HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

Similar documents
Composite Insulator Components

Polluted Outdoor Insulators Maintenance and Washing

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Transmission Silicone Insulators Line Post 69 kv to 230 kv

INSULATOR REQUERIMENTS:

Energy Division Insulators

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION

Outdoor High Voltage Non-Ceramic Insulators

Comparison of effects of Various Contaminations on SiR insulators

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

Manufacturing and Application of Cage Design High Voltage Metal Oxide Surge Arresters

ECONOMIC ANALYSIS OF 400 KV TRANSMISSION TOWERS WITH CROSS ARMS INSULATORS

CHAPTER 2 STRUCTURE AND CRITICAL E-FIELDS

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

INSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle.

Pins Insulator. Composite/Polymers Insulators

ENGINEERING SPECIFICATION EE SPEC

fire Charcoat Charcoat IC Passive Protection

Electrical Field Simulation for Different Cases of Polymer Insulators Using FEM

GROUP A. Polymeric Insulators.

ILMOS Insulator Leakage Current Monitor

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

Development of Composite Line Spacers for Distribution Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines

Composite insulators. Features. Sicat 8WL3068, 8WL3078 and 8WL3088 for overhead contact line systems. siemens.com/rail-electrification

PS2: Lifetime management, deterioration and ageing of substation equipment

Panagiotis Charalampidis

PI Electrical Equipment - tourse PI 30.2 INSULATION. On completion of this module the student will be able to:

Design of MO Surge Arresters with Polymeric Housings

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

INTERNATIONAL STANDARD

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN

Electric field analysis of 132kV EPDM insulator and correlation with ageing features

Polymer and FRP Technology - An Alternative to Conventional Porcelain for Future Power Sector

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development

CS type composite silicone insulators up to 750 kv overhead lines for all pollution of the atmosphere levels

TEMPERED GLASS INSULATORS

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

Resin impregnated paper bushings. Product information

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

Design a surge arrester performs in service

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

Diagnostic Techniques of Composite Insulators

NPS/003/001 Technical Specification for 33kV, 66kV and 132kV Voltage Transformers

A-PDF PPT TO PDF DEMO: Purchase from to remove the watermark

11KV PORCELAIN INSULATORS AND FITTINGS

Maharashtra State Electricity Distribution Co. Ltd.

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination

Specification for Polymer Disc Insulator

8. Hydrophobicity classification guide STRI guide 1.92/1 9. Radio interference characteristics of overhead power lines and high-voltage equipment

Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R

Maharashtra State Electricity Distribution Co. Ltd.

Data Sheet 110kV TD123II dry type outdoor termination

SPECIFICATION FOR POLYMER DISC INSULATOR

The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDERNO. 9/2013 FOR THE SUPPLY OF INSULATORS AND FITTINGS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

Design features - Polymer-housed arresters, PEXLIM

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test

SPECIFICATION FOR DISC INSULATORS (Standard Type)

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation

Characterisation of Textured Insulators for Overhead Lines and Substations

Comments on Document from Richard Martin, Canada

15~35KV Termination Kit

3M Cold Shrink Joint, SC145-II/SS145-II

IEEE T&D Insulators 101

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

6C-001 High-Voltage Pin-Type Insulator

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS

Silicone rubber Product information

ISO Rules Part 500, Facilities Division 502, Technical Requirements Section Bulk Transmission Technical Requirements

INSULATORS NEW. See page J-4 for more information.

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

United States Department of Agriculture Rural Development Rural Utilities Service. RUS Bulletin 1724E-220

An Investigation Into The Methodology To Develop An Insulator Pollution Severity Application Map For South Africa

Polymer Cutout Testing Recommendations

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages:

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines

Failure of a suspension or tension insulator

PRY-MOULD. High Voltage Accessories for Extruded Cables

Transcription:

HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium (ACSR) conductors, is a good insulating material, provided that the electric stress is kept below the ionisation threshold. It is, however, necessary to attach the conductors at certain points onto the cross arms of the pylons. The problem of reliably suspending the conductors of high voltage transmission lines has therefore been with us since the turn of the century. The task is particularly complex, bearing in mind the multiple extreme stresses present: mechanical, electrical and environmental. ELECTRICAL High voltage have developed rapidly since early this century, beginning with simple porcelain (I). Today, modern polymeric are used, as well as the earlier materials. A classification of the main types of is shown schematically in figure 1. Pin HV Conductor Cap and pin Ceramic Insulators Porcelain pin type These are manufactured from porcelain or glass and are based on the same principles as pin-type. A number of units are connected together by steel caps and pins to form an insulator string. These strings are used for suspension and tension. The caps and pins are fixed to the glass or porcelain disc with cement. The conical shapes of the fittings ensure high mechanical strength under tensile stress. Typically an insulator string can handle loads of up to 120 kn, i.e. 12 tons. A typical cap and pin disc is shown in figure 3. Pin-type and cap and pin are classified as Class B ; the shortest distance between the metal electrodes through the porcelain or glass is less than 50% Glass Cap & pin Bushings & hollow core Post type & line post Porcelain Pin-type Longrod Polymeric Insulators (Nonceramic) Composite : fibreglass rod with polymeric shed (line post or suspension) Cast cycloaliphatic epoxy resin (line post, suspension or bushings) These were originally used for telephone lines and lightning conductors, have been adapted for power transmission and some variations are still in use for medium voltage systems. A pin-type insulator is shown schematically in figure 2. Figure 2 Schematic representation of a section through a pin-type insulator HV Insulators of the shortest distance through the electrodes. The porcelain or glass can therefore be punctured by severe electrical stress. The manufacturing process of glass includes thermal cooling that ensures that the glass sheds shatters in the event of a puncture. A faulty disc is therefore clearly visible. The mechanical integrity of the insulator remains intact. EPDM rubber Figure 1 The classification of power line Shed Silicone rubber Figure 3 Typical cap and pin disc Cap Cement Pin

Post-type and line post These consist of a solid porcelain cylinder, corrugated to increase the leak- age length, with metalware on each end. They are used to support the high voltage conductor and are mounted on pedestals or on the power line cross arms. Post are tall and are mainly used in substations. These are Class A; the shortest distance through the porcelain exceeds 50% of the shortest distance through air between the electrodes. They are therefore unpuncturable. A typical example of a post insulator is shown schematically in figure 4. Porcelain longrod Longrod are similar to post but are lighter, slimmer and are used as suspension. Longrod have the apparent advantage over cap and pin in that metal fittings exist only at the ends of the. Air Oil HV Tank Bushings Composite polymeric These are similar to longrod but consist of: Bushings are used to insulate the conductors of the high voltage terminals of a transformer as is shown schematically in figure 5. Traditionally, transformer bushings are manufactured using porcelain. Capacative grading, using foil cylinders is often used to improve the axial and radial field distribution. Figure 5 Typical post-type insulator A glass fibre reinforced resin core to provide the mechanical strength, while resisting the electrical stress Elastomer sheds to provide the required creepage and stress reduction to withstand the stresses prevailing on the system. Two commonly used materials are silicone rubber and EDPM (ethylene propylene diene monomer) rubber. A typical method of construction is shown schematically in figure 6. The metal end fittings are usually crimped onto the glass fibre rod from the environment and the interfaces between the elastomer and the metal fittings are very important. Tests to ensure the quality of composite are contained in IEC 1109 [2]. A major advantage of composite polymeric is an up to 90% weight reduction when compared to ceramic equivalents. They are also reasonably vandal-proof. Glassfibre rod Cyclo-aliphatic epoxy resin Elastomeric shed Elastomeric sheath HV Conductor Figure 4 Typical post-type insulator Figure 6 A schematic representation of a typical polymeric composite insulator End fitting Cyclo-aliphatic resin can be used to cast similar to porcelain and linepost for distribution voltages. In severe environments the surfaces of the become rough - a factor that may affect the reliability of the insulator, when incorrectly applied.

Terminology When applying, it is necessary to describe the insulator dimensions, using the following terms: Creepage distance: the shortest distance between the metalware at the two ends of the insulator, when following the contours of the insulator, excluding intermediate metal fittings. This distance is easily measured by sticking masking tape to the insulator surface. Specific creepage distance: The quotient of the creepage distance in mm and the line-to-line rms. voltage of the three phase system in kv Connecting length: the axial length of the insulator between the end terminals Arcing distance: the distance between the metalware, measured as the length of a tightly pulled piece of string Intershed spacing: the distance between corresponding points on adjacent sheds. Pollution deposition process Insulators exposed to the environment collect pollutants from various sources. Pollutants that become conducting when moistened are of particular concern. Two major sources are considered: Coastal pollution: the salt spray from the sea or wind-driven salt laden solid material such as sand collects on the insulator surface. These layers become conducting during periods of high humidity and fog. Sodium chloride is the main constituent of this type of pollution. Industrial pollution: substations and power lines near industrial complexes are subject to the stack emissions from nearby plants. These materials are usually dry when deposited; they may then become conducting when wetted. The materials will absorb moisture to different degrees, and apart from salts, acids are also deposited on the insulator. The role of the weather Wind is instrumental in the deposition process. High humidity, fog or light rain cause wetting of the pollution layers. Heavy rain removes the pollution layer especially on the upper sides of the sheds. Air flashover versus pollution flashover If the electric stress in air at atmospheric pressure exceeds 3 kv/mm, ionisation can occur. Depending on the gap configuration, flashover may follow. The power flashover voltage of a clean dry single cap and pin insulator with a 280 mm creepage distance is 72 kv. It is estimated that using a 15 mm per kv specific creepage distance under medium pollution conditions will cause a flashover at 3.67 kv - an almost tenfold reduction in performance. This dramatic reduction in flashover voltage is attributed to the presence of the conducting layer on the surface of the insulator. Leakage current flows over the insulator surface and the heating effect of the current causes drying out of the layer at certain spots and the formation of 'dry bands'. Arcs occur across these bands and if the pollution is of sufficient severity, the insulator may flash over [1]. Hydrophilic versus hydrophobic As indicated above, the presence of a conducting layer on the surface of an insulator is essential for pollution flashover to take place. In particular, sufficient wetting of the dry salts on the insulator surface is required to form a conducting electrolyte. The ability of a surface to become wet is described by its hydrophobicity. Ceramic materials and some polymeric materials such as EDPM rubber are hydrophilic, i.e. water films out easily on its surface. In the case of some shed material such as silicone rubber, water forms beads on the surface due to the high surface energy. When new, the hydrophobic properties of silicone rubber are excellent; however, it is known that severe environmental and electrical stressing may destroy this hydrophobicity. Silicone rubber materials also have the property that, once lost hydrophobicity can be regained after a 'resting period'. These aspects are being researched in several countries.

Failure modes of Flashovers, caused by air breakdown or pollution, generally do not cause physical damage to the and the system can often be restored by means of autoclosing. Some other events, however, cause irreparable damage to the. Puncture As previously mentioned, porcelain pin-type and cap and pin may suffer punctures between the pin and the either the pin or the high voltage conductor. These occurrences are usually caused by very steep impulse voltages, where the time delay for air flashover exceeds that of puncture of porcelain. Punctures caused by severe stress over dry bands also occur on composite on sheds and through the sheath. A puncture of the sheath is particularly serious as this exposes the glass fibre rod to the environment (see brittle fracture below). Shattering Glass shatter when exposed to severe arcing or puncturing due to vandalism. One advantage is that they retain their mechanical integrity. Erosion Prolonged arcing of glass leads to erosion of the surface layer of the glass. This may lead to shattering of the glass discs - a result of the tempering process used during manufacture. Arcing and corona over long periods may cause removal of shed or sheath material in the case of polymeric. Severe erosion may lead to the exposure of the glass fibre core (see brittle fracture) Tracking Tracking occurs when carbonised tracks form because of arcing. These tracks are conductive. This phenomenon only occurs in carbon-based polymers. Brittle fracture Water entry into the glass fibre core of composite, coupled with the influence of weak acids, has been shown to lead to brittle fracture of the rod. The by-products of partial discharges in the presence of water can lead to the formation of weak acids. The integrity of the metal/polymer and glass/polymer interfaces is therefore extremely important - especially if acid-resistant glass is not used. Corrosion The corrosion of metal fittings clearly affects the mechanical performance and lifetime of. The corrosion products, running onto the insulator sheds can also initiate deterioration. Remedies Washing Substation or line can be washed when de-energised or when energised. Automatic washing schemes and helicopters have been used for this purpose. The costs are usually prohibitive. Greasing A thin layer of silicone grease, when applied to ceramic increases the hydrophobicity of the surface. Pollution particles that are deposited on the insulator surface are also encapsulated by the grease and protected from moisture. The disadvantage of greasing is that the spent grease must be removed and new grease applied, usually annually. Coatings Room temperature cured silicone rubber coatings are available to be used on ceramic substation. These coatings have good hydrophobic properties when new. Research is still in progress to evaluate their aging processes.

Increase creepage distance If the clearances allow, additional discs may be added to increase the reliability of a line. In the case of longrod and post, the increased creepage length must not result in an inadequate shed spacing. This solution is usually not possible and expensive. Replace hydrophilic with hydrophobic One possibility may be to replace hydrophilic with hydrophobic insulation of the same connecting length and creepage distance. This solution is, however, expensive and it must be known with certainty that the original problem is pollution related. Application guide The design of a new line and the choice of is a specialised task. Apart from the coordination of the line insulation to cope with lightning and switching impulses, the pollution severity of the area must be known - through either direct measurement or experience. Recommendations by the IEC indicate design criteria for ceramic [3]. Choice of creepage length The recommended specific creepage lengths for ceramic are given in table 1. When using non-ceramic, it Table 1 is advisable to use a shorter creepage length, especially in locations of severe pollution. Recent research indicates that under conditions of severe humidity and dry band arcing, silicone rubber may lose hydrophobicity. Until more conclusive research results or revised specifications are available, it is considered a safe approach to use IEC 815 for nonceramic as well. Choice of profile Suitable spacing and shed overhang/spacing ratios have to be chosen [3]. A long creepage distance, obtained by using many closely spaced sheds may be inadequate as intershed breakdowns can occur. Choice of shed material Hydrophobic materials are preferred for areas near sources of pollution. Conclusion During the earlier part of this century ceramics, glass and porcelain have been established as reliable materials for high voltage insulation. Over the past few decades, new technologies involving polymeric materials have increasingly been used for transmission and distribution systems. These have many advantages over other materials. References Site pollution severity Specific creepage length (mm/kv) Low Medium High Very high 16 20 25 >31 [1] Looms, J. S. T., "Insulators for High Voltages". Peter Peregrinus, London, 1988. [2] IEC 1109: 1992. "Composite Insulators For AC Overhead Lines With Nominal Voltages Larger Than 1000 V - Annexure C". [3] IEC 815. "Guide for the Selection of Insulators in Respect Of Polluted Conditions". IEC Recommendations. Publication 815, 1986. [4] Vosloo, W. L., Holtzhausen J. P., Roediger A. H. A. "Leakage Current Performance of Naturally Aged Non-ceramic Insulators Under a Severe Marine Environment". Africon, September 1996, Stellenbosch, 1996. [5] Holtzhausen J. P. "Leakage Current Monitoring On Synthetic Insulators at a Severe Coastal Site". The Transactions of the South African Institute of Electrical Engineers. September 1994.