Technical Service Bulletin

Similar documents
Technical Service Bulletin

Cooling Tower Treatment Chemicals

MEMBRANE PRODUCTS PLEASE CONTACT YOUR LOCAL NORLEX CHEMICALS PARTNER FOR MORE INFORMATION ON THESE TYPES OF PRODUCTS.

BIOXIDE. Slimicide, Biocide, Biodispersant, Bio-oxidation

Membrane Technology: From Manufacture to. May Production

Technical Service Bulletin September 2018 TSB131.11

4709 Hwy 36 South, Suite 10 Rosenberg, TX Phone:

Operation of Hydranautics New ESNA Membrane at St. Lucie West, FL Softening Plant

SANITIZING OF MILK CASE WASHERS AND TRANSPORT CONVEYORS: AN OVERVIEW OF CURRENT PRACTICES AND ADVANTAGES OF CHLORINE DIOXIDE USE

Improved Robustness and Chemical Resistance of Nanofiltration Membranes GeoEnergy 2018

Chloramine: An Effective Biocide for Produced Waters. Andrew K. Boal, Ph.D. and Charles Mowery

FILMTEC Membranes System Design: Introduction

Cleaning. DATA Monitoring

Ozone Technology for Winery Applications presented by DEL Ozone. Page 1

AQUCAR 742 Water Treatment Microbiocide for the Oilfield (NA, LA, Europe)

Scale and Deposition are Often the First Problem Associated With Tower and Refrigeration Systems

1. Cleaning of RO membrane... 3

Operating Guidelines Cleaning

REQUEST FOR PROPOSALS DESAL ANTISCALANT/CLEAN-IN-PLACE CHEMICALS BID NO: ADDENDUM 1

An Unmanned Approach for the Optimization of a Chemical Injection Program at a Salt Water Disposal Facility

Some Standard Membranes: Filmtec Membrane, Hydronatics Membrane, Torry membrane and Koch Membrane.

Reverse Osmosis. Background to Market and Technology

Zero Discharge Treatment Method for Cooling Towers and Heat Exchangers with SP3, I-SOFT-OB, OXYDES & KATALOX LIGHT

1. The Antiscalant, and/or CIP chemicals where specified, provided under this contract shall meet the following specifications:

Application solution ph: * (1 %, 20 C, 0 d water) P3-ultrasil 73 is, under the application conditions described below, compatible with

Bringing new ground in

Compatibility of Scale Inhibitors and Biocides with Fracturing Fluids. Christy C. Wentworth, Ph.D.

Direct count methods should be preferred, because they are much faster and more accurate than culture techniques.

REVERSE OSMOSIS WATER TREATMENT

Technical Service Bulletin January 2018 TSB

Treatment of all source water influent & effluent for user application, be it commercial, industrial, domestic, to defined & required standards.

The New Rules: Desalination, Chloramination and Beyond

Submission of comments on ' Q&A on production of WFI by non-distillation methods - RO and biofilms and control strategies' (EMA/INS/489331/2016)

Advances in Membrane Performance

1. Inspection and monitoring... 3

Improved control of SRB s in hydraulic fracture fluid using chlorine dioxide

Session 311: Effects of TSS on Peracetic Acid Dosing for CSO Events

Technologies for Removing Contaminants from Produced Water

Biological Control of Water

Using a Novel Hybrid NF-RO to Enhance Sodium Chloride Removal

OsmoBC Integrated Membrane Systems

Sepro Cleaning Guidelines for Spiral E-Coat Elements

What is Chlorine Dioxide and Why You Should Learn About It Now?

Treatment for Blended Produced and Fresh/Brackish Water

Application solution ph: (1 %, 20 C, 0 d water) Conductivity: ms/cm * (1 %, 20 C, deionized water)

Water Quality in Broiler Houses

White Paper. A Reliable Alternative to Chemicals for Cooling Water Treatment. GWS-1107-D 10/31/11 Copyright 2011 All Rights Reserved

Summary of Issues Strategies Benefits & Costs Key Uncertainties Additional Resources

RO System Design & CSMPRO v6.0 Program

Water sanitation at its best

PRODUCT SUMMARY. Water Treatment Chemicals. Aug 2016

Water supplied by Marafiq does not meet the process requirements.

PLANT OPTIMIZATION FOR AN INLAND INDUSTRIAL RO REUSE FACILITY. Abstract

GRUNDFOS WHITE PAPER. Chlorine dioxide offers increased efficiency and

Kuriverter IK 110. Biofilm control agent for membrane systems Dosage Automatisation ISBN

Introducing the Roving Blue OZO-Pen OZO-Pod and Ozo-Flow Line of Commercial Water Ozone Generators: Efficient and affordable electrolytic ozone

How can liquid ozone be used in different industries?

AQUCAR GA 30 LT Water Treatment Microbiocide

Property of ChemTreat, Inc. Do not copy without permission.

Split partial second pass design for SWRO plants

AD26 Systems for Iron, Manganese, Sulfide and Arsenic Removal

Novel Low Fouling Nanofiltration Membranes. Craig Bartels, PhD, Hydranautics, Oceanside, CA Warren Casey, PE, Hydranautics, Houston, TX

Gregory E. Choryhanna and Alan R. Daza, SEPROTECH SYSTEMS INC. Process Development Division Ottawa, Canada

Reduced Footprint Water Treatment Technology

DESALINATION CHEMICALS: CHEMICAL USE IN WATER TREATMENT

BENEFICIAL USE OF PRODUCED WATER SOUNDS SIMPLE ENOUGH. Rick McCurdy, Ground Water Protection Council s Annual UIC Conference February 21-23, 2017

Breaking new ground in

Schematic diagram of a cooling water system

New Generation of Low Fouling Nanofiltration Membranes

CENTRAL DISINFECTION SYSTEM

1. Fouling and Scaling in RO Membrane Systems... 3

Design Parameters Affecting Performance

Risk to GSHP Closed Circuit Systems Methodology & Analysis. John Westerman

ACUMER ACUMER 4450 ACUMER 4800

BIOBAN CWT Brand of 25% Aqueous TRIS(HYDROXYMETHYL)NITROMETHANE Cooling Water Treatment Microbicide EPA Reg. No

City of Boca Raton s NF Plant: A Plant History

Water Treatment. Industrial Water Treatment

Beer Line Disinfection System

March 28, 2019 Maintaining a Clean Brewery Presenter: Richard Rench Q&A Session

EXHIBIT A UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES

P3-ultrasil 67. Properties. Description: Product strengths: Neutral, enzymatic, liquid detergent for membrane filtration plants

PRESENTATION OF DESALINATION VIA REVERSE OSMOSIS

MICROBICIDES FOR COOLING WATER SYSTEMS

RO OPERATION. Problems & Latest Solutions. Iran May 2015 HOSSEIN OSTOVAR

STANDALONE ADVANCE DISINFECTION SYSTEM FOR SWIMMING POOL WATER TREATMENT

FILMTEC Membranes. FILMTEC Membranes Reclaim Waste Water at 86% Recovery in Singapore. Case History

Bucking the Industry Trend. Simple Change to Water System Saves New Jersey Manufacturer $23,000 Annually

Breaking new ground in

Cartwright Consulting Co.

Compatible with all PWT pretreatments.

Cartwright Consulting Co.

Membrane Treatment Technologies for Wastewater Treatment

USE OF CHLORINE DIOXIDE FOR BIOFILM CONTROL IN A PACKED-BED, VOC SCRUBBER SYSTEM

Membrane BioReactor: Technology for Waste Water Reclamation

Aeration for Produced Water Management

MIC on level Bridle. Presented by: Amilcar Oberto Corrosion Engineer

Evaluation of New Generation Brackish Water Reverse Osmosis Membranes. William Pearce City of San Diego. Manish Kumar MWH, Pasadena

White Paper. Chemical dosing and blending - the role of precision actuators

The motors used on Thunder 500, 1000, 1500, 1800 and 2500 systems are carbonator motors. They are available in 110/220 volt 50/60 hertz 1 phase.

The printed material you requested is attached. fyi

Transcription:

Technical Service Bulletin March 2015 TSB110.12 Biocides for Disinfection and Storage of Hydranautics Membrane Elements This bulletin provides general information about biocides that may be used with Hydranautics membrane elements for disinfection and/or storage. Before storage or disinfection of Hydranautics elements, one should become familiar with Technical Service Bulletins 108 and 118 which describe the general storage and flushing procedures for all Composite Polyamide, and PVD membrane elements. Also, one should confirm which type of membrane elements are actually in the system. Since elements may be composed of either composite polyamide membrane or polyvinyl derivative, it is imperative to be certain of the type to be disinfected. If any uncertainty exists regarding the type of elements in use, please contact Hydranautics for confirmation of compatibility of specific procedures with membrane types. Warning: Some of the biocides listed in this procedure are toxic in some degree to humans. Allow ample time for system flushing to remove the presence of the biocides before commencing normal operation. Hydranautics assumes no liability for the misuse of any chemical listed herein, and all safety issues are the responsibility of the end user. Consult manufacturers material safety data sheets (MSDS s) for proper handling and disposal of any of the listed chemicals.

TSB110.12 Page 2 Biocides which can be used with Composite Polyamide (ESPA, ESNA, Nano, CPA, LFC, SWC) and Polyvinyl Derivative (PVD) Membrane Elements DBNPA It is understood in the membrane industry that thin film composite polyamide membranes have limited resistance to chlorine based oxidants. Therefore, operators have relatively few options regarding chemicals which can be safely used to disinfect RO/NF systems and prevent biogrowth/biofouling. One option is the chemical, 2,2-Dibromo-3-nitrilopropionamide (DBNPA), which is a fastacting, non-oxidizing biocide which is very effective at low concentrations in controlling the growth of aerobic bacteria, anaerobic bacteria, fungi and algae. The chemical formula of DBNPA is: DBNPA is an advantageous disinfectant since it also quickly degrades to carbon dioxide, ammonia and bromide ion when in an aqueous environment. This allows the effluent to be safely discharged even in sensitive water bodies. It is degraded by reactions with water, nucleophiles, and UV light (rate is dependent on ph and temperature). The approximate half-life is 24 hr @ ph 7, 2 hr @ ph 8, 15 min @ ph 9. The vast majority of microorganisms that come into contact with it are killed within 5 to 10 minutes. Product Forms Most RO/NF chemical suppliers have a premixed private label version with varying solution concentrations of 5% to 20% or available as a white crystalline solid. Recommended Usage for RO/NF Systems For slug dosing, the supplier recommends 10 30 ppm of active ingredient for 30 minutes to 3 hours every 5 days (for waters less prone to biological fouling).

TSB110.12 Page 3 Slug dosing can be performed during service operation, during a low pressure flush mode, or by a batch CIP (Clean-In-Place) system. RO/NF permeate may need to be diverted to drain as operations dictate, though it is estimated that greater than 98% of the DBNPA is rejected by brackish water membranes and greater than 99.5% by seawater membranes. For waters containing > 100 CFU/ml (or if you already have biofilm within the RO/NF system), suppliers recommend 30 ppm active ingredient for a full 3 hours. During slug dosing, the permeate should be dumped to drain if product water is for a potable use. If a biofilm is present, sanitization should be preceded by an alkaline cleaning. For continuous dosing during service operation, between 0.5 to 2 ppm of active ingredient is recommended to maintain a biostatic environment. RO/NF permeate may need to be diverted to drain as operations dictate. Continuous dosing can be significantly more expensive in terms of operating costs so the site situation will dictate if this is instituted. DBNPA is deactivated by reducing agents, so a higher concentration of DBNPA will be required if residual reducing agents are present in the feed water. For example, Sodium Bisulfite (SBS) will deactivate DBNPA. If SBS is dosed during service or flushing operations, additional DBNPA will be required at a suggested dose rate of 1.0 to 1.3 ppm DBNPA per 1 ppm of SBS to account for deactivation. Excess SBS can also be used to accelerate the deactivation of DBNPA in discharged waters. Although DBNPA is non-oxidizing, it will give an ORP reading of about 400 mv when in the range of 0.5 3 ppm ( for comparison, 1 ppm chlorine typically gives an ORP reading of about 700 mv). For CIP use, 30-50 ppm of active ingredient for 1 hour would be recommended. For heavy biofilms, it should be followed by an alkaline cleaning. Test kits are available from the chemical suppliers to verify that DBNPA is at the desired concentration or has been completely rinsed from the system. Warnings DBNPA is corrosive to metals, so plastics are preferred for storage and metering pumps. This is not as much of a concern at the very low concentrations used in RO/NF systems. DBNPA has minimal toxicology concerns, but the supplier recommends that for potable water systems the permeate be dumped during slug-dosing. Only off-line use of DBNPA is recommended for potable water systems.

TSB110.12 Page 4 DBNPA is classified as a weak sensitizer. As when handling any chemical, reference the Material Data Safety Sheet (MSDS) for precautions and proper handling and storage. Although DBNPA is useful as a disinfectant, it should not be used for storage since it is not long-acting IMPORTANT: Users should review all technical product documents and talk to their supplier to ensure that they have the most recent and accurate information regarding precautions associated with the use of DBNPA. Isothiazolin Isothiazolin is another broad spectrum, non-oxidizing biocide. It is used to target aerobic and anaerobic bacteria, fungi and algae. Common forms of Isothiazolin are: Isothiazolin has a much less rapid kill rate than DBNPA, therefore, DBNPA may be the initially preferred biocidal product to try. Slug dose rate for isothiazolin is typically in the range of 50 100 ppm, with a contact time of about 4 hours. Isothiazolin is more effective than DBNPA in waters with high organic content, and can be used at low dose rates on a continuous basis (10 20ppm). It should be used in a ph range of 6-9. It is recommended to clean the RO/NF of foulants, particularly organic in nature, prior to the use of isothiazolin. Continuous dosing of active isothiazolin can be instituted to inhibit microbial growth, and it should be injected as far upstream in the process as possible to limit microbial growth over the entire system. Isothiazolin is highly effective for train preservation for controlling biological growth in off-line trains for extended periods. The recommended long term preservation dose is 500-1000 ppm. The maximum period is six months.

TSB110.12 Page 5 Warnings The supplier recommends that for potable water systems the permeate be dumped during slug-dosing. Only off-line use of Isothiazolin is recommended for potable water systems. Isothiazolin is classified as a sensitizer. As when handling any chemical, reference the Material Data Safety Sheet (MSDS) for precautions and proper handling and storage. IMPORTANT: Users should review all technical product documents and talk to their supplier to ensure that they have the most recent and accurate information regarding precautions associated with the use of Isothiazolin Sodium Bisulfite Sodium bisulfite (SBS) can be used as a non-oxidizing inhibitor of biological growth at higher doses, particularly for aerobic bacteria. SBS at higher doses may be considered to have biostatic properties that inhibit biological growth, in part by removing available oxygen to aerobic bacteria, which in turns creates a hostile environment for bacteria, algae, and fungi to grow. To control biological growth with sodium bisulfite, it is applied at a dosing rate of 500 ppm for 30 to 60 minutes daily. Sodium bisulfite at a 1% concentration can also be used as a preservative during long term storage of the membrane elements. Membranes preserved in a 1% SBS solution in a pressure vessel should be checked on a monthly basis to assure proper preservation. If the ph of the preservation solution drops below 3.0 due to oxidation by air, the solution must be replaced to prevent membrane damage. Formaldehyde A formaldehyde solution of 0.1 to 1.0% concentration may be used for system disinfection and as a preservative for long term storage. The membrane elements should be operated for at least 24 hours before being exposed to formaldehyde. (See NOTE below.)

TSB110.12 Page 6 Glutaraldehyde A glutaraldehyde solution of 0.1 to 1.0% concentration may be used for system disinfection and as a preservative for long term storage. The membrane elements should be operated for at least 24 hours before being exposed to glutaraldehyde. (See NOTE below.) NOTE: Addition of formaldehyde and/or gluteraldehyde to new elements may cause flux reduction of 10-50% depending on specific membrane chemistry. To minimize the chances of flux reduction, membrane elements should be run for a minimum of 24-hours prior to exposure to formaldehyde and or gluteraldehyde. Regardless, first time exposure to formaldehyde and/or gluteraldehyde may result in permanent flux loss. Subsequent exposure to formaldehyde and/or gluteraldehyde will result in additional temporary flux loss and will require significant flushing to return to pre-exposure flux rates. Hydrogen Peroxide If the feed water contains any hydrogen sulfide or dissolved iron or manganese, the oxidating disinfectant (hydrogen peroxide) should not be used. Please contact Hydranautics for alternative methods of disinfection. Hydrogen peroxide or a solution of hydrogen peroxide with paracetic acid can be used for disinfection. Special care must be taken that transition metals (Fe, Mn) are not present in the feed water, since in the presence of transition metals oxidation of the membrane surface may occur resulting in membrane degradation. The concentration of hydrogen peroxide in the disinfecting solution should not exceed 0.2%. Hydrogen peroxide should not be used as a preservative for long term storage of membrane elements. During application of hydrogen peroxide the water temperature should not exceed 25 C.

TSB110.12 Page 7 THPS Tetrakish(hydroxymethyl) phosphonium sulfate (THPS) is used on oil production offshore platforms for sulfate-reducing bacteria (SRB) control. It is reported to be an environmental friendly biocide that is proved to be useful against SRB. THPS is stable and persistent under abiotic conditions at acid phs. When ph is above 8, it degrades within a week. The degradation products are trishydroxymethyl phosphine (THP) and trishydroxymethyl phosphine oxide (THPO). Slug dosing rate may be used at 50-100 ppm. The continuous dosing rate may be used at 10-20 ppm. The recommended long term preservation concentration is 600 ppm to 1000 ppm for RO and NF treatment system for SRB control on offshore oil production application. This can lead to 25-30% flux reduction right after the chemical dosing. Studies have shown that this flux loss can be recovered by caustic or certain surfactant cleaning. HYDRANAUTICS 401 Jones Rd. Oceanside, CA 92058 Tel# (760) 901-2500 Fax# (760) 901-2578 e:mail: info@hydranautics.com www.membranes.com