Postprint.

Similar documents
On the performance of confluent jets ventilation system in office space

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

ON THE ENERGY CONSUMPTION OF HIGH- AND LOW-LEVEL AIR SUPPLIES

Performance of Wall Confluent Jets Ventilation System in School Environment compared with Displacement Ventilation

A COMPARATIVE STUDY OF DIFFERENT AIR DISTRIBUTION SYSTEMS IN A CLASSROOM

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Indoor comfort and air quality in spaces equipped with eco-ventilation systems

VALIDATED CFD STUDY OF INDOOR ENVIRONMENTAL CONDITIONS IN A HIGHLY GLAZED, CROSS-VENTILATED MEETING ROOM

Application of CFD Predictions to Quantify Thermal Comfort for Indoor Environments

Sustainable Designed Air-Conditioned Mosque For Thermal Comfort

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Performance of radiant cooling ceiling combined with personalized ventilation in an office room: identification of thermal conditions

Performance Investigation of Building Ventilation System by Calculating Comfort Criteria through HVAC Simulation

VARIABILITY OF THERMAL STRATIFICATION IN NATURALLY VENTILATED RESIDENTIAL BUILDINGS. Stephanie Gauthier 1, David Shipworth 1

Research of Thermal Comfort for Side Air Supply Pattern in Office

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

CAN AIR HEATING ALONE BE USED IN PASSIVE HOUSE OFFICE BUILDING IN COLD CLIMATES? REVIEW OF THE OBTAINED RESULTS

Designing Air-Distribution Systems To Maximize Comfort

Air Distribution and Microenvironment Evaluation of a Desktop Task. Conditioning System 1

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

Numerical analysis of eccentric orifice plate using ANSYS Fluent software

ABSTRACT. Keywords: Energy-saving, Regional air conditioning, Airflow management

Evaluation of thermal comfort, indoor air quality and energy saving of a Local Exhaust Ventilation system in an Office room (LEVO)

COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

The Pennsylvania State University. The Graduate School. Department or Architectural Engineering THERMAL AND VENTILATION PERFORMANCE

DISPLACEMENT VENTILATION

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

CFD Analysis for Production of Carbon Nanotubes

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K.

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher.

NUMERICAL STUDY ON AIRFLOW IN AN OFFICE ROOM WITH A DISPLACEMENT VENTILATION SYSTEM Yukihiro Hashimoto 1 1

Analysis of the Window Side Thermal Environment Formed by Air Barrier. Technique in Winter Conditions and Its Economy

The Air Distribution Around Nozzles Based On Active Chilled Beam System

Analysis of Lecturing Room using Computational Fluid Dynamics Natural and Forced Ventilation

Proceedings of Clima 2007 WellBeing Indoors

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

CFD Modelling of an Aerosol Exposure Chamber for Medical Studies G. Manenti, M. Derudi, G. Nano, R. Rota

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

Published in: Proceedings of the 7th International Conference on Healthy Buildings 2003, Singapore, December 2003, Vol. 2

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space

Floor-Supply Displacement Ventilation in a Small Office

Analysis of Thermal Comfort Conditions and Actual Energy Efficiency for Different Heating Systems in Test Buildings

EXPERIMENTAL INVESTIGATION OF THERMAL AND VENTILATION ANALYSIS FOR STRATUM VENTILATION CFD STUDY

FLOOR-SUPPLY DISPLACEMENT VENTILATION FOR WORKSHOPS. Josephine Lau and Qingyan Chen*

Modelling Thermal Comfort and Energy Saving Enhancements in an Office Room Served by Stratified Air Distribution Systems

Energy efficient thermal comfort. Bin Yang Assistant Professor (Umeå University) Mar 24 th, 2017

Ventilation performance measurement of a decentralized mechanical system with heat recovery using Tracer gas decay method

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance

An experimental investigation of a passive chilled beam system in subtropical

DECREASE THE OUTLET WATER TEMPERATURE OF CROSS FLOW COOLING TOWER

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection

Work Package 2: Performance of naturally ventilated buildings

ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS

Federation of European Heating, Ventilation and Air-conditioning Associations

IMPACT OF THE AIRFLOW INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS WITH ACTIVE CHILLED BEAMS

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

CFD Analysis of Air Conditioning Equipment of CAD Lab for Enhancing its Performance

BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE

CFD Analysis on Capture Efficiency in Commercial Kitchen using Low Radiative Cooking Equipment with Concentrated Exhaust Chimney

Thermal comfort recent challenges

CFD INVESTIGATION OF AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES

MODELLING COMBUSTION AND THERMAL NO X FORMATION IN ELECTRIC ARC FURNACES FOR THE PRODUCTION OF FERRO-SILICON AND SILICON-METAL

Thermal Comfort Evaluation of a Heat Pump System using Induced-air Supply Unit

Individually controlled localized chilled beam in conjunction with chilled ceiling: Part 1 Physical environment

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

ISSN (ONLINE): , ISSN (PRINT):

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Practical Guide Comfort level measurement in the workplace :32. PMV PPD measurement protocol Default Point Graphic Date/Time

3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics

Energy and indoor temperature consequences of adaptive thermal comfort standards

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory

Thermal comfort study of naturally ventilated office

CFD in Ventilation, case studies from REHVA CFD guidebook

An Evaluation of Heat Transfer Coefficient in an Independent Zonal Temperature Controls with CFD

A TRNSYS-FLUENT COUPLED SIMULATION OF THE THERMAL ENVIRONMENT OF AN AIRPORT TERMINAL SPACE WITH A MIXING AND DISPLACEMENT AIR CONDITIONING SYSTEM

Examples of IEQ factors. Healthy IEQ and energy efficiency. What type of system is the best? Ideas and concepts from research and reality.

Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement

Heat transfer enhancement in fire tube boiler using hellically ribbed tubes

The Nottingham eprints service makes this work by researchers of the University of Nottingham available open access under the following conditions.

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

This is a repository copy of A study of passive ventilation integrated with heat recovery.

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

Transcription:

http://www.diva-portal.org Postprint This is the accepted version of a paper presented at 13th International Conference on Indoor Air Quality and Climate, July 7-12, 2014, Hong Kong. Citation for the original published paper: Karimipanah, T., Larsson, U., Cehlin, M. (2014) Investigation of flow pattern for a confluent-jets system on a workbench of an industrial space. In: Indoor Air 2014: 13th International Conference on Indoor Air Quality and Climate (pp. 192-199). N.B. When citing this work, cite the original published paper. Permanent link to this version: http://urn.kb.se/resolve?urn=urn:nbn:se:hig:diva-17859

Topic A7: Thermal comfort INVESTIGATION OF FLOW PATTERN FOR A CONFLUENT-JETS SYSTEM ON A WORKBENCH OF AN INDUSTRIAL SPACE Taghi KARIMIPANH *, Ulf LARSSON, and Mathias CEHLIN Faculty of Engineering and Sustainable Development, Department of Building, Energy and Environmental Engineering, University of Gävle, Sweden * Corresponding email: tkh@hig.se Keywords: Workbench, Ventilation, Thermal comfort, Confluent Jets, CFD SUMMARY A new air supply terminal based on confluent jets was installed on a workbench, in vicinity of a CNC machine, of an industrial space. The flow pattern and temperature field was carried out by CFD calculations and infrared camera imaging technique. A main goal of this technique is to save energy therefore the jet should distribute the air where it is desired. This is possible because the confluent jets system uses the benefits of both mixing (high momentum for better spreading of the air jet) and displacement (cleaner air in occupied zone). The results show that thermal comfort and air quality analysis relies on consistent facts and is in good agreements with the existed standards. It was shown that the supply terminal is able to spread the fresh air to the needed work area. This is an advantage of the high momentum air distribution system used in this investigation. INTRODUCTION As in residential and office buildings, the industrial spaces require also good ventilation performance to guarantee a healthy environmental condition and a better productivity. In investigation of Seppänen et al (2006) has been shown that there is a strong relationship between ventilation rate and working performance. Karimipanah et al (2007 and 2008) have tested the performance of this system against other ventilation strategies, both experimentally and numerically. Cho et al (2008) compared confluent jets system with displacement ventilation system. They derived an empirical equation for the decay of maximum velocity from jet centerline based on the measured velocities. They also showed that the wall confluent jets system produces a greater horizontal spread over the floor than displacement jet and they confirmed that the confluent jet system in most cases performed better than the other existed ventilation systems. This paper focuses on simulations of temperature field and flow pattern of an industrial warehouse using a confluent jets air supply terminal for a single worker. The results were verified by the infrared camera images taken at different sections of workplace. The supply system is very likely as a personalized ventilation system, because of the airflow is distributed close to worker to avoid unnecessary ventilation of other part of the work place. This modern confluent jets ventilation system developed and tested by a Swedish ventilation company in close collaboration with our university; have the capacity for both cooling and heating of residential, offices and industrial ventilation applications.

The purpose was to examine the flow pattern from two newly mounted Confluent Jets supply air terminal using FLIR infrared camera and Computational Fluid Dynamics (CFD) for studying the flow pattern. MODEL SET-UP The system analyzed, as can be figured out from Figure 1, is a single worker, his workbench and the confluent jets blowing into the corner. Figure 1 (right) represents the confluent jets only (with any expanded metal). It should be noted that without adding the metal sheet, right figure below, the airflow may cause draught. As shown in figure 1 (left) the worker is exposed directly to the air jet flow, thus we use an expanded metal to avoid the draught problem. In case without expanded metal and empty room, figure 1 (right) we blow directly to the wall for damping the highly flow turbulence. Figure 1. Confluent jets supply device blowing towards worker with expanded metal. The target is to analyze the indoor climate and develop an approach to thermal comfort and air quality parameters. The results are compared with ISO 7730 in order to conclude whether the implemented ventilation system helps the company to follow this standard. Here, a model with some simplifications sets up to make it feasible for CFD simulations. In first case, see figure 2 (right) a single room with dimensions of 5x5x5 m 3 ; consists of a confluent jets supply device will be regarded as the main calculation domain. But for the second case, see figure 2 (left) a single room with dimensions of 5x5x5 m 3 ; consists of a worker, workbench and confluent jets supply device will be regarded as new calculation domain. In order to analyze how the flow pattern and temperature field, issued from a confluent supply device, the ANSYS Gambit (modelling and meshing) and Fluent (simulation) software are used. The supply diffuser has its exhaust directed against a column with 11 cm from the wall. The reason for the placement is to create a good working environment for the standing worker at the workbench. The devices were plugged and adjusted so that the diffuser with expanded metal sheet to the arm of the machine had 63 Pa pressure drop. The main pipe has a diameter of 15 cm, 136 open nozzles of 5.6 mm in diameter; 33 l / s air flow and 27.5 ºC supply temperature for heating purposes as shown in Figure 2 (left). In CFD calculations these 136 small holes will be transformed into an equivalent area in order to simplify modelling and computation. The confluent Jets device itself is designed by using the spacing approach as described in Awbi (2003). Finally, the worker mannequin and workbench are included in the model built with Airpak, whilst the simulation takes place in Fluent (2013). Some ventilation parameters such as Air Change Rate (ACR), mean age of air and Predicted Percentage of Dissatisfied (PPD) among the others, will be carried on. Furthermore, mesh independency, y plus, residuals and mesh quality are confirmed as well, to verify the quality of models.

For these calculations we use the well-known Renormalization Group (RNG) k-ɛ turbulence model. This method is a sub-method of the standard k- ɛ model developed by Yakhot and Orszag of Princeton University, see Lam (1992). The effects of the small scale turbulence are represented by means of random forcing function in the Navier-Stokes equation and they are continuously deleted from the governing equations expressing their effect through larger scale motions and a modified viscosity. Enhanced Wall Treatment method for K-ɛ RNG turbulence model was chosen for all model run here, both the one coming from Gambit and the one coming from Ansys Airpak. This combination was chosen because many researchers recommend it and provides more accurate solutions for jet impinging to a surface (walls) and also for economic reasons. Figure 2. Model mock up for CFD simulations with worker and workbench (left) empty room (right). In order to verify the mesh quality for the model; we used three runs for coarse grid, middle fine and fine grids. Meshes with hexahedral nodes which result in more accurate solutions than the others available are used, see André Bakker (2002). The amount of cells, mesh density, has to be the adequate to capture the relevant flow parameters and the near wall zone mesh has to be accurate enough to deal with the boundary layer flow (y+, see Wall treatment under theory); in this zone quad and hex nodes are preferred than tetrahedral between others. Poor quality grid will cause imprecise solutions and probably slow convergence. The chosen mesh has 1,010,250 elements (every edge meshed at 0.02 m). The other three parameters, skewness, smoothness and aspect ratio have strongly influence the convergence and solution of the model. Starting from the skewness, the picture taken from Gambit shows up that most of the nodes performing the mesh are in skewness 0 or top quality, although the worst element has a skewness value of 0.518005 what is almost 0.5 which was the maximum objective value. Since there are no parameters to measure smoothness and aspect ratio quality, they were assessed while meshing. Since temperature field is a key factor for thermal comfort, the energy model is going to be used in order to take into account and set temperatures of every element as well as to show how it is spread throughout the room. It is worth mentioning that the images with FLIR infrared camera taken in workplace are used to properly define the temperature of every different part of the mock up. Infrared thermography systems typically have accuracy specifications of ±1.5 or ±2.0 C. Through proper camera handling, thermography images can provide quantitative surface temperatures on flat high emissivity materials (ε > 0.90) with relatively high accuracy. It have been shown that the difference between instantaneously infrared thermography measurements individual thermocouples are within ±0.6 C for temperatures around 17 25 C (Cehlin et al

2000). However, aanalytical and experimental investigation performed with a high-emissivity solid screen placed in a typical airflow from a low-velocity diffuser in an office room show that the temperature of a solid screen can be around 1-2 C warmer than the ambient air due to surrounding radiation (Cehlin et al 2002). In order to provide and extract accurate values from the provided images, software called ThermaCAM Researcher Professional 2.8 (see FLIR 2006) is used. The Temperatures obtained with this software are shown in table 1. The temperatures defined on table 1 were used as boundary conditions in addition to supplier velocity, equal to 9.85 m in a normal to s boundary direction and assuming a density value ρ = 1.225 kg m3. The calculated effective area of the air supply terminal is equal to: A = 3.3496 10 3 m 2 and the flow rate as Q = v A = 0.033 m3 = 33 l s s In the boundary conditions the turbulent kinetic energy of backflow air supply was reduced from 1 m2 m2 s2 (default value) to 0.1 s2 due to the fact that the backflow air entering the room normal to the pressure outlets is low turbulent air. Table 1. Calculated temperatures for different part of model (used as boundary conditions for CFD calculations). Element Temperature(ºC) Floor 22 Ceiling 24 Large wall 24 Corner 24 Pressure outlets 23 Pipe 24.5 Supplier 27.5 RESULTS AND DISCUSSION In order to validate the developed model for the temperature field, the temperatures obtained on the simulation and the ones coming from the infrared camera measurement are compared. The first part compared was the flow spreading over the large wall in a zone close to the supply device. Points 1, 2 and 3, in figure 3 left, are chosen for analysis and comparison with the CFD results from figure 4 right (points 1, 2 and 3 ). Now, the images taken by infrared camera in the presence of worker will be analysed and compared with the CFD results. We chose an image taken by infrared camera very close to the worker, see figure 4 (left). The analogous plane for this image using the CFD results (figure 4, right) would be a plane crossing the worker at X = 3 m. As can be seen from the both figures, comparing the zone closer to the worker and workbench, both temperature fields have a pretty similar distribution. Two random areas close to the worker and one more on the upper zone of the room where chosen using ThermaCam Researcher Professional 2.8. The corresponding area and points are chosen for CFD simulation, as in figure 4.

Comparison between points 1, 2 and 3 for both camera image and CFD result is shown in table 3. Figure 3. The supplier zone temperature from infrared camera image (left) and Obtained from Fluent (CFD) at z=0.08 is zoomed for deep analysis (right). Comparing the results in both parts of figure 3 is shown in table 2. As one may observe, the differences are not significant and agree almost well with each other. Table 2. Temperature difference comparison between CFD results and camera image, figure 3. Minimum T [ºC] Maximum T [ºC] Average T [ºC] Object 1 23.4 23.7 23.5 1 23 23.6 23.3 Temp. difference 0.4 0.1 0.2 2 23.4 24.3 23.8 2 23.6 24.2 23.9 Temp. difference 0.2 0.1 0.1 3 24.2 24.8 24.5 3 24.2 24.8 24.5 Temp. difference 0 0 0 Error was defined as: error = (number number ) 100 number To be able to analyse and make a proper study of thermal comfort conditions we focus on the near zone (occupied zone) part of the workplace. Two interesting planes at Z = 1m and X = 3m have been chosen for thermal comfort discussions. For thermal comfort calculations, a worker which releases 2 met while standing and doing a medium effort activity was considered. This metabolic rate, 2 met, is equal to 116 W/m 2, and it is implemented into Fluent by means of worker boundary conditions, in addition to its corporal temperature, i.e. 37 ºC; workbench s temperature is set at 24.5 ºC. The operative temperature was checked by using ISO Standard 7730, see Olesen (2002). The clothing consist of briefs, T-shirt, normal trousers, thin sweater, socks, and shoes with gives I clu = 0.04 + 0.09 + 0.25 + 0.2 + 0.02 + 0.02 = 0.62 Clo. The results show that for Clo-value=0.62 and met=2 the operative temperature should be between 23 and 18 ºC which is inside the near zone temperature (23 ºC).

Figure 4. Selected points from infrared camera with worker image (left) and corresponding selected points for temperature field (blue square) nearby the worker at X = 3 m from CFD (right). Table 3. Worker temperature comparison. Object Minimum T [ºC] Maximum T [ºC] Average T [ºC] 1 26.2 30.7 29.4 1 28.3 29.2 0.6 Temp. difference 2.1 1.5-2.18 2 24.8 27 26.1 2 25.4 26.4 25.9 Temp. difference 0.6 0.6 0.2 3 22.1 23 22.4 3 21.7 22.6 22.1 Temp. difference 0.4 0.4 0.3 In order to evaluate the level of dissatisfied with the vertical air temperature difference, the temperature values at neck and ankle level are required. As it is inferred from the following figure 5 (left), the neck temperature is 296 K, while ankle temperature is 295.8 K and hence the temperature difference is 0.2 K. Since every temperature difference below 1 K means 1 % of dissatisfied, a temperature difference of 0.2 results in PPD = 1 %, which is below the upper limit, i.e. 5 %. As in table 1, the floor temperature is set at 295 K, i.e. 22 ºC. By using PPD curve or equation from ISO7730 this floor temperature value gives a predicted percentage of dissatisfied of PPD = 7 %, which is an acceptable value since it is below 10 %, the upper threshold, see Iso7730. For checking the possible draught problem two methods are carried out here. The first one is to check that velocity at near zone is not higher than 0.15 m/s for heating purposes, while the second uses a formula taking into account mean values for temperature, velocity and turbulence. Therefore these values are to be obtained from Fluent post-processing. The mean temperature that is inferred from vertical air temperature difference study, has a value of 296 K (23 ºC). The other data is gathered from the following two figures. It is important to note that the average values obtained may vary due to the calculation complexity, so approximations are presented here.

Figure 5. Neck and ankle zone definitions (left), Near zone mean velocity (middle) U mean = 0.27 m/s and near zone mean turbulence intensity (right) TI mean = 11.8 % at Z = 1m and X = 3m. It has to be pointed out that the first method requirements are not fulfilled since velocity mean value almost doubles the limitation. By means of the second method PD draught (Predicted Dissatisfied due to draught) is calculated as: 0.6223 PD draught = ( 34? Tm ) ( U m 0.05) ( 3.143 + 0.3696 mu TI m ) = 0.6223 [ 34? 23 0.27 0.05 ] 3.143 + 0.3696 0.27 11.8 = 18.52 %? ( ) ( ) ( ) The most relevant parts of the human body with regards to draught discomfort are the ankle, the waist and the neck. Therefore, velocity is measured in these places. U ankle = 0.12 m/s; U waist = 0.18 m/s; U neck = 0.1 m/s These values are considered adequate as they fall below maximum recommended velocity (0.15 m/s). The contours for mean age of air (sec), Predicted Mean Vote (PMV) and Predicted Percentage of Dissatisfied (PPD) are shown in figure 6. Figure 6. Contours of mean age of air in sec (left), Predicted Mean Vote (PMV, middle) and Predicted Percentage of Dissatisfied (PPV, right) for two cross sections: x=0.01 m and z=1 m). It is worth mentioning that when developing the model several simplifications were assumed. The real ventilation system consists of 136 air nozzles of 5.6 mm diameter each. This represents a 3.35 10 3 m 2 area, which has been modelled as a cylindrical section area. It has to be noted that in this investigation, it is assumed that all the airflow is equally distributed between all the nozzles. In addition, the velocity has been set normal to boundary of the air supply area, which is an approximation to reality. Nevertheless, the results obtained represent the expected flow behavior for such a supply terminal. CONCLUSIONS

This paper focused on infrared camera imaging for temperature mapping and computer simulations of temperature and flow field on an industrial warehouse using a confluent jets air supply. Concerning thermal comfort, it has to be pointed out that the near zone temperature (23 ºC) is within the operative temperature range (18 23 ºC). Since this value is at the limit of acceptable temperature range, it is recommended that the supply hot air temperature for this building is reduced. The perceived air quality (PD = 4 %) as well as other indicators, gives PD values below 10 %, which means that ISO 7730 is fulfilled. From draught analysis it is inferred that values in the occupied zone are slightly higher (U mean = 0.27 m/s) than the recommended value (0.15 m/s). Due to the work activity, higher velocities are considered acceptable while the air velocity in the neck (0.12 m/s), waist (0.18 m/s) and ankle (0.1 m/s) levels are equal or lower than 0.15 m/s. Since velocity at waist level is higher than the acceptable value, it is recommended that the supply outlet velocity is reduced. It is also pointed out that the higher momentum of Confluent Jets which dominates the thermal buoyancy forces is a major benefit of this system. Observing the velocity and temperature fields, the stratification effects make the system very close to the known displacement ventilation system. Because of limitation of the traditional displacement system for heating (the displacement system is only designed to work for cooling purposes) the confluent jets system can successfully be applied for heating purposes too. ACKNOWLEDGEMENT The Swedish Knowledge Foundation (KK.Stiftelsen) is acknowledged for supporting the project. The Authors are also grateful for helps from our students Mr Luis Viguer and Mr Borje Fatas for analyzing our taken images. REFERENCES Awbi HB (2003) Ventilation of buildings. London, Spon Press; 2003. AIRPAK13.6. User guide. 2007. ANSYS 14.5. ANSYS Fluent user guide. 2013. Karimipanah T, Awbi H.B., Sandberg M and Blomqvist C (2007) Investigation of air quality, comfort parameters and effectiveness for two floor-level air supply systems in classrooms. Journal of Building and Environment 42, Issue 2 (2007) 647-655. Bakker A (2002). Applied Computational Fluid Dynamics (Lecture 7- meshing), Fluent inc. (2002). Cho Y-J, Awbi H B and Karimipanah T (2008). Theoretical and experimental investigation of wall confluent jets ventilation and comparison with wall displacement ventilation. Journal of Building and Environment, 43 (6). pp. 1091-1100. ISSN 0360-1323. Cehlin M, Moshfegh B, Sandberg M. (2000) Visualization and Measuring of Air Temperatures Based on Infrared,. 7 th International Conference on Air Distribution in Rooms. Vol1, pp. 339-347. Cehlin M, Moshfegh B, Sandberg M. (2002) Measurements of air temperatures close to a low-velocity diffuser in displacement ventilation using an infrared camera. Energy and Buildings. 34:687-98. FLIR Systems (2006) ThermaCAM TM Researcher, Publ. No 1 558 072, Revision a196, Basic Edition, Version 2.8 SR1. Issue date December 21, 2006. Lam S H (1992). On the RNG Theory of Turbulence, Physics of Fluids A, 4, pp. 1007-1017, May 1992. Olesen BW (2002). Standards for ventilation, IAQ and thermal comfort; 2002. Seppänen, O., W.J. Fisk, and Q.H. Lei (2006) Ventilation and performance in office work. Indoor Air, 2006. 16(1): p. 28-36.