QUALITY CONTROL TESTING OF PLASTERBOARD FOR BRACING APPLICATIONS. Y L Liew Vicroads Victoria, Australia

Similar documents
The influence of plasterboard clad walls on the structural behaviour of low rise residential buildings

CEILING DIAPHRAGM ACTIONS IN COLD FORMED STEEL- FRAMED DOMESTIC STRUCTURES

MIDPLY Portal Frame as Lateral Bracing System in Light- Frame Wood Buildings

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

The development of generic span tables for cold formed steel studs in residential and low-rise construction

Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture Norbord Inc., Toronto, Ontario, Canada

research report Performance of Cold-Formed Steel-Framed Shear Walls: Alternative Configurations RESEARCH REPORT RP REVISION 2006

Predicting racking performance of walls sheathed on both sides

VERTICAL AND HORIZONTAL LATERAL LOAD SYSTEMS

The influence of washer reinforced nail connections on the lateral resistance of shear walls with large openings

research report Estimating the Response of Cold-Formed Steel Frame Shear Walls RESEARCH REPORT RP REVISION 2006

Tests on Partially Anchored Wood-Framed Shear Walls

REPORT NUMBER: ISSUE DATE: PAGE: ST August of 25

Monotonic Tests of Cold-Formed Steel Shear Walls with Openings

Numerical Modeling and Finite Element Analysis of Steel Sheathed Cold-Formed Steel Shear Walls

NEW COMPOSITE CONSTRUCTION OF HYBRID BEAMS COMBINING STEEL INVERTED T-SECTION AND RC FLANGE

IAPMO ES. Cover Sheet. Evaluation Criteria of. COLD-FORMED STEEL or WOOD FRAMED / STEEL-SHEATHED SHEAR WALLS

COMBINED ADHESIVE-STEEL PIN APPLICATIONS FOR CFS FRAME SHEAR WALLS

Pull-Through Failure Tests of Thin Steel Roof Battens under Wind Uplift Loads

Frame Wood Systems. Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture National Association of Home Builders

Frame Wood Systems. Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture National Association of Home Builders

Shear tests of hollow flange channel beams with stiffened web openings

Development of a Frame for Wide Openings in Residential Construction

research report Monotonic Tests of Cold- Formed Steel Shear Walls With Openings RESEARCH REPORT RP REVISION 2007

research report Cold-Formed Steel Walls with Fiberboard Sheathing Shear Wall Testing RESEARCH REPORT RP REVISION 2006

Structural Testing of Corrugated Sheet Steel Shear Walls

Gold Bond BRAND Gypsum Sheathing

Inelastic behavior of cold-formed braced walls under monotonic and cyclic loading

Investigating the Performance of Wood Portal Frames as Alternative Bracing Systems in Light-Frame Wood Buildings

TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION

Prefabricated Hybrid Wall Panel System for Lightweight Steel Construction in Seismic Prone Regions

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing

In-Plane Behavior of Cold-Formed Steel-Framed Shear Wall Panels Sheathed with Fibre Cement Board

Post-Earthquake Performance of Sheet Bracing Systems

STUDY REPORT No. 131 (2004)

SOFIE Project - Cyclic Tests on Cross-Laminated Wooden Panels

PROJECT NUMBER: ISSUE DATE: PAGE: ST October of 7

ESR-1812 Reissued October 1, 2012 This report is subject to renewal November 1, 2013.

research report The Strength of Stiffened CFS Floor Joist Assemblies with Offset Loading RESEARCH REPORT RP REVISION 2006

The Wood Products Council and AIA/CES. Concept, Performance and. Learning Objectives. FPInnovations - Background

FULL SCALE TESTING OF EXTENDED BEAM-TO-COLUMN AND BEAM- TO-GIRDER SHEAR TAB CONNECTIONS SUBJECTED TO SHEAR

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018

Modelling the seismic response of light-timber-framed buildings

DEVELOPMENT OF LONG SPAN COMPOSITE TRUSS BRIDGES

GA GYPSUM BOARD TYPICAL MECHANICAL AND PHYSICAL PROPERTIES

NON-LINEAR FINITE ELEMENT ANALYSIS OF BASE-PLATE CONNECTIONS USED IN INDUSTRIAL PALLET RACK STRUCTURES

Lateral Loading Response of CFS Framed Shear Wall with Cement Board Panels

Cold-Formed Steel Special Bolted Moment Frames: Cyclic Testing and Numerical Modeling of Moment Connections

Invention: Seismic Retrofitting by Exterior Steel Brace Structural Building Jacketing System

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO.

Shear Wall Design Guide

Monotonic Tests of Long Shear Walls with Openings

Defining Appropriate Limit States for Design of Timber Connections in Australia and New Zealand

The effects of humidity on gypsum plasterboard used as lateral load bracing for buildings

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

TECHNICAL NOTE No.5 Cyclic Testing of Solar Panels

research report Steel Sheet Sheathing Options for Cold-Formed Steel Framed Shear Wall Assemblies Providing Shear Resistance - Phase 2

The Development of Strain Penetration in Lightly Reinforced Concrete Shear Walls

Statewide Alternate Method January 2015 No Cross-Laminated Timber Provisions

steel stud drywall ceiling systems

SEISMIC BEHAVIOUR OF RING SHAPED STEEL PLATE SHEAR WALL

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)

DISTORTIONAL BUCKLING BEHAVIOUR OF FIRE EXPOSED COLD-FORMED STEEL COLUMNS

TECHNICAL NOTE On Cold-Formed Steel Construction

City of Long Beach Department of Development Services Building and Safety Bureau. Design Limitation for Wood Shear Walls

USING WOOD STRUCTURAL PANELS FOR SHEAR AND WIND UPLIFT APPLICATIONS

EXPERIMENTAL EVALUATION OF THE INFLUENCE OF SEISMIC CLIPS ON GRID JOINTS IN A SUSPENDED CEILING SYSTEM

FE MODELING OF CFRP STRENGTHENED CONCRETE BEAM EXPOSED TO CYCLIC TEMPERATURE, HUMIDITY AND SUSTAINED LOADING

Vulnerability modelling of metal-clad industrial buildings to extreme wind loading

GA APPLICATION OF GYPSUM SHEATHING

Seismic design of braced frame gusset plate connections

Performance of Deep Leg L-headers

An Experimental Study on the Effect of Opening on Confined Masonry Wall under Cyclic Lateral Loading

Evaluation of the High-Heel Roof-to-Wall Connection with Extended OSB Wall Sheathing

LIGHT-GAUGE PANELIZED WALL SYSTEMS. Michael Waggoner Mark Schroeder

Wall bracing panel requirements

TER No Cultured Stone & ProStone Applications Over Continuous Insulation

Insulation Fastener Guide IKO Ener-Air & IKO Enerfoil Wall Insulation

Finite Element Analysis of Concrete Filled Steel Tube Flexural Model

2008 Special Design Provisions for Wind and Seismic

WOOD I-JOIST AWARENESS GUIDE

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS

Influence of Longitudinal FRP Straps on the Behaviour of Circularised and FRP Wrapped Square Hollow RC Concrete Specimens

REVIEW ON SHEAR SLIP OF SHEAR KEYS IN BRIDGES

Behavior and Strength of Cold-formed Steel Framed Shear Walls Sheather with Composite Panels

SECURE. UNIVERSAL. MOUNTING. Tilt Kit Installation Manual

ANALYTICAL MODELING OF IN PLANE SHEAR OF BRICK VENEER AND WOOD STUD WALLS

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604.

ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) PREFACE

Experimental study on the seismic performance of RC moment resisting frames with precast-prestressed floor units.

SIPA Technical Committee Update SIPA Annual Meeting & Conference Jacksonville, FL February 26-28, 2018

Results from the city of Los Angeles-UC Irvine shear wall test program

Numerical Modelling and Analysis of Structural Behaviour of Wall-stud Cold-formed Steel Shear Wall Panels under In-plane Monotonic Loads

Proceedings of the Institution of Civil Engineers

Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit

SEISMIC STRENGTHENING AND REPAIR OF REINFORCED CONCRETE SHEAR WALLS

CONTINUOUS TIMBER DIAPHRAGMS

In-plane testing of precast concrete wall panels with grouted sleeve

The Effects of Building Parameters on the Modal Displacement Shapes of Tall Buildings

Transcription:

Int. Journal for Housing Science, Vol.32, No.1 pp. 51-60, 2008 Published in the United States QUALITY CONTROL TESTING OF PLASTERBOARD FOR BRACING APPLICATIONS Y L Liew Vicroads Victoria, Australia E F Gad The University of Melbourne and Swinburne University of Technology Victoria, Australia C F Duffield The University of Melbourne Victoria, Australia ABSTRACT It is well recognized around the world that plasterboard clad walls can provide significant bracing to light framed residential structures. In Australia, local codes of practice allow up to 50% of lateral bracing to be provided by such walls. While plasterboard contributes to the structural performance, associated quality control tests do not explicitly cover the bracing quality of plasterboard. The majority of existing quality control tests are related to other performance criteria such as damage during handling and punching of nail or screw heads through the plasterboard in ceiling applications. This paper reports the findings of a study into the adequacy of existing plasterboard quality tests as a measure of its bracing capacity. The paper also reports the development of a new test method, described herein as fastener bearing test, as an alternate quality control method for bracing capacity of plasterboard. This fastener bearing test is subsequently validated through an extensive experimental program. The paper concludes that the proposed test is a simple and reliable method to assess the bracing capacity of plasterboard. Key words: Light-framed Structures, Plasterboard, Gypsum, Testing, Bracing. 0146-6518/01/ 51-60, 2008 Copyright 2008 IAHS

52 Liew, Gad, Duffield Introduction Historically, the Australian residential housing industry treated plasterboard as a nonstructural material when designing houses. However, the growing body of research demonstrating that plasterboard provides significant bracing capacity, even with nominal fixing, has led to the 1999 version of the Australian Standard for Residential Timber-Framed Construction (AS1684, 1999) incorporating a contribution up to 50% of the lateral bracing from plasterboard where nominally fixed plasterboard clad walls are adopted. The inclusion of the bracing strength of plasterboard into AS 1684-1999 was done without any associated changes or controls being put in place to ensure that the assumed structural properties of plasterboard are available. As a result, plasterboard manufacturers may modify the properties of plasterboard without any requirement to ensure the bracing performance of the plasterboard. It is understood that modifications are frequently made to plasterboard by way of the paper lining and plaster mix constituents of the board. Further, the majority of existing quality control tests are related to other performance criteria such as damage during handling and punching of nail or screw heads through the plasterboard in ceiling applications. Plasterboard manufacturers would require additional tools and knowledge on the structural behaviour of plasterboard if they are required to meet the expectation of designers of residential structures and to guarantee the structural strength of their product. This paper reports the findings of a study into the adequacy of existing plasterboard quality tests as a measure of its bracing capacity. The paper reports the development of a new test method, described herein as fastener bearing test, as a specific quality control method for bracing capacity of plasterboard. This fastener bearing test is subsequently validated through an extensive experimental program and analytical modelling. Approach This study has conducted a detailed literature review along with field work at a number of plasterboard manufacturing plants. In addition, an extensive experimental program and analytical assessment have been undertaken. From the literature review and the interviews with the plasterboard manufacturers, it has been found that: National and international standard test methods for plasterboard, such as AS/NZS 2588-1998, ISO 6308-1980 and ASTM C473-2000, do not provide any provisions related to the bracing quality of plasterboard. To safely utilise plasterboard as a bracing material, a representative test for quality control must be developed. Current quality control tests for plasterboard have primarily been developed for transportation and handling issues, with no intention to ensure the bracing performance of plasterboard.

Plasterboard Quality Control 53 Detailed analysis of load transfer mechanisms in typical light-framed structures indicates that all walls (both structural and non-structural) parallel to the applied lateral load contribute to the lateral capacity of the structure (Gad et al. 1999 and Liew et al. 2002). The specific strength and stiffness contribution of each wall vary significantly depending on wall length, bracing material and building system. The lateral bracing performance of houses is directly related to the performance of in-plane (racking) walls. It is well established that the performance of an individual racking wall is directly related to the load-slip characteristics of sheathing-to-framing connections (shear connections) on the wall, which are highly influenced by the material properties of the sheathing. To understand the relative performance and contribution of plasterboard to the overall house response, full-scale racking tests of isolated walls combined with shear connection tests are concluded to be an appropriate methodology. Based on the knowledge gained from a detailed literature review (Liew, 2004), information gleaned from the field works conducted in plasterboard manufacturing plants and correlation of data on the existing quality control test methods with the density of plasterboard, led to the development of a new test method, (described here as fastener bearing test) (Liew et al. 2004). Figure 1 illustrates the apparatus for the developed fastener bearing test. Applied Load Jacket Plasterboard Brackets Standard Nail Perspex Base Plate Figure 1: Schematic details of the full test setup of the proposed fastener bearing test apparatus (dimensions are in mm).

54 Liew, Gad, Duffield Experimental Program and Results The experimental program of this study, as summarized in Figure 2, was developed to evaluate and verify the proposed fastener bearing test. It comprised two phases with the first phase involving the conduct of a large number of density tests, fastener bearing tests and shear connection tests on plasterboard. This phase sought to correlate and verify the proposed fastener bearing test against the current shear connection test. In phase two of the testing program, full-scale, isolated wall racking tests and some supplementary shear connection tests were performed. This phase was aimed to further verify the fastener bearing test against a full-scale isolated wall racking test as well as to determine the load-slip curves for typical shear connections on plasterboard clad walls. Such curves were also used to facilitate the development of analytical models. It should be noted that this study is concerned with light-framed structures built in low seismicity and non-cyclonic areas that include the majority of Australian cities and many other parts of the world. A monotonic loading regime, which is typically adopted by industry testing facilities and manufacturers (e.g. Experimental Building Station TR440, 1978 and ASTM-E72, 1998) was thus employed in this study. Fastener Bearing Tests Shear Connection Tests Full-Scale Isolated Wall Racking Tests Phase 1 Phase 2 Figure 2: Summary of experimental program. Table 1 summarises the results obtained in Phase 1 of the testing program. To reduce the variability of the plasterboard specimens, four batches of 10 mm thick plasterboard sheets, named here as Types A to D plasterboard, with different plaster

Plasterboard Quality Control 55 mix but identical linerboard supplied by a single manufacturer, were used for testing throughout Phase 1. Details of the setup for the tests conducted in this phase can be found in Liew et al. 2004. Analyses of the results of these tests led to the following conclusions: The failure modes and load-displacement curves from the fastener bearing tests showed similar characteristics to those observed in shear tests of connections as well as typical failure of connections in racking tests of full walls. Typical load- displacement curves from the fastener bearing tests are shown in Figure 3. A very strong correlation exists between fastener bearing test and shear connection test has been found. This is illustrated by the relationship between the mean ultimate loads from the fastener bearing tests (MULFB) and the mean ultimate loads from the shear connection tests (MULSC) which are plotted in Figure 4. The results show the trend of increasing mean ultimate load from the fastener bearing tests with increasing mean ultimate load from the shear connection tests. For MULFB and MULSC the line of best fit using a linear least squares regression analysis was calculated from the test data as follows: MULFB = 0.75 MULSC + 44.67 (1) For this relationship, the correlation coefficient, R, of 0.9996 was obtained, indicating that approximately 99.96% of the variation of the mean ultimate load from the shear connection tests can be explained by the mean ultimate load from the fastener bearing tests. The error bars in Figure 4 represent the maximum and minimum results of each test. These error bars show that the simplicity of the fastener bearing test presented in this study achieved higher consistency of experimental results compared with that of the shear connection test results. 700 600 500 Load (N) 400 300 200 Type A Plasterboard Type B Plasterboard 100 Type C Plasterboard Type D Plasterboard 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Displacement (mm) Figure 3: Typical load-slip curves from the fastener bearing tests.

56 Liew, Gad, Duffield Table 1: Summary of results from Phase 1 which comprised density tests, fastener bearing tests and shear connection tests Plasterboard Sample Size per Test Mean Density (kg/m 3 ) Mean Ultimate Load (N) Fastener Bearing Shear Connection Type A 36 640 (0.65) 315 (3.7) 365 (4.4) Type B 36 674 (0.84) 407 (5.7) 480 (5.4) Type C 36 824 (0.70) 561 (4.1) 683 (7.1) Type D 36 872 (0.79) 644 (4.1) 806 (12) Note: Values in parentheses represent Coefficient of Variation in percentage. 750 700 Fastener Bearing Test - Load (N) 650 600 550 500 450 400 350 300 250 300 400 500 600 700 800 900 1000 Shear Connection Test - Load (N) Figure 4: Mean ultimate loads from shear connection tests versus mean ultimate loads from fastener bearing tests For all the plasterboard specimens, their ultimate failure modes in both the fastener bearing tests and shear connection tests were very similar, in which the maximum load was associated with excessive tearing of the face linerboard. Both the plaster mix and linerboard play a significant role in providing the bracing capacity of plasterboard. While gypsum provides the medium to transfer the applied load, the linerboard confines the gypsum from expanding and breaking outwards.

Plasterboard Quality Control 57 To effectively utilize the proposed fastener bearing test, plasterboard manufacturers need to set their acceptance criteria in order to suit the different products and their designated performance. Tables 2 and 3 summarize the results of the full-scale isolated wall racking tests conducted in Phase 2 of the experimental program. A total of four walls were tested, named here as Walls 1 to 4. Walls 1 and 2 were clad with normal density (Type A) plasterboard, while Walls 3 and 4 with high density (Type D) plasterboard. These plasterboard sheets were nailed to frames using 2.8 mm 30 mm plasterboard nails with various spacing as listed in Table 2. Adhesive was not applied to these wall specimens as its durability, over the actual design life of the structure, may be questionable. The purpose of employing various nail spacing for the same type of plasterboard was to cover a range of typical nailing patterns and to examine the effect of the number of nails used on the ultimate racking capacity of a plasterboard clad wall. Plasterboard Type Table 2: Summary of Phase 2 results: Full-scale isolated wall racking tests. Nail Spacing (mm) Perimeter Studs and Plates Intermediate Studs Displacement at Ultimate Load (mm) Ultimate Load (N) Wall 1: Type A 150 300 19.2 5414 Wall 2: Type A 300 300 26.2 3011 Wall 3: Type D 150 300 12.7 9491 Wall 4: Type D 300 300 20.9 5644 Table 3: Loads measured at serviceability displacements. Load at +8mm deflection (N) Load at -8mm deflection (N) Wall 1: Type A 4343-4814 Wall 2: Type A 2781-2774 Wall 3: Type D 8467-9187 Wall 4: Type D 5063-4638 The test setup and loading protocol adopted in these full-scale isolated wall racking tests were based on the recommendations by TR440 (Experimental Building Station, 1978) for lateral wind loading, with the inclusion of uplift restraints to simulate the continuity of top plates, return walls and other boundary conditions which are often provided in actual houses. The uplift restraints were provided in the form of five steel rollers on the top of each stud. The steel rollers were pushed snug tight to the top

58 Liew, Gad, Duffield plate, thus, only a minimum amount of load was applied vertically. Each of these rollers was connected to a load cell to monitor the load imposed on the rollers. In addition, each wall specimen was prevented from out-of-plane movement by employing four rubber rollers which were fitted snug tight on each side of the wall. The specimen was pulled (North) and pushed (South) to complete a full cycle at serviceability displacement (typically equals Height/300 which is 8 mm for 2400 mm high walls) before pulling to failure. It was considered to have failed when the applied load decreased below 80% of the maximum load recorded or when a sudden rupture occurred leading to a significant loss of load, whichever happened first. Details of the test setup for these full-scale isolated wall racking tests are reported in Liew, 2004. The findings obtained from the above described full-scale isolated wall racking tests are summarized as below: The ultimate load of Wall 4 (clad with highest-density plasterboard, i.e. Type D) was approximately 1.8 times of Wall 1 s (clad with lowest-density plasterboard, i.e. Type A) ultimate load. This compares with the results of the shear connection tests and the fastener bearing tests conducted in Phase 1, in which the ultimate load of Type D plasterboard was found to be approximately 2.1 times of Type A plasterboard. The limited number of fullscale isolated wall racking tests conducted in this study had an error of approximately 15% between the predictions from the fastener bearing tests and those from the full-scale isolated wall racking tests and, as a result, can be considered in good agreement. This not only demonstrates that the results from the fastener bearing tests are consistent with the shear connection test results but also with those obtained from the full-scale isolated wall racking tests. Adding twice the number of nails at the perimeter of the wall had an increase in the ultimate load of 80% and 68% for Type A (lowest density) and Type D (highest density) plasterboard, respectively. The ultimate loads for the four wall specimens were only about 10% to 25% higher than the loads measured at serviceability displacement (8 mm), suggesting that plasterboard clad walls may reach their ultimate loads close to their design serviceability deformation. This should be taken into account in the design of light-framed residential structures, in particular when different cladding materials with different load-deflection characteristics are used for the same wall or within the same house. The plasterboard sheathings of all the wall specimens experienced significant translation and rotation. These mechanisms are not commonly observed in a full-scale house test where plasterboard is typically restricted from vertical and horizontal movements by ceiling cornices and return walls. The distribution of lateral forces in the end studs is dependent on the nailing pattern (i.e. spacing of nails between the plasterboard and studs).

Plasterboard Quality Control 59 Limitations The developed fastener bearing test is designed for quality control of plasterboard and does not attempt to replicate the full behavior of fasteners connecting plasterboard to framing members. For example, this test does not consider the influence of the fastener head on the connection behavior and the bending of fastener shank under bearing. In addition, this test has not been correlated with shear connection tests in which screw is used as an alternative fastener. However, it is expected that using screws as fasteners would produce similar results to that of using nails. The fastener bearing test presented in this study is developed and verified for monotonic loading protocol only. However, it can be easily adapted for different loading protocols (e.g. cyclic) to align with the loading protocol that is used to assess the performance of racking walls. Conclusion This study has successfully proposed, developed and verified a new test method, described herein as fastener bearing test, through an extensive experimental program and subsequent analyses. The test enables plasterboard manufacturers to reliably control the bracing quality of plasterboard, hence, allowing engineers to safely design the overall bracing capacity of light-framed residential structures. The contributions of each component of plasterboard and its effects on the bracing performance of plasterboard have also been examined and discussed. It should be noted that although this and other studies proves that plasterboard has the capability to provide significant bracing capacity, the deformation compatibility of plasterboard with other types of bracing material has to be studied further. That is, plasterboard clad walls may have higher initial stiffness than other bracing walls in the structure (e.g. those with diagonal cross strap bracing or plywood clad) and may also achieve their full strength at lower deformation. Hence, the direct addition of strengths from all individual walls without regard to the deformation compatibility may not reflect the true lateral performance of the overall structure. References 1. Standards Australia, 1999. AS1684: Residential timber-framed construction. Standards Association of Australia. Sydney Australia. 2. Standards Australia, 1998. AS/NZS2588: Gypsum plasterboard. Standards Association of Australia. Sydney Australia.

60 Liew, Gad, Duffield 3. International Organisation for Standardization. 1980. ISO 6308: Gypsum plasterboard specification. 4. American Society for Testing Materials. 1998. ASTM-E72 Standard methods of conducting strength tests of panels for building construction. 5. American Society for Testing Materials. 2002. ASTM-C473: Standard test methods for physical testing of gypsum panel products. 6. Liew YL, Duffield CF and Gad EF. 2002. The influence of plasterboard clad walls on the structural behavior of low rise residential buildings. The Electronic Journal of Structural Engineering, 2: 1 16. 7. Liew YL, Gad EF and Duffield CF. 2004. Development of a test method for determining plasterboard bracing performance. Journal of Structural Engineering, ASCE, 130 (7): 1108 1116. 8. Gad EF, Chandler AM, Duffield CF and Stark G. 1999. Lateral behavior of plasterboard-clad residential steel frames. Journal of Structural Engineering, ASCE, 125 (1): 32 39. 9. Liew YL. 2004. Plasterboard as a bracing material: From quality control to wall performance. PhD thesis, Department of Civil and Environmental Engineering, The University of Melbourne, Australia. 10. Experimental Building Station. 1978. Guidelines for testing and evaluation of products for cyclone-prone areas (TR440). Technical Record 440, Cyclone Testing Station, James Cook University of North Queensland, Australia.