History of Cable Systems HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES. Nigel Hampton

Similar documents
PILC Replacement: Getting the Lead Out

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

PV Solar Wiring Solutions

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

STANDARD FOR CONCENTRIC NEUTRAL CABLES RATED 5 THROUGH 46 KV

Accelerated Aging Tests for MV Cables

NORMAS DE REFERENCIA AEIC CS 1: ASTM B

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

EHV XLPE CABLES CDCC LINE

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES

Clark Public Utilities

NEMA Standards Publication No. WC ICEA Publication No. S

*** Supercedes: BECO E and COM , , & ***

«CABLE T 92» WORKSHOP BALI, INDONESIA JUNE, 1992 POWER CABLES IN TROPICAL ENVIRONMENTS : SYNTHESIS. By L. DESCHAMPS SEE / EDF (France)

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854

XLPE MATERIAL NATIONAL CABLES INDUSTRY XLPE INSULATED MEDIUM VOLTAGE CABLES

BLACK EPR INSULATED MEDIUM VOLTAGE CABLES. Ronald F. Frank, Eng. Consultant

INTERNATIONAL STANDARD

U.V resistance UL Sunlight Resistance. Flame retardant IEC

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

7/20/2017 MEETING--- POST MEETING MARKUP

COMPOUNDS & FLUIDS FOR POWER & COMMUNICATION CABLES

3 MODIFICATIONS TO EXISTING STANDARDS

15 kv EPR Insulated, Jacketed, URD Cable

Mining Products. Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items

Mining Products Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items Fon

SECTION WIRES AND CABLES

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

DEVELOPMENT OF HIGH VOLTAGE EXTRUDED CABLES: THE ITALIAN EXPERIENCE

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

For the 6/15/2017 meeting review

345 kv Underground Report

THE PERFORMANCE OF XLPE WATER TREE RESISTANT INSULATION SYSTEMS AGAINST THE REQUIREMENTS OF DIN VDE /A3

ANSI/NEMA WC ICEA S Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

MATERIAL STANDARD FOR CABLES AND WIRES

INTERNATIONAL STANDARD

UNDERGROUND CABLE DISTRIBUTION UP TO AND INCLUDING 33kV AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD)

H. Underground Transmission System Design

ANSI/NEMA WC 71 ICEA S Nonshielded Cables Rated V for Use in the Distribution of Electric Energy

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables.

26/35kV Copper XLPE Insulation Electric Cable

Glossary Of Terms M-1

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

Article-No. Type. All dimensions in mm. Subject to technical changes. Other dimensions, reel lengths or colours available on request.

PRY-MOULD. High Voltage Accessories for Extruded Cables

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire

Electrical Insulating Tapes

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

Cables ELE E L CT E C R T R IC I C A A L L

Construction guideline

Selection of the Correct Optical Cable Outer Jacket for the Application

FLEXIBLE POLYMERS WIRE & CABLE GRADES FOR MEDIUM/HIGH VOLTAGE POWER CABLES.... we make better polymers

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

UNIFIED FACILITIES GUIDE SPECIFICATIONS

THE PATHWAY TO POWER HIGH AND EXTRA HIGH VOLTAGE CABLES

POLYMERIC ARMOR DESIGN OF AN IMPROVED PROTECTION TO MECHANICAL STRESSES AND FLUIDS FOR OIL GAS AND PETROCHEM (OGP) APPLICATIONS

Serv. Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

INSTRUMENTATION, CONTROL AND THERMOCOUPLE CABLES

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

ANSI/NEMA WC ICEA S Standard for Control, Thermocouple Extension, and Instrumentation Cables

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

SERV-RITE Wire and Cable

A REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES

40/69 kv to 127/220 kv XLPE

Una e mpre sa Vi akab l e GLOSSARY.

A Deep Insight on Improvement in HV and EHV XLPE AC Cable Technology

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

Underground System Design TADP 547

NPS/002/023 Technical Specification for 132kV Power Cables.

Comparison of BS 5308, PAS 5308 and BS EN

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

Engineering Recommendation G81- Part 2: Materials Specification

3M Cold Shrink Joint, SC145-II/SS145-II

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for

THE PROVISION AND INSTALLATION OF ELECTRICITY SERVICE, INTAKE AND DISTRIBUTOR CABLES TG-PS-881

Asset Management of MV Cables using Data Driven Health Indices for Water Treeing

CG78-06B1A. Product Classification. Dimensions. Electrical Specifications. Environmental Specifications. General Specifications

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

Instrumentation and Thermocouple Cables

Instrumentation and Thermocouple Cables

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

LONG TERM SUSTAINABILITY OF CABLES. David E. Griffiths Olex New Zealand Limited

URD CABLE DESIGNS FOR THE FUTURE. Bruce S. Bernstein Consultant Rockville, Maryland

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems

COMPOUNDING OF SEMICONDUCTIVES FOR HIGH VOLTAGE CABLES

FURUKAWA ELECTRIC TAPE FOR ELECTRICAL USES


Your Partner for Custom Interconnectivity Solutions. ISO 9001 AS9100C ISO ISO Qualified

Analysis and design of composite structures

PVC Insulating Tape. Electrical Tapes

Your Partner for Custom Interconnectivity Solutions. ISO 9001 AS9100C ISO ISO Qualified

TI 20 PVC TI 20 INSULATED TELEPHONE WIRE

Transcription:

HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES Nigel Hampton Copyright GTRC 2012

Objective To present the evolution of cables in time to understand the lessons from the past: the legacy problems and their solution Outline Timeline Cable components Legacy problems - Cables Current challenges 2

Timeline 3

Cable History Historical perspective is important, it tells us: What works What does not What is still out there What challenges it presents How large the problems may be or become How to avoid mistakes 4

Timeline 1812-1942 1812: First cables used to detonate ores in a mine in Russia 1870: Cables insulated with natural rubber 1880: DC cables insulated with jute in Street Pipes Thomas Edison 1890: Ferranti develops the concentric construction for cables 1942: First use of Polyethylene (PE) in cables 1937: Polyethylene (PE) developed 1925: The first pressurized paper cables 1917: First screened cables 5

Timeline 1963-1990 1963: Invention of crosslinked polyethylene XLPE 1967: HMWPE insulation on UG cables in the US (Unjacketed tape shields) 1968: First use of XLPE cables for MV (mostly unjacketed, tape shields) 1972: Problems associated with water trees (MV) and contaminants (HV) Introduction of extruded semicon screens 1990: Widespread use of WTR materials - Be, Ca, De, Ch & US 1989: Supersmooth conductor shields for MV cable in North America 1982: WTR materials for MV in USA & Germany 1978: Widespread use of polymeric jackets in US & Ca 6

Insulation History - Global Ref [11] 600 500 Voltage (kv) 400 300 200 100 Type Paper Polymer 0 1900 1925 1950 Year 1975 2000 7

AEIC Standards Development - MV Edition Number 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 MV Cables 1900 1920 1940 1960 1980 2000 2020 Year Laminated Insulation: AEIC CS1 Extruded Insulation: AEIC CS8 (previous CS5 and CS6) Laminated Insulation Extruded Insulation 8

AEIC Standards Development HV / EHV Edition Number HV-EHV Cables 9 8 7 6 5 4 3 2 1 0 1920 1940 1960 1980 2000 2020 Year Laminated Insulation Low-Medium Pressure Laminated Insulation High Pressure Extruded Insulation Laminated Insulation: AEIC CS4 (Low- Medium Pressure) AEIC CS2 (High Pressure) Extruded Insulation: AEIC CS7, CS9 and CG4 9

Initial American Installations Ref [7] 10

From Edison s to Today s Cable Picture: Brian Besconnal Picture: Black, 1983 Edison Street Pipe Picture: Southwire Pictures: Prysmian 11

Cable Components 1. Conductor 2. Conductor Shield or Screen 3. Insulation 4. Insulation Shield or Screen 5. Metallic Shield 6. Jacket (Recommended) Picture: Southwire 12

Carries the current 1. Conductor Resistance should be small to reduce power losses: P = R x I 2 Flexibility, weight and susceptibility to corrosion are concerns together with economical issues such as cost, availability, and salvage value 13

Conductor Characteristics Conductor Aluminum Copper Stranded Solid Stranded Blocked Unblocked Blocked Unblocked 14

2. Conductor Shield Provides for a smooth interface between the conductor and the insulation With no conductor shield, electric field lines are concentrated, creating high stress points at the conductor/insulation interface. High Stress Finite Element Simulation 15

Conductor Shield Characteristics Conductor shields are semiconductive, so they are neither an insulator nor a conductor. Semiconducting materials are based on carbon black (manufactured by controlled combustion of hydrocarbons) that is dispersed within a polymer matrix On larger conductor sizes, tape shields are often used to prevent material fall-in between the strands during manufacture Conductor Shield Bonded Conventional Supersmooth Superclean (SS/SC) 16

3. Insulation Contains voltage between the conductor and ground Must be clean Must have smooth interfaces with the conductor and insulation shields Must be able to operate at the desired: Electrical Stress Temperatures 17

Insulation - MV Insulation Laminated Extruded PILC Thermoplastic Thermoset HMWPE XLPE Prior Technologies Today s Technologies WTR XLPE EPR 18

MV Cable Installed Capacity In USA Ref [18] Oldest Youngest 19

MV Extruded Cable Installed in USA Ref [18] MV cables installed in the US (Millions of ft) 7000 6000 5000 4000 3000 2000 1000 EPR TR XLPE XLPE HMWPE 0 1964 1970 Data courtesy of Glen Bertini 1976 1982 Year 1988 1994 2000 20

Insulation HV / EHV Insulation Laminated Extruded Self Contained Pipe Type Thermoset Paper XLPE Prior Technologies Today s Technologies PPL - EHV only EPR HV only 21

Examples of Laminar Insulation Cables Pictures: Prysmian Picture: Southwire 22

Examples of Extruded Insulation Cables Pictures: Prysmian Pictures: Southwire 23

4. Insulation Shield Keeps the voltage and stress within the insulation With no insulation shield, electric field lines are concentrated, creating high stress points on the outside surface of the insulation. High Stress Finite Element Simulation 24

Belted Cables Early laminated cables had a belt of insulation over the core insulation. This led to tangential stresses that were a cause of a lot of early failures Finite Element Simulation 25

Conductor and Insulation Shield (CS & IS) Effect Finite Element Simulation When both shields are: smooth intact Then, electric field lines are uniform, with a controlled electrical stress distribution. 26

Insulation Shield MV, HV, and EHV Often same compound as CS Preferred in North America, Asia & parts of Europe. Thought to permit easier termination & splicing of cables but service performance is very dependent upon the workmanship / training of the installer, which is often variable Laminated Insulation Carbon Black Paper Perforated metallized paper 27

Types of Metallic Shields Metallic Shield Concentric Copper Wire Corrugated Sheath Laminated Sheath Tape Extruded Copper Lead Wire Copper Copper Aluminum Aluminum Flat Strap Aluminum Aluminum Stainless Steel 28

Examples of Metallic Shields Courtesy of Southwire A B C D E A Welded Copper Corrugated Sheath B Welded Aluminum Corrugated Sheath C Concentric Copper Neutrals D Copper Neutrals with Copper Composite Laminate Sheath E Copper Neutrals with Aluminum Composite Laminate Sheath Pictures: Southwire 29

Types of Jackets Materials Jacket Semiconductive Special Standard Carbon black filled co polymers Enhanced Grounding Neoprene Nylon Polypropylene LSF Hypalon* * No longer available PE Chemical / Thermal Resistance PVC LLDPE MDPE HDPE PP 30

Legacy Issues Cables 31

Differing designs Belted vs. shielded Jacketed vs. unjacketed PILC Cables Lead corrosion (PILC) Temperature performance and stability of impregnants Draining of compounds Dry insulations Collapsed Joints Overheating due to high dielectric losses Moisture ingress leading to overheating Loss of impregnant due to lead sheath leaks Combinations of the above 32

Remaining PILC in US Networks Ref [15] Where PILC remains on the system it retains a significant presence Estimated for US Utilities in 2010 (some utilities segregated) 33

The PILC experience teaches us that today s decisions will be with engineers for a very long time Ref [15] 34

Extruded Cables Differing designs Jacketed vs unjacketed Extruded shields vs graphite shields Dirty insulation compounds (PE, early XLPE) Insulations that were susceptible to water treeing (PE, early XLPE) Poor manufacturing processes Open compound handling procedures Changing Formulations (EPR) Inadequate cable designs Unblocked conductors Unjacketed cables Cables with inadequate neutral designs Combinations of the above 35

Current Challenges 36

Percentage of Failures per each Component Percentages of failures of each component Ref [17] Termination 1.4% Cable 43.2% Joints 55.4% Accessories: Joints or splices, and Terminations 37

Failure Modes Ref [17] Corrosion 4% Overheat 4% Aging 6% Moisture 4% Event 3% Overload 2% Dielectric breakdown 10% Maintenance failure 2% Mechanical Damage 1% Manufacturing problem 14% Contamination 1% Poor workmanship 49% 38

Building a Reliable Cable System Awareness Customer Service Application Design Materials Specs Manufacturing Testing Installation Operation 39