XLP neut., triplex, type USE, 600 volt 350 Aluminum 19 strand XLP with 4/0 aluminum 19 strand XLP neut., triplex, type USE, 600 volt Secondary cables to be furnished and installed by PES. Primary Connectors (LBT) 15kv load break elbow terminators, 200amp, dead-front, for bushing inserts, feed-thru junctions, and parking stands. To be furnished and installed by PES. Secondary transformer connectors (TSC) Dead-front flood seal for one hole aluminum compression plug lug, with sealing sleeves, for phase, and bare ku-bar conn. For neut., 4 place and 8 place (HOMAC FTU) for transformer threaded stud. To be furnished and installed by PES. Transformers (PMT) Low profile pad Mounted 7200-120/240 volt single phase, with bayonet expulsion, and backup current limiting fuse(where fault current dictates), in series, and with co-coordinated pressure relief device to prevent catastrophic failure, with two-way load bread feed through bushings and two parking stands. To be furnished and installed by PES. Primary switching enclosure (PSW) Low profile pad mounted 15kv, with three single-phase feed through junctions and six parking stands, 200 amp Continental Columbus CW- 360 (Typical) to be furnished and installed by PES. Secondary to service connectors (T Conn) Submersible PVC covered parallel connectors with sealing sleeves for one-hole AL compression lugs, 4 place and 6 place, HOMAC flood seal bus connector. To be furnished and installed by PES. 6

Secondary Pedestal Enclosure (SP) Fiberglass bell-shape covered enclosure for above ground secondary pedestal connectors, Blackburn SDF. Conduit Use schedule 80 PVC 3 for below grade at 36 or 48 depth, with 12 minimum separation vertically, and 12 minimum horizontally from other utilities. Use galvanized sweep elbow stub-ups (36 radius for primary). Surge Arresters MOV type elbow and riser arresters, 8.3kv MCOV Outdoor terminators, 200amp (OD Term) Heat shrink type with rain shields and one-hole AL compression lug. Warning Tape Red warning tape buried 12 below final grade in trench above electrical facilities. Provided by PES at time of passed inspection, to be install by O/D. Conduit Standoff Bracket for pole risers Alumaform 6CSO-18 with STK-3 strap. Furnished by O/D and install as per drawings. Termination Stub Compression pin connector with sleeve, Burndy Hyplug AYP. To be installed on multiple service applications Secondary to service pull box (SPB) Enclosure with flush mounted cover, Blackburn SDR2G Feed Through Enclosure (FTE) Primary enclosure for use at future transformer location, Kearney 653-0033 CTC with feed through junction (2-way) and 2 parking stands. Stub-outs for Future Conduit stub-outs for future primary, secondary, or service must extend five feet beyond pad, sleeve, pull box, etc., with ends sealed. Concrete Pad Poured reinforced concrete mounting pad with stub-outs for transformer, switching enclosure, or feed through enclosure, to be used where specified. Concrete Pad with retaining wall Concrete pad with retaining wall to be used on slope as required. 7

3-1c URD Cable Ampacities 2-25-81 Aluminum Conductor Concentric Bare Neutral In duct in earth (Applies for PVC elbow stub-outs) (Based on 75% L.F. in 25deg C) AMPS Size Full N. 1/3 N. #2 146 --- 1/0 180 --- 2/0 200 --- 4/0 250 250 350 kcmil 325 330 500 kcmil 390 403 750 kcmil 469 495 1000 kcmil 528 563 Ref.: 2-25-81 Curve sheet & IEEE Table 9 8