PRO-TEC SENTRY BUILDING PONY WALL 90' WIDTH FOUNDATION MANUAL

Similar documents
This guide can be used to prepare a specification for incorporating wall bracket jib cranes into a competitively bid construction project.

WALL MOUNTED ARTICULATING JIB CRANE

Owner s Manual & Safety Instructions

SKATEWHEEL FLOW RACK

SK2000 Boltless Pallet Rack Installation and Assembly Manual

ASSEMBLY MANUAL FOR LADDERS, SAFETY CAGES, & PLATFORMS FOR THE FOLLOWING TANKS

STANDARD PRACTICE INSTRUCTION

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

Panel Jack Pro System BRACING, ALIGNMENT AND SCAFFOLDING EQUIPMENT

CEILING MOUNTED ARTICULATING JIB CRANE

HORSE SHELTERS 6, 12, 15, 18, & 24 SHELTERS ASSEMBLY MANUAL

PROFESSIONAL SOUND SYSTEMS WPB OPERATING MANUAL AND USER GUIDE. WPB User Manual.indd :21:39

POST FRAME BUILDING STANDARDS

INSTALLATION MANUAL. Guardian Series. QSUS 18 x 40. Manual

SECTION LATCHWAYS CONSTANT FORCE POSTS

Streamline Solar Photovoltaic Structural Criteria for Residential Rooftop Solar Energy Installations (Streamline Solar Form 5)

SK3000 Structural Pallet Rack Installation and Assembly Manual

Scaffold Safety

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

SECTION STEEL JOIST FRAMING

WALL CANTILEVER WORK STATION JIB CRANE

OVERALL STRUCTURAL SYSTEM

55-Gallon Tilting Drum Ring

DynoRaxx EVOLUTION PR Guide to Code Compliant Installation

SafeDeck Supported Scaffold System

SECTION FABRICATED ENGINEERED STRUCTURES. A. Pre-engineered, shop-fabricated structural steel building with formed purlin framing.

Aluminum Headache Rack

Loseke Technologies, Inc. p r e s e n t s

USER'S GUIDE FOR INSPECTION OF DAMAGED STORAGE RACK SYSTEMS DON T WAIT UNTIL IT S TOO LATE!

Standard Duty Cantilever Rack Installation and Assembly Guide

SECTION PLATE CONNECTED WOOD TRUSSES

Safety Documents > Safety Manual > Scaffolds

Structural Criteria for Residential Rooftop Solar Energy Installations

Structural Criteria for Residential Rooftop Solar Energy Installations

Structural Criteria for Residential Rooftop Solar Energy Installations

Model m x 1.98 m NPRM with Roof Pads For 1.2 m Antenna Systems

Preference Slimline 5537 Utility Console I NSTALLATION GUIDE

Designed To Meet Your Operational Needs

Building and Safety Division 245 E Bonita Avenue Ph:

Conergy SolarFamulus II

Open-Web Truss Long Span Installation Guidelines

.1 American Institute of Steel Construction (AISC) Specifications for Steel Buildings AISC

SECURE. UNIVERSAL. MOUNTING. Tilt Kit Installation Manual

Structural Criteria for Residential Rooftop Solar Energy Installations

Page 10-1 Hubbell Power Systems, Inc. All Rights Reserved Copyright 2014 LIGHTING AND SIGNS

Sectional Scaffold. Scaffold Access Unit Installation Instructions

Structural Criteria for Residential Rooftop Solar Energy Installations

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM

F500 Steeplechase Waterjump with Valve Option

SECTION DECORATIVE METAL RAILINGS

CITY OF MOUNT DORA LIFT STATION CHAINLINK FENCE AND GATE SPECIFICATIONS

American Residential Deck Railing Design Guide

Pallet Gate Installation Instructions and Operators Manual

PE45 AMAZON MONKEY BARS OWNER'S MANUAL

Series 8009A 9-Meter Earth Station Antenna. Site Preparation Manual

DEALER PRICE BOOK CO, KS, MD, NM, OH, PA. 210 Airport Rd. Mount Airy, NC Toll Free: Fax:

Structural Criteria for Residential Rooftop Solar Energy Installations

ALUMINUM CURB RAMP. Model 98037

CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

Structural Criteria for Residential Rooftop Solar Energy Installations

Owner s Manual & Safety Instructions

ASSEMBLY INSTRUCTIONS RESIDENTIAL SOLUTION CROSSRAIL GROUND MOUNT SYSTEM USA

Modular Simplicity Dero

Houston Community College 3200 Main Parking Garage November 15, 2010 Houston Community College

SECTION COLD-FORMED METAL TRUSSES

Comparison letter for MegaMet s MegaStorm Door against door construction details in FEMA 361 section 7.4.1

OPERATOR S SAFETY MANUAL

City of Santa Monica. Building and Safety Division. Structural Criteria for Residential Rooftop Solar Energy Installations

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading

USER'S GUIDE FOR INSPECTION OF DAMAGED STORAGE RACK SYSTEMS DON T WAIT UNTIL IT S TOO LATE!

1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.

Reliant Holdings Ltd Safety Management System

Technical Assignment 3 December 3, 2007

Draft. Not yet Approved

C Series Mechanical Pit Levelers. P.O. Box 338 Spring Hill, Tennessee fax:

PS 3000 Installation Manual Step-By-Step Procedures C.9. DOOR AND WINDOW OPENINGS C.9.1 PREPARE IN ADVANCE. C.9.2 VBUCK CONSTRUCTION.

WIND SPEED AND DESIGN CRITERIA FOR FLEXIBLE FACE SIGNS CONSTRUCTED OF ABC EXTRUSIONS

STATE UNIVERSITY CONSTRUCTION FUND. UNIVERSITY CON DIRECTIVE 5-1 Issue date: October 2014

Systems Scaffold Tubular Scaffold Access Unit Installation Instructions

Installation Instructions

Owner s Manual & Safety Instructions

VHSR-SERIES RACKS FOR SHEET MATERIAL

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

KE DURASOL GENNIUS PERGOLA SYSTEMS

GroundTrac. Installation Manual

Multi-Purpose Scaffolding Instruction Manual

TABLE OF CONTENTS. 1.0 INTRODUCTION 1.1 Greenstone Structural Engineered Panels 1.2 Drawing and Element Numbers

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM

Made in U.S.A. Wave Style Bike Rack Submittal Sheet. Materials: 1.5 Schedule 40 Steel Pipe (1.

SECTION PRE-ENGINEERED EXTRUDED ALUMINUM DECKING WALKWAY COVERS SPECIFICATION

Steps in Building a Shed

Structural Criteria for Residential Rooftop Solar Energy Installations

SECTION STRUCTURAL METAL FRAMING

Building Specifications for City of Pleasant Hill

SECTION ARCHITECTURAL ORNAMENTAL HANDRAILS AND RAILINGS Casino Modular Railing System

Made in U.S.A. Sunrise Bike Rack Submittal Sheet. Materials: Finishes: Mount Options: Capacity: Setbacks:

SJI Code of Standard Practice

SECTION ORNAMENTAL ALUMINUM RAILING

Elevation "L" ASTOR II DESIGN CRITERIA: 2012 International Residential Code with Georgia Amendments

Transcription:

MANUAL NO. 192035 KAG 2010- REV A PRO-TEC SENTRY BUILDING PONY WALL 90' WIDTH FOUNDATION MANUAL IMPORTANT - TO THE DEALER OR ERECTOR: RETURN THIS MANUAL TO THE OWNER FOR THEIR FUTURE REFERENCE SIOUX STEEL COMPANY, P.O. BOX 1265, SIOUX FALLS, SOUTH DAKOTA 57101 1-800-557-4689

Dear Sentry Building Owner, We would like to take this opportunity to thank you for purchasing a SIOUX STEEL PRO-TEC BUILDING. We believe that it will serve you well for many years. The framework uses quality certified structural grade steel tubing. All welded rafter assemblies are powder coated to provide maximum corrosion protection. We believe in providing QUALITY, RELIABILITY, DURABILITY, VERSATILITY, and COMMITMENT to meet the needs of our customer. Should you have any questions or comments during or following the installation, please feel free to call your SIOUX STEEL PRO-TEC BUILDING dealer or manufacturer. We will be glad to assist you in any way we can. IMPORTANT Improper Site Preparation, Assembly and Maintenance may invalidate warranty and cause unnecessary and costly mistakes. READ MANUAL FIRST If you have any questions, contact your local dealer or Call: Sioux Steel Co. at 1-800-557-4689 1

TABLE OF CONTENTS SAFETY PAGE 3 GENERAL INFORMATION (30 PSF, 40 PSF, & 50 PSF) PAGE 4-6 COMPONENTS PAGE 7 TOOLS & EQUIPMENT PAGE 8 FOUNDATION LAYOUT PAGE 9-11 ANCHOR BOLT INSTALLATION PAGE 12-13 RATCHET MOUNT INSTALLATION PAGE 14 ANCHOR BOLT INSTALLATION ON INSIDE PAGE 15 FACE OF FOUNDATION END WALL FOUNDATION (IF REQUIRED) PAGE 16-20 2

SAFETY Watch for this symbol. It points out important safety precautions. It means Attention Be Alert! DEFINITIONS: CAUTION: Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury. WARNING: Indicates a hazardous situation, which, if not avoided, could result in death or serious injury. DANGER: Indicates a hazardous situation, which, if not avoided, will result in death or serious injury. When constructing foundation: Use appropriate safety practices during construction of foundation. Hard hats are recommended to prevent injury to head. Gloves and other heavy clothing are recommended to prevent cuts and abrasions to hands and other body parts. Appropriate equipment and proper training in the operation of this equipment, are important factors for the safe construction of foundation. Reading, understanding, and following the instructions in this book are also very important for the safe construction of foundation. Sioux Steel Company includes all reasonable means for accident prevention, except a safe and careful operator. After foundation is complete: Ensure foundation area remains safe prior to erection of building. 3

GENERAL INFORMATION (30 PSF SNOW LOAD) 16 FT RAFTER SPACING Foundation for Sentry Building: In all cases, the soil and foundation must be sufficiently stable and deemed suitable to support the forces produced by the structure (listed below). It is recommended that the customer consult a qualified engineer to certify the soil conditions and foundation for their location. Soil and foundation must be able to withstand forces which meet or exceed the structural forces below. MAXIMUM BUILDING REACTIONS AT SERVICE LOADS In. (+X) lbs. Up (+Y) lbs. Down. (-Y) lbs. Induced Moment (ft-lbs) Service Load Out. (-X) lbs. (Z) lbs Dead Load 475 0 0 1025 n/a 210 Snow Load 6550 0 0 9950 250 2250 Wind Load 2775 7525 14000 4750 2450 6625 -Building reactions are based on occupancy category I outlined in ASCE 7-05, Table 1-1. -Building reactions are based on a building which is classified as partially enclosed as specified in ASCE 7-05, Section 1.2. -A total of 500 pounds may be suspended from each frame, as long as no single point force exceeds 250 pounds. -Customer should contact their dealer with any requests for other loading scenarios. Site Conditions for Sentry Building: The installation site must be sufficiently level to permit uniform wall assembly on a support foundation. In all cases, the area surrounding the Sentry Building must provide sufficient drainage to prevent soil erosion around the foundation. The structure has been designed to meet 90 mph exposure C wind load and 30 psf ground snow load, for open terrain with obstructions having heights generally less than 30 feet. This terrain must extend upwind for a distance greater than 2600 feet. The building must be positioned at least 20 feet away from existing structures with a higher eave to prevent excessive load from drifting snow. Contact your insurance agent prior to assembly to insure you are covered in case of inadvertent accidents that may occur during erection. NOTE: Sioux Steel Company is not responsible or liable for: - Any damage or failure that may occur due to incorrect erection of building. - Any soil analysis or foundation design, - Substitution of components not specified in the construction manual that lead to damage or failure. - Unstable soil conditions or foundation that lead to structure damage or failure. - Damage caused by leaning sidewalls. - Any modification of design or structure. - Any bodily injury that occurs during the assembly of the building or as a result of modification to the design or improper construction. Z Y X 4

GENERAL INFORMATION (40 PSF SNOW LOAD) 12 FT RAFTER SPACING Foundation for Sentry Building: In all cases, the soil and foundation must be sufficiently stable and deemed suitable to support the forces produced by the structure (listed below). It is recommended that the customer consult a qualified engineer to certify the soil conditions and foundation for their location. Soil and foundation must be able to withstand forces which meet or exceed the structural forces below. MAXIMUM BUILDING REACTIONS AT SERVICE LOADS In. (+X) lbs. Up (+Y) lbs. Down. (-Y) lbs. Induced Moment (ft-lbs) Service Load Out. (-X) lbs. (Z) lbs Dead Load 425 0 0 900 n/a 185 Snow Load 6600 0 0 10075 275 3925 Wind Load 3275 5700 10950 5725 2625 5025 -Building reactions are based on occupancy category I outlined in ASCE 7-05, Table 1-1. -Building reactions are based on a building which is classified as partially enclosed as specified in ASCE 7-05, Section 1.2. -A total of 500 pounds may be suspended from each frame, as long as no single point force exceeds 250 pounds. -Customer should contact their dealer with any requests for other loading scenarios. Site Conditions for Sentry Building: The installation site must be sufficiently level to permit uniform wall assembly on a support foundation. In all cases, the area surrounding the Sentry Building must provide sufficient drainage to prevent soil erosion around the foundation. The structure has been designed to meet 90 mph exposure C wind load and 40 psf ground snow load, for open terrain with obstructions having heights generally less than 30 feet. This terrain must extend upwind for a distance greater than 2600 feet. The building must be positioned at least 20 feet away from existing structures with a higher eave to prevent excessive load from drifting snow. Contact your insurance agent prior to assembly to insure you are covered in case of inadvertent accidents that may occur during erection. NOTE: Sioux Steel Company is not responsible or liable for: - Any damage or failure that may occur due to incorrect erection of building. - Any soil analysis or foundation design, - Substitution of components not specified in the construction manual that lead to damage or failure. - Unstable soil conditions or foundation that lead to structure damage or failure. - Damage caused by leaning sidewalls. - Any modification of design or structure. - Any bodily injury that occurs during the assembly of the building or as a result of modification to the design or improper construction. Z Y X 5

GENERAL INFORMATION (50 PSF SNOW LOAD) 10 FT RAFTER SPACING Foundation for Sentry Building: In all cases, the soil and foundation must be sufficiently stable and deemed suitable to support the forces produced by the structure (listed below). It is recommended that the customer consult a qualified engineer to certify the soil conditions and foundation for their location. Soil and foundation must be able to withstand forces which meet or exceed the structural forces below. MAXIMUM BUILDING REACTIONS AT SERVICE LOADS In. (+X) lbs. Up (+Y) lbs. Down. (-Y) lbs. Induced Moment (ft-lbs) Service Load Out. (-X) lbs. (Z) lbs Dead Load 475 0 0 1025 n/a 210 Snow Load 6550 0 0 9950 250 2250 Wind Load 2775 7525 14000 4750 2450 6625 -Building reactions are based on occupancy category I outlined in ASCE 7-05, Table 1-1. -Building reactions are based on a building which is classified as partially enclosed as specified in ASCE 7-05, Section 1.2. -A total of 500 pounds may be suspended from each frame, as long as no single point force exceeds 250 pounds. -Customer should contact their dealer with any requests for other loading scenarios. Site Conditions for Sentry Building: The installation site must be sufficiently level to permit uniform wall assembly on a support foundation. In all cases, the area surrounding the Sentry Building must provide sufficient drainage to prevent soil erosion around the foundation. The structure has been designed to meet 90 mph exposure C wind load and 50 psf ground snow load, for open terrain with obstructions having heights generally less than 30 feet. This terrain must extend upwind for a distance greater than 2600 feet. The building must be positioned at least 20 feet away from existing structures with a higher eave to prevent excessive load from drifting snow. Contact your insurance agent prior to assembly to insure you are covered in case of inadvertent accidents that may occur during erection. NOTE: Sioux Steel Company is not responsible or liable for: - Any damage or failure that may occur due to incorrect erection of building. - Any soil analysis or foundation design, - Substitution of components not specified in the construction manual that lead to damage or failure. - Unstable soil conditions or foundation that lead to structure damage or failure. - Damage caused by leaning sidewalls. - Any modification of design or structure. - Any bodily injury that occurs during the assembly of the building or as a result of modification to the design or improper construction. Z Y X 6

COMPONENTS 1" CENTER OF RAFTER ARROW INDICATES TEM 21/32 4" 7" 8" 2 1/4" 7 3/4" 192092 CENTER TEM ARROW INDICATES TEM INSIDE OF WALL CENTER OF RAFTER 2" 21/32 5" 6" 2" 5 5/8" 10 7/16" 192093 CORNER TEM 1'-3 1/4" 1'-6 7/8" 1'-8 7/8" CENTER HOLE 1 1/2" 3/4" 190644 RATCHET MOUNT TEM 3/4" 17/32 2 1/2" 4 1/4" 5" NOTE: If templates were not ordered, construct out of plywood or other material based off of drawings above. 7

TOOLS AND EQUIPMENT (Customer Supplied) Measuring Tools: Transit-recommended String level String line (Long enough for your specific building) 300 Tape measure 4' level Plumb bob Excavating Tools: Spade Type Shovel Equipment to dig foundation. Material: Anchor bolts, 5/8 thread, 70 ksi min. tensile strength, four (4) for each center base plate and five (5) for corner base plate Inside face of foundation anchor bolts, 5/8" thread, 70 ksi min. tensile strength, six (6) for each center base plate (will be used during erection of structure) Anchor bolts, 1/2" thread, 70 ksi min. tensile strength two (2) for each ratchet mount location End Wall if required Anchor bolts, 5/8" thread, 70 ksi min. tensile strength, quantity will vary depending on end wall option 8

FOUNDATION LAYOUT (STEP 1) IMPORTANT: These foundation details are suggestions only. Soil conditions vary and should be checked with a qualified engineer. SIOUX STEEL IS NOT RESPONSIBLE FOR THE FOUNDATION DESIGN. IMPORTANT: Other foundation options are available, but must meet the loading requirements as stated on the GENERAL INFORMATION page of this manual. See pages 4-6. Step 1.1 Select a site to place your new Pro-Tec Sentry building and prepare by leveling and grading. See general information on pages 4-6 on site selection. Step 1.2 Stake out two corner posts A & B as shown in diagram below. A B DISTANCE IS EQUAL TO STATED LENGTH OF BUILDING + 4" 9

FOUNDATION LAYOUT (STEP 1) (CONT.) Step 1.3 Stake out other two corner posts C & D as shown in diagram below. Step 1.4 Verify diagonal measurements are equal to check squareness. Note: Cover will not fit properly if foundation is not square. Step 1.5 Recheck width measurement shown in diagram below. A B DIAGONAL DISTANCE ARE EQUAL 90' 9/16 TEMS DIAGONAL DISTANCE ARE EQUAL C DISTANCE IS EQUAL TO STATED LENGTH OF BUILDING + 4 D 10

FOUNDATION LAYOUT (STEP 1) (CONT.) Step 1.6 String a level line from A to B and C to D corner posts for the length of the building extending past each corner and as close to the ground as possible (6" maximum). Step 1.7 String a level line from A to C and B to D corner posts for the width of the building extending past each corner and as close to the ground as possible (6" maximum). Step 1.8 String a level line 8" in from A to B and C to D corner posts for inside location of foundation. This measurement is critical for installation of center rafters. A STRING LINE TEMS B STRING LINE INSIDE OF FOUNDATION STRING LINE TEMS 88-4 9/16 INSIDE OF FOUNDATION STRING LINE TEMS STRING LINE INSIDE OF FOUNDATION MIN C STRING LINE TEMS D 11

Step 2.1 Construct foundation. ANCHOR BOLT INSTALLATION (STEP 2) Step 2.2 Utilizing Corner Templates (192093), install (5) 5/8" anchor bolts (customer supplied) at each corner template location. Verify using diagram below for proper orientation and placement of templates. Leave 2" exposed above the concrete surface. Protect the exposed threads from concrete or damage. NOTE: If templates were not ordered, construct out of plywood or other material based off of drawings on page 7. VERIFY CORRECT ORIENTATION OF ARROWS ON TEMS TEMS INSIDE OF FOUNDATION 90-9/16 OUTSIDE TO TEMS TEMS (4X) CORNER TEM (192093) INSIDE OF FOUNDATION TEMS OUTSIDE TO TEMS DISTANCE IS EQUAL TO STATED LENGTH OF BUILDING + 4 12

ANCHOR BOLT INSTALLATION (STEP 2) (CONT.) Step 2.3 Utilizing Center Templates (192093), install (4) 5/8" anchor bolts (customer supplied) at each arch interval location. Verify using diagram below for proper orientation and placement of templates. Leave 2" exposed above the concrete surface. Protect the exposed threads from concrete or damage. NOTE: If templates were not ordered, construct out of plywood or other material based off of drawings on page 7 NOTE: Arch intervals are based off of desired snow load. See chart below for correct snow load to arch interval. Step 2.4 Recheck all foundation measurements to assure they are maintained. INSIDE OF FOUNDATION 90-9/16 TEMS SNOW LOAD TO ARCH INTERVAL 30 PSF- 16' ARCH INTERVAL 40 PSF- 12' ARCH INTERVAL 50 PSF- 10' ARCH INTERVAL 88-4 9/16 INSIDE OF FOUNDATION MEASURE FROM CENTER OF NOTCH CENTER TEM (192092) VERFIY CORRECT ORIENTATION OF ARROW ON TEM INSIDE OF FOUNDATION 13

RATCHET MOUNT INSTALLATION (STEP 3) Step 3.1 Utilizing Ratchet Mount Template (190644), install (2) 1/2" anchor bolts (customer supplied) at each ratchet mount location. See drawing below for proper placement. Leave 2" exposed above the concrete surface. Protect the exposed threads from concrete or damage. NOTE: If templates were not ordered, construct out of plywood or other material based off of drawings on page 7 NOTE: Ratchet mount interval are based off of desired snow load. See chart below for correct snow load to ratchet mount interval. CORNER OF FOUNDATION MEASURE FROM CENTER RATCHET MOUNT TEM (190644) 5" FIRST RATCHET MOUNT LOCATION 8', 6', OR 5' ADDITIONAL RATCHET MOUNT LOCATION INSTALL EVERY 16', 12' OR 10 SNOW LOAD TO RATCHET MOUNT INTERVAL FIRST RATCHET MOUNT 30 PSF- 8' RATCHET MOUNT INTERVAL 40 PSF- 6' RATCHET MOUNT INTERVAL 50 PSF- 5 RATCHET MOUNT INTERVAL ADDITIONAL RATCHET MOUNT 30 PSF- 16' RATCHET MOUNT INTERVAL 40 PSF- 12' RATCHET MOUNT INTERVAL 50 PSF- 10' RATCHET MOUNT INTERVAL 14

ANCHOR BOLT INSTALLATION ON INSIDE FACE OF FOUNDATION (STEP 4) Anchor bolts on inside face of foundation will be installed when building is erected. See structural manual instructions. 15

END WALL FOUNDATION (IF REQUIRED) BASE TEMS ARROW REPRESENTS WALL 2" 2" 8" 5" 11/16" CENTER OF TOWER 8" 5" CENTER OF TOWER 11/16" 1 1/4" 192646TPL BASE 4 1/2" 7 3/4" 9" 1 1/4" 193813TPL HALF BASE 4 1/2" 6 1/4" ARROW REPRESENTS WALL 2 1/4" 10 1/2" 5 1/4" 8 1/4" CENTER OF TOWER 11/16" 1 1/4" 194372TPL BASE 4 1/2" 7 3/4" 9" 16

END WALL FOUNDATION (IF REQUIRED) INSTRUCTIONS Step 1 Select End Wall Foundation layout drawing from following pages. Step 2 Construct necessary Base Plate Templates from previous page out of wood or other material. Step 3 Layout and construct desired foundation. Step 4 Utilizing Base Plate Templates install 5/8" anchor bolts (customer supplied) at each tower location. See correct End Wall Foundation layout on following pages for proper placement. Leave 2" exposed above the concrete surface. Protect the exposed threads from concrete or damage. 17

END WALL FOUNDATION (IF REQUIRED) SOLID END WALL FOUNDATION 9" 17'-2 1/4" 194372TPL BASE 10 1/2" OUTSIDE OF WALL 35'-5 3/4" 9" 192646TPL BASE ARROW INDICATES OUTSIDE OF WALL 53'-9 3/4" 72'-1 1/4" 90'-9/16" OUTSIDE TO TEMS 9" 192646TPL BASE OUTSIDE OF WALL 9" 194372TPL BASE 10 1/2" OUTSIDE OF WALL 18

END WALL FOUNDATION (IF REQUIRED) 18' DOOR END WALL FOUNDATION 9" 17'-1 3/4" 194372TPL BASE 10 1/2" OUTSIDE OF WALL 35'-5 3/4" 6 1/4" 193813TPL HALF BASE ARROW INDICATES WALL 54'- 1/2" 72'-1 3/4" 90' 9/16" OUTSIDE TO TEMS 6 1/4" 193813TPL HALF BASE OUTSIDE OF WALL 9" OUTSIDE OF WALL 194372TPL BASE 10 1/2" 19

END WALL FOUNDATION (IF REQUIRED) 2-18' DOORS END WALL FOUNDATION 6 1/4" 17'-1 3/4" 193813TPL HALF BASE OUTSIDE OF WALL 35'-8 1/2" 6 1/4" 53'-9 3/4" 193813TPL HALF BASE 72'-4 1/2" ARROW INDICATES WALL 90'-9/16" OUTSIDE TO TEMS 6 1/4" 193813TPL HALF BASE OUTSIDE OF WALL 6 1/4" 193813TPL HALF BASE OUTSIDE OF WALL 20