EXPERMENTAL STUDY ON FLOW AND THERMAL CHARACTERS OF CALCIUM CHLORIDE HYDRATE SLURRY

Similar documents
TO CONDUCT THE PERFORMANCE TEST ON CHILLER UNIT BY USING NANOFLUID COOLED CONDENSER

Keywords - Heat transfer, heat exchanger, wavy twisted tape, turbulent, pressure drop, friction factor, 1 P a g e

ISSN (ONLINE): , ISSN (PRINT):

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant

Effect of alumina nanoparticles in the fluid on heat transfer in double-pipe heat exchanger system

Numerical Study of Corrugation on Performance of Double Pipe Heat Exchanger

PERFORMANCE EVALUATION OF PARALLEL AND COUNTER FLOW HEAT EXCHANGER USING NANOFLUID

EXPERIMENTAL INVESTIGATION OF RELATIVE PERFORMANCE OF WATER BASED TiO 2 AND ZnO NANOFLUIDS IN A DOUBLE PIPE HEAT EXCHANGER

CFD Modelling and Analysis of Different Plate Heat Exchangers

Research Article. Kallalu Harika *, Tummala.Likhitha, Pulla Varsha Rani and R.Ramakanth. Abstract

Convective heat transfer and flow characteristics of Cu-water nanofluid

Performance Evaluation of Molten Salt Cavity Tubular Solar Central Receiver for Future Integration with Existing Power Plants in Iraq

Performance Improvement on Water-cooled Cold-Plate

Experimental Investigation on Melting Heat Transfer of Paraffin Wax-Al 2 O 3 Storage System

A Design of the Organic Rankine Cycle for the Low Temperature Waste Heat

An experimental investigation of cold storage in an encapsulated thermal storage tank

ANALYSIS AND CHARACTERIZATION OF METAL FOAM-FILLED DOUBLE-PIPE HEAT EXCHANGERS

Evaluation of heat available from calcium chloride desiccant hydration reaction for domestic heating in San Francisco, CA

Numerical Prediction of Thermodynamics and Heat Transfer Characteristics of Nano Fluid.

Analysis of Heat Transfer Coefficient of CuO/Water Nanofluid using Double Pipe Heat Exchanger

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER

Experimental Study on Phase Change Material based Thermal Energy Storage System

EHD-ASSISTED CONDENSATION OF REFRIGERANT R-134a ON TUBE BUNDLES

Effect of Twisted Tape Inserts On Heat Transfer in A Concentric Tube Heat Exchanger

The Experimental Study on Enhanged heat Transfer Performance in Plate Type Heat Exchanger

Improvement of Energy Efficiency using Porous Fins in heat Exchangers

Heat Exchanger Design for use in an Under Hood Shower

FLOW BEHAVIOR OF ERYTHRITOL SLURRY AS LATENT HEAT STORAGE MATERIAL FOR LOW LEVEL HEAT UTILIZATION

*Corresponding authors. Tel.: x415, address: (N. Zhu)

Performance Analysis of Shell and Tube Heat Exchanger Using Miscible System

SINGLE-PASS SHELL & TUBE HEAT EXCHANGER MANUAL-SAMPLE. CNAT Doc. No.:

NUMERICAL SIMULATION OF PCM INTERGRATED SOLAR COLLECTOR STORAGE WATER HEATER

SCHOOL OF COMPUTING, ENGINEERING AND MATHEMATICS SEMESTER 1 EXAMINATIONS 2015/2016 ME257. Fluid Dynamics

THERMAL PERFORMANCE OF MICROENCAPSULATED PHASE MATERIAL (MPCM) SLURRY IN A COAXIAL HEAT EXCHANGER. A Thesis KUN YU

DESIGN OF AN EXPERIMENTAL SET-UP TO DETERMINE THE INFLUENCE OF CORROSION ON HEAT TRANSFER

EXPERIMENT MODULE CHEMICAL ENGINEERING EDUCATION LABORATORY GAS GAS HEAT EXCHANGER (HXG)

Enlargement of englacial conduits in cold ice basic theory and some simple experiments

CFD Modelling of Finned-tube CO2 Gas Cooler for Refrigeration Systems

Numerical simulation analysis of flow and heat transfer of supercritical LNG in the IFV condenser

Heat transfer enhancement in fire tube boiler using hellically ribbed tubes

Experimental verification of a solar hot water heating system with a spiral-jacketed storage tank

Thermal Performances of U Shape Molten Salt Steam Generator

Effect of geometrical parameters on heat transfer and pressure drop characteristics of plate fin and tube heat exchangers

Validation of Deration of Heat Transfer Coefficient with Brine Usage

Pipe Flow Hydraulics

Scientific Journal Impact Factor: (ISRA), Impact Factor: [Son, 3(10): October, 2014] ISSN:

OPTIMIZATION OF PCM NUMBER IN HOT WATER TANK FOR THE APPLICATION OF SOLAR DRIVEN ADSORPTION CHILLER IN TROPICAL CLIMATE

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems

EXPERIMENTAL INVESTIGATION ON HEAT TRANSFER ENHANCEMENT BY USING POROUS TWISTED PLATE AS AN INSERT IN A FITTED TUBE

EXPERIMENTAL ANALYSIS OF HEAT AND MASS TRANSFER IN A PACKED BED. Suryapet , India, Warangal , India

Performance Evaluation of Solar Assisted Heat Pump Water Heating System

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Thermal Analysis and Modelling of Thermal Storage in Solar Water Heating Systems

Nuclear Power Plants Authority, 4 El-Nasr Avenue, Nasr City, P.O. Box 8191, Nasr City 11371, Cairo, Egypt

oe4625 Dredge Pumps and Slurry Transport Vaclav Matousek October 13, 2004

Partial Load Characteristics of the Supercritical CO2 Gas Turbine System for the Solar Thermal Power System with the Na-Al- CO2 Heat Exchanger

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Research on a Magnetic Refrigeration Cycle for Hydrogen Liquefaction

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS

1. To improve heat exchange between a gas & a liquid stream in a heat exchanger, it is decided to use fins. Correct the suitable option.

THE EFFECT OF USING SMALL CYLINDRICAL ALUMINUM PIECES AS A PACKING MATERIAL ON THE DOUBLE PIPE HEAT EXCHANGER PERFORMANCE

HEAT TRANSFER STUDY OF 3-D PRINTED AIR-COOLED HEAT SINKS

A COMPARATIVE STUDY OF HEAT EXCHANGER EFFECTIVENESS FOR DOUBLE HELICAL AND STRAIGHT CIRCULAR GEOMETRY

Effect of Corrugation Angle on Heat Transfer Studies of Viscous Fluids in Corrugated Plate Heat Exchangers

DECREASE THE OUTLET WATER TEMPERATURE OF CROSS FLOW COOLING TOWER

HIGH EFFICIENCY NANOFLUID COOLING SYSTEM FOR WIND TURBINES

Crystal Growth and Viscosity Behaviors of Ammonium Alum Hydrate Solution with PVA in Shear Flow

Calculation and Analysis the Influence on the Cooling Water Velocity and Hot Metal Circulation to the Long Life Blast Furnace

Estimation of Boil-off-Gas BOG from Refrigerated Vessels in Liquefied Natural Gas Plant

NUMERICAL SIMULATION OF THERMAL PROCESS IN WELDING

CFD modeling of heat charging process in. a direct-contact container. for mobilized thermal. energy storage

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Computational Analysis of Blast Furnace Pulverized Coal Injection For Iron Making

Analysis the impact of energy storage techniques in a cold distribution system

ICMIEE-PI Experimental and Numerical Investigation of an Air to Water Heat Exchanger

A Simplified Model for Velocity and Temperature Evolution of Alloy Droplets in Centrifugal Atomisation and Spray Deposition

Experimental study of supercooling and ph behaviour of a typical phase change material for thermal energy storage

Performance study on solar assisted heat pump water heater using CO 2 in a transcritical cycle

2

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

EMISSION AND TRENDS IN RECLAIMING WASTE HEAT IN INDUSTRIAL INSTALATIONS

Development of Phase Change Materials for Refrigerated Transportation of Fruits and Vegetables Ru-he XIE 1, Wen-bo TAO 2 and Guang-hai LIU 1

Optimization Of Recuperative Heat Exchanger In Gas. Turbine Shrishail G Sr.Design Engineer CYIENT LTD Hyderabad

Zafer URE.

ADVANCES in NATURAL and APPLIED SCIENCES

Experimental Investigation of Heat Transfer Enhancement of a Double Pipe Heat Exchanger with Helical Fins in the Annulus Side

Water-side Systems. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology

Computational Study of Hybrid Water Heater with Evacuated Glass Tube Solar Collector and Rice Husk Combustion

Performance Improvement of Mechanical Induced Draft Cooling Tower by Using Aluminum as Fill Medium

Design of Ammonia Water Vapour Absorption Air Conditioning System for a Car by Waste Heat Recovery from Engine Exhaust gas

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Performance Evaluation of Heat Exchangers for Application to Ocean Thermal Energy Conversion System

Enhancement of Heat Transfer in Concentric Tube Heat Exchanger using Water Based Nano Fluid ( )

POTENTIAL USE OF PHASE CHANGE MATERIALS IN GREENHOUSES HEATING: COMPARISON WITH A TRADITIONAL SYSTEM

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

HORIZONTAL SHELL SIDE FLUIDIZED BED HEAT EXCHANGER, DESIGN CONSIDERATIONS AND EXPERIENCES FROM A PILOT UNIT

Design and development of an Earth Air Tube Heat Exchanger

Estimation of natural circulation flow based on temperature in the FASSIP-02 large-scale test loop facility

Available online at ScienceDirect. Energy Procedia 69 (2015 )

Thermal Performance of an Integrated Earth-Air Tunnel System with Building s External Wall in UAE

Transcription:

EXPERMENTAL STUDY ON FLOW AND THERMAL CHARACTERS OF CALCIUM CHLORIDE HYDRATE SLURRY Abstract Aryadi Suwono, M. Irsyad, Yuli S. Indartono, Ari D. Pasek Faculty of Mechanical and Aerospace Engineering, Institut Teknologi Bandung, Jl. Ganesa 1, Bandung 4132, Indonesia, Tel. +62-22-25-4243, +62-22-253-499 Email: aryadi@termo.pauir.itb.ac.id Received Date: December 25, 214 Phase change material has been used as secondary refrigerant mixing ingredients to reduce energy consumption. Salt hydrate from calcium chloride with the composition of 55% calcium chloride dihydrate and 45% water matched with the temperature of chiller evaporator. Flow of slurry has given effect on the flow and heat transfer characteristics. Equipment used to know this is double pipe heat exchanger with flow counter flow. Pipe material is copper. The test results showed that the temperature salt hydrate containing solid particles. Salt hydrate slurry can improve the heat transfer coefficient, but the pressure drop and friction factor was also increased. Keywords: Calcium Chloride, Phase Change Material, Secondary Refrigerant Introduction Air conditioning (AC) chiller type where water as a secondary refrigerant can reduce the using of primary refrigerant and this able reduce the greenhouse effect. In commercial buildings use AC provide a major contribution to the energy consumption of buildings [1,2,3]. One method currently being developed to minimize the energy consumption of air conditioning systems are the use of phase change materials (PCM). In its application, the PCM is used as the secondary refrigerant mixing ingredients. PCM serves as a thermal energy storage in the form of latent heat. Several studies have shown positive results on reducing energy consumption, such as the use of trimethylolethane (TME) can reduce energy consumption 54% [4], and tetrabutylammonium bromide (TBAB) clathrate hydrate slurry (CHS) by 42%. [5]. PCM based on materials are classified; organic, inorganic, and eutectic. Salt hydrate is a kind of inorganic PCM which has high latent heat and thermal conductivity [6]. Use of this PCM on the secondary refrigerant can improve the thermal density. At the evaporator working temperature range of 5-12 o C, flows in the form of slurry. In these conditions, for the process of cooling generated of the solid particles, and for the heating process occurs melting of solid particles. Replacement of water into a slurry influence the flow losses in the piping system, so the impact on the pump power. Increasing the concentration of solids in the slurry can improve the pressure drop in the pipe [7]. Calcium chloride is a salt hydrate-forming material. Mixing calcium chloride dihydrate with water at a ratio of 55%: 45% have freezing temperatures 5.36-5.26 o C [8]. This composition matches the chiller evaporator working conditions. This study aims to investigate the characteristics of flow and heat transfer salt hydrate of calcium chloride. ASEAN Engineering Journal Part A, Vol 5 No 2, ISSN 2229-127X p.9

Experimental Apparatus and Procedure Material Salt hydrate used is a mixture of calcium chloride dihydrate 55% and 45% water. Calcium chloride dihydrate (CaCl 2.2H 2 O) have been containing 75.49% calcium chloride. At low temperature, salt hydrates are turn into slurry. Determination of the concentration of CaCl 2 is based curve salt hydrate phase diagram, as shown in Figure 1. Temperature o C 18 16 14 12 1 8 6 4 2-2 -4-6 Solution &Ice Solution Ice & CaCl 2.6H 2 O CaCl 2.4H 2 O & Solution CaCl2.6H2O & Solution CaCl 2.H 2 O & Solution CaCl 2.6H 2 O & CaCl 2.4H 2 O CaCl 2.2H 2 O & Solution CaCl 2.4H 2 O &CaCl 2.2H 2 O CaCl 2.2H 2 O & CaCl 2.H 2 O 1 2 3 4 5 6 7 8 Weight Percent CaCl 2 Figure 1. Phase diagram of calcium chloride and water compound [9] Some properties of calcium chloride hydrate salt needs to be known for the calculation of the flow and heat transfer characteristics are shown in Table 1. Table 1. Properties of Calcium Chloride Hydrate Properties Value References Density (kg/m 3 ) 1352 [1] Viscosity (Pa.s).188 [11] Thermal conductivity (W/m.K).54 [12] Specific heat capacity (kj/kg.k) 3.58 [11] Latent heat (kj/kg) 315.57 [1] Solid Factor Test Solid factor is the ratio between the solid mass contained in the slurry with slurry mass. Solid mass for the cooling process is taken after a once cooling and heating cycles. While the solid mass of the heating process is taken after it was once cooling cycle. Temperature range testing cycle is 15 2 o C. Flow and Thermal Characteristic Test Flow and heat transfer characteristics testing were made on test equipment with the scheme shown in Figure 2. The flow characteristics were tested on a copper pipe with a diameter of ½ inch and 3.2 meters long. Pressure drop was measured using the U manometer. Fluid of manometer is CCl 4. Heat transfer characteristics were tested in double-pipe heat exchanger counter flow type. The geometry of equipment is as follow: the length of pipe is 3 m, the ASEAN Engineering Journal Part A, Vol 5 No 2, ISSN 2229-127X p.1

inner diameter of pipe is ½ inch and outer diameter of pipe is 1 inch. The material of pipe is copper. Temperatures inlet and outlet of each pipe was measured using a thermocouple type K and data logger Omega OM-DAQ-USB-241. T 1 T 4 Heat exchanger T 3 P 1 P 2 T 2 Heater Temperature data logger h Manometer Cooler Result and Discussion Figure 2. Schema of flow and heat transfer characteristic test Salt hydrate tested is in the form of slurry. In the cooling process of the formation of solid particles and the heating process occurs melting of solid particles. Solid mass percentages in the slurry at cooling and heating processes are shown in Figure 3. From the test results in the cooling process, the solid mass formed at temperatures of 15 o C is 4.3% and at a temperature of 2 C is 44.9%. While in the heating process after a cooling cycle, the percentage of solid mass has been decreases with temperature increasing. Solid mass that remains is slightly more than the cooling process at the same temperature. This shows that the melting temperature slightly higher than the freezing temperature. Solid mass fraction is needed in the calculation of the heat transfer coefficient. Solid mass fraction (%) 6 5 4 3 2 1 Cooling Heating 5 1 15 2 Temperature ( o C) Figure 3. Solid mass fraction of calcium chloride slurry to cooling and heating process Visualization of flow in the test of flow and heat transfer characteristics have shown that salt hydrate already slurry, as shown in Figure 4. Solid particles in slurry have very small and soft. ASEAN Engineering Journal Part A, Vol 5 No 2, ISSN 2229-127X p.11

Water flow CaCl 2 x H 2 O slurry flow Solid phase of CaCl 2 x H 2 O Pressure Drop/ Friction Factor Figure 4. Visualization of water and slurry flow Pressure drop that occurs in the pipeline based on the Darcy-Weisbach equation is affected by the coefficient of friction, fluid density, length and diameter of the pipe, and the flow rate, as shown in equation 1. L mayor = f l D V 2 2g (1) Pressure drop (Pa/m)) 6 5 4 3 2 1 Calcium chloride x hydrate Water.1.2.3.4.5 Velocity (m/s) Figure 5. Pressure drops as function of velocity of the water and salt hydrate slurry Figure 5 shows the pressure drop that occurs to some velocity flow at temperatures of 5 C. In laminar flow with velocity lower than.2 m/s, the difference of pressure drop for the flow of salt hydrate slurry is very small compared to water. But in turbulent flow with velocity higher than.2 m/s, the difference of pressure drop increase in line with the increase in velocity. This is in accordance with the Darcy-Weisbach equation where the pressure drop is proportional to the square of the velocity. In addition, the value of salt hydrate density greater than water, also affect the increase in pressure drop. Friction factor experimental results calculated using Darcy-Weisbach equation. Friction factor of theoretical for laminar flow is calculated by equation 2 by assuming Newtonian fluid. f = 64 Re D As for the turbulent flow and very smooth pipe used to Blasius equation, as written in equation 3. (2) ASEAN Engineering Journal Part A, Vol 5 No 2, ISSN 2229-127X p.12

f =.316 Re.25 (3) Thomas equation used for turbulent flow and non-newtonian fluid, as written in equation 4. f =.1988 Re.211 (4) Compared with water, friction factor for the salt hydrate slurry is greater in laminar flow and turbulent flow. At 5 C test temperature, solid particles that have a lot of formed can improve the flow resistance. Analysis of liquid solid two phase flow is more complex than a single-phase flow, where there is interaction among the solid particles, solid particles with a carrier fluid and the pipe wall. Friction flow of slurry is divided into two parts namely; (1) mechanical friction caused by the interaction of solid particles and the walls of the pipe; (2) the viscous friction caused by fluid viscosity [13]. Improving of the friction factor caused to increased interaction with other solid particles and the wall. For turbulent flow with a Reynolds number limit of 5, the difference with the fluid friction factor of water is not too large. This condition is almost the same when compared to the friction factor using the Blasius equation. These results are consistent with the results of testing using ammonium alum hydrate slurry fluid [14]. Friction Factor (-).12.1.8.6.4.2 calcium chloride x hydrate (Laminar) water (Laminar) calcium chloride x hydrate (Turbulent) Thermal Characteristic Figure 6. Friction factor of salt hydrate slurry Heat transfer occurs in the double-pipe heat exchanger with counter flow satisfy the following equations. Overall heat transfer rate can be formulated in equation 5. q = UA T lm Total heat transfer coefficient (U) with the assumption of negligible fouling due to the condition of the pipe that was new, formulated as follows 1 = 1 = UA U i A i 5 Reynolds Number (-) 5 1 U o A o = 1 + ln D o D i (A) i 2πkL (5) + 1 (A) o (6) T lm is the average temperature difference of heat exchangers. To flow in the opposite direction, the value of T lm is as follows. T lm = T,o T c,i T,i T c,o ln T,o T c,i T,i T c,o (7) In addition, the rate of heat transfer to the cold and hot fluid satisfies the equation 8. q = m C p T (8) ASEAN Engineering Journal Part A, Vol 5 No 2, ISSN 2229-127X p.13

To know the correlation of heat transfer characteristics with fluid flow used equations Chilton-Colburn Analogy as follows. C f 2 = f 8 = St Pr2/3 = Nu d Re d Pr Pr2/3 (9) Convection coefficient values will be compared with the empirical formula is used as theoretical equation in this research that Dittus-Boelter equation. Nu d =.23 Re d 4/5 Pr n (1) Heat transfer characteristics of the test results are shown in Figure 7 and 8. The use of salt hydrates of calcium chloride can improve heat transfer compared to water. Nusselt number and convection coefficient increased. Improved heat transfer in salt hydrate slurry caused by interactions among the particles of solid, fluid carrier and walls. This interaction is better than a single-phase flow, like water. Other research, such as the use of the use of ammonium alum hydrate slurry [14] showed similar results, with an increase in heat transfer. 6 Nusselt number Nu (-) 5 4 3 2 1 Water Calcium chloride x hydrate Dittus Boelter Eq to calcium chloride x hydrate 1 1 Reynold Number Re (-) Figure 7. Nusselt number of salt hydate slurry 3 Convection coeficient, h ( W/m 2 K) 25 2 15 1 5 Water Calcium chloride x hydrate 1 1 Reynolds number Re (-) Figure 8. Convection coefficient of salt hydrate slurry ASEAN Engineering Journal Part A, Vol 5 No 2, ISSN 2229-127X p.14

Conclusion In the present study, salt hydrate of calcium chloride containing solid particles that store thermal energy as latent heat. Flow of slurry has given effect to the increasing in pressure drop. Friction factor is slightly higher than water. The interaction of among the solid particles, solid particles with a carrier fluid and wall in slurry flow has improved the heat transfer. Nomenclature A Area (m 2 ) St Stsnton number (-) C f Fanning friction factor (-) T Temperature ( o C) C p Specific heat capacity (J/kg. o C) U Total heat transfer coefficient D Pipe diameter (m) (W/m 2 K) f Friction factor (-) v Velocity (m/s) h L Head losses (m) Subscripts l Length (m) c cool Nu Nusselt number (-) h hot Pr Prandtl number (-) i inlet q Heat transfer rate (W) o outlet References [1] J. Xia, T. Hong, Q. Shen, W. Feng, L. Yang, P. Im, and A. Lu, Bhandari M 214 comparison of building energy use data between the United States and China, Energy and Buildings 78 (214), pp. 165 175. [2] Saidur R 29, Energy consumption, energy savings, and emission analysis in Malaysian office buildings, Energy Policy 37 (29), 414 4113. [3] JICA Study on Energy Efficiency and Concervation Improvement in Indonesia 27-28, Available: http://eneken.ieej.or.jp/en/data/pdf/491.pdf. diakses, [Accessed: 8 October, 212] [4] Y.S. Indartono, N.T. Setioputro, N.P. Tandian, A.D. Pasek, and A. Suwono, 28, Devlopment of Energy Saving Air Conditioning Sistem by Subsituting Primary and Secondary Refrigerants, Proceeding of International Conference on Cooling and Heating Technologies, Jinhae, Korea, 28-31 October 28. [5] O. Hidemasa, and T. Shingo, 24, Air-Conditioning Sistem Using Clathrate Hydrate Slurry, JFE Technical Report, No. 3. [6] D. Zhou, C.Y. Zhou, and Y. Tian, 212, Review on Thermal Energy Storage with Phase Change Materials (PCMs) in Building Applications, Applied Energy, 92, 593-65. [7] Z.W. Maa, P. Zhang, Wang, S. Furui, and G.N. Xi, 21, Forced flow and convective melting heat transfer of clathrate hydrate slurry in tubes, International Journal of Heat and Mass Transfer, 53, 3745 3757. [8] M. Irsyad, A. Suwono, Y.S. Indartono, A.D. Pasek, and W.C. Mahendra, 214, Studi Karakteristik Garam Hidrat Sebagai Kandidat Refrigeran Sekunder Pada Sistem Pengkondisian Udara Jenis, Chiller, Proceeding Seminar Nasional Tahunan Teknik Mesin XIII (SNTTM XIII), Depok, 15 16 Oktober 214. [9] Calcium Chloride, A Guide to Physical Properties. Occidental Chemical Corporation. ASEAN Engineering Journal Part A, Vol 5 No 2, ISSN 2229-127X p.15

[1] Calcium chloride handbook, A Guide to Properties, Forms, Storage and Handling, The Dow Chemical Company, Available: http://www.progunivers.com/img/pdf/calcium Chlorid- Handbook.pdf. diakses tanggal. [Accessed: 11 February 215] [11] A. Suwono, Y.S. Indartono, M. Irsyad, and I.C. Al-Afkar, 214, Application of calcium chloride as an additive for secondary refrigerant in the air conditioning system type chiller to minimized energy consumption, 7th International Converence on Cooling and Heating Technologies, Subang, Malaysia, 4 6 November 214. [12] V.V. Tyagi, and D. Buddhi, 28, Thermal cycle testing of calcium chloride hexahydrate as a possible PCM for latent heat storage, Solar Energy Materials & Solar Cells, 92, 891 899. [13] V. Matousek, 22, Pressure drops and flow patterns in sand-mixture pipes, Exp. Therm. Fluid Sci. 26, 693 72. [14] H. Suzuki, T. Konaka, Y. Komoda, and T. Ishigami, 213, Flow and heat transfer characteristics of ammonium alum hydrate slurries. ASEAN Engineering Journal Part A, Vol 5 No 2, ISSN 2229-127X p.16