XHBN.FF-D-0044 System No. FF-D-0044 November 05, 2003 Assembly Rating 2 Hr Nom Joint Width 1 in. Class II and III Movement Capabilities 50% Compression or Extension 1. Floor or Wall Assembly Reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m 3 ) concrete having a min thickness of 4-1/2 in. (114 mm) at stepped-edges receiving joint cover (Item 3). 2. Mechanical Joint Assembly* Nom width of joint (at time of installation of joint system) is 1 in. (25 mm). The joint system fire barrier consists of a foil heat shield and an insulation block. The joint system fire barrier shall be installed in accordance with the installation instructions accompanying the units. CONSTRUCTION SPECIALTIES INC RFX-1F 3. Joint Cover Min 0.030 in. (0.76 mm) thick joint cover formed of aluminum, bronze, stainless steel or galv steel. As an alternate, where the linear joint opening is enclosed within a chase wall and is non load bearing, a cover consisting of a creased sheet of min 2 mil stainless steel foil secured with 1 in. wide continuous galv steel washer strips along each side of the joint opening may be used. Joint cover anchored to floor slab on each side of joint opening, continuous over entire length of joint, in accordance with the manufacturer's installation instructions. *Bearing the UL Classification Mark This page and all contents are Copyright 2004 by Underwriters Laboratories Inc.
XHBN.WW-D-0060 Page Bottom Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Listed or Classified products, equipment, system, devices, and materials. Authorities Having Jurisdiction should be consulted before construction. Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field. When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction. Only products which bear UL's Mark are considered as Classified, Listed, or Recognized. See General Information for System No. WW-D-0060 July 29, 2004 Assembly Rating 1 Hr Nom Joint Width 1 in. Class II and III Movement Capabilities 50% Compression or Extension
1. Wall Assembly Min 4-1/2 in. (114 mm) thick lightweight or normal weight (100-150 pcf or 1600-2400 kg/m 3 ) reinforced structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Mechanical Joint Assembly* Nom width of joint (at time of installation of joint system) is 1 in. (25 mm). The joint system fire barrier consists of an insulation block. The joint system fire barrier shall be installed in accordance with the installation instructions accompanying the units. CONSTRUCTION SPECIALTIES INC RFX-1W 3. Joint Cover Min 0.030 in. thick joint cover formed of aluminum, bronze, stainless steel or galv steel. Joint covers anchored to each side of wall on both sides of joint opening, continuous over entire length of joint, in accordance with the manufacturer's installation instructions. As an alternate, in the area from the finished ceiling to the floor above, a cover consisting of a creased sheet of min 2 mil stainless steel foil secured with 1 in. wide continuous galv steel washer strips along each side of the joint opening may be used. *Bearing the UL Classification Mark Last Updated on 2004-07-29 Questions? Print this page Notice of Disclaimer Page Top Copyright 2011 Underwriters Laboratories Inc. The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright 2011 Underwriters Laboratories Inc. "
XHBN.WW-D-0049 System No. WW-D-0049 November 05, 2003 Assembly Rating 2 Hr Nom Joint Width 1 in. Class II and III Movement Capabilities 50% Compression or Extension 1. Wall Assembly Min 6 in. (152 mm) thick lightweight or normal weight (100-150 pcf or 1600-2400 kg/m 3 ) reinforced structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Mechanical Joint Assembly* Nom width of joint (at time of installation of joint system) is 1 in. (25 mm). The joint system fire barrier consists of an insulation block. The joint system fire barrier shall be installed in accordance with the installation instructions accompanying the units. CONSTRUCTION SPECIALTIES INC RFX-1W 3. Joint Cover Min 0.030 in. thick joint cover formed of aluminum, bronze, stainless steel or galv steel. Joint covers anchored to each side of wall on both sides of joint opening, continuous over entire length of joint, in accordance with the manufacturer's installation instructions. As an alternate, in the area from the finished ceiling to the floor above, a cover consisting of a creased sheet of min 2 mil stainless steel foil secured with 1 in. wide continuous galv steel washer strips along each side of the joint opening may be used. *Bearing the UL Classification Mark This page and all contents are Copyright 2004 by Underwriters Laboratories Inc.
XHBN.WW-D-0059 - Page 1 of 3 XHBN.WW-D-0059 Page Bottom Print-friendly version Questions? Previous Page See General Information for System No. WW-D-0059 July 29, 2004 Assembly Rating 1 Hr Nom Joint Width 1 in. Class II and III Movement Capabilities 50% Compression or Extension mhtml:file://t:\ul%20listings\rfx\ww-d-0059.mht 5/15/2006
XHBN.WW-D-0059 - mhtml:file://t:\ul%20listings\rfx\ww-d-0059.mht Page 2 of 3 5/15/2006 1. Wall Assembly The 1 hr fire rated framed gypsum wallboard wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. Wood studs to be nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. B. Gypsum Board* Gypsum board sheets to be installed to a min total thickness of 5/8 in. (16 mm) on each side of wall and on each stud face within joint opening. 2. Mechanical Joint Assembly* Nom width of joint (at time of installation of joint system) is 1 in. (25 mm). The joint system fire barrier consists of an insulation block. The joint system fire barrier shall be installed in accordance with the installation instructions accompanying
XHBN.WW-D-0059 - mhtml:file://t:\ul%20listings\rfx\ww-d-0059.mht Page 3 of 3 5/15/2006 the units. CONSTRUCTION SPECIALTIES INC RFX-1W 3. Joint Cover Min 0.030 in. thick joint cover formed of aluminum, bronze, stainless steel or galv steel. Joint covers anchored to each side of wall on both sides of joint opening, continuous over entire length of joint, in accordance with the manufacturer's installation instructions. As an alternate, in the area from the finished ceiling to the floor above, a cover consisting of a creased sheet of min 2 mil stainless steel foil secured with 1 in. wide continuous galv steel washer strips along each side of the joint opening may be used. *Bearing the UL Classification Mark Last Updated on 2004-07-29 Page Top UL Listed and Classified Products Notice of Disclaimer UL Recognized Components Questions? Products Certified for Canada Previous Page This page and all contents are Copyright 2005 by Underwriters Laboratories Inc. The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright 2005 Underwriters Laboratories Inc. "
XHBN.WW-D-0048 System No. WW-D-0048 November 05, 2003 Assembly Rating 2 Hr Nom Joint Width 1 in. Class II and III Movement Capabilities 50% Compression or Extension 1. Wall Assembly The 2 hr fire rated framed gypsum board wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. Wood studs to be nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. B. Gypsum Board* Gypsum board sheets to be installed to a min total thickness of 1-1/4 in. (32 mm) on each side of wall and on each stud face within joint opening. 2. Mechanical Joint Assembly* Nom width of joint (at time of installation of joint system) is 1 in. (25 mm). The joint system fire barrier consists of an insulation block. The joint system fire barrier shall be installed in accordance with the installation instructions accompanying the units. CONSTRUCTION SPECIALTIES INC RFX-1W This page and all contents are Copyright 2004 by Underwriters Laboratories Inc.
3. Joint Cover Min 0.030 in. thick joint cover formed of aluminum, bronze, stainless steel or galv steel. Joint covers anchored to each side of wall on both sides of joint opening, continuous over entire length of joint, in accordance with the manufacturer's installation instructions. As an alternate, in the area from the finished ceiling to the floor above, a cover consisting of a creased sheet of min 2 mil stainless steel foil secured with 1 in. wide continuous galv steel washer strips along each side of the joint opening may be used. *Bearing the UL Classification Mark This page and all contents are Copyright 2004 by Underwriters Laboratories Inc.