On-Site Leaching Chamber Specifications & Features. Design & Installation Manual Ohio

Similar documents
On-Site Leaching Chamber Specifications & Features. Design & Installation Manual New York

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH

GEO-flow Pipe Leaching System Specifications & Features. Design & Installation Manual Maine

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH

NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WATER PROTECTION SECTION

Oklahoma. Oklahoma. Design and Installation Manual for Quick4 Chambers, Septic Tanks, Risers and Aquaworx Remediator in Oklahoma

GEO-flow Pipe Leaching System Specifications & Features. Design & Installation Manual Indiana

Mono County Health Department Construction Guide for Residential and Commercial On-Site Sewage Treatment & Disposal System I.

Pennsylvania. Pennsylvania. Design and Installation Manual for Quick4 Chambers in. Pennsylvania. Infiltrator Chambers in Pennsylvania

Design and Installation Manual for Quick4 Chambers in New Brunswick, Canada

Geotextile Sand Filter

StormTech Construction Guide

StormTech Construction Guide

Geotextile Sand Filter

StormTech Construction Guide

Montana. Design and Installation Manual for the Infiltrator ATL TM System in Montana. Infiltrator ATL System in Montana

Georgia. Georgia. Design and Installation Manual for Quick4 Plus Chambers in Georgia. Infiltrator Chambers in Georgia

Contactor & Recharger

Australia Design & Installation Manual

On-lot System Component Requirements

StormTech Construction Guide

Commonwealth of Massachusetts City/Town of Septic System Installation Checklist

SANDERS COUNTY ENVIRONMENTAL HEALTH PROPERTY OWNER SEPTIC INSTALLATION BOOKLET

Louisiana. Louisiana. Design and Installation Manual for Quick4 Chambers, EZflow, Septic Tanks and Risers in. Louisiana

Common Septic System Installation Mistakes

Indiana. Design and Installation Manual for the Infiltrator ATL TM System in Indiana. Infiltrator ATL System in Indiana

Arizona Design & Installation Manual

Massachusetts Design & Installation Manual

Name: Company: Address: Telephone: PEI Cert. #

SPECIAL SPECIFICATION 3504 Septic Tank System

San Joaquin County. Residential Onsite Systems Bulletin

Geotextile Sand Filter

Introduction to Advanced Enviro-Septic Wastewater Treatment System

Rhode Island Design & Installation Manual

Klickitat County. On-Site Sewage System. Construction Manual

Site Plan: General: Common Omissions-Mistakes on Plans: Ohio EPA Southeast District Office Logan, Ohio November 22, 2005 Bruce Goff, P.E.

ADS SPECIFICATIONS TABLE OF CONTENTS

Oregon. Oregon. Design and Installation Manual for Infiltrator Quick4 Chambers in. Oregon. Infiltrator Chambers in Oregon

Design and Installation Manual for the Infiltrator ATL System in British Columbia

Product Registration Renewal #2 Notice of Proprietary Distribution Product Listing

StormTech Construction Guide An company

LANDSCAPE RETAINING WALLS

Septic Tank Soil Treatment Systems

GUIDELINES FOR INSTALLATION OF ON-SITE SEWAGE SYSTEMS

INYO COUNTY ENVIRONMENTAL HEALTH SERVICES RESIDENTIAL ONSITE SEWAGE TREATMENT AND DISPOSAL GUIDE

TABLE OF CONTENTS

I. Preconstruction Meeting and Site Preparation Date: Inspector: A. MDE Certified Installer Name

Handling and Installation Instructions

Maelstrom. Installation and Specification Guide

Appendix 4. Bills of Quantities

Geotextile Sand Filter

Section 10 Design Criteria: Components

BMP 6.4.4: Infiltration Trench

Woodford County Health Department 1831 S. Main Street, Eureka, IL Phone: (309) Fax: (309)

DRIP EMITTER SYSTEM STUDY GUIDE

SECTION STORM DRAINAGE SYSTEM Excavating, Backfilling, and Compaction for Utilities Cast-in-place Concrete.

Alabama. Alabama. Design and Installation Manual for Infiltrator Chambers in Alabama. Infiltrator Chambers in Alabama

Geotextile Sand Filter

The Most Advanced Name in Water Management Solutions TM. The most cost-effective slotted and trench surface drain systems.

Geotextile Sand Filter

FLOWTECH WASTEWATER TRENCH SYSTEMS Manufactured with 100% Recycled Artificial Aggregate

***************************************************************************************************************

The Most Advanced Name in Water Management Solutions TM. The most cost-effective slotted and trench surface drain systems.

Wastewater treatment for single houses. D. O Dowd

Beacon Hill Water & Sewer District Standard Specifications

Product Dimensions (Width x Length x Height) (inches)

Gravity Wall. A force to be reckoned with... Gravity (SRW) segmental retaining wall systems are structures

APPENDIX A LOW PRESSURE DOSED SAND FILTERS

Technical Data Sheet NEC/GRAN/95:01

The Presby Wastewater Treatment System Idaho

CULTEC STORMWATER CHAMBER SYSTEMS

ON-SITE SEWAGE CONTRACTOR EXAMINATION STUDY GUIDE

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA

GRAY WATER RECYCLING SYSTEMS

Redi Rock Specification and Installation Manual

GRAVITY RETAINING WALL TECHNICAL MANUAL

THIS IS A COURTESY COPY OF THIS RULE. ALL OF THE DEPARTMENT S RULES ARE COMPILED IN TITLE 7 OF THE NEW JERSEY ADMINISTRATIVE CODE.

1.0 BACKGROUND 2.0 DIAGRAMS. The attached diagrams illustrate a typical NDDS system. 3.0 CDPHE OWTS REGULATION #43

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7)

Pressure Distribution Systems

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Water Standards and Facility Regulation Harrisburg, PA

Section 11: Evapotranspiration Absorption Beds. 11. Evapotranspiration Absorption Beds

Section 9: Sand Mounds. 9. Sand Mounds

Precast Concrete Trench Drain Systems INSTALLATION INSTRUCTIONS

Other Septic Tank Effluent Dispersal Options

BIG 'O' HDPE Tubing CORRUGATED TUBING FOR AGRICULTURAL, RESIDENTIAL AND HIGHWAY DRAINAGE. Proudly owned and operated in Canada. aquaq.

A. This section includes the furnishing and installation of a foundation drainage system.

Garden WallScape Installation Guide

Geotextile Sand Filter

BIG O HDPE TUBING HDPE CORRUGATED TUBING FOR AGRICULTURAL, RESIDENTIAL AND HIGHWAY DRAINAGE INCREASE CROP YIELDS LOWER PRODUCTION COSTS

INSTALLATION INSTRUCTIONS

SECTION PLUMBING DRAINAGE AND CONTAINMENT. Copyright Specialloy Industries Inc. dba Slot Drain Systems - All rights reserved

Anchorplex retaining wall construction guide. Building. Anchorplex. Retaining Wall Systems

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS

System Design & Installation Manual

SEPTIC TANK CONSTRUCTION GUIDELINES

SECTION LANDSCAPE SUBDRAINAGE. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

MUTUAL MATERIALS TECH SHEET RomanStack. Coverage* 4.5 pcs / ft² (48.44 pcs / m²) 3,242 lb (1,470 kg) 4 x 8 Cap Unit. 1.6 pcs / ln ft (4.

Appendix B.2. Construction Specifications for Infiltration Practices


Transcription:

On-Site Leaching Chamber Specifications & Features Design & Installation Manual Ohio 1

This manual provides general design and installation information for use of Arc plastic leaching chambers in the State of Ohio. All Arc chamber configurations and installations must comply with applicable state and local rules. This manual contains a brief description for each chamber model and general design and installation procedures. For more detailed information please contact ADS/Hancor customer service at 1-800-821-6710. For CAD drawings refer to our website at: www.ads-pipe.com. Contents Introduction 2 Product Specifications Arc 18 System 4 Arc 24 System 6 General Instructions 8-9 Typical Installations 10-15 Trench System 10 Pressure Dosing System 11 Bed Configuration 12 Pump Systems 13 Shallow Cover Trench Configuration 14 Serial Configuration 15 2

INCLUDED SYSTEMS Arc 18 System 16" Wide Chamber New Lightweight Design with Articulating Joints H 10 load rated with proper installation See Pages 8-9 Arc 24 System 22" Wide Chamber New Lightweight Design with Articulating Joints H 10 load rated with proper installation See Pages 8-9 3

Arc 18 System Before beginning installation, please note the following engineered features of the Arc 18 model chambers and end caps. Arc 18 System Each chamber end is either marked Dome or Post on the round observation/vent knockout ports. These indicate direction of assembly, dome over post. Arc 18 Chamber Length 67 Repeat Length 60 Overall Width 16 Sidewall Height 7.7 Overall Height 12 Capacity 3.42 cu ft (25.6 gal) Calculations and dimensions are nominal Arc 18 Chamber Top, Side, and End Views (not to scale) 60 Effective Length 16 Arc 18 End Cap Side, and End Views (not to scale) 4

Arc 18 System Arc 18 Features Base flanges on the chambers ends over lock during final engagement to form a very strong joint. The Arc 18 chamber feet are designed with an extra large surface area to provide support particularly in sandy soils. Sidewall louvers are designed to allow effluent to exit the chamber sidewalls in high flow situations, while preventing soils from migrating into the chamber void. Observation/venting knockout ports provide for inspection of system performance as well as a convenient location for drain field ventilation pipes. Each chamber end has small knockouts on the roof positioned in the Post end joint. When removed, these knockouts are for the use of zip ties to support piping in dosing systems. Overlocking Ends Observation Port Louvers and Feet Zip Tie Knockouts Arc 18 End Cap Upper and lower knockouts accommodate both Schedule 40 and SDR 35 piping. Dimples are also offered for the positioning of hole saw pilot drills. End caps are designed to attach the chamber s dome or post end. Arc 18 Swivel Feature Each chamber s post end has swivel lockout tabs at either base flange. When removed, the incoming chamber will turn up to ten degrees in the direction of the removed lockout tab. Without removal of the swivel lockout tab, the chambers will align in a straight pattern. Swivel lockout tabs may be removed carefully with a utility knife. Arc 18 System Configurations Trench Installation: Page 10 Pressure Dosing System: Page 11 Bed Configuration: Page 12 Pump Systems: Page 13 Shallow Cover Trench Configuration: Page 14 Serial Configuration: Page 15 5

Arc 24 System Before beginning installation, please note the following engineered features of the Arc 24 model chambers and end caps. Arc 24 System Each chamber end is either marked Dome" or Post on the round observation/vent knockout ports. These indicate direction of assembly, dome over post. Arc 24 Chamber Length 67" Repeat Length 60" Overall Width 22" Overall Height 12" Capacity 5.02 cu ft (37.5 gal) Calculations and dimensions are nominal Arc 24 Chamber Top, Side, and End Views (not to scale) 60" Effective Length 22" Arc 24 End Cap Side, and End Views (not to scale) 6

Arc 24 System Arc 24 Features Base flanges on the chambers ends over lock during final engagement to form a very strong joint. The Arc 24 chamber feet are designed with an extra large surface area to provide support particularly in sandy soils. Sidewall louvers are designed to allow effluent to exit the chamber sidewalls in high flow situations, while preventing soils from migrating into the chamber void. Observation/venting knockout ports provide for inspection of system performance as well as a convenient location for drain field ventilation pipes. Each chamber end has small knockouts on the roof positioned in the Post end joint. When removed, these knockouts all for the use of zip ties to support piping in dosing systems. Overlocking Ends Observation Port Louvers and Feet Zip Tie Knockouts Arc 24 End Cap Upper and lower knockouts accommodate both Schedule 40 and SDR 35 piping. Dimples are also offered for the positioning of hole saw pilot drills. End caps are designed to attach the chamber s dome or post end. Arc 24 Swivel Feature Each chamber s post end has swivel lockout tabs at either base flange. When removed, the incoming chamber will turn up to ten degrees in the direction of the removed lockout tab. Without removal of the swivel lockout tab, the chambers will align in a straight pattern. Swivel lockout tabs may be removed with a striking blow to the tab and then peeling off the remaining piece of plastic. Arc 24 Side Port Coupler (SPC) SPC component snaps in place to allow side entry at any joint throughout the trench line. This accessory provides a variety of design and installation options. Refer to page 10 for design configurations. Arc 24 System Configurations Trench Installation: Page 10 Pressure Dosing System: Page 11 Bed Configuration: Page 12 Pump Systems: Page 13 Shallow Cover Trench Configuration: Page 14 Serial Configuration: Page 15 7

Arc Leaching Systems: Installation Procedures Preparation Excavate to proper width and depth as described in the system design or permit and as required by state and local codes. Smooth irregularities in the excavation and clear any large rocks or debris from the bottom surface area. The slope of the bottom area shall be determined by the system design, as well as state and local codes. Absorption bed installations require 4 to 6 inches of soil separation between chamber lines. Installation Installation of any ADS/Hancor Arc leaching system begins with laying the first chamber onto the prepared bottom surface area dome end first. Each additional chamber is then laid dome over post by raising the post end of the incoming chamber and slightly pulling the chamber back until the dome stops at the underlying post. As the incoming chamber is laid flat on the excavation bottom, slide the lower base flanges under the raised base flanges of the previously-installed chamber. Turns (continued) (Note: The Arc 24 is designed with lockout tabs) If a turn application is desired with the Arc 24 chamber, the lockout tab should be removed before installing the incoming chamber. The lockout tab is located at the base flange of the previously-installed chamber (on its Post end). Strike or cut the lockout tab and tear the remaining tab material away from the chamber. If sharper turns are required, 4 pipe and fittings may be used. Installation of End Caps & Pipe Connections Prior to installing end caps, remove the appropriate knockout for pipe connections. Snap an end cap on each end of the drain lines with the product or company logo facing out (knockouts can be removed with a knife or a 4 hole saw). As the incoming chamber is lowered down onto the excavation bottom, the two chambers fully engage in a straight-line pattern creating a very strong joint. (Note: if the following chamber is simply laid onto the preceding chamber the joint will not be fully engaged.) Turns The Arc 24 chamber is designed with an articulating joint which allows up to 20 of movement, with a maximum of 10 in either direction. Upper end cap 4 knockouts - always used as inlet for each line. Lower endcap 4 knockouts are always used for return lines or continuous circuit piping for bed or mound systems. These lower knockouts should also be used to create turns in the drain lines greater than the ten degrees provided by the chamber swivel feature. Splash Plates Splash plates must be installed on each inlet end cap. Splash plates are provided with Arc system end caps. Knockout material may be used if screwed to the base flange of the end cap with a stainless steel screw. Low Pressure Dosed Piping (If Required) Choose a hole saw that matches the outside diameter of the specified PVC distribution pipe. Use the provided dimple on the upper knockout as a drill guide to drill the hole. Small knockouts or openings are provided on the roof of each chamber s post end to accommodate heavy duty black zip ties 8

Arc Leaching Systems: Installation Procedures (Continued) for the hanging of distribution pipes under the roof of the chamber lines. Pressure pipes should be installed with holes facing upward. (Additional information and drawings for low pressure dosing systems can be found on pp 11.) Filter Fabric Under certain conditions, filter fabric is recommended to drape over the sidewalls to prevent sand intrusion while allowing water and air to pass through. The following single or combination of conditions warrant the use of filter fabric: The backfill material is uncompactable and subject to sloughing, e.g., single-grain sand and very fine sand. The drain field will be left uncovered for an extended period of time (over 5 days or during rainy season). The drain field will not be sodded. The bottom of the drain field will be less than 12 from seasonal high water level. Filter fabric should meet the following specifications and can be purchased from your ADS/Hancor Arc distributors: Fabric: Spun bonded, made up of nylon fibers, hydrophilic in nature. Weight: 0.4-0.6 oz/yd2 Ventilation Drain field ventilation is recommended, but not required, to allow oxygen to access the drain field especially when cover soil quality is questionable. The dome/post feature of the Arc 24 chamber acts as a knock-out for observation/vent ports. Here a PVC pipe may be introduced into the chamber and vented to atmosphere. Make certain the vent is assembled in such a fashion as to prevent rainwater from entering, effluent water from exiting, and possible odors from causing issues. Several outlet products are available for this purpose. Shallow Placement Ohio Department of Health rules allow for the installation of drain field systems in "shallow placement" applications. In these applications, the Arc 18 and Arc 24 chambers may be installed at a minimum of two inches (2") into the native soil. The remainder of the chamber units in the system (up to 10" in height, as the Arc 18 and Arc 24 are 12" tall) will then be backfilled above grade. Backfill material in this application should be coarse in nature (loamy sand, sandy loam), and only slightly compacted along the chamber sidewall. Backfilling After chamber assembly is complete and any time before or during final covering, modestly compact the sidewall area backfill material by simply walking down the sides of the chambers. Sidewall compaction is important to begin the stabilization process of the soil, to support the chamber sidewalls, and help prevent the migration of fines into the chamber louvers. Mound systems require a minimum of six inches of cover. More cover may be required initially to allow for settling. Do not drive heavy equipment over chamber installation. Use lightweight or tracked equipment to push the soil onto the system to the proper height set forth by local and state codes. Final Grade Arc leaching system installer is responsible for the final cover of the drainfield. Make certain that storm water is diverted away from the drain field. System final grade should be crested or sloped, never left flat or concave. Channel water away from the drain field. Final grade material should be slightly to moderately limited soil to help maintain an aerobic state in the drain field. Stabilize the drain field area with grass-type vegetation prior to heavy rains if possible. Cover Requirements Arc 18 and Arc 24 chambers carry the following minimum cover requirements: For H-10 load bearing capability, 12" of compacted cover material; For up to 4,400 pounds per axle, 6" of cover material; and If less than 6" of cover is specified, the minimum amount of cover shall be 4". In applications where less than 6" of cover material is installed, only tracked vehicles may be introduced onto the system. 9

Installation Configurations: I. Trench Configuration Typical Trench: Subsurface Cross Section 12" Min. 22" 24" Typ Typical Trench: Plan View Sewer & Drain and/or Triple Wall or Per Local Regulation (Installed in Upper Knockouts) Splash Plate Required on Inlet End of Each Chamber Row Spacing per local regulation. Septic Tank D-Box (4 Header Pipe Manifold May Be Used in Lieu of D-Box Distribution) Inspection Ports End Caps Must be Installed on Both Ends of Every Chamber Row 10

Installation Configurations: II. Pressure Dosing System Pressure dosing systems can be arranged in trench or bed configurations, as subsurface or mound installations. Pressure Dosing: Plan View with Detail Pressure Pipe Detail: Pressure Pipe Must Be Installed With Holes Facing Upward (Per Design or Engineer Spec) Inspection Ports Septic Tank Pump Tank Pipe Type and Size Specified by Designer or Per Local Regulation (Installed in Upper Knockouts) Spacing per local regulation. End Caps Must be Installed on Both Ends of Every Chamber Row Pressure Dosing, Hung-Pipe: Installation Cross Section Pressure Dosing, Valve Box: 6 Min Backfill 22 24 Typ Chamber Pressure Pipe with Holes at 12 O Clock 4 Perforated Pipe with All Weather Pipe Straps at Every Chamber Connection Valve Box (Typical Per Lateral) 90 Long Sweep 11

Installation Configurations: III. Bed Configuration Typical Bed: Subsurface Cross Section 12 Min Backfill 22 Typ 4 Min/6 Max Typical Bed: Plan View Sewer & Drain and/or Triple Wall or Per Local Regulation (Installed in Upper Knockouts) Splash Plate Required on Inlet End of Each Chamber Row 4 Min/6 Max Between Chamber Rows Septic Tank D-Box (4 Header Pipe Manifold May Be Used in Lieu of D-Box Distribution) Backside: Complete 4 Header Pipe Manifold Assembly (Installed in Lower Knockouts) Inspection Ports End Caps Must be Installed on Both Ends of Every Chamber Row 12

Additional Configurations: IV. Pump Systems: Pump to D-Box Pump to D-Box: D-Box Section View Force Main from Pump Tank 3 to 4 Overflow to Top Inlet of End Pipe 1/4 Hole Facing Wall of D-Box D-Box (D-Box Enlarged View) Pump to D-Box: Plan View Minimum Length 4" and Level Determined by State and Local Codes Septic Tank Pump Tank D-Box Inspection Ports 13

Additional Configurations: V. Shallow Cover Trench Configuration Shallow Cover Trench Configuration: Cross Section 6" Min. Backfill 4" Diameter Pipe Inlet Invert = 6.24" 18-24" Shallow Cover Trench Configuration: Plan View Minimum Length 4" and Level Determined by State and Local Codes Septic Tank D-Box Inspection Ports 14

Installation Configurations: VI. Serial Configuration Side Port Coupler (SPC) Header Connection, Middle of Row, & Radius Bend Configurations End Caps Header Connections Using Side Port Chambers Connections in Middle of Row Using Side Port Chambers Radius Bend Using Side Port Chambers From Septic Tank 4 Pipe Typ 15

Advanced Drainage Systems, the ADS logo, the green stripe, The Most Advanced Name in Drainage Systems and ARC are registered trademarks of Advanced Drainage Systems, Inc. Hancor is a registered trademark of Hancor, Inc. ADS Terms and Conditions of Sale are available on the ADS website, www.ads-pipe.com. 2011 Advanced Drainage Systems, Inc. INS10775/0211 Notes/comments Innovation in product, process and technology. That s ADS and Hancor. 16 800-733-3555 www.ads-pipe.com 888-FOR PIPE (367-7473) www.hancor.com