SECTION PACKAGE BOOSTER PUMP STATIONS

Similar documents
SUGGESTED SPECIFICATIONS Pump Frames through 64132

SPECIFICATIONS - DETAILED PROVISIONS Section Horizontal Centrifugal Water Pumps C O N T E N T S

1DIVISION 15- MECHANICAL Section Fire Pumps. A. Single Stage, Double Suction, 9100 Series Horizontal Splitcase Fire Pump (Base Mounted)

DIVISION 15- MECHANICAL Section Fire Pumps

SPECIFICATIONS - DETAILED PROVISIONS Section Progressing Cavity Pump C O N T E N T S

SD/SW/VS50 SD50 SW50 VS50

SHEF40. Performance Data. Wholesale Products Page: Section: Performance Data Dated: April 2002 Supersedes: January 2001

SUGGESTED SPECIFICATIONS

SECTION PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS

SECTION SLUDGE HOLDING TANK DECANTER PUMP

Series Sump and Sewage Systems

HUP. Performance Data. Wholesale Products Page: Section: Performance Data Dated: January RPM: 1550 Discharge: 1" Solids: 1/8" GPM: TDH:

2. Water Pressure Booster Systems. 3. Duplex Pedestal Type Sump Pumps.

SPX50/SPX50H. Performance Data. Wholesale Products Page: Section: Performance Data Dated: October 2007

SK50. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK50 SK Liters/Second Capacity-U.S. G.P.M.

SECTION PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS

G2DT Series Performance Data Discharge: 1-1/4 Solids: 1/4. Wholesale Products Page: JP10074SSD-1 Section: Performance Data Dated: January, 2011

HPGR200 2 HP. Capacity-U.S. G.P.M.

HYDROMATIC BV-40 SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

G2D Series Performance Data Discharge: 1-1/4 Solids: 1/4. Wholesale Products Page: JP10075SSD-1 Section: Performance Data Dated: January, 2011

DIVISION 33 UTILITIES SECTION PACKAGED SEWAGE GRINDER PUMPING UNITS

A. This Section includes the following sump pumps and accessories, inside the building, for building storm drainage systems:

SECTION COOLING TOWER

SUBMERSIBLE SEWAGE EJECTOR

MODEL 16ASX T/S - SPECIFICATION

HYDROMATIC SKV50 SEWAGE EJECTOR PERFORMANCE DATA SKV50. Wholesale Products Page: RPM: 1650 Discharge: 2 Solids: 2.

HYDROMATIC W/D/V-A1 SUBMERSIBLE SUMP/EFFLUENT

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

SECTION INFLUENT EQUALIZATION TANK PUMPS

SECTION SUBMERSIBLE GRINDER PUMPS FOR WASTEWATER (LESS THAN 10 HORSEPOWER)

High Light. Motors are fully submersible Pumps can handle up to 2 spherical solids Indoor and outdoor installation Easy installation and removal

VSS S U B M E R S I B L E S E W A G E P U M P S

SK75/100. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK100 SK Liters/Second Capacity-U.S. G.P.M.

Index - Section 40M Medium Sump / Drainage Pumps Bulletins 4508

SECTION MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS

SUGGESTED SPECIFICATIONS

A. Operation and Maintenance Data: For pumps and controls, to include in operation and maintenance manuals.

Stainless Steel Aeration Equipment Specification

DIAGRAM FOR CALCULATING PIPE SIZES, DISCHARGE VELOCITIES AND LOSS OF HEAD IN STANDARD STEEL PIPE PIPE FRICTION LOSS CHART

B. Wiring Diagrams: For power, signal, and control wiring.

High Light. Motors are fully submersible Pumps can handle up to 2½ spherical solids (for 3 Discharge pumps only) Indoor and outdoor installation

TARRANT COUNTY PURCHASING DEPARTMENT

SECTION ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED

W ARR A NTY FAIRBANKS NIJHUIS 1600 SERIES SINGLE STAGE END SUCTION PUMPS. Certified to NSF/ANSI 372.

SECTION CISTERN SYSTEMS

SECTION HVAC PUMPS. A. Provide centrifugal HVAC pumps, called for in drawing schedule, and as needed for a complete and proper installation.

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT

High Light. Motors are fully submersible Pumps can handle up to ½ spherical solids Indoor and outdoor installation Easy installation and removal

LABORATORY & DEIONIZED WATER SYSTEMS DESIGN AND CONSTRUCTION STANDARD

Wilo MC Self Priming, Horizontal Multi-Stage, High Pressure Pumps. Engineering Specification

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...

SECTION MOTORS AND PUMPS FOR PLUMBING SYSTEMS

SECTION The specification section is organized by placing information in three standard parts:

SECTION FIELD ERECTED INDUCED DRAFT COOLING TOWER

SERIES 800 Quality Design Features Assure Long, Trouble-Free Service

FAIRBANKS NIJHUIS SUBMERSIBLE SOLIDS HANDLING PUMPS.

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition

Rugged, reliable and efficient sump pumps... your assurance of a dry basement!

special needs surface trajectory costs. High Efficiency 3. 4.

FAIRBANKS NIJHUIS SUBMERSIBLE SOLIDS HANDLING PUMPS.

SINGLE STAGE END SUCTION PUMPS AURORA Series. Distributed By: Model 3804

Pump Specifications 450 Series 1/2 hp Submersible Sump Pump

SPECIFICATIONS - DETAILED PROVISIONS Section Chlorination System (On-site Sodium Hypochlorite Generation System) C O N T E N T S

FYBROC SERIES 2530 CLOSE-COUPLED SEALLESS PUMPS

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL

VSS-2 ½ D HIGH HEAD SUMP PUMP FREE STANDING

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...

Close Coupled Sealless Pumps

The motor shall be high-starting torque, ball bearing, rated at 460 V, 3 phase

t y p e V S A S E W A G E P U M P

SECTION LINEAR MOTION SLUDGE MIXERS

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

griswold EF&G Heavy Duty end suction

Submersible Axial Flow Propeller Pumps

Technical Handbook. ASME B73.1 Chemical Processing Pump. Model

A. Product Data shall be provided for each type of product indicated.

C o l u m n S u m p P u m p s

T Series. Self-Priming Centrifugal Pumps

VALLECITOS WATER DISTRICT SECTION POLYVINYL CHLORIDE (PVC) PRESSURE PIPE

SECTION FIRE HYDRANTS

Self-Priming pumps, when it really matters

Close Coupled Sealless Pumps

Weir Specialty Pumps. WEMCO Torque-Flow

SUBMERSIBLE PUMPS FOR WASTEWATER (S-114)

SECTION VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

N N O V A T I O N E F F I C I E N C Y Q U A L I T Y VTG. Vertical Turbine Generator

Model EVMS Vertical Multistage Pumps for the Global Market

Series A-C Single Stage Double Suction Large Split Case. TECHNICAL Brochure BAC9100

YEOMANS SUBMERSIBLE SOLIDS-HANDLING WASTEWATER PUMPS YEOMANS

FF200, FOUR-FOLD DOORS CONSULT MANUFACTURER FOR ADDITIONAL OPTIONS OR MODIFICATIONS.

Goulds API ISO / API 610 VS4 Vertical Sump Pump

SECTION MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT

Goulds Two Stage, Horizontally Split Case Pump

University of Delaware

MJ / MJ-B Series Standard Non Metallic Magnetic Drive Pumps

SECTION VERTICAL TURBINE PUMPS AND APPURTENANCES

SPECIFICATIONS - DETAILED PROVISIONS Section Stainless Steel Sluice Gates C O N T E N T S

ARCHITECTURAL DESIGN SPECIFICATIONS CRB CRASH BEAM VEHICLE BARRIER. PART I General

LIQUID-SPECIFIC PRODUCT LINE: ABRASIVE LIQUID PUMPS SERIES DESCRIPTION OPERATING RANGE: IMPROVEMENTS NOMINAL FLOW RATES:

Transcription:

SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to the new water tank proposed for the project and/or to serve as a booster station to maintain system pressures in outlying or elevated areas. Owner shall use allowance item in the bid to purchase booster pump stations complete with pumps, enclosure, lighting, electrical boxes, and other appurtenances. Submittals: Once locations are selected for the pump stations, Contractor shall submit written plan for approval by Owner for installation including descriptions of road access construction, fencing, concrete slab for setting of booster pump station, provision for getting electrical power to the station and any other aspects of the work required to complete a working installation. Products: A. Pumps : The pumps shall be End Suction, Centerline Discharge as manufactured by Blackmer, or equal. All pumps shall be NSF 61 approved. B. Casing: The pump casing shall be made of ductile iron material. The casing is to be supported on two (2) legs made of ductile iron, to prevent misalignment of the pump casing at elevated temperatures. The suction and discharge neck will be drilled and taped with ¼ NPT connections for pressure gauges and/or auxiliary piping. C. Centerline Support Legs and Universal Foot: The centerline casing support legs and bearing frame universal foot are to be slotted construction, to allow for best alignment with suction and discharge piping, to minimize pipe strain and eliminate the need for shimming. The universal foot shall be provided with jack bolt to permit vertical positioning. D. Shaft: The pump shaft shall be solid 316 SS with no sleeve. Minimum shaft diameter at stuffing box face, 1.875 inches. The stiffness ratio (L3/D4) shall not exceed a value of 55 in order to establish satisfactory mechanical seal life. Minimum shaft diameter at the coupling shall be 1.375 inches. E. Bearings: The thrust bearings shall be dual angular contact type, one side ground for mounting back to back. Double row filled slot bearings are not acceptable. The thrust bearing shall be locked into the cartridge by a bolted-on retainer cover, to minimize the end play of the shaft, and to permit a positive lock of the thrust bearing outer face. A snap ring thrust bearing retainer is not acceptable. Radial and thrust bearings shall be C3 rated clearance. Radial bearing shall be 6310 or equal, thrust bearing shall be 7310 BYG or equal. F. Bearing Oil Seals: Each end of the bearing frame assembly shall incorporate non-contacting labyrinth oil seals, lip seals are not acceptable. G. Bearing Frame : The bearing frame shall be heavy duty construction cast iron with radial fins for maximum cooling. The oil sump shall contain a minimum of one (1) quart of oil to allow for more heat dissipation, better lubrication and a cooler running element. The oil level within the bearing frame shall be monitored by an oil sight glass. The oil sight glass shall have a white color perforated background, to permit visual inspection of the condition of the oil, an oil drain plug is required at the bottom of the bearing frame. Two (2) magnetic pipe plugs shall be located near the bottom of the bearing frame.

331223-2 H. Impeller Clearance Adjustment: The thrust bearing end of the bearing frame shall incorporate a micrometer impeller adjustment external of the thrust cartridge (a threaded thrust cartridge is not acceptable). All adjustments must be made without the use of shims, dial indicators, or feeler gauges. I. C-Frame Motor Adapter: The pump shall have a C-Frame motor adapter which permits mounting of motors up through frame size 365TS. J. Mechanical Seal : The pump shall be equipped with a single cartridge type, O-Ring mounted, balanced mechanical seal. The rotating face shall be constructed of tungsten carbide and the stationary face shall be made of pure unfilled carbon. Both faces must be one piece O-Ring mounted. K. Pump and Motor Design Conditions(per pump station): Pumps shall meet or exceed the following requirements: Pump Stations at Location to be Determined Number of Units Type Pump Speed 2 pumps per station End Suction Centrifugal Design Conditions (per pump) Design Flow Total Dynamic Head (at design flow) Pump Station at Location to be Determined Number of Units Type Pump Speed 2 each End Suction Centrifugal Design Conditions (per pump) Design Flow Total Dynamic Head (at design flow) L. Nameplates: All equipment shall be provided with stainless steel embossed nameplates mounted in easily visible locations and shall contain at least the following information. (1) Pumps a. Manufacturer b. Model designation c. Maximum speed (rpm) d. Maximum horsepower required e. Bearing type and lubrication f. Design flow and head g. Net weight (2) Motors a. Manufacturer b. Model designation c. Rated horsepower

d. Electrical specifications per current NEMA standards e. NEMA frame designation f. Bearing type and lubrication g. Speed (rpm) h. Net weight i. Voltage and amp j. NEMA code k. Service factor 331223-3 M. Pump Motor: The pump motors shall be as required to deliver designed flow and pressure, 120/240/460 volt 3 Phase, 1750 or 3600 rpm, C-Face, TEFC with a 1.15 Service Factor. N. Factory Testing: Pumps shall be tested at the place of manufacture in accordance with the standards of the Hydraulic Institute for testing of pumps. When tested, each pump shall be driven by a certified, calibrated motor. The pump manufacturer s certified test reports on each pump shall be submitted to the Owner prior to shipment of the pumps. The certified test reports shall include the following information: 1. Capacity vs. head curve U.S. gallons per minute and feet. 2. Efficiency vs. flow curve in percent. 3. Brake horsepower vs. flow curve. 4. Speed of rotation. 5. Impeller size and number. 6. Torque vs. speed. Implementation: A. Installation: After a complete inspection of all equipment by the Owner for factory defects or transportation/handling damages, the equipment shall be installed in accordance with the manufacturer s recommendations and the installation drawings. B. Pump Start-Up and Operation: The pump manufacturer shall furnish the services of a factory-trained field engineer specializing in this work to inspect and adjust the equipment after installation, to test the equipment, supervise start-up, and instruct the Owner s personnel in its proper use. The manufacturer shall also provide a minimum of two days of operator training for both operation and routine maintenance requirements for the pumps and motors. (1) Field Tests: a. The manufacturer s field engineer shall test each unit under actual operating conditions to show that each pump unit operates satisfactorily without cavitation, overheating, or overloading, and free from excessive vibration and noise throughout the complete head and capacity range at rated speed. b. The Owner shall be present to observe the field tests. Written notice shall be provided to the Owner at least 10 days prior to performing any testing. c. The Contractor shall make, at his expense, all necessary changes, modifications, and/or adjustments required to assure satisfactory and efficient operation. d. The pump manufacturer s authorized representative shall provide a written report to the Owner noting that pumps and motors have been installed in accordance with manufacturer s recommendations, are in conformance with project performance requirements, and are ready for operation.

331223-4 (2) Warranty: The pump shaft shall be guaranteed against breakage and/or fretting corrosion on the functional areas under the labyrinth seals and mechanical seal. The guarantee shall be for a period of ten (10) years from the start-up date. The bearings shall be guaranteed for a period of five (5) years from the start-up date. The mechanical seal shall be guaranteed for a period of two (2) years from the start-up date. C. Pump House Installation: The Contractor shall construct the pump houses as detailed in the drawings. The Contractor shall also be responsible for all plumbing, electrical service, and pump tie-ins for the pump house required by the Owner. The header piping for the pump house shall be field constructed of stainless steel piping and shall be welded in place with NSF 61 approved materials. A suction and discharge stub-out, compatible with the pump selection, shall be constructed in the header piping for each pump (2 per pump station). D. Additional Pump Station Requirements: Pump stations shall include an underground electrical service entrance. Each pump station shall have a main disconnect switch and a breaker starter combo for each pump. Two inch conduit shall be provided in the pump station foundation from the breaker starter combo to each pump. The Contractor shall install a ¾ diameter copper service from the inlet and outlet main to the pump house. The services should include a cutoff, snubber and a 0 to 200 psi gauge for monitoring and should be securely attached to the inlet and outlet piping for support of the copper line. E. Site Preparation: The Contractor will be responsible for clearing and grubbing the selected site as necessary to prepare the site for installation of the package booster pump station. F. Road / Access: The Contractor shall install a 12 wide road for access to the pump station. Backfill under roads shall be compacted to 95 percent of the maximum dry density. Roads shall comprise a 6 layer of #57 stone with a minimum of 2 of graded aggregate base applied and compacted to the surface. G. Receiving, Unloading and Storage: The Contractor shall unload the pump station in accordance with the manufacturer s recommendations. Immediately upon receipt, the Contractor shall inspect the pump station to ensure that all parts and components have been received in good condition. The Contractor shall store the pump station in accordance with manufacturer s recommendations. If the unit is not to be installed immediately, then the equipment should be installed in a clean, non-corrosive atmosphere and protected against loss, weather damage and foreign materials such as dust, sand, and moisture. Indoor storage is required unless the Owner or Owner s Engineer approve other storage arrangements. H. Foundation: Foundations for package pump stations shall be constructed on soils with a minimum bearing capacity of 1,500 pounds per square foot. Soils placed as backfill for pump station foundations shall be compacted to 95 percent of the maximum dry density. Six inches of compacted, crushed stone shall be placed beneath all foundations. A concrete foundation in accordance with the dimensions shown in the plans shall be installed in accordance with the specifications for concrete in Section 6. Class A concrete with fiber at the rate of one and one half pounds of fiber per cubic yard of concrete shall be used to construct the foundation. I. Fencing: An 8 fence around site with a 16 double gate at the access road with barbed wire shall be installed around the booster package pump station in accordance with the dimensions shown in the plans.

331223-5 J. Piping and Mechanical Work: The Contractor shall install all necessary water piping and appurtenances as shown in the plans to connect the package booster pump station to the distribution network. K. Electrical Work: The Contractor shall be responsible for providing all necessary conduit and wire from the local power company s pole to the package booster pump station and for making final connections at the booster pump station. L. Payment: No separate payment shall be made for the above work. END OF SECTION