The potential of earth-air heat exchangers for low energy cooling of buildings in South Algeria

Similar documents
Available online at ScienceDirect. Energy Procedia 61 (2014 )

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

CFD Analysis of Earth-Air Heat Exchanger to Evaluate the Effect of Parameters on Its Performance

Numerical and analytical analysis of groundwater influence on the pile ground heat exchanger with cast-in spiral coils

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

CFD Modelling and Analysis of Different Plate Heat Exchangers

Development of a hot water tank simulation program with improved prediction of thermal stratification in the tank

Design and development of an Earth Air Tube Heat Exchanger

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Analysis on the influence of rotational speed to aerodynamic performance of vertical axis wind turbine

An Evaluation of Heat Transfer Coefficient in an Independent Zonal Temperature Controls with CFD

CFD Simulation Studies on Integrated Approach of Solar Chimney and Earth Air Tunnel Heat Exchanger for Building Space Conditioning

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

CFD ANALYSIS OF THERMAL INFLUENCE ZONE OF EARTH AIR TUNNEL HEAT EXCHANGER UNDER TRANSIENT CONDITIONS

Available online at

Simulation of Solar Air-Conditioning System with Salinity Gradient Solar Pond

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Heat transfer enhancement in fire tube boiler using hellically ribbed tubes

Computational and field test analysis of thermal comfort performance of user-controlled thermal chair in an open plan office

Project Background (long term goals)

ADVANCES in NATURAL and APPLIED SCIENCES

Vipac Engineers & Scientists Ltd

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at ScienceDirect. Procedia Engineering 105 (2015 )

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room

Available online at ScienceDirect. Procedia Engineering 89 (2014 )

BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

ADVANCES in NATURAL and APPLIED SCIENCES

Thermal Performance of an Integrated Earth-Air Tunnel System with Building s External Wall in UAE

Modeling a Novel Shallow Ground Heat Exchanger

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings

Computational Analysis of Blast Furnace Pulverized Coal Injection For Iron Making

Study on the heat transfer model and the application of the underground pipe system

Optimum design on impeller blade of mixed-flow pump based on CFD

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

Numerical analysis of eccentric orifice plate using ANSYS Fluent software

Computational Fluid Dynamics on Performance of Earth Tube Heat Exchanger with Constant velocity for Heating

Flow and heat distribution analysis of different transformer sub-stations

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

heat exchanger modelling for generator ventilation systems

Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector Control

CFD Analysis of Pelton Runner

ENERGY SAVING IN BUILDING USING PCM IN WINDOWS

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

Numerical Analysis of Two-phase Flow and Heat Transfer in External Cyclic Purification Hot-dip Galvanizing Bath

Dynamic thermal simulation of horizontal ground heat exchangers for renewable heating and ventilation of buildings

EXPERIMENTAL AND NUMERICAL STUDY OF AN EARTH-TO-AIR HEAT EXCHANGER FOR BUILDINGS AIR REFRESHMENT IN MARRAKECH. Ayyad University, Marrakech.

Numerical Investigation of Swirl's Effects in the Outer Annulus of a Reverse-flow Gas Turbine Combustor

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Numerical Prediction of Thermodynamics and Heat Transfer Characteristics of Nano Fluid.

Numerical thermal analysis of helical-shaped heat exchanger to improve thermal stratification inside solar storage tank

Thermal Management of Densely-packed EV Battery Set

Experimental Study of Thermal Comfort in Arid Zones (South West of Algeria)

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

CFD modeling of heat charging process in. a direct-contact container. for mobilized thermal. energy storage

Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher.

Available online at ScienceDirect. Procedia Technology 23 (2016 )

CFD ANALYSIS OF SOLAR HEATER WATER PIPE WITH DIFFERENT INCLINATION

ISSN (ONLINE): , ISSN (PRINT):

Available online at ScienceDirect. Procedia Engineering 169 (2016 )

Numerical study of the influence of injection/production well perforation location on CO 2 -EGS system

CFD analysis of Metallic Foam-Filled Triple Tube Concentric Heat Exchanger

Working parameters affecting earth-air heat exchanger (EAHE) system performance for passive cooling: A review

Experimental and theoretic investigations of thermal behavior of a seasonal water pit heat storage

Study of water falling film over horizontal drop shaped and inverted drop shaped tubes

Available online at ScienceDirect. Energy Procedia 70 (2015 )

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Potentials of the new design concepts of district heating and cooling toward integration with renewable energy sources

ScienceDirect. CFD Analysis of a Kerosene Fuel Tank to Reduce Liquid Sloshing

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at ScienceDirect. Procedia Engineering 99 (2015 )

Effect of Corrugation Angle on Heat Transfer Studies of Viscous Fluids in Corrugated Plate Heat Exchangers

Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump

Heriot-Watt University

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

Available online at ScienceDirect. Energy Procedia 78 (2015 )

COMSOL Multiphysics Simulation of Flow in a Radial Flow Fixed Bed Reactor (RFBR)

CFD simulations of RTD of a strawberry pulp in a continuous ohmic heater

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR)

Computational Fluid Dynamics Analysis of Greenhouses with Artificial Heat Tube

Numerical Analysis of Solar Updraft Tower with Solar Load applied to Discrete Ordinate Model

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance

CFD Modelling of Finned-tube CO2 Gas Cooler for Refrigeration Systems

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Experimental investigation on a ceiling capillary radiant heating system

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Heat transfer modelling of slot jet impinging on an inclined plate

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

Numerical Study of the Effect of Transverse Magnetic Field on Cylindrical and Hemispherical CZ Crystal Growth of Silicon

Computational Fluid Dynamics (CFD) Simulations of Dispersed Flow of Viscous Oil in Water in a Horizontal Pipe

INVESTIGATION OF FLOW CHARACTERISTICS OF HELLER-TYPE COOLING TOWERS WITH DIFFERENT COOLING DELTA ANGLES

A review on heat transfer enhancement of borehole heat exchanger

Quenching steels with gas jet arrays

Transcription:

Available online at www.sciencedirect.com Energy Procedia 18 (2012 ) 496 506 The potential of earth-air heat exchangers for low energy cooling of buildings in South Algeria Abdelkrim.Sehli *, Abdelhafid.Hasni, Mohammed.Tamali Energy Systems Laboratory in arid zone; Bechar University; BP No. 417, 08000, Bechar, Algeria Abstract A one-dimensional steady numerical model is proposed to estimate the performance of earth-to-air heat exchangers, installed at different depth, used for building cooling/heating. Two parameters are considered to evaluate the performance of the system (Reynolds number and the form factor).with appropriate simplifications; Numerical simulation treatment is proposed to predict the temperature fields of the fluids in the pipe and the soil in the proximity of the buried pipe, taking into account meteorological data of south Algeria. Moreover, the agreement with some experimental data available in the literature is very satisfactory. 2012 Published by by Elsevier Ltd. Ltd. Selection All rights and/or reserved peer review under responsibility of The TerraGreen Society. Open access under CC BY-NC-ND license. Keywords: Earth-to-air heat exchanger, numerical simulation, Turbulence k- 1. Introduction Background The achievement of indoor thermal comfort whilst minimizing energy consumption in buildings is a key aim in most countries and is a particular challenge in desert climates. The desert climate can be classified as hot and arid and such conditions exist in a number of areas throughout the world [1, 9]. One such area is South Algeria, with an average ambient temperature of around 45 C during summer months. In general, most people feel comfortable indoors when the temperature is between 22 and 26 C and relative humidity is within the range of 30 50%. Such conditions are often achieved through the use of air-conditioning in desert climates; hence there is a significant use of energy in the domestic air conditioning sector. Methods of reducing this energy demand would thus have clear economic and * Corresponding author. Tel.: +213 7 70125851. E-mail address: abdelkrim.sehli@yahoo.fr. 1876-6102 2012 Published by Elsevier Ltd. Selection and/or peer review under responsibility of The TerraGreen Society. Open access under CC BY-NC-ND license. doi:10.1016/j.egypro.2012.05.061

A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 497 environmental benefits. In South Algeria, domestic air-conditioning operates from the beginning of May to the end of September and buildings in this sector consume about 75 80% of the total electric power, The average electricity peak load for the months May September is 45% higher than the yearly average electricity peak load. For these reasons it would be beneficial to investigate earth air heat exchangers as auxiliary cooling devices together with air-conditioning. Cooling the outdoor air through buried pipes by means of an earth air heat exchanger (EAHE) has energy demand [1]. There are many reported experimental and analytical studies on EAHE; however the use of EAHE systems for buildings has not been investigated in the case of desert climates like that of South Algeria. The EAHE (or earth cooling pipe) functions by transferring heat from the sub-soil environment to air flowing in a buried pipe. In summer this provides pre-cooling of the outdoor ventilation air, which serves to reduce the cooling load of the building. Amara et al [2] studied the ancient Fouggara system and investigated its possible use as a source for heating, cooling and ventilation of buildings. The Fouggara consistes of: The source where the water seeps into the channel from a ground water source, An underground channel which brings the water to its intended destination, An over ground channel which leads to a network of channels feeding the water to particular areas or fields for irrigation. Since the Fouggara is at a depth below ground surface where the seasonal temperature changes do not reach, the Fouggara temperature is close to the annual mean air temperature. In Adrar in the south of Algeria the mean annual temperature is 21 C. Pumping air through the Fouggara means that the air temperature will approach this temperature. Moummi et al [3] presented an analytical model of the earth cooling pipe, the results were compared with experimental data obtained in south Algeria (university of Biskra). Nomenclature T Temperature, C U X velocity, m/s V Y velocity, m/s E Dimensionless turbulent kinetic energy dissipation K Dimensionless turbulent kinetic energy Re Reynolds number Pr Brandt number Turbulent viscosity, m 2 /s Form factor

498 A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 2. The desert climate of South Algeria South Algeria is typical of a dry desert climate with the highest air temperature being recorded in July and August with an afternoon average maximum of 45 C. Summer starts at the beginning of May and continues until the end of September, with a mean air temperature of 37 C [4]. In addition, the air is generally dry. In winter, the weather is comfortably cool, generally mild, with a monthly mean temperature of 10 C, and a minimum temperature recorded being occasionally below 1 C. 3. Principle of The earth to air heat exchanger (EAHE) The principle of the EAHE is that a pipe or several pipes buried in the ground. One end of the pipe system (the inlet) acts as the entrance for outdoor ambient air, whilst the other end of the pipe system (the outlet) releases air to the interior of a building. Ambient air is drawn into the pipe inlet, the air travelling through the pipe exchanging heat with the pipe walls which are in contact with the surrounding underground environment. In this way, heat is transferred to or from the surrounding soil by conduction through the pipe wall and convection with the tunnel air, tempering the air as it flows through the pipe Fig.1 illustrates this concept. Fig.1: Simplified diagram of earth to air heat exchanger To find the temperature at the outlet of the pipe, we follow the diagram below Fig.2

A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 499 Fig 2: Prediction of the outlet air temperature of ETHE diagram 3.1. Soil temperature model: According to the previous works; experimental, numerical and analytical solutions gives good agreements. For this reasons, in this present paper, we use only the analytical solutions [6,10] - The soil surrounding the pipe is isotropy, with homogenous thermal conductivity in all ground. - The surface temperature of the ground can be approximated to the ambient air temperature, which equals the inlet air temperature because the soil thermal conductivity depends on the soil moisture and decreases for dry soils. Therefore for dry and arid soils the heat storage capacity of the ground is much smaller (case south Algeria) [5]. (1) Where and : The mean annual ground temperature. : The temperature wave amplitude at the ground surface (z=0). : The frequency of the annual temperature wave.

500 A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 Table1: physical properties of sandy Soil type Sandy : Thermal conductivity (W/m. C) 2.01 Cpsol: specific heat (J/kg. C) 1380 : density (kg/m3) 2300 6.333X10-7 3.2. ETHE model: Air flow Fig. 3 in the pipe is turbulent and its can be considered as incompressible flow. The governing equations for the mass, momentum and energy can simplified as equations (2-6) with the assumption: Twall Tin D Air( Pr,Re) T outlet L Fig 3: simplified diagram of the pipe The flow and heat transfer are one-dimensional (only X direction) Viscous dissipation and work of pressure forces are negligible The physical properties of the fluid are constant The fluid is Newtonian and incompressible. Steady state flow Is adopted for the closure of our model k- proposed by Jones and Launde[7]. The dimensionless quantities used are: (2) (3) (4)

A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 501 4. Turbulence modeling Using the K- (5) (6) Correction functions,, and constants used in equations (5~ 6) are those proposed by R. Saim et al [8], and also the coefficient 4.1. Boundary conditions At the entrance of the channel(x=0) ET Solid Wall of the duct: At exist of the channel (X=1): 4.2. Mesh development The computational domain is discredited to two smoothly adjacent regions, i.e., the boundary layer with a fine grid and the outer region with a relatively coarse one. 4.3. Technical solution: This study used a fully structured finite volume CFD solver, for simulation. The SIMPLE algorithm is applied for the pressure-velocity coupling in the segregated solver. A second order upwind scheme is adopted for the discretization of the governing equations. The convergence criteria for all variables were set are 10-4 except for energy to be 10-6.

502 A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 5. Results and Discussions 5.1. Soil temperature model Soil Temperature C Fig 4: Soil temperature during the year soil type: Sand at different depths Time (hours) The application of Eq(1),considering the input parameters presented in table1,allows the prediction and measured soil temperatures at depths 1,2,3,4 and 5 m are presented in (fig4).it has been shown that the suitable depth for the installation of the earth to air heat exchanger system is 4m.At this level,the predicted and measured sub soil temperatures range from 22 C to 23 C. 5.2. ETHE model The effects of three parameters (Reynolds number, installation depth and form factor) significantly affecting the performance of an ETHE system were investigated through the parametric analysis. 5.3. Model validation The model developed was validated by experimental data recorded by Moumi et al [3] at university of Biskra in south Algeria. The detailed input parameters for the comparison to experimental studies are described in table 2. As can be seen, the results show good agreement.

A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 503 Table 2: Input parameters for comparative validation Pipe length Pipe diameter Air velocity Kinematic viscosity Input temperature Soil temperature (z=4m) 60 m 0,21m 3.79 m/s 16,96x10-6 m2/s 37 C 24 C Temperature C Length (m) Fig 5: Outlet temperature vs length: Comparison our results and the results of Moummi N. et al, [3]. Table 3: The parameters used for numerical simulation Name Expression Value Description Sigma L /D 250-1000 Form factor Re 2500-10000 Reynold number Pr 0,71 Prandt number Tin 42 C Input temperature Twall 23 C Wall Temperature

504 A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 5.4. Influence of pipe depth Figs. 6 show the influence of pipe depth under the ground surface. As the pipe depth increases, the outlet air temperature decrease, indicating that the ETHE should be placed as deeply as possible. However, the trenching cost and other economic factors should be considered when installing earth to air heat exchanger. 5.5. Influence of form factor sigma ( ) Figs.6 presents the effect of pipe factor form on the outlet air temperature at the highest ambient air temperature (45 C).As the form factor increases, the outlet air temperature decreases due to the fact that the longer pipe provides a longer path over which heat transfer between the pipe and the surrounding can take place given the same overall heat coefficient of earth tube. 5.6. Influence of Reynolds number Figs.6 presents the effect of Reynolds number on the outlet air temperature of earth to air heat exchanger. As the Reynolds number increase, the outlet air temperature increases, since the air spends more less in the tube and thus in contact with lower soil temperature. 26 25.5 sigma=250 sigma=500 sigma=750 sigam=1000 Temperature Outlet ( C) 25 24.5 24 23.5 23 22.5 4000 6000 8000 10000 12000 14000 Reynolds Number Fig 6: Variation of outlet temperature ( C) vs Re for different sigma (factor of the form) and for depth z=4m

A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 505 To avoid an increasing of the pumping power of the ventilator which installed at the end of the pipe Fig. 1, we are plotted the heat loss vs Reynolds number at different form factor Fig 7. Heat loss N/m 2 Reynolds Number Fig 7 : P pressure drop (N/m2) vs. Re-sigma vary- 6. Conclusion In this paper an earth to air heat exchanger model has been presented. The model was validated against other studies: Moumi et al [3]. The validation process shows that the proposed EAHE model does agree with the previous model with respect to the input parameters given and is therefore considered to be appropriate for simulation the thermal behavior of an EAHE of the design examined. The depth z=4m for EAHE can be used for both refresh and heating the buildings. The geometry for form factor equal 250 can be used The EAHE system alone cannot maintain indoor thermal comfort, but it could be used to reduce energy demand in domestic building in south Algeria if used in conjunction with an air conditioning system

506 A.Sehli et al. / Energy Procedia 18 ( 2012 ) 496 506 References [1] F.AL-Ajmi et al, The cooling potential of earth-air heat exchangers for domestic buildings in desert climate, Building and Environment 41(2006) 235-244 [2] S.Amara et al, Using Fouggara for Heating and Cooling Buildings in Sahara, Energy Procedia 6 (2011) 55 64 [3] N.Moummi et al, Le rafraichissement par la géothermie : étude théorique et expérimentale dans le site de Biskra, Revue des Energies Renouvelables, Vol 13 N 3 (201à) 399-406 t sur le confort thermique au sud -34 [5] G.Mihalakakou, On the application of the energy balance equation to prediction ground temperature profiles, solar energy 60(1997)181-190 [6] H.Ben Jmaa Derbel and O.Kanoun, Investigation of the ground thermal potential in Tunisia focused towards heating and cooling applications, Applied thermal engineering(2010) [7] Jones W.P. and Launder B.E... (1972);The prediction of laminarization with a two-equation model of turbulence; Int. J. Heat and Mass Transfer, pp. 15-301. [8] R.Saim, Simulation Numérique de la convection force turbulente dans les échangeurs de chaleur a faisceau et calandre munis des chicannes transversales, Algerian Journal of Applied Fluid Mechanics, Vol 2(2007)-ISNN 1718-5130 [9] Shingari BK, Earth tube heat transfer exchanger,poulty International 1995 ;34 (PT 14 ):92-7 [10] J.Taine J.P Petit, Transferts thermiques, Dunod,Paris 1995